Model T6000 Electro-Pneumatic I/P, E/P Transducer

Features T6000 Standard Range

B
• Field reversible feature provides output
which is directly or inversely proportional to
the input signal.
• RFI/EMI Protection eliminates susceptibility
to electromagnetic and radio interference.
Model
T6000
• Six output pressure ranges meet final
control element requirements.
• Six input signal ranges meet most process
and machine requirements.
• Compact size permits use in space
restricted areas.
• Explosion-Proof NEMA 4X, IP65, Type 4
Enclosure available for outdoor and indoor T6000 Extended Range
installations.
• Input and Output ports on both front and
rear simplifies pneumatic piping.

Operating Principles
The T6000 Series is designed for Standard Range
precision applications providing The T6000 Series is an electro-pneumatic
maximum versatility. The modular device that converts a DC input signal to a
construction permits any basic unit pneumatic output. This device is made up
to be used in the explosion-proof, of two sections, the Primary Converting
rack, wall, pipe, panel, DIN rail or 3, Section and the Pneumatic Relay Section.
5, 10, or 15 unit manifold The Coil and Suspension Spring, in the
configurations. Servicing or Primary Converting Section, is used as a
calibration is quick and easy. Flapper. Together the Flapper and Nozzle
work to control the signal pressure. The
signal pressure acts on the Upper Control
Diaphragm, in the Pneumatic Relay Section,
which sets the output pressure. The output
pressure is sensed by the Lower Control
Diaphragm, in the Pneumatic Relay Section,
which maintains the output pressure.
Extended Range
The Extended Unit is made up of three
sections, the Primary Control Section, the
Pneumatic Relay Section, and an additional
Pneumatic Relay Section. The additional
Relay Section is used to amplify the output
pressure.

84
800-334-8422
Model T6000 Electro-Pneumatic I/P, E/P Transducer

Specifications:
T6000 Standard Range Transducers
TA6000 Standard Range

Output psig 3-15 3-27 6-30

B
Range [BAR] [0.2-1.0] [0.2-1.8] [0.4-2.0]
(kPa) (20-100) (20-180) (40-200)

Supply psig 20-120 32-120 35-120


Pressure1 [BAR] [1.5-8.0] [2.2-8.0] [2.4-8.0]
(kPa) (150-800) (220-800) (240-800)
Model
Minimum psig 5 10 10 T6000
Span [BAR] [0.35] [0.7] [0.7]
(kPa) (35) (70) (70)

Impedance 4-20 mA
(OHMS) / 10-50 mA
197 204 204

Input Signal 0-5 VDC


TT6000 Standard Range 79 82 82

0-10 VDC
550 532 532

1-5 VDC
1100 1064 1064

1-9 VDC
500 483 483
1000 970 970

Air Consumption 5.0 6.0 6.0


(per ISA S51.1) SCFH (.14 m3/HR) (.17 m3/HR) (.17 m3/HR)

Independent Linearity +0.5% FS +0.5% FS +0.5% FS


(per ISA S51.1)

Hysteresis & Repeatability 0.25% FS 0.25% FS 0.25% FS


(per ISA S51.1)

Supply Pressure Effect on Output


TD6000 Standard Range 0.25 psig, [0.17 BAR], (1.7 kPa) for a 25 psig, [1.7 BAR], (170 kPa) supply
change

Flow Rate (SCFM)


2.5 (4.25 m3/HR) @ 25 psig, [1.7 BAR, (170 kPa) Supply & 9 psig, [0.6 BAR],
(60 kPa) Output.
9.0 (15.3 m3/HR) @ 120 psig, [8.0 BAR, (800 kPa) Supply & 9 psig, [0.6
BAR], (60 kPa) Output.

RFI / EMI Effect


Less than 0.5% of Span @ 30 v/m class 3 Band ABC (20-1000 mHz) per
SAMA PMC 33.1 1978 and less than 0.5% of Span @ 10 v/m level 3, 27-500
mHz Band per IEC Standard 801-3 1984. EMC Directive 89/336/EEC
European Norms EN 50081-2 and EN 50082-2.

