Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Socomec Itys Ups

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Single-phase

UPS ITYS
from 1 to 10 kVA
business IT & Industrial applications continuity solutions

High protection and high a


­ vailability Simple to install and easy to use Operating efficiency and versatility
• The ITYS series is a range of compact UPS • The UPS comes ready for power up with • The versatility of these models means that
systems available in the following models: the internal batteries connected and fully they can be used to protect a wide range of
1, 2, 3, 6 and 10 kVA with on-line double ­charged. The auto restart function assures applications: from professional IT systems,
conversion technology (VFI) and sinusoidal automatic restart even in the event of corporate networks and critical devices in
absorption. ­prolonged power failure. industrial contexts.
• ITYS guarantees permanent regulation • ITYS UPS systems are easy to install The standard configuration and the
• 
of output voltage and frequency. This requiring no special plant preparation
­ communications accessories can easily
technology is compatible with all IT as they have built-in magneto-thermal be adapted to a wide range of operating
and industrial ­ applications, operating protection. environments.
environments and when used in conjunction • The intuitive LED command / control panel • 
The manual bypass means that on site
with a generator set. and buzzer make the system easy to periodic and / or emergency maintenance
­­
• The wide tolerance of the input voltage use. The power distribution graphic display can be performed on the 6 and 10 kVA
limits the number of switchovers to battery shows at-a-glance if the system is working models ­without having to disconnect the
mode, thus significantly prolonging the correctly or not. Battery health can be loads. The communication software can
battery life. checked either via the control panel or be used to program scheduled start-up
• The automatic bypass takes over imme­ using a remote PC. and shutdown where automatic power
diately in the event of overloads or faults, management procedures are required.
ensuring continuous power supply to the
loads. Communication option
• Dry contacts interface for insertion in the
rear slot shows the status of the UPS via
5 ­potential-free contacts and provides an
input for remote emergency power off
(EP0).
• UNI VISION software for the control
and ­automatic shutdown of applications
connected to Windows™ and Linux.
Free download from our website: www.
socomec.com.
• UNI VISION PRO software for management
of connected applications and to control
automatic shutdowns. Serial cable
included.
• NET VISION Interface SNMP / WEB
­manager for connection of the UPS to the
Ethernet network. This accessory can be
integrated in the UPS by means of the slot
located on the back panel.

Your protection > Professional workstations


for > Server and corporate
GAMME_066_A

networks
> Storage systems
> Industrial automation
> Security systems
> Telecom systems

24
Single-phase
UPS ITYS
from 1 to 10 kVA

Connection Battery extension


(available with LB models only)
3
2

ITYS 015 A
1

3 2 3 2
13
13
ITYS UPS +1 EBM
1 1 8
7 3000 30 min. +1 (ITY-EX030B)
3 2 6000 50 min. +1 (ITY-EX0100B)

ITYS 011 A
1 1
12
10 10000 27 min. +1 (ITY-EX0100B)
1
5 (@ 75% of nominal load)
8 8 4
ITYS 010 A

4 9
8
ITYS 012 B

ITYS 013 B
6 5 4
5 6 6 11

ITYS 1 kVA ITYS 2 kVA ITYS 3 kVA ITYS 6 - 10 kVA

ITYS 016 A
1. Fan 8. Input protection (Thermal breaker)
2. Slot for optional communication boards 9. Output terminals
ITYS UPS +2 EBM
3. RS232 serial port (JBUS protocol) 10. Input / output terminals 3000 75 min. +2 (ITY-EX030B)
4. Telephone / modem / ASDL line protection 11. Wheels with security lock 6000 100 min. +2 (ITY-EX0100B)
5. Output sockets (IEC 320) 12. Selective protection fuse on output sockets 10000 58 min. +2 (ITY-EX0100B)
6. Input socket (IEC 320) 13. Connection
 for external battery cabinet (@ 75% of nominal load)

7. Manual by pass (LB models only)

The command / control panel

ITYS 017 A
Graphic operating status:
1. Battery indicator ITYS UPS +3 EBM
1 2. LED bar - % of connected load 3000 120 min. +3 (ITY-EX030B)
5 3. LED bar - % battery available 6000 150 min. +3 (ITY-EX0100B)
10000 90 min. +3 (ITY-EX0100B)
4. O n / off button and deactivation of the buzzer
2/3 6 (@ 75% of nominal load)
5. Overload indicator
6. Fault indicator
4
ITYS 014 A

Technical data

POWER VA / WATT 1000 VA / 700 W 2000 VA / 1400 W 3000 VA / 2100 W 6000 VA / 4200 W 10000 VA / 7000 W
ITEM CODE ITY-TW010B ITY-TW020B ITY-TW030B / LB ITY-TW060B / LB ITY-TW100B / LB
INPUT
Input voltage 230 V AC (160÷300 V AC ; up to 110 V AC at 60 % of the load) 230 V AC (176÷276 V AC)
Frequency 50 / 60 Hz nominal
Power factor 0.98
OUTPUT
Output voltage (Vout) 230 V AC (can be set to 220 / 240 V AC) ± 1.5 % 230 V AC (can be set to 220 / 240 V AC) ± 1 %
Output frequency stability (for 50 Hz) Syncro range 46÷54 Hz (50 ± 0.2 Hz in battery mode) Syncro range 46÷54 Hz (50 Hz ± 0.05 Hz in battery mode)
Overload (with mains present) Up to 150 % for 30 seconds Up to 130 % for 10 minutes
Global efficiency Up to 90 %
Acceptable crest factor 3:1
Communication port RS 232 on DB9 connector
BACK-UP TIME*
75 % of the nominal load (min.) 10 17 9 13 9
PHYSICAL
Noise level (at 1 m) 45 dB 55 dB
UPS dimensions W x D x H (mm) 145 x 400 x 220 192 x 460 x 350 260 x 570 x 715
Colour (Pantone scale) Case 430C ; plastic panel 431C
UPS net weights (kg) 14 34 35 / 16 84 / 35 93 / 38
COMPLIANCE WITH STANDARDS
Standards EN62040 and CE marking / IEC 60529 (IP20)
Safety / EMC standard (EN) IEC 62040-1-1 (safety) EN50091-2 / IEC62040-2 (EMC) - Equipped with input filters to eliminate atmospheric disturbance
* at 25 °C with efficient battery.

25
VALID FOR FRANCE VALID FOR ITALY
www.socomec.com
dcg_84073

Non contractual document.


ISO 9001 ISO14001 © 2011, Socomec SA. All rights reserved.
FM 28237 EMS 553476

You might also like