ALPHA 4/8/12
Installation
Commissioning
Operation
Installation Manual Document : 01 NGP 1145
ALPHA 4/8/12 GBR Index :B
Conventional Fire Alarm Control Date : 19/03/04
Panel Page : 2/34
SUMMARY
INTRODUCTION ............................................................................. 3
INSTALLATION .............................................................................. 4
Mounting ...................................................................................................................... 4
Connections ................................................................................................................ 4
COMMISIONING ............................................................................. 5
Preliminary inspections.............................................................................................. 5
Configuration............................................................................................................... 6
Panel configuration..................................................................................................... 8
CONTROLS AND TESTS ............................................................. 17
Connection ................................................................................................................ 17
Test power supply..................................................................................................... 17
Working tests ............................................................................................................ 17
Final work .................................................................................................................. 18
Electrical and mechanical characteristics .............................................................. 19
Relay card .................................................................................................................. 20
Electrical characteristics of extinguishing card..................................................... 20
Type of Actuators and Type of command............................................................... 20
APPENDIX .................................................................................... 21
Mechanical drawing .................................................................................................. 21
Mains connecting plan ............................................................................................. 22
Panel connecting plan .............................................................................................. 23
Detector and Sounders connection plan ................................................................ 24
Extinguishing configuration and connecting plan................................................. 26
Input lines connection .............................................................................................. 27
Output connection .................................................................................................... 28
Checklist Commissioning ........................................................................................ 29
User Maintenance / System Inspection................................................................... 30
12 relay card configuration and connecting plan .................................................. 31
Operation instructions of Extinguishing module................................................... 33
Operation instructions.............................................................................................. 34
Installation Manual Document : 01 NGP 1145
ALPHA 4/8/12 GBR Index :B
Conventional Fire Alarm Control Date : 19/03/04
Panel Page : 3/34
INTRODUCTION
This manual provides information of the conventional fire alarm panel ALPHA 4/8/12.
• ALPHA 4/8/12 Basic panel with 4 lines
• EX4A4 Option: 4 line extension card
• REP4R Option: 4 relays card
• R12P2 Option: 12 relays card
• DEAG Option: extinguishing card
The following information is given to benefit the safety of persons, to avoid damaging the installed
equipment and to ensure the correct operation of the system.
The whole panel documentation shall be printed and placed close to the panel.
All modules are designed to comply with the EN 54-2 and EN 54-4 standards and with the draft of EN
12094-1 standard for the extinguishing part.
Access levels
Level 2 protected access for operator / safety officer (by digital code).
Safety relevant operation is enabled. E.g. switch detection lines on/off
Caution :
Before any intervention on the power supply of the equipment, make sure the mains (230V) is
powered down using the external device of the building's electrical installation.
Installation Manual Document : 01 NGP 1145
ALPHA 4/8/12 GBR Index :B
Conventional Fire Alarm Control Date : 19/03/04
Panel Page : 4/34
INSTALLATION
Mounting
Fix the panel box to the wall using the 3 attaching holes (see drawing in the appendix)
The installation of the two batteries and the optional cards will be done during the commissioning.
Other equipment refer to their individual instruction manuals.
Connections
Cable inlets
In order to keep the initial degree of protection (IP31), the cables will enter either by the preformed
orifice plate at the bottom or at the back of the box.
Do not connect the wires at the panel now, the connections will be done during the commissioning.
Power supply
The panel will be powered from the mains (230 VAC 50 Hz).
Use the mains terminal block of the cabinet (at the right bottom).
A dedicated power line shall be used for the fire security.
The line shall be protected against high voltage peaks and high frequency voltage.
The panel has to be connected to electrical earth.
(Recommendation:
Use the earth of weak signal equipment: «weak current earth» or «computing earth».