Temperature Range (per ISA S51.1)


TR6000 Standard Range -20 oF to +150oF, (-30oC to +65oC)
Materials of Construction
Body and Housing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Aluminum
Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Zinc Plated Steel
Diaphragm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Nitrile
Orifice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Nickel Plated Brass
1
Supply Pressure must be no less than 5 psig, [0.35 BAR],
(35 kPa) above minimum output.

NOTE: Model TR6000 Transducer is designed for use with the


TR Rack Kit. Physically, it is the same as the TT6000 Unit except
that the terminal block has been rotated to the rear.

85
800-334-8422
Model T6000 Electro-Pneumatic I/P, E/P Transducer
TA6000 Extended Range Specifications:
T6000 Extended Range Transducers

Output psig 0-30 0-60 0-120

B
Range [BAR] [0-2.0] [0-4.0] [0-8.0]
(kPa) (0-200) (0-400) (0-800)

Supply psig
Pressure1 [BAR]
35-150 65-150 125-150

(kPa)
[2.5-10.0] [4.6-10.0] [8.8-10.0]
(250-1000) (460-1000) (880-1000)
Model Minimum psig
T6000 Span [BAR]
12 25 50

(kPa)
[0.8] [1.5] [3.5]
(80) (150) (350)

Impedance 4-20 mA
(OHMS) / 10-50 mA
250 256 270

Input Signal 0-5 VDC


100 103 108

0-10 VDC
439 469 446

1-5 VDC
TT6000 Extended Range 878 938 893

1-9 VDC
400 453 430
800 750 714

Air Consumption 12.0 13.0 17.0


(per ISA S51.1) SCFH (.34 m3/HR) (.36 m3/HR) (.48 m3/HR)

Independent Linearity ±0.75% FS ±1.0% FS±1.0% FS


(per ISA S51.1)

Hysteresis & Repeatability <1.0% FS @ <1.0% FS @ <1.0% FS @


(per ISA S51.1) 35 psig, 65 psig, 125 psig,
[2.5 BAR], [4.6 BAR], [8.8 BAR],
(250 kPa) (460 kPa) (880 kPa)

Supply Pressure psig


Effect on Output [BAR]
0.5 1.0 1.5

(kPa)
[0.03] [0.07] [0.1]
For a 25 psig, (4.0) (7.0) (10.5)
TD6000 Extended Range [1.7 BAR], (170 kPa)
supply change

Flow Rate (SCFM)


11 (18.7 m3/HR) @ 150 psig, [10 BAR, (1000 kPa) Supply & 9 psig, [0.6
BAR], (60 kPa) Output.

RFI / EMI Effect


Less than 0.5% of Span @ 30 v/m class 3 Band ABC (20-1000 mHz) per
SAMA PMC 33.1 1978 and less than 0.5% of Span @ 10 v/m level 3, 27-500
mHz Band per IEC Standard 801-3 1984. EMC Directive 89/336/EEC
European Norms EN 50081-2 and EN 50082-2.

Temperature Range (per ISA S51.1)


-20 oF to +150oF, (-30oC to +65oC)
Materials of Construction
TR6000 Extended Range Body and Housing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Aluminum
Orifice. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Nickel Plated Brass
Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Zinc Plated Steel
Diaphragm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Nitrile
1
Supply Pressure must be no less than 5 psig, [0.35 BAR],
(35 kPa) above maximum output.

NOTE: Model TR6000 Transducer is designed for use with the


TR Rack Kit. Physically, it is the same as the TT6000 Unit except
that the terminal block has been rotated to the rear.

86
800-334-8422
Model T6000 Electro-Pneumatic I/P, E/P Transducer

Hazardous Area Specifications


Explosion-Proof Intrinsically Safe
Factory Mutual

B
(FM) Approvals
Class I, Division 1, Groups B, C and D; Class I, II, and III, Division 1, Groups A, B, C,
Class II, Division 1, Groups E, F, and G; D, E, F, and G.
Entity Parameters
NEMA 4X Enclosure.

