Liquisys M Oxigen
Liquisys M Oxigen
Liquisys M Oxigen
Liquisys M COM223/253
Transmitter for Dissolved Oxygen
BA199C/07/en/09.05
51500272
valid as of:
Software-version 2.40
Brief operating instructions
This explains how to use these Operating Instructions to commission your transmitter quickly and
safely:
Safety instructions
Page 5 ff. General safety instructions
Page 6 ff. Explanation of the warning symbols
You can find special instructions at the appropriate position in the chapter in question. The
positions are indicated with the icons Warning #, Caution " and Note !
▼
Installation
Page 10 ff. Here you can find information on installation conditions and the dimensions of the transmitter.
Page 12 ff. You can find information on how to install the transmitter on these pages.
▼
Wiring
Page 16 ff. Here you can find out how to connect sensors to the transmitter.
▼
Operation
Page 29 ff. The display and operating elements are described here.
Page 33 ff. The operating concept is explained here.
Page 40 ff. The system configuration is explained here.
Page 67 ff. You can find information on how to calibrate the sensor on these pages.
▼
Maintenance
Page 71 ff. Here you can find information on the maintenance of the entire measuring point.
Page 75 ff. The accessories which can be delivered for the transmitter are listed on the pages indicated.
Page 79 ff. Here you can find information on trouble-shooting.
Page 86 ff. Here you can find an overview of the spare parts which can be delivered as well as an overview
of the system.
▼
Technical data
Page 10 ff. Dimensions
Page 93 ff. Ambient and process conditions, weight, materials etc.
▼
Appendix
Page 98 ff. Here you can find the operating matrix
Endress+Hauser
Liquisys M COM223/253
Table of contents
1 Safety instructions . . . . . . . . . . . . . . . . 5 6 Commissioning . . . . . . . . . . . . . . . . . . 36
1.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 6.1 Function check . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
1.2 Installation, commissioning and operation . . . . . . . . 5 6.2 Switching on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
1.3 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . 5 6.3 Quick start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
1.4 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 6.4 System configuration . . . . . . . . . . . . . . . . . . . . . . . 40
1.5 Notes on safety icons and symbols . . . . . . . . . . . . . . 6 6.4.1 Setup 1 (Oxygen) . . . . . . . . . . . . . . . . . . . . 40
6.4.2 Setup 2 (Salinity and temperature) . . . . . . . 41
2 Identification . . . . . . . . . . . . . . . . . . . . 7 6.4.3 Current input . . . . . . . . . . . . . . . . . . . . . . 41
6.4.4 Current outputs . . . . . . . . . . . . . . . . . . . . . 44
2.1 Device designation . . . . . . . . . . . . . . . . . . . . . . . . . 7 6.4.5 Monitoring functions . . . . . . . . . . . . . . . . . 49
2.1.1 Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . 7 6.4.6 Relay contact configuration . . . . . . . . . . . . 53
2.1.2 Product structure . . . . . . . . . . . . . . . . . . . . 7 6.4.7 Service . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
2.1.3 Additional functions of the Plus Package . . . 8 6.4.8 E+H Service . . . . . . . . . . . . . . . . . . . . . . . 66
2.2 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 6.4.9 Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . 67
2.3 Certificates and approvals . . . . . . . . . . . . . . . . . . . . 8 6.5 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
6.6 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
3 Installation . . . . . . . . . . . . . . . . . . . . . . 9
3.1 Quick installation guide . . . . . . . . . . . . . . . . . . . . . . 9 7 Maintenance . . . . . . . . . . . . . . . . . . . . 71
3.1.1 Measuring system . . . . . . . . . . . . . . . . . . . . 9 7.1 Maintenance of the entire measuring point . . . . . . . 71
3.2 Incoming acceptance, transport, storage . . . . . . . . . 10 7.1.1 Cleaning the transmitter . . . . . . . . . . . . . . 71
3.3 Installation conditions . . . . . . . . . . . . . . . . . . . . . . 10 7.1.2 Test variant 1 (DX/DS with COS41) . . . . . 72
3.3.1 Field instrument . . . . . . . . . . . . . . . . . . . . 10 7.1.3 Test variant 2 (WX/WS with COS31 or
3.3.2 Panel-mounted instrument . . . . . . . . . . . . 11 COS71) . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
3.4 Installation instructions . . . . . . . . . . . . . . . . . . . . . 12 7.1.4 Maintenance oxygen sensors . . . . . . . . . . . 73
3.4.1 Field instrument . . . . . . . . . . . . . . . . . . . . 12 7.1.5 Maintenance assembly . . . . . . . . . . . . . . . . 73
3.4.2 Panel-mounted instrument . . . . . . . . . . . . 15 7.1.6 Connecting lines and junction boxes . . . . . 74
3.5 Post-installation check . . . . . . . . . . . . . . . . . . . . . . 15 7.2 "Optoscope" service tool . . . . . . . . . . . . . . . . . . . . 74
4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . 16 8 Accessories . . . . . . . . . . . . . . . . . . . . . 75
4.1 Electrical connection . . . . . . . . . . . . . . . . . . . . . . 16 8.1 Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
4.1.1 Electrical connection variant 1 8.2 Connection accessories . . . . . . . . . . . . . . . . . . . . . 75
(DX/DS with COS41) . . . . . . . . . . . . . . . . 17 8.3 Mounting accessories . . . . . . . . . . . . . . . . . . . . . . . 76
4.1.2 Measuring cable and sensor connection . . . 19 8.4 Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
4.1.3 Electrical connection variant 2 8.5 Software and hardware add-ons . . . . . . . . . . . . . . . 78
(WX/WS with COS31/71 or COS61) . . . . 21 8.6 Optoscope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
4.1.4 Measuring cable and sensor connection . . . 23
4.1.5 Electrical connection variant 2
(WX/WS with COS61) . . . . . . . . . . . . . . . 24
9 Trouble-shooting . . . . . . . . . . . . . . . . . 79
4.1.6 Measuring cable and sensor connection . . . 26 9.1 Trouble-shooting instructions . . . . . . . . . . . . . . . . . 79
4.1.7 Alarm contact . . . . . . . . . . . . . . . . . . . . . . 28 9.2 System error messages . . . . . . . . . . . . . . . . . . . . . . 79
4.2 Post-connection check . . . . . . . . . . . . . . . . . . . . . . 28 9.3 Process specific errors . . . . . . . . . . . . . . . . . . . . . . 81
9.4 Instrument specific errors . . . . . . . . . . . . . . . . . . . . 84
5 Operation . . . . . . . . . . . . . . . . . . . . . . 29 9.5 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
9.5.1 Dismantling the panel mounted instrument 86
5.1 Quick operation guide . . . . . . . . . . . . . . . . . . . . . . 29 9.5.2 Panel mounted instrument . . . . . . . . . . . . . 87
5.2 Display and operating elements . . . . . . . . . . . . . . . 29 9.5.3 Dismantling the field instrument . . . . . . . . 89
5.2.1 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 9.5.4 Field instrument . . . . . . . . . . . . . . . . . . . . 90
5.2.2 Operating elements . . . . . . . . . . . . . . . . . . 30 9.5.5 Replacing the central module . . . . . . . . . . . 92
5.2.3 Key assignment . . . . . . . . . . . . . . . . . . . . . 31 9.6 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
5.3 Local Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 9.7 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
5.3.1 Automatic/manual mode . . . . . . . . . . . . . 33
5.3.2 Operating concept . . . . . . . . . . . . . . . . . . . 34
Endress+Hauser 3
Liquisys M COM223/253
10 Technical data . . . . . . . . . . . . . . . . . . . 93
10.1 Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
10.2 Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
10.3 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
10.4 Performance characteristics . . . . . . . . . . . . . . . . . . 95
10.5 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
10.6 Mechanical construction . . . . . . . . . . . . . . . . . . . . 96
10.7 Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
11 Appendix. . . . . . . . . . . . . . . . . . . . . . . 98
Index . . . . . . . . . . . . . . . . . . . . . . . . . 110
4 Endress+Hauser
Liquisys M COM223/253 Safety instructions
1 Safety instructions
Endress+Hauser 5
Safety instructions Liquisys M COM223/253
1.4 Return
If the device requires repair, please send it cleaned to the sales centre responsible. Please use the
original packaging, if possible.