Cable types
Recommendation:
Pair-wise twisted and shielded
24VDC Output 2 x 1.5mm² or 2 x 2.5mm²
Internal repetition by relay Cable (pre installed)
(optional)
Sounders 2 x 1.5mm² or 2 x 2.5mm²
Cable protected according to national standard
Programmable input ≥ 1 mm² (maximum length = 1Km)
Extension card Fire detection lines See under main card
Relay Card Information transmit ≥ 2x 0.5mm²
Extinguishing -Extinguishing Manual Call ≥ 2x 1 mm² (maximum length = 1Km)
Card Point Input
-Remote inhibition Input
-Low pressure Contact
Input
24V external power supply ≥ 2x 1.5 mm²
for evacuation indicators
and extinguishing
actuators
-Extinguishing indicators ≥ 2x 1.5 mm²
-Extinguishing actuators
Installation Manual Document : 01 NGP 1145
ALPHA 4/8/12 GBR Index :B
Conventional Fire Alarm Control Date : 19/03/04
Panel Page : 5/34
COMMISIONING
Preliminary inspections
Line checks
Before connecting and powering up the panel, the monitored lines for
• Detectors
• Sounders and Extinguishing indicators, Extinguishing actuators if used
• Input of main card and Inputs of Extinguishing card if used
shall be checked for their quality.
For each line, check its line resistance, rating resistance and insulation.
Remove the short circuit and connect the Line Terminal Resistor (LTR=3,9kΩ) at the end of the line.
Measure the resistance at the beginning of the line between the wires «+» and «-».
RR shall be between 3750Ω and 4200Ω
Configuration
Generalities
Hardware configuration:
All equipment is powered off.
(If the panel is powered, first remove the battery and then the mains.)
If there are optional cards: mount the extension or Extinguishing card(s) and make sure that the
jumper ST1 at the left card is set, and the jumper ST1 at the right card is removed.
For the Extinguishing Card(s), select the different jumpers according the chosen configuration for the
type of actuators, the actuators supply and sounders/indicators supply (see appendix).
Software configuration:
When the panel is powered, it allows to define some parameters and functions. This must be done,
every time you remove or add a card, or a parameter has to be changed.
These settings will be saved in a non-volatile memory and can be changed only be overwriting.
Powering Up
The panel displays «System Fault», this LED turns off after a few seconds (initialisation time), then the
fire detection lines are disabled.
Software Parameters
As the first step, you have to enable the fire detection lines (see chapter “Enable / disable fire
detection ”). Now make the panel configuration according the site requirements.
The main parameters of the commissioning as follows:
(This is an overview. The function are described in more detail further down in this document)
Parameters Access Function
Enable/ disable fire detection line Level 2 Inhibition of information given by a fire detection line.
On/off test mode of fire detection line Level 2 Enable to test the detectors of the installation without
activation of the control device.
Detection mode (alarm on one Level 3 Allows to configure the line in 2 detectors alarm mode.
detector or on two detectors) code BABA This mode is forbidden for Manual Call Points.
Joining alarm zone with Level 3 Allows to join the alarm zone to one or several fire detection
detection zone (AZ/DZ) code ABBB zones. By default all fire detection zones are joined to the
alarm zone.
If extinguishing card is used, Allows to join the extinguishing
zone to two (minimum) or several detection zones.
Sounders delay Level 3 Delay between an alarm and the actuation of sounders line.
code BAAA 0 to 7 minutes in 1 minute steps. Default: no delay.
If extinguishing card is used, Delay between the activation
extinguishing indicators and the activation extinguishing
actuators.
Enable/ disable sounders line Level 3 Disabling of the sounders line.
code BABA
Access Level 2
The panel can have two different level 2 access codes (see chapter “Code modification level 2
access”)
Access Level 3
The Level 3 can be accessed if the panel is in level 2 and if the system is not in alarm.
The level 3 access codes are described in the list above.
Indication after a valid access level 3 code:
- The LED «level 2 or 3» is off and the LED «Fault system» is blinking.
- One other LED of the main panel will activate, according to the code which has been set.
The validation of the settings is done either automatically or by pressing the «Reset» key, depending
on the chosen function.
The level 3 exit is done by pressing the key «Silence Buzzer».