Vmax1 = 40 VDC Ci3 = O µ F


Imax2 = 125 mA Li4 = 3 mH
Vmax = Max. Voltage Ci = Capacitance
Model
1 3

Imax = Max. Current Li = Inductance T6000


2 4

Canadian Standards
Association (CSA)
Class I, Division 1, Groups B, C and D; Class I, Division 1, Groups A, B, C and D;

Approvals
Class II, Division 1, Groups E, F, and G; Temperature Code T3C.
Type 4 Enclosure. Rated 4-20 mA, 30 VDC Maximum.

Approvals are valid when connected


through a Shunt Zener Diode Safety
Barrier meeting the following
parametric requirements:
System Type 1: Single Channel Polarized Rated:
28V Max. 300 Ohm Min.

System Type 2: Dual Channel Polarized Rated:


28V Max. 300 Ohm Min.
System Type 3: a. 28V Max. 300 Ohm Min. &
10V Max. 50 Ohm Min. return.
b. 28.5V Max. 300 Ohm Min. &
9V Max. 50 Ohm Min. return.

ATEX Approvals II 1G EEx ia IIC T4 (Ta = -20°C to +65°C)

Transducer Parameters
Umax1 = 28 V Pi3 = 0.653 W
Imax2 = 93 mA Ci4 = 0
Li5 = 0
1
Umax = Max. Voltage 3
Pi = Max. Power
2
Imax = Max. Current 4
Ci = Capacitance
5
Li = Inductance

1
ATEX not available for Explosion-Proof.
2
Intrinsically Safe for Current Inputs Units Only.

87
800-334-8422
Model T6000 Electro-Pneumatic I/P, E/P Transducer

Mounting Kits Catalog Information


Catalog Number T 6000

B
Electrical Connections
1/2 NPT Conduit . . . . . . . . . . . A
Fitting with Pigtail
DIN43650 Connection . . . . . . . D
Rack Mount . . . . . . . . . . . . . . . R
Terminal Block . . . . . . . . . . . . T
Model (leave blank for
T6000 Explosion-Proof) . . . . . . . .
Mounting Bracket: 16799-1
Underwriting Group
Canadian Standards . . . . . . . . . . . . C
ATEX . . . . . . . . . . . . . . . . . . . . . . . E
1

Factory Mutual . . . . . . . . . . . . . . . . F
Approval Class
Explosion-Proof. . . . . . . . . . . . . . . . . . . . . . XPD
Dust Ignition-Proof (includes NEMA
4X/IP 65)
Intrinsically Safe 2 . . . . . . . . . . . . . . . . . . . I
None (leave blank) . . . . . . . . . . . . . . . . . .
Mounting Bracket: 16893-1

Input
4-20 mA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
10-50 mA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1-5 VDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
0-5 VDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1-9 VDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
0-10 VDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Output (Select appropriate psig, [BAR], or (kPa) range.)
3-15 psig . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 01
Mounting Bracket: 19254-1 3-27 psig . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 02
6-30 psig . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 03
0-30 psig . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 04
0-60 psig . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 05
0-120 psig . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 06

[0.2-1.0 BAR] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
[0.2-1.8 BAR] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
[0.4-2.0 BAR] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
[0-2.0 BAR] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
[0-4.0 BAR] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
[0-8.0 BAR] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

(20-100 kPa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
(20-180 kPa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
(40-200 kPa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Mounting Bracket: 18187-1
(0-200 kPa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
(0-400 kPa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Model T6000 Transducer Kits (0-800 kPa) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
& Accessories Options
Mounting Bracket Kits . . . . 16799-1 (included with unit) BSPT Thread 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . U
1
ATEX not Available for Explosion-Proof.
16893-1 (included with unit)
19254-1 (sold separately)
18187-1 (sold separately) 2
Intrinsically Safe for Current Input Units Only.
3
Not Available for CSA Explosion-Proof Units.

88
800-334-8422