Safety icons
Warning!
# This symbol alerts you to hazards. They can cause serious damage to the instrument or to persons
if ignored.
Caution!
" This symbol alerts you to possible faults which could arise from incorrect operation. They could
cause damage to the instrument if ignored.
! Note!
This symbol indicates important items of information.
Electrical symbols
%
Direct Current (DC)
A terminal at which DC is applied or through which DC flows.
&
Alternating Current (AC)
A terminal at which (sine-form) AC is applied or through which AC flows.
Ground connecting
) A terminal, which, from the user’s point of view, is already grounded using a grounding system.
Alarm relay
b
Input
Output
DC voltage source
Temperature sensor
6 Endress+Hauser
Liquisys M COM223/253 Identification
2 Identification
2.1.1 Nameplate
Compare the order code on the nameplate (on the transmitter) with the product structure (s.b.) and
your order.
The device version can be identified from the order code.
! Note!
The release codes for retrofitting the software for Chemoclean (to the left of the forward slash) or
the Plus Package (to the right of the forward slash) are listed under "Codes".
131085-4D 131085-4D
C07-COM2x3xx-18-06-00-xx-001.eps C07-COM2x3xx-18-06-00-xx-002.eps
Version
DX Sensor COS41 / 4 / 4HD, basic functions
DS Sensor COS41 / 4 / 4HD, with additional functions (Plus package)
WX Sensor COS31 / 61 / 71 / 3 / 3HD, basic functions
WS Sensor COS31 / 61 / 71 / 3 / 3HD, with additional functions (Plus package)
Output
0 1 x 20 mA, dissolved oxygen
1 2 x 20 mA, dissolved oxygen and temperature/actuating variable
3 PROFIBUS PA
4 PROFIBUS DP
5 1 x 20 mA, dissolved oxygen with HART®
6 2 x 20 mA, dissolved oxygen with HART® and temperature/actuating variable
COM253-
complete order code
COM223-
Endress+Hauser 7
Identification Liquisys M COM223/253
Version Approval
COM253-..4...
COM223-..4... ATEX II 3G [EEx nAL] IIC
COM223-..6...
8 Endress+Hauser
Liquisys M COM223/253 Installation
3 Installation
3.1 Quick installation guide
# Warning!
If the measuring point or parts of the measuring point are in explosion-hazardous areas you have to
follow the "Safety instructions for electrical apparatus certified for use in explosion-hazardous
areas". These instructions (XA 194C/07/a3) are part of the scope of delivery.
Proceed as follows to completely install the measuring point:
• Install the transmitter (see "Installation instructions" section).
• If the sensor is not yet installed in the measuring point, install it (see Technical Information of the
sensor).
• Connect the sensor to the transmitter as illustrated in the "Electrical connection" section.
• Connect the transmitter as illustrated in the "Electrical connection" section.
• Commission the transmitter as explained in the "Commissioning" section.
3 5
REL 1
ALARM
REL 2
CAL REL
REL 1
E REL 2
7 6
REL 1
ALARM
REL 2
CAL REL
REL 1
E REL 2
C07-COM2x3xx-14-06-00-xx-002.eps
Endress+Hauser 9
Installation Liquisys M COM223/253
Pg 13.5
Pg 7
Pg 16
11/
0.43
M5
157 / 6.18
REL 1
ALARM
REL 2
CAL REL
REL 1
247 / 9.72
E
70 / 2.76
REL 2
Ø 0.24
Ø6/
154 / 6.06
170 / 6.69
mm / inch
C07-CxM253xx-06-06-00-en-001.EPS
! Note!
There is a hole in the punching for the cable entry (connection of supply voltage). It serves as a
pressure balance during air freight dispatching. Make sure no moisture penetrates the inside of the
housing before the cable installation. The housing is completely air-tight after the cable installation.
10 Endress+Hauser
Liquisys M COM223/253 Installation
1 4
C07-CxM253xx-11-06-00-xx-001.eps
6/
0.24
96 / 3.78
92 / 3.62
90 / 3.54
149.5 / 5.89
139 / 5.47
mm / inch
C07-CxM223xx-06-06-00-en-001.EPS
Endress+Hauser 11
Installation Liquisys M COM223/253
! Note!
When mounting in the open air with unprotected exposure to weather conditions, a weather
protection cover (see Accessories) is required.
Ø 0.24
Ø6/
154 / 6.06
mm / inch
C07-CxM253-11-06-00-en-002.eps
12 Endress+Hauser
Liquisys M COM223/253 Installation
! Note!
You require a post mounting kit to secure the field device to horizontal and vertical posts or pipes
(max. Ø 60 mm(2.36")). This can be acquired as an accessory (see "Accessories" section).
Ø max. 60 /
1
2.36
2
C07-CxM253xx-11-06-00-en-003.eps
Endress+Hauser 13
Installation Liquisys M COM223/253
You can also secure the field device to a square universal post in conjunction with the weather
protection cover. These can be acquired as accessories, see "Accessories" section.
3
2
1
3
C07-CxM253xx-11-06-00-xx-004.eps
Fig. 9: Mounting field device with universal posts and weather protection cover
14 Endress+Hauser
Liquisys M COM223/253 Installation
+0.5 +0.02
92 / 3.62
92+0.5 / 3.62+0.02
1
2
3.62
92 /
90 / 3.54
96 / 3.78
3
3
57 / 2.24
1.30
33 /
max. 45 /
approx. 25 / 139 / 5.47 1.77 6/
0.98 0.24
approx. 165 / 6.50*
C07-CxM223xx-11-06-00-en-001.eps
Endress+Hauser 15
Wiring Liquisys M COM223/253
4 Wiring
16 Endress+Hauser
Liquisys M COM223/253 Wiring
A S
11 41
BN
42
NTC G
RD 12 43
K 90 47
K
WH
O2 48
H
A 91 49
A
GN
57
31
mA 58
I
B 32 59
O2
51
33
mA 52
J
C 34 53
* 81 54
55
D 10-50 V K
82 56
* 93 23 +
24 -
10-50 V L
E 94
mA
~ =
85 L1 L+
15 V
F 86 N L–
M
C07-COM2x3xx-04-06-00-xx-001.eps
! Note!
The device is approved for protection class II and is generally operated without a protective ground
connection.
The circuits "C" and "F" are not galvanically isolated from each other.
Endress+Hauser 17
Wiring Liquisys M COM223/253
" Caution!
• Always protect plugs, terminals and cables against humidity.
• Terminals marked NC may not be wired.
• Unmarked terminals may not be wired.
54 55 56 51 52 53 57 58 59 47 48 49 41 42 43
GN RD Mains
Hilfsenergie
NC A 12 NC
NC
NC 31 32 33 34 NC 85 86 93 94 81 82 23 24 NC L1 N (AC)
+ - + - + - + - + - + - + - (DC)
4..20mA
Digital 2
Digital 1
NC K 11 S
WH BN
(opt.)
Temp.
10mA
+15V
O2
COM 253
131093-4F
C07-COM253xx-04-06-00-xx-002.eps
! Note!
Please label the sensor terminal block with the sticker provided.