Installation Manual Document : 01 NGP 1145
ALPHA 4/8/12 GBR Index :B
Conventional Fire Alarm Control Date : 19/03/04
Panel Page : 8/34
Panel configuration
Enable / disable fire detection zones, or enable / disable manual mode and/or automatic mode
of extinguishing module
Extinguishing:
• Press the key « LEVEL 2 » of « AUTOMATIC MODE
DISABLED/MANUAL MODE DISABLED » to enable or disable each
mode
• LED « AUTOMATIC MODE DISABLED » and/or LED « MANUAL
MODE DISABLED » :
On = automatic mode or manual mode disabled
Off = automatic mode or manual mode enabled
FUNCTIONS Allows to activate the test mode of each detection zone and/or extinguishing
channel.
CODE Level 2
STATE LED « ACCESS LEVEL 2 OR 3 » is on
KEY and LED • Press the key « LED – BUZZER TEST »
• LED « TEST » on
For exit of test mode press « RESET PANEL » (see note below )
Note: Once the zones have been programmed in test mode wait 10s before pressing « RESET
PANEL » for exit. Exit of test mode is possible only when the zones in test mode are no longer in
alarm status. On the other hand, you can reach Level 3 from test mode and this way disable test mode
without taking the delay of 10s into account.
Installation Manual Document : 01 NGP 1145
ALPHA 4/8/12 GBR Index :B
Conventional Fire Alarm Control Date : 19/03/04
Panel Page : 9/34
2 detectors mode
FUNCTIONS 1) Allows to activate Mode 1 (single detection) or Mode 2 (double detection) for
each detection zone.
• Mode 1: Zone switches into alarm status if one detector is in alarm
• Mode 2: Zone switches into alarm status if a second detector of the
same zone is in alarm.
2) Allows to check the mode of each zone
CODE At level 2, set the code BABA, then press AB simultaneously
STATE LED « SYSTEM FAULT » is blinking
LED « FAULT WARNING » in on
KEY and LED • Press the key « LEVEL 2 » of the function « DISABLE (TEST) » of
each detection zone to switch the line from mode 1 to mode 2 or from
mode 2 to mode 1.
• LED « FAULT/DISABLED/TEST »:
Off = mode 1
On = mode 2
To validate this setting you must reset the panel by pressing the key «
SILENCE BUZZER »
Note: After any setting in double detection mode you must validate this mode by pressing the key «
ON/OFF » of the function « DAY/NIGHT » (LED « ACTIVE » on). This manipulation will be done under
access Level 2.
FUNCTIONS 1) Allows to enable/disable the line of the main card dedicated to sound
broadcasters.
2) Allows to check the state of the sounders line (on or off)
CODE At level 2, set the code BABA, then press AB simultaneously
STATE LED « SYSTEM FAULT » is blinking
LED « FAULT WARNING » is on
KEY and LED • Press the key « ON/OFF » of the sounders line to switch on/off the
line.
• LED « FAULT WARNING » of the sounders line :
Off = Line is on
On = Line is off
To validate this setting you must reset the panel by pressing the key «
SILENCE BUZZER »
Installation Manual Document : 01 NGP 1145
ALPHA 4/8/12 GBR Index :B
Conventional Fire Alarm Control Date : 19/03/04
Panel Page : 10/34
FUNCTIONS 1) Allows to associate one or several detection zones DZ to the alarm zone AZ
Note: The alarm zone AZ corresponds to the line of the main card dedicated to
the sound broadcasters.
For exit you must reset the panel by pressing the key « SILENCE BUZZER »
Association setting
( you must be in check mode)
• Press the key « LEVEL 2 » of the function « DISABLE (TEST) » to
associate or not the chosen detection zone to the alarm zone.
• LED « FAULT/DISABLED/TEST » :
On = DZ associated to AZ
Off = DZ not associated to AZ
Validation
• Press the key « RESET PANEL » to save the association settings and
for exit of setting.
• LED « EVACUATE » of the sounders line is off.
Note: As long as you have not reset the panel you can reach the
association setting by pressing « ON/OFF » of the sounders line. Then a
new association setting can be done.
Exit
Press the key « SILENCE BUZZER » to return to standard operation
Installation Manual Document : 01 NGP 1145
ALPHA 4/8/12 GBR Index :B
Conventional Fire Alarm Control Date : 19/03/04
Panel Page : 11/34
For exit you must reset the panel by pressing the key « SILENCE BUZZER »
Association setting
( you must be in check mode)
• Press the key « LEVEL 2 » of the function « DISABLE (TEST) » to
associate or not the chosen detection zone to the extinguishing zone.
• LED « FAULT/DISABLED/TEST » :
On = DZ associated to EZ
Off = ZD not associated to EZ
Validation
• Press the key « RESET PANEL » to save the association settings and
for exit of setting.
• LED « (TEST) DISABLED » of the extinguishing line is off.
Note: As long as you have not reset the panel you can reach the association
setting by pressing « LEVEL 2 » of the function « (TEST) DISABLED » of the
extinguishing card. Then a new association setting can be done.
Exit
Press the key « SILENCE BUZZER » to return to standard operation
Installation Manual Document : 01 NGP 1145
ALPHA 4/8/12 GBR Index :B
Conventional Fire Alarm Control Date : 19/03/04
Panel Page : 12/34
Sounders delay
FUNCTIONS 1) Allows to apply a delay for the activation of the sounders line.
You must reset the panel by pressing the key « SILENCE BUZZER » for exit
Setting
(You must be in check mode)
• Press the key A or B to decrease or to increase the delay.
Validation
• Press the key « RESET PANEL » to save the settings.
Exit
Press the key « SILENCE BUZZER » to return to standard operation.
Installation Manual Document : 01 NGP 1145
ALPHA 4/8/12 GBR Index :B
Conventional Fire Alarm Control Date : 19/03/04
Panel Page : 13/34
Extinguishing delay
FUNCTIONS 1) Allows to apply a delay for the activation of the extinguishing zone.
For automatic mode or manual mode, the extinguishing card displays the
programmed delay as follows :
• LED C (at the right) of the function « FAULTS IDENTIFICATION » is
on = 10s
• LED B (at the middle) of the function « FAULT IDENTIFICATION » is
on = 20s
• LED A (at the left) of the function « FAULT IDENTIFICATION » is on =
40s
• The various combinations of those LEDS allow to read a delay from 0
to 60 seconds.
• All the LEDS are off = no delay
You must reset the panel by pressing the key « SILENCE BUZZER » for exit
Setting
(You must be in check mode)
• Press the key « LEVEL 2 » of the function « TEST (DISABLED) » of
the extinguishing card to decrease or increase the delay of one or the
other of the 2 modes.
Validation
• Press the key « RESET PANEL » to save the settings.
Exit
Press the key « SILENCE BUZZER » to return to standard operation.
Installation Manual Document : 01 NGP 1145
ALPHA 4/8/12 GBR Index :B
Conventional Fire Alarm Control Date : 19/03/04
Panel Page : 14/34
Modification of access code level 2 and modification of the faults delay for zones of the main
card
2) Allows to modify the faults delay for zones of the main card.
CODE At level 2, set the code AAAA, then press AB simultaneously
STATE LED « SYSTEM FAULT » is on
LED « EVACUATE » of the sounders line is on
LED « DISABLED » is on
KEY and LED Simple access code level 2
• Press the key A to install the simple access code level 2.
• LED « FIRE ALARM » of zone 1 is on.
Short delay (only for the 4 detection zones of the main card):
• Press the key « LEVEL 2 » of the function « DISABLE (TEST) » of
zone 4 to set a short delay (1 s for a short-circuit and 4 s for an open
circuit).
• LED « FAULT/DISABLED/TEST » of zone 4 is on = short delay.
Note: For the detection zones of the optional cards, the delay remains the
same (1 s for a short-circuit and 12 s for an open circuit).
For the extinguishing card, the delay remains the same (5 s for a
short/open circuit in the low pressure line, 2 s for a short/open circuit in the
manual extinguishing line, 1 s for a short/open circuit in the 3 others lines).