18 Endress+Hauser
Liquisys M COM223/253 Wiring
131084-4C 131080-4C
Mains
L1 +
NC N -
C07-COM223xx-04-06-00-xx-001.eps
" Caution!
• Terminals marked NC may not be wired.
• Unmarked terminals may not be wired.
Endress+Hauser 19
Wiring Liquisys M COM223/253
Terminal Assignment
S
S Outer screen
RD 12 Active inner screen (NTC)
12
90 Cathode
WH
K 90 91 Anode
GN 11 NTC temperature sensor
A 91
BN 11
C07-COS41xxx-04-05-00-xx-001.eps
! Note!
For further information on cables and junction boxes refer to chapter "Accessories".
Example of connecting an oxygen sensor
Connection of the oxygen sensor COS41:
O2
S
Schirm / 11 12 90 91
Screen BN RD WH GN
K A
CYK71
C07-COM2x3xx-04-06-00-xx-002.eps
20 Endress+Hauser
Liquisys M COM223/253 Wiring
A B C
S
YE 1 YE 87 +
GY 2 GY 0 0 8,5 V DC
BN 5 BN 88 - 8,5 V DC
BU 4 BU 97 B 41
RS 485 42
I
PK 3 PK 96 A 43
WH 7 WH 18 47
O2 48
J
GN 6 GN 19 49
57
31
mA 58
D K
32 59
O2
51
33
mA 52
L
E 34 53
* 81 54
55
F 10-50 V M
82 56
* 93 23 +
24 -
G 10-50 V N
94
mA
~ =
85 L1 L+
15 V
H 86 N L–
O
C07-COM2x3xx-04-06-00-xx-003.eps
! Note!
The device is approved for protection class II and is generally operated without a protective ground
connection.
The circuits "E" and "H" are not galvanically isolated from each other.
The signals "Sensor signal" (18) and "Alarm" (19) are not used at the TOP68 version.
Endress+Hauser 21
Wiring Liquisys M COM223/253
WH BU GR YE 54 55 56 51 52 53 57 58 59 47 48 49 41 42 43
B Mains
Hilfsenergie
18 97 0 87
NC
NC 31 32 33 34 NC 85 86 93 94 81 82 23 24 NC L1 N (AC)
+ - + - + - + - + - + - + - (DC)
4..20mA
Digital 2
Digital 1
19 96 88 S
A
(opt.)
Temp.
10mA
+15V
O2
GN PK BN 97
analog:
96 133226-4C
C07-COM253xx-04-06-00-xx-003.eps
! Note!
Please label the sensor terminal block with the sticker provided.
Panel-mounted instrument connection
To connect a sensor to the panel mounted instrument you have to take off the sensor plug. Connect
the cable conductors directly to the terminals of the transmitter. If you need a pluggable connection
you can install a VS junction box between sensor and transmitter.
133228-4B
131084-4C Contacts: max. 2A, AC:250V/500VA, DC:30V/60W
49 Sensor
31 + 87 + YE
REL1 47 O2
32 - 0 GR
COM 48
33 + 88 - BN
59 Temp.
(opt.)
REL2 57 34 - 97 B BU
COM 58 NC 96 A PK
53 85 + 19 GN
+15V
10mA
REL3 51 86 - 18 WH
COM 52 93 + S
Digital 2
56 94 - 42
REL4 54 81 + 43
Digital 1
COM 55
82 - 41
- 24 AC DC
4..20mA NC
Mains
L1 +
+ 23
NC N -
C07-COM223xx-04-06-00-xx-002.eps
" Caution!
• Terminals marked NC may not be wired.
• Unmarked terminals may not be wired.
22 Endress+Hauser
Liquisys M COM223/253 Wiring
COS31/61/71 with fixed cable OMK with SXP VS junction box + OMK cable
connection plug
COS31/61/71 with TOP68 connection CYK71 with SXP VS junction box + OMK cable
plug
! Note!
For further information on cables and junction boxes refer to chapter "Accessories".
Example of connecting an oxygen sensor
Connection of the oxygen sensor COS31/61/71.
8,5 V DC
8,5 V DC
O2
RS 485
S _
+ 0
87 0 88 97 96 18 19
Schirm /
YE GY BN BU PK WH GN
Screen
OMK
C07-COM2x3xx-04-06-00-xx-005.eps
Fig. 20: Connection of COS31/71 with OMK cable
! Note!
The signals Sensor signal and Alarm are not used by COS61 and the TOP68 versions.
Endress+Hauser 23
Wiring Liquisys M COM223/253
A B C
S
YE 1 YE 85 15 V
86
H
GY
87 + 41
GY 2 GY 0 0 8,5 V DC 42
I
43
BN 5 BN 88 - 8,5 V DC
BU 4 BU 97 B 47
RS 485 48
J
PK 3 PK 96 A 49
WH 7 WH 18 57
O2
58
K
GN 6 GN 19 59
51
31
mA
52
D L
32
53
O2
33 54
mA mA
55
P E 34 M
mA 56
* 81 23 +
24 -
F 10-50 V N
82
mA
~ =
* 93 L1 L+
N L–
G 10-50 V O
94
C07-COM2x3xx-04-06-00-xx-006.eps
! Note!
The device is approved for protection class II and is generally operated without a protective ground
connection.
The circuits "E" and "H" are not galvanically isolated from each other.
The signals "Sensor signal" (18) and "Alarm" (19) are not used at the TOP68 version.
24 Endress+Hauser
Liquisys M COM223/253 Wiring
Sensor COS61 uses the auxiliary voltage 15 V. This eliminates the galvanic isolation to the "signal
output 2".
To connect both signal outputs to a process control system, the inputs of the process control system
must be galvanically isolated. If the inputs are not galvanically isolated, you can connect "signal
output 2" via an isolation converter (0/4 - 20 mA / 0/4 - 20 mA) to the input of the process control
system.
Field instrument connection
Plug the sensor plug into the SXB socket. Additionally, you have to modify the terminal wiring:
• Remove the yellow wire (from SXB socket pin 1) from terminal 87 and connect it to terminal 85.
• Terminal 87 will not be connected.
• Connect an additional wire from terminal 86 to terminal 0.
Introduce all other cables through the cable glands and connect them according to the connection
diagram.
WH BU GR YE 54 55 56 51 52 53 57 58 59 47 48 49 41 42 43
B Mains
Hilfsenergie
18 97 0 87
NC
NC 31 32 33 34 NC 85 86 93 94 81 82 23 24 NC L1 N (AC)
+ - + - + - + - + - + - + - (DC)
4..20mA
Digital 2
Digital 1
19 96 88 S
A
(opt.)
Temp.
10mA
+15V
O2
GN PK BN 97
analog:
96 133226-4C
C07-COM253xx-04-06-00-xx-003.eps
! Note!
Please label the sensor terminal block with the sticker provided.
Endress+Hauser 25
Wiring Liquisys M COM223/253
To connect a sensor to the panel-mounted instrument, you have to take off the sensor plug. Connect
the cable wires directly to the terminals of the transmitter. If you need a pluggable connection, you
can install a VS junction box between sensor and transmitter.
COS31/61/71 with fixed cable OMK with SXP VS junction box + OMK cable
connection plug
COS31/61/71 with TOP68 connection CYK71 with SXP VS junction box + OMK cable
plug
OMK CYK
1 yellow +UB +UB yellow
2 grey 0V 0V white
3 pink RS 485 (NTC) RS 485 (NTC) green
4 blue RS 485 (NTC) RS 485 (NTC) brown
5 brown -UB -UB coax inner
6 green Alarm NC
7 white Sensor signal NC
C07-COS41xxx-04-05-00-xx-001.eps
! Note!
For further information on cables and junction boxes refer to chapter "Accessories".
26 Endress+Hauser
Liquisys M COM223/253 Wiring
8,5 V DC
8,5 V DC
O2
RS 485
S _
+ 0
87 0 88 97 96 18 19
Schirm /
YE GY BN BU PK WH GN
Screen
OMK
C07-COM2x3xx-04-06-00-xx-005.eps
! Note!
The signals Sensor signal (18) and Alarm (19) are not used by COS61 and the TOP68 versions.
Panel-mounted instrument connection
Connect the sensor according to the connection diagram.
Field instrument connection
Plug the sensor plug into the SXB socket. Additionally, you have to modify the terminal wiring:
• Remove the yellow wire (from SXB socket pin 1) from terminal 87 and connect it to terminal 85.
• Terminal 87 will not be connected.
• Connect an additional wire from terminal 86 to terminal 0.
Endress+Hauser 27
Wiring Liquisys M COM223/253
A B
41 41
42 42
43 43
C07-CxM2x3xx-04-06-00-xx-001.eps
Are the transmitter and cables damaged on the outside? Visual inspection
Are the signal lines correctly connected in accordance with the wiring
diagram?
28 Endress+Hauser
Liquisys M COM223/253 Operation
5 Operation
! Note!
For operation via HART or PROFIBUS PA/DP, please read the relevant sections in the additional
Operating Instructions:
• PROFIBUS PA/DP, field communication for Liquisys M CXM223/253, BA 209C/07/en
• HART®, field communication for Liquisys M CXM223/253, BA 208C/07/en
The following section only explains operation via the keys.
5.2.1 Display
LED display
REL 1
Indicates the activated relay in the "Manual" mode (red LED)
REL 2
Endress+Hauser 29
Operation Liquisys M COM223/253
LC display
1 2 3 4 5
6
mg/l
12
11
185 R232 7
Setpoint
8
10
9
C07-COM2x3xx-07-06-00-en-001.eps
1 7
mg/l
1.85 R232
Setpoint
2 6
3 5
4
C07-COM2x3xx-19-06-00-en-001.eps
30 Endress+Hauser
Liquisys M COM223/253 Operation
CAL key
When you press the CAL key, the device first prompts you for the
calibration access code:
• Code 22 for calibration
• Code 0 or any other code for reading the last calibration data
Use the CAL key to accept the calibration data or to switch from field to
field within the calibration menu.
ENTER key
When you press the ENTER key, the device first prompts you for the setup
mode access code:
• Code 22 for setup and configuration
• Code 0 or any other code for reading all configuration data.
The ENTER key has several functions:
• Calls up the Setup menu from the measuring mode.
• Saves (confirms) data entered in the setup mode.
• Moves on within function groups.
PLUS key and MINUS key
In the setup mode, the PLUS and MINUS keys have the following
functions:
• Selection of function groups.
! Note!
Press the MINUS key to select the function groups in the order given in
the "System configuration" section.
• Configuration of parameters and numerical values
• Operation of the relay in manual mode
In the measuring mode, you get the following sequence of functions by
repeatedly pressing the PLUS key:
1. Temperature display in F
2. Temperature display hidden
3. Measured value display in mg/l
4. Measured value display in %SAT
5. Measured value display in hPa
6. Sensor current in nA/mA
7. Current input signal in %
8. Current input signal in mA
9. Return to basic settings
In the measuring mode, the following is displayed in sequence by
repeatedly pressing the MINUS key:
1. Current errors are displayed in rotation (max. 10).
2. Once all the errors have been displayed, the standard measurement
display appears. In the function group F, an alarm can be defined
separately for each error code.
Endress+Hauser 31
Operation Liquisys M COM223/253
REL key
In the manual mode, you can use the REL key to switch between the relay
and the manual start of cleaning.
REL 1 In the automatic mode, you can use the REL key to read out the switch-on
points (for limit contactor) or set points (for PID controller) assigned to the
REL 2
relay in question.
Press the PLUS key to jump to the settings of the next relay. Use the REL
key to get back to the display mode (automatic return after 30 s).
AUTO key
You can use the AUTO key to switch between automatic mode and manual
mode.
Escape function
If you press the PLUS and MINUS key simultaneously, you return to the
main menu or are taken to the end of calibration if calibrating. If you press
the PLUS and MINUS key again, you return to the measuring mode.
32 Endress+Hauser
Liquisys M COM223/253 Operation
1. The transmitter is in Automatic mode. The top LED beside the AUTO
key is lit.
2. Press the AUTO key. The bottom LED beside the AUTO key lights up.
3. To enable the manual mode, enter the code 22 via the PLUS and
MINUS keys.
5. Switch the relay. It is switched on with PLUS and switched off with
MINUS.
The relay remains in its switched state until it is switched over again.
6. Press the AUTO key to return to the measuring mode, i.e. to the
automatic mode. All the relays are triggered again by the transmitter.
! Note!
• The operating mode remains in effect even after a power failure.
• The manual mode has priority over all other automatic functions (Hold).
• Hardware locking is not possible in the manual mode.
• The manual settings are kept until they are actively reset.
• Error code E102 is signalled in the manual mode.
Endress+Hauser 33
Operation Liquisys M COM223/253
Operating modes
Measuring mode:
standard mode of
operation, displaying
current measured values
Code
! Note!
If no key is pressed in the setup mode for approx. 15 min, the device automatically returns to the
measuring mode. Any active Hold (Hold during setup) is reset.
Access codes
All device access codes are fixed and cannot be altered. When the device requests the access code,
it distinguishes between different codes.
• Key CAL + Code 22: access to Calibration and Offset menu
• Key ENTER + Code 22: access to the menus for the parameters which make configuration and
user-specific settings possible
• Keys PLUS + ENTER: locks the keyboard
• Keys CAL + MINUS: unlocks the keyboard
• Key CAL or ENTER + any code: access to read mode, i.e. all the settings can be read but not
modified.
The device continues measuring in the read mode. It does not shift to the Hold status. The current
output and the controllers remain active.
34 Endress+Hauser
Liquisys M COM223/253 Operation
Menu structure
The configuration and calibration functions are arranged in function groups.
• In the setup mode, select a function group with the PLUS and MINUS keys.
• In the function group itself, switch from function to function with the ENTER key.
• Within the function, select the desired option with the PLUS and MINUS keys or edit the settings
with these keys. Then confirm with the ENTER key and continue.
• Press the PLUS and MINUS keys simultaneously (Escape function) to exit programming (return
to the main menu).
• Press the PLUS and MINUS simultaneously keys again to switch to the measuring mode.
! Note!
• If a modified setting is not confirmed with ENTER, the old setting is retained.
• An overview of the menu structure is provided in the Appendix to these Operating Instructions.
1
-
3
E E E E
C07-CxM2x3xx-19-06-00-xx-002.eps
! Note!
• Hold settings can be found in the "Service" section.
• During Hold, all contacts will go to their normal positions.
• An active Hold has priority over all other functions.
• With every Hold, the I-component of the controller is set to zero.
• Any alarm delay is reset to "0".
• This function can also be activated externally via the Hold input (see Wiring diagram; binary
input 1).
• The manual Hold (field S3) remains active even after a power failure.
Endress+Hauser 35
Commissioning Liquisys M COM223/253
6 Commissioning
6.2 Switching on
Familiarise yourself with the operation of the transmitter before it is first switched on. Please refer
in particular to the "Safety instructions" and "Operation" sections.
After power-up, the device performs a self-test and then goes to the measuring mode.
Now calibrate the sensor in accordance with the instructions in the "Calibration" section.
! Note!
During commissioning, the sensor must be calibrated so that the measuring system can return
precise measurement data.
Then perform the first configuration in accordance with the instructions in the "Quick start-up"
section. The values set by the user are kept even in the event of a power failure.