Remarks
Simple access code level 2 = «AB»
Standard access code level 2 = «AB, A,B,A,B, AB»
Installation Manual Document : 01 NGP 1145
ALPHA 4/8/12 GBR Index :B
Conventional Fire Alarm Control Date : 19/03/04
Panel Page : 15/34
Output setting
Successively press the key «A» or «B» to select the function as follows:
• LED « FIRE ALARM » of detection zone is on (standard mode)
• LED « FIRE ALARM » of detection zone is blinking (mode 2 detectors,
if mode « DAY/NIGHT » activated)
• LED « FIRE ALARM » of the main card for mode 2 detectors (if used)
is blinking
• LED « DISABLED » is on
• LED « TEST » is on
• LED « SYSTEM FAULT » is on
• LED « POWER SUPPLY FAULT » is on
• LED « FAULT WARNING » of the sounders line is on
• LED « EVACUATE » of the sounders line is on
• Active buzzer state ( short beep)
• Reset panel state (long beep)
Validation:
• Press the key « RESET PANEL » to save the settings.
This will switch off the leds of the chosen zone and the chosen function.
New settings can be done at this moment. (Press the key « LEVEL 2 » of the
function « DISABLE (TEST) » of the corresponding zone).
Exit
Press the key « SILENCE BUZZER » to validate the setting and to return to
reset the system.
Installation Manual Document : 01 NGP 1145
ALPHA 4/8/12 GBR Index :B
Conventional Fire Alarm Control Date : 19/03/04
Panel Page : 16/34
WARNING !
Working tests
Note
These tests are a real control of the fire detection installation.
It is recommended to make these tests in a first step having the fire safety control equipment
neutralised. When the test are ok., repeat all test having the fire safety control equipment connected.
Before carrying out these tests, make sure the security department is informed about the fire alarm
testing.
Evacuation Function
• Press the sounders key «On/Off» during 3 seconds.
• Check the LED sounders «Active» is on.
• Check the correct working of sounders and other equipment associated to the evacuation.
• Press the sounders key «On/Off» to switch off the sounders.
Extinguishing Function
• Make sure that all the monitored lines connected to the panel are in a normal status.
• In case of anomaly, identify the fault before continuing with the next test.
• For all monitored lines, Disconnect it from the panel and make sure that panel signals the
corresponding fault.
• Plug again it with the panel and make sure the fault warning disappears.
• After having checked that the actuators are disconnected, activate the automatic zone alarm
inputs and make sure the extinguishing cycle starts with the correct operations and delay.
• Reset the system and activate the manual extinguishing input and make sure the
extinguishing cycle starts with the correct operations and delay.
• Reset the system and make sure the remote inhibition line and 2nd stage MCP (Manual Call
Point) line operate correctly.
Final work
After completing the tests successfully
• Note the software settings.
• Put the line names on the panel
Hand over the system to the customer, including:
• Instruction of the responsible person(s)
• System manual
• Software settings
• Installation drawings
Installation Manual Document : 01 NGP 1145
ALPHA 4/8/12 GBR Index :B
Conventional Fire Alarm Control Date : 19/03/04
Panel Page : 19/34
Relay card
REP4R
input lines
number of lines 4
Type To be driven from ALPHA 4/8/12 open collector outputs .
Output
number of outputs 4
Type 1 relay, potential free, switch over contact 5A/230VDC
R12P2
Output
Quantity of output 12
Type 1 relay, potential free, switch over contact 30V/1A
NOTA : If the internal power supply is used to command the evacuation indicator and the
extinguishing actuators, don‘t forget this internal power supply is limited to 950mA by Electronic
protection.