The following function groups are available in the transmitter (the groups only available in the Plus
Package are marked accordingly in the functional description):
Setup mode
• SETUP 1 (A)
• SETUP 2 (B)
• CURRENT INPUT (Z)
• CURRENT OUTPUT (O)
• ALARM (F)
• CHECK (P)
• RELAY (R)
• SERVICE (S)
• E+H SERVICE (E)
• INTERFACE (I)
Calibration and offset mode
• CALIBRATION (C)
! Note!
A detailed explanation of the function groups available in the transmitter can be found in the
"System configuration" section.
Function display:
The displayed code indicates
s the function position in the
2 F3 function group.
C07-CLD132xx-07-06-00-en-003.eps
36 Endress+Hauser
Liquisys M COM223/253 Commissioning
Factory settings
The first time it is switched on, the device has the factory setting for all functions. The table below
provides an overview of the most important settings.
All other factory settings can be found in the description of the individual function groups in the
"System configuration" section (the factory setting is highlighted in bold).
Language English
Endress+Hauser 37
Commissioning Liquisys M COM223/253
Language
NEL = Dutch
ESP = Spanish
mg/l
10. In A2, select display unit and press F to confirm. ppm mg/l A2
ppb
Unit
38 Endress+Hauser
Liquisys M COM223/253 Commissioning
%
17. In B1, select salinity of the medium.
Press F to confirm.
0.0 %
0.0 ... 4.0 %
0.0 B1
Salinity
°C
18. In B2, enter correct process temperature.
Press F to confirm.
current meas. value
-10 ... 60 °C
0.0 B2
RealTemp
Endress+Hauser 39
Commissioning Liquisys M COM223/253
Function group
A A Basic settings.
SETUP 1
SETUP 1
mg/l = oxygen concentration
%SAT = oxygen saturation index
hPa = oxygen partial pressure
mg/l
A1 Select operating mode %SAT mg/l A1 "Any change
Caution!
in operating mode causes an
hPa
Unit automatic reset of user settings.
If the oxygen value only needs to be read
switch display using the PLUS key.
mg/l
A2 Select display unit ppm mg/l A2
ppb
Unit
m
A4 Enter altitude
0m
0 ... 4000m
0 A4 Only available if the pressure compensation in
A2 is switched off or not available.
Altitude
Measured value damping causes averaging
over the specified number of individual
A5
Enter measured value
damping
1
1 ... 60
1 A5 measured values. It is used, for example, to
stabilise the display with applications that
Damping fluctuate a great deal.
There is no damping if “1” is entered.
40 Endress+Hauser
Liquisys M COM223/253 Commissioning
Function group
B B Setups for salinity and temperature.
SETUP 2
SETUP 2
%
B1 Enter salinity
0,0 %
0,0 ... 4,0 %
0.0 B1 Input of salinity.
Salinity
current meas. value °C The display value can be edited. You can make
B2
Enter correct process
temperature
-10,0 ... 60,0 °C 0.0 B2 an adjustment of max. ±5 °C. Due to the high
accuracy, adjustment is not usually necessary.
RealTemp
°C
B3
Displays temperature
difference (offset)
Current offset
-5,0 ... 5,0 °C
0.0 B3 The offset is the difference between measured
and entered temperature.
Temp.Offs
Endress+Hauser 41
Commissioning Liquisys M COM223/253
1
A
1
B
Z2 Z3
0
C
0
E
D F
C07-CPM2x3xx-05-06-00-xx-001.eps
Fig. 32: Alarm signalling and dosing switch-off by the main stream
A Flow in main stream F Flow restoration
B Relay contacts of PID controller Z2 Delay for controller switch-off, see field Z2
C Alarm relay Z3 Delay for controller switch-on, see field Z3
D Flow below switch-off limit Z 4 or flow failure 0 Off
E Flow alarm 1 On
1 2 3 4
7
ENDRESS+HAUSER
LIQUISYS M
8 0.42
mg/l
25.0 °C
REL 1
ALARM
REL 2
CAL REL
REL 1
E REL 2
6 5
4 ... 20 mA
C07-COM2x3xx-05-06-00-xx-001.eps
Fig. 33: Arrangement example for feedforward control of the flow rate in the main stream to the PID controller
1 Measuring water extraction point 5 Reducing agent
2 Static mixer 6 Oxidising agent
3 Injection points 7 Liquisys M COM253
4 Flowmeter 8 COA250 with COS31
42 Endress+Hauser
Liquisys M COM223/253 Commissioning
Feedforward control is a multiplying function as illustrated in the figure below (example with factory
setting):
1,5
0,5
0 20 40 Z7 60 80 100 X
C07-CPM2x3xx-05-06-00-de-003.eps
CURRENT INPUT Z
Z Current input settings.
function group
CUR.INPUT
Endress+Hauser 43
Commissioning Liquisys M COM223/253
Enter value for When the value is set, the controller actuating
%
Z7
feedforward control at 50%
which gain = 1 0 ... 100%
50 Z7 variable is the same size when feedforward
control is switched on as when feedforward
applies Kinflu=1 control is switched off.
O2
[mg/l]
10
5
D Signal
0 4 8 12 16 20
D[mA] [mA]
C07-COM2x3-05-06-00-xx-002.eps
44 Endress+Hauser
Liquisys M COM223/253 Commissioning
The current output characteristic must be strictly monotonously increasing or strictly monotonously
decreasing.
The distance per mA between two table value pairs must be greater than:
Temperature -10 ... 60 °C (14 ... 140 °F) 0.45 °C (0.81 °F)
The values for the sample characteristic (Fig. 35) are entered in the following table. The distance
per mA can be calculated from ∆ signal / ∆ mA.
1 0 4
2 2.5 14 0.25
3 10 20 1.25
First enter the desired current output configuration into the following blank table with a pencil.
Calculate the resulting signal distance per mA to observe the necessary minimum slope. Then enter
the values in the device.
Endress+Hauser 45
Commissioning Liquisys M COM223/253
Sel.Range
46 Endress+Hauser
Liquisys M COM223/253 Commissioning
– Version DX/DS or
WX/WS with COS61:
0.00 mg/l*
0.00 ... 20.00 mg/l
0.0 %SAT
0.0 ...200.0 %SAT
0 hPa
0 ... 400 hPa
– WX/WS with COS31: Here you can enter the O2 or temperature
0.00 mg/l* value at which the min. current value
0/4 mA value: 0.00 ... 60.00 mg/l (0/4 mA) is applied at the transmitter
mg/l
0.00 O312
Enter corresponding 0.0 %SAT output.
O312 0.0 ... 600.0 %SAT
O2 or temperature Minimum distance between 0/4 mA and
0 hPa
value
0 ... 1200 hPa 0/4 mA 20 mA value: see field O313
– Version DX/DS or
WX/WS with COS61:
10.00 mg/l*
0.00 ... 20.00 mg/l
100.0 %SAT Here you can enter the O2 or temperature
0.0 ...200.0 %SAT value at which the max. current value
200 hPa (20 mA) is applied at the transmitter output.
0 ... 400 hPa Minimum distance between 0/4 mA and
– WX/WS with COS31: 20 mA value must be:
10.00 mg/l* Oxygen:
20 mA value: 0.00 ... 60.00 mg/l – DX/DS or WX/WS with COS61:
mg/l
10.00 O313
Enter corresponding 100.0 %SAT 0.2 mg/l / 2 %SAT / 4 hPa
O313 0.0 ... 600.0 %SAT
O2 or temperature – WX/WS with COS31:
200 hPa
value
0 ... 1200 hPa 20 mA 0.6 mg/l / 6 %SAT / 12 hPa
– WX/WS with COS71:
– WX/WS with COS71: 0.02 mg/l / 0.2 %SAT / 0.4 hPa
10.000 mg/l*
0.000 ... 20.000 mg/l Temperature:
All versions: 7 °C
100.0 %SAT
0.0 ... 200.0 %SAT
200 hPa * Display depends on setting in A2
0 ... 400 hPa
40.0 °C
-10.0 ... 60.0 °C
mA
O321 Enter simulation value
Current value
0.00 ... 22.00 mA
4.00 O321 Entering a current value results in this value
being directly output at the current output.