APPENDIX
Mechanical drawing
Product equipment
Main card
Card connectors
230VAC
General connecting area
Wall mounting
28mm
3 holes Ø 6 mm
300mm
28mm
115 mm 115 mm
Installation Manual Document : 01 NGP 1145
ALPHA 4/8/12 GBR Index :B
Conventional Fire Alarm Control Date : 19/03/04
Panel Page : 22/34
Cable clamp
Installation Manual Document : 01 NGP 1145
ALPHA 4/8/12 GBR Index :B
Conventional Fire Alarm Control Date : 19/03/04
Panel Page : 23/34
Automatic detectors
SR95
Contact NO 60V/0,2A
S95
Shield
Shield
LTR
LTR
S95
4 IA : Remote Indicator
S95
Shield
LTR
BMY2
BMLY2
Sounders line
LTR
Installation Manual Document : 01 NGP 1145
ALPHA 4/8/12 GBR Index :B
Conventional Fire Alarm Control Date : 19/03/04
Panel Page : 26/34
Ract Ract
1KΩ 1KΩ
1/4W Reol
Manual Extinguishing 1/4W 3,9KΩ
Input 1/4W
Ract Ract
1KΩ 1KΩ
1/4W Reol
Extinction/Inhibition 1/4W 3,9KΩ
Input 1/4W
Ract
1KΩ Reol
Low Pressure input 1/4W 3,9KΩ
1/4W
Installation Manual Document : 01 NGP 1145
ALPHA 4/8/12 GBR Index :B
Conventional Fire Alarm Control Date : 19/03/04
Panel Page : 28/34
Output connection
Connection For Electromagnetic actuators
1N5406 1N5406
Extinguishing actuators
Type Electromagnetic Reol
24 Vdc for 30 s 3,9KΩ
2A maximum 1/4W
1N4004 1N4004
-
Electromagnetic actuator
Checklist Commissioning
This is a brief instruction. For detailed information refer to the corresponding chapter in the manual.
1. If needed, mount the optional card(s).Make sure that the jumper ST1 at the left card is installed
and the jumper ST1 at the right card is removed.
2. All the detector lines must have an end resistor of 3kΩ (2850Ω ...3150Ω).
Check this value by means of a multimeter
3. The sounders line and the input of ALPHA4/8/12 must have an end resistor of 3k9Ω. If
extinguishing card is used, all input lines and output lines must have an end resistor of 3k9Ω.
Check this value by means of a multimeter
5. Put the 2 batteries in the box. Connect the bridge from bat.1 «+» to bat.2 «-».
Connect the battery cables from the panel to bat.1 «-» and to bat.2 «+».
8. Make the required software settings. When you are in access level 2, use the following code.
Rem.: By default, all the lines are associated to the alarm zone.
WARNING !
DAILY INSPECTION
Check that the System Energised LED is lit.
Check no other LEDS are lit and that no sounders are operating.
Report any faults to the designated site maintenance engineer.
WEEKLY TEST
Press the Led/Buzzer Test to check that all LEDs lights show and the warning beeper sounds.
Switch off the mains supply and verify the fault signalling are given.
Stop the beeper sounds.
Switch on again the mains supply.
MONTHLY TEST
One Fire Detector Point or one Manual Call Point have to be tested to check the system can operate
in case of Fire. During each control, Test a different zone each week and always use a different call
point or smoke/heat detector for each test so that all devices are tested in rotation.
Check that the alarm sounders operate.
QUARTERLY TEST
Visually inspect the battery and it’s connections. Please note : Lethal voltages are present inside
the panel . Do not open the panel unless you are qualified to do so and DO NOT touch the
power supply unit.
Operate a call point or sensor in each zone to test the fire alarm as in the monthly test above.
Remove the mains supply and check that the battery is capable of supplying the alarm sounders.
ANNUAL TEST :
As for the monthly and quarterly test but check every detector, call point, sounder, and all auxiliary
equipment for correct operation.
EVERY 2 to 3 YEARS :
Clean the smoke/ heat detector s to ensure the correct operation and freedom from false alarms.
SERVICING :
REGULAR SERVICING IS HIGHLY RECOMMENDED, preferably on a continuous maintenance
contract and by a competent organisation. A full-itemised report of the installation should be obtained
at least annually.