Simulat.
Endress+Hauser 47
Commissioning Liquisys M COM223/253
– Version DX/DS or
WX/WS with COS61:
0.00 mg/l*
0.00 ... 20.00 mg/l
0.0 %SAT
0.0 ...200.0 %SAT
0 hPa
0 ... 400 hPa
– WX/WS with COS31:
0.00 mg/l*
0.00 ... 60.00 mg/l
mg/l x value = measured value specified by user.
0.00 O334
00.0 %SAT
O334 Enter x value 0.0 ... 600.0 %SAT
0 hPa * Display depends on setting in A2
0 ... 1200 hPa Meas.val.
– WX/WS with COS71:
0.000 mg/l*
0.000 ... 20.000 mg/l
0.0 %SAT
0.0 ... 200.0 %SAT
0 hPa
0 ... 400 hPa
0.0 °C
-10.0 ... 60.0 °C
Back to O3.
Message as to
O336 whether table status is
yes
no
yes O336 If status = no, correct table (all settings made
up until now are retained) or back to
OK
Status ok measuring mode (table is deleted).
48 Endress+Hauser
Liquisys M COM223/253 Commissioning
ALARM function
F F Alarm function settings.
group
ALARM
Cont.Type
s
F3 Enter alarm delay
0 s (min)
0 ... 2000 s (min)
0 F3 Depending on the option selected in F2, the
alarm delay is entered in s or min.
Err.Delay
This selection must be made even if all error
reporting is switched off in F5.
F4 Select error current
22 mA
2.4 mA
22mA F4
" Caution!
If "0-20 mA" was selected in O311, "2.4 mA"
Err.Curr may not be used.
Endress+Hauser 49
Commissioning Liquisys M COM223/253
F8
Automatic cleaning
function start
no
yes
no F8 This field is not available for certain errors, see
"Trouble-shooting and fault elimination"
CleanTrig
section.
F9
Select return to menu
or next error
next = next error
←R
next F9 If ←R is selected, you return to F, if next is
selected, you go to F5.
Select
Check
The CHECK function group is only available for devices with a Plus Package.
In the CHECK function group, you can select different monitoring functions for the measurement.
All the monitoring functions are off in the factory setting. The Sensor Check System adapts to the
current application conditions by adding and setting suitable functions.
Controller monitoring
For oxygen measurement with simultaneous entry control, sensor errors not only lead to incorrect
measured values but also have a direct impact on the state of the process medium. Particularly in
the case of oxygenation control in sewage treatment works, the risk exists due to the control loop
that the ventilation does not switch on if the measured value is constantly too high. A too low
oxygen supply creates a considerable risk for the microbes and their cleaning performance. On the
other hand, a measured value which is permanently too low due to the uninterrupted operation of
the ventilation units leads to increased operating costs. Such cases are recognised and signalled
using freely settable monitoring times for the maximum permitted controller switch-on and
switch-off periods.
50 Endress+Hauser
Liquisys M COM223/253 Commissioning
off —
The function group "Check" is used to monitor the lower und upper limits of the measured value
and to initiate alarms.
Basic version does not include functions in italic.
CHECK function
P P Settings for sensor and process monitoring
group
CHECK
Off
Low
Alarm signalling optionally with or without
High
P1
Select alarm threshold
monitoring
Lo+Hi off P1 simultaneous controller switch-off.
XXXX = without controller switch-off
Low!
A.Thresh
XXXX! = with controller switch-off
High!
Lo+Hi!
Endress+Hauser 51
Commissioning Liquisys M COM223/253
– Version DX/DS or
WX/WS with COS61:
0.00 mg/l*
0.00 ... 19.00 mg/l
0.0 %SAT
0.0 ...190.0 %SAT
0 hPa
0 ... 380 hPa
– WX/WS with COS31:
0.00 mg/l*
mg/l
P3
Enter lower alarm
threshold
0.00 ... 59.00 mg/l
0.0 %SAT
0.00 P3 * Display depends on setting in A2
0.0 ... 590.0 %SAT
0 hPa LowAlarm
0 ... 1180 hPa
– WX/WS with COS71:
0.000 mg/l*
0.000 ... 19.000 mg/l
0.0 %SAT
0.0 ... 190.0 %SAT
0 hPa
0 ... 380 hPa
– Version DX/DS or
WX/WS with COS61:
20.00 mg/l*
1.00 ... 20.00 mg/l
200.0 %SAT
0.0 ...200.0 %SAT
400 hPa
20 ... 400 hPa
– WX/WS with COS31:
20.00 mg/l*
mg/l
P4
Enter upper alarm
threshold
1.00 ... 60.00 mg/l
200.0 %SAT
20.00 P4 * Display depends on setting in A2
10.0 ... 600.0 %SAT
400 hPa HighAlarm
20 ... 1200 hPa
– WX/WS with COS71:
20.000 mg/l*
0.010 ... 20.000 mg/l
200.0 %SAT
0.5... 200.0 %SAT
400 hPa
20... 400 hPa
Off
AC = sensor activity check
AC
CC = controller check
Select process CC mg/l
P5 monitoring AC+CC off P5 AC checking limits:.
±0.1 mg/l or ±1 %SAT or ±2 hPa in 1 h
(PCS alarm) AC!
CC! ProcMonit XXXX = without controller switch-off
XXXX! = with controller switch-off
AC+CC!
Enter maximum
permissible duration min
P6 for lower CC setpoint
480 min
0 ... 2000 min
480 P6 Only when P6 = CC or AC+CC
limit violation
(field P8) Tmax Low
Enter maximum
permissible duration min
P7 for upper CC setpoint
240 min
0 ... 2000 min
240 P7 Only when P6 = CC or AC+CC
limit violation (field
P8) Tmax High
52 Endress+Hauser
Liquisys M COM223/253 Commissioning
– Version DX/DS or
WX/WS with COS61:
5.00 mg/l*
0.00 ... 20.00 mg/l
50.0 %SAT
0.0 ...200.0 %SAT
200 hPa
0 ... 400 hPa
– WX/WS with COS31:
Setpoint for external controller (process
5.00 mg/l*
mg/l control system) must match with setpoint in
P8
Enter CC setpoint (for
P6/P7)
0.00 ... 60.00 mg/l
50.0 %SAT
5.00 P8 P8.
0.0 ... 600.0 %SAT
200 hPa Setpoint * Display depends on setting in A2
0 ... 1200 hPa
– WX/WS with COS71:
1.000 mg/l*
0.000 ... 20.000 mg/l
10.0 %SAT
0.0 ... 200.0 %SAT
20 hPa
0 ... 400 hPa
Endress+Hauser 53
Commissioning Liquisys M COM223/253
5
6
1
4
2
A 3
7
t1 t2 t3 t4 t5 t6 t7 t
7
3
2
B 4
6
1 5
t1 t2 t3 t4 t5 t6 t7 t
C07-CxM2x3xx-05-06-00-xx-003.eps
P(ID) controller
You can define various controller functions for the transmitter. On the basis of the PID controller,
P, PI, PD and PID controllers can be implemented. For an optimum control system, use the
controller that best suits your application. Depending on the option selected in the R 237 field, the
actuating signal can be output via relays or via current output 2 (if available).
• P controller
Used for simple linear control purposes with small system deviations. Where major changes are
to be controlled, overshooting may occur. In addition, a lasting control deviation is to be expected.