Installation Manual Document : 01 NGP 1145
ALPHA 4/8/12 GBR Index :B
Conventional Fire Alarm Control Date : 19/03/04
Panel Page : 31/34
ST1 ST2 ST3 ST4 ST5 ST6 ST7 ST8 ST9 ST10 ST11 ST12
S1 S3 S5 S7 S9 S11
ON ON ON ON ON ON
S2 S4 S6 S8 S10 S12
1 1 1 1
K1 K4 K7 K10
2 2 2 2
3 3 3 3
B1 K2 B2 K5 B3 K8 B4 K11
4 4 4 4
5 5 5 5
6
K3 6
K6 6
K9 6
K12
J2
J1
Terminal blocks
B1 B2 B3 B4
B1.1 COM Relay B2.1 COM Relay B3.1 COM Relay B4.1 COM Relay
B1.2 N.O./N.C. K1 B2.2 N.O./N.C. K4 B3.2 N.O./N.C. K7 B4.2 N.O./N.C. K10
B1.3 COM Relay B2.3 COM Relay B3.3 COM Relay B4.3 COM Relay
B1.4 N.O./N.C. K2 B2.4 N.O./N.C. K5 B3.4 N.O./N.C. K8 B4.4 N.O./N.C. K11
B1.5 COM Relay B2.5 COM Relay B3.5 COM Relay B4.5 COM Relay
B1.6 N.O./N.C. K3 B2.6 N.O./N.C. K6 B3.6 N.O./N.C. K9 B4.6 N.O./N.C. K12
Installation Manual Document : 01 NGP 1145
ALPHA 4/8/12 GBR Index :B
Conventional Fire Alarm Control Date : 19/03/04
Panel Page : 32/34
Contact association
Red Steady
At least a detection line associated
with the extinguishing channel is in
alarm.
Red Steady Yellow Steady
Extinguishing cycle (delay) in Extinguishing channel is disabled
progress. At least two detection Blinking con T=2s.
lines associated with the Extinguishing channel is in test
extinguishing channel is in alarm. mode
Red Steady
Discharge actuators are activated. Help the user to detect the
functions of the extinguishing
channel in fault status.
Yellow Steady.
Yellow Steady
Discharge command is inhibited
A function of the extinguishing
thanks to the inhibition input line.
channel is in fault
Yellow Blinking T=1s.
Yellow Steady
More then one function of the
The automatic mode is off.
extinguishing channel is in fault
Yellow Steady
The manual mode is off
Operation instructions
A B
LED on: Control field of fire detection zone «DZ »:
Mains failure (230V) Each detection zone is associated to a control
LED blinking: Fire alarm Fire alarm field with two indicators and one push button.
Battery fault. Each control field is associated to an identified
In case of mains failure, the system is Fault/ Fault/ installation area
operating a period of at least 24 hours. disabled/ disabled/
LED on and Buzzer intermittent:
test Led – Silence Reset
test Fire alarm in the zone.
LED + 2 access keys A, B (level 1 access): buzzer buzzer Panel LED blinking:
test One detector is active.
Code management for accessing level 2 or 3 Disable Level Level 2 Disable Level
(see chapter configuration). The zone is in 2 detectors mode (pre-alarm
(test) 2 (test) 2
mode)
It is used to change system parameters.
LED on:
Key Test Led/Buzzer (level 1 access): The zone is disabled.
Activates the buzzer and all LEDs at the panel Key Silence Buzzer (level 1 access): Key Reset Panel (Level 2 access): Key Disable (level 2 access): LED blinking fast and Buzzer continuous:
incl. extension cards for test purpose. Allows at any time the internal buzzer signal to After the cause of the alarm has been Allows to enable/disable the The line is in fault (open circuit, short circuit,
At level 2 access, this key is used to enter in be switched off temporary; it then remains eliminated, this key allows the panel to zone or to enter the zone in detector fault or removed detector)
test mode. available for any further information. be reset. test mode. LED slow blinking:
Caution: During the delay mode, the alarm It is also used to exit from test mode. (For test mode, at first press The zone is in test mode. This indication has
process can be stopped by pressing « Silence the key Test Led/Buzzer). less priority than the others.
Buzzer » at level 2 access during 3 seconds.