• PI controller
Is used for control systems where overshooting is to be avoided and no lasting control deviation
should occur.
• PD controller
Is used for processes that require quick changes and where peaks are to be corrected.
• PID controller
Is used for processes where a P, PI or PD controller does not control sufficiently.
Configuration options of the PID controller
The following configuration options are available for a PID controller:
• Change control gain Kp (P influence)
• Set integral action time Tn (I influence)
• Set derivative action time Tv (D influence)
Basic load dosing (Basic)
The basic load dosing (field R231) is used to set a constant dosage (field R2311)
54 Endress+Hauser
Liquisys M COM223/253 Commissioning
A
100 %
100 % C
C07-CxM2x3xx-05-06-00-xx-010.eps
Fig. 37: Control characteristic PID controller with basic load dosing
A PID with basic load
B Basic load
C PID
Commissioning
If you do not yet have any experience for setting the control parameters, set the values that yield
the greatest possible stability in the control circuit. Proceed as follows to optimise the control circuit
further:
• Increase the control gain Kp until the controlled variable just starts to overshoot.
• Reduce Kp slightly and then reduce the integral action time Tn so that the shortest possible
correction time without overshooting is achieved.
• To reduce the response time of the controller, also set the derivative action time Tv.
Control and fine optimisation of the set parameters with a recorder
A A
1 2
B B
A A
3 4
B B
B
C07-CxM2x3xx-05-06-00-xx-004.eps
Endress+Hauser 55
Commissioning Liquisys M COM223/253
A t1 A
t2 t1
1 1
0 0
t [s] t [s]
T T1 T2
C07-CLM2x3xx-05-06-00-xx-005.eps
Fig. 39: Signal of a pulse-length modulated controller contact (left) and of a pulse-frequency modulated controller
contact (right)
A Contact 1 = on, 0 = off T Period length
B Time [s] t1 = ton t2 = toff T1 T2 Impulse period length (impulse freq. 1/T1 and 1/T2)
Constant controller
Via the current output 2, the minimum actuating variable (0 %) of the controller is output with
0/4 mA and the maximum actuating variable (100%) of the controller is output with 20 mA.
Control characteristic for direct and inverse control action
You can choose between two control characteristics in the R236 field:
• Direct control action = maximum function
• Inverse control action = minimum function
Y
100 %
– XW XW
Y
100 %
– XW XW
C07-CxM2x3xx-05-06-00-xx-006.eps
Fig. 40: Control characteristic of a proportional controller with direct and inverse control action
A Direct = max. function
B Inverse = min. function
56 Endress+Hauser
Liquisys M COM223/253 Commissioning
! Note!
Timer and Chemoclean do not work independently of one another. While one of the two functions
is active, the other cannot be started.
A
t1 t2
1
0
t
B t3
1
0
t
C07-CLM2x3xx-05-06-xx-007.eps
Fig. 41: Connection between cleaning time, pause time and Hold dwell period
A Wiper and/or spray cleaning system t1 Cleaning time (0 ... 999 s)
B Hold function t2 Pause time between two cleaning intervals
0 Inactive (1 ... 7200 min)
1 Active t3 Clean Hold dwell period (0 ... 999 s)
Chemoclean function
Just like the timer function, Chemoclean can also be used to start a cleaning cycle. However,
Chemoclean also gives you the added option of defining different cleaning and rinsing intervals.
As a result, it is possible to clean irregularly with different repeat cycles and to separately set the
cleaning times with post rinse times.
! Note!
• To use the Chemoclean function the transmitter has to be equipped with a designated relay board
(see product structure or chapter "accessories").
• Timer and Chemoclean do not work independently of one another. While one of the two
functions is active, the other cannot be started.
• For the Chemoclean function, the relays 3 (water) and 4 (cleaner) are used.
• If the cleaning is prematurely aborted, a post rinse time always follows.
• If the setting is "Economy", cleaning only takes place with water.
Endress+Hauser 57
Commissioning Liquisys M COM223/253
1
A 0
1
B 0
1
0
C
t0 t1 t2 t3 t4 t5
C07-CxM2x3xx-05-06-00-xx-008.eps
RELAY function
R Relay contact settings.
R group
RELAIS
R211
Switch function of R2
(1) off or on
Off
On
off R211 All the settings are retained.
Function
58 Endress+Hauser
Liquisys M COM223/253 Commissioning
– Version DX/DS or
WX/WS with COS61:
20.00 mg/l*
0.00 ... 20.00 mg/l
200.0 %SAT
0.0 ...200.0 %SAT
400 hPa
0 ... 400 hPa
– WX/WS with COS31: Never set the switch-on point and the
20.00 mg/l* switch-off point to the same value!
mg/l
R212
Enter the switch-on
point of the contact
0.00 ... 60.00 mg/l
200.0 %SAT
20.00 R212
(Only the operating mode selected in A1 is
displayed.)
0.0 ... 600.0 %SAT
400 hPa
On value * Display depends on setting in A2
0 ... 1200 hPa
– WX/WS with COS71:
20.000 mg/l*
0.000 ... 20.000 mg/l
200.0 %SAT
0.0 ... 200.0 %SAT
400 hPa
0 ... 400 hPa
– Version DX/DS or
WX/WS with COS61:
20.00 mg/l*
0.00 ... 20.00 mg/l
200.0 %SAT
0.0 ...200.0 %SAT
Entering a switch-off point selects either a
400 hPa
Max contact (switch-off point < switch-on
0 ... 400 hPa
point) or a Min contact (switch-off point >
– WX/WS with COS31:
switch-on point), thereby implementing a
20.00 mg/l*
mg/l hysteresis that is constantly required (see
R213
Enter the switch-off
point of the contact
0.00 ... 60.00 mg/l
200.0 %SAT
20.00 R213 "Illustration of the alarm and limit functions"
figure).
0.0 ... 600.0 %SAT
400 hPa
Off value (Only the operating mode selected in A1 is
displayed.)
0 ... 1200 hPa
– WX/WS with COS71:
* Display depends on setting in A2
20.000 mg/l*
0.000 ... 20.000 mg/l
200.0 %SAT
0.0 ... 200.0 %SAT
400 hPa
0 ... 400 hPa
s
R214 Enter pick-up delay
0s
0 ... 2000 s
0 R214
On Delay
s
R215 Enter drop-out delay
0s
0 ... 2000 s
0 R215
Off Delay
Endress+Hauser 59
Commissioning Liquisys M COM223/253
– Version DX/DS or
WX/WS with COS61:
20.00 mg/l*
0.00 ... 20.00 mg/l
200.0 %SAT
0.0 ...200.0 %SAT
400 hPa If the alarm threshold is undershot/overshot,
0 ... 400 hPa this triggers an alarm with the error message
– WX/WS with COS31: and error current at the transmitter (note
20.00 mg/l* alarm delay in field F3).
mg/l
R216 Enter alarm threshold
0.00 ... 60.00 mg/l
200.0 %SAT
20.00 R216
If defined as a Min contact, the alarm
threshold must be < switch-off point.
0.0 ... 600.0 %SAT
400 hPa
A.Thresh (Only the operating mode selected in A1 is
displayed.)
0 ... 1200 hPa
– WX/WS with COS71: * Display depends on setting in A2
20.000 mg/l*
0.000 ... 20.000 mg/l
200.0 %SAT
0.0 ... 200.0 %SAT
400 hPa
0 ... 400 hPa
R217
Display status for limit
contactor
MAX
MIN
MAX R217 Display only.
LC State
LC PV = limit contactor O2 (1)
Configure limit LC °C = limit contactor T By confirming with ENTER, another relay
R2 (2)
contactor for
temperature
(2)
PID controller (3)
LC °C R2 function already switched on is switched off
and its settings are reset to the factory
measurement Timer (4)
Clean = Chemoclean (5)
Sel.Type settings.
R221
Switch function of R2
(2) off or on
Off
On
off R221
Settings made for the limit contactor are not
deleted by switching the function off.
Function
0 R224
0s s
R224 Enter pick-up delay
0 ... 2000 s
On Delay
60 Endress+Hauser
Liquisys M COM223/253 Commissioning
0 R225
0s s
R225 Enter drop-out delay
0 ... 2000 s
Off Delay
If the alarm threshold is undershot/overshot,
this triggers an alarm with the error message
60.0 C (140 °F)
60.0 R226
Enter alarm threshold ¡C and error current at the transmitter (note
R226 -10.0 ... 60.0 C
(as absolute value) alarm delay in field F3).
(14 ... 140 °F)
If defined as a Min contact, the alarm
A.Thresh threshold must be < switch-off point.
R227
Display status for limit
contactor
MAX
MIN
MAX R227 Display only.
LC State
Off
On = PID controller
R231
Switch function of R2
(3) off or on
On
Basic
off R231 Basic = basic load dosing
PID+B = PID controller + basic load dosing
Function
PID+B
– Version DX/DS or
WX/WS with COS61:
5.00 mg/l*
0.00 ... 20.00 mg/l
50.0 %SAT
0.0 ...200.0 %SAT
200 hPa
0 ... 400 hPa The set point is the value to be maintained by
– WX/WS with COS31: the control system. Using this control process,
5.00 mg/l* this value is restored upwards or downwards
5.00 R232
0.00 ... 60.00 mg/l mg/l when a deviation occurs.
R232 Enter set point
50.0 %SAT (Only the operating mode selected in A1 is
0.0 ... 600.0 %SAT displayed.)
200 hPa Setpoint
0 ... 1200 hPa * Display depends on setting in A2
– WX/WS with COS71:
5.000 mg/l*
0.000 ... 20.000 mg/l
50.0 %SAT
0.0 ... 200.0 %SAT
200 hPa
0 ... 400 hPa
Kp
Endress+Hauser 61
Commissioning Liquisys M COM223/253
Time Tv
D-component)
PulsePer.
and entries continue with R239.
s
R2310
Enter minimum
switch-on time tON
0.3 s
0.1 ... 5.0 s
0.3 R2310 This field only appears if pulse length is
selected in R237.
Min.PTime
When you select the basic load, you enter the
desired dosing quantity.
%
R2311 Enter basic load
0%
0 ... 40 %
0 R2311 100% basic load would correspond to:
– Constantly on for R237 = len
BasicLoad – Fmax at R237 = freq (field R239)
– 20 mA at R237 = curr
R241
Switch function of R2
(4) off or on
Off
On
off R241
Settings made for the timer are not deleted by
switching the function off.
Function
62 Endress+Hauser
Liquisys M COM223/253 Commissioning
s
R242
Enter rinsing/cleaning 30 s
time 0 ... 999 s
30 R242 Settings for Hold and relay are active for this
time.
RinseTime
min
R244
Enter minimum pause
time
120 min
1 ... R243 min
120 R244 The minimum pause time prevents constant
cleaning if a cleaning trigger is present.
Min.Pause
Configure cleaning LC PV = limit contactor O2 (1)
with Chemoclean (for LC °C = limit contactor T (2) See "Chemoclean function" section.
version with four By confirming with ENTER, another relay
Clean R2
PID controller (3)
R2 (5) contacts , Timer (4) function already switched on is switched off
Chemoclean option Clean = Chemoclean (5) and its settings are reset to the factory
and contacts 3 and 4 Sel.Type settings.
assigned)
R251
Switch function of R2
(5) off or on
Off
On
off R251 Settings made for the timer are not deleted by
switching the function off.
Function
Int = internal
The cycle for the "int" function is started by
(time-controlled)
the end of the pause time (R257).
R252
Select type of start
pulse
Ext = external (digital input 2)
I+ext = internal + external
int R252 No real time clock is available.
External suppression is required for irregular
CleanTrig
I+stp = internal, suppressed
time intervals (e.g. weekends).
by external
s
R253 Enter pre-rinse time
20 s
0 ... 999 s
20 R253 Rinsing with water takes place.
PreRinse
s
R254 Enter cleaning time
10 s
0 ... 999 s
10 R254 Cleaning with cleaning agent and water takes
place.
CleanTime
s
R255 Enter post rinse time
20 s
0 ... 999 s
20 R255 Rinsing with water takes place.
PostRinse
Endress+Hauser 63
Commissioning Liquisys M COM223/253
R256
Enter number of
repeat cycles
0
0 ... 5
0 R256 R253 ... R255 is repeated.
Rep.Rate
min
R257 Enter pause time
360 min
1 ... 7200 min
360 R257 The pause time is the time between two
cleaning cycles (see "Timer function" section).
PauseTime
Enter number of
After cleaning with cleaner, up to 9 cleaning
cleaning cycles
R259 without cleaning
0
0 ... 9
0 R259 sessions can be carried out with water only
until the next cleaning session with cleaner
agent (economy
function) EconomyCl takes place.
6.4.7 Service
SERVICE function
S Service function settings.
S group
SERVICE
ENG = English
GER = German
S1 Select language
FRA = French
ITA = Italian
ENG S1
Language
NL = Dutch
ESP = Spanish
S3 Manual Hold
Off
On
off S3
The setting is retained even in the event of a
power failure.
Man. HOLD
s
S4
Enter Hold dwell
period
10 s
0 ... 999 s
10 S4
Cont.Time
64 Endress+Hauser
Liquisys M COM223/253 Commissioning
S7
Order number is
displayed
COM253-W order S7
If the device is upgraded, the order code is not
automatically adjusted.
PR0005
S8
Serial number is
displayed
4A135705G00 SerNo S8
12345678
Reset the device to the
Sens = last calibration is deleted and is reset to
basic settings No
S9 Sens = sensor data no S9
factory setting.
Facty = all data (apart from A1 a. S1) are
Facty = factory settings
deleted and reset to the factory setting!
S.Default
Test
Endress+Hauser 65
Commissioning Liquisys M COM223/253
E+H SERVICE
E E Information on the device version
function group
E+H SERV
E111
E121 If E1 = contr: instrument software
E131
Software version is
displayed
xx.xx E111 If E1 = trans, main, rel: module firmware
E141 If E1 = sens: sensor software
E151 SW-Vers.
E112
E122
E132
Hardware version is
displayed
xx.xx E112 Only display function
E142
E152 HW-Vers.
E113
E123
E133
Serial number is
displayed
SerNo E113 Only display function
E143
E153 12345678
E114
E124
E134
Module ID is
displayed
LSG E114 Only display function
E144
E154 Modul-ID
66 Endress+Hauser
Liquisys M COM223/253 Commissioning
6.4.9 Interfaces
I2
Display of measuring
point
Tag I2
@@@@@@@@
6.5 Communication
For devices with a communication interface, please also refer to the separate Operating Instructions
BA208C/07/en (HART®) or BA209C/07/en (PROFIBUS®).
6.6 Calibration
To access the "Calibration" function group, press the CAL key.
This function group is used to calibrate and adjust the measuring point. The sensor is calibrated in
air or in the medium.
! Note!
• At first start-up, sensor calibration of amperometric sensors is absolutely required in order for the
measuring system to be able to generate accurate measuring values.
• The optical oxygen sensor COS61 does not need a calibration at first start-up.
• If the calibration procedure is aborted by pressing the PLUS and MINUS keys at the same time
(return to C113 or C124) or if the calibration is faulty, then the previous calibration data are
reinstated. A calibration error is indicated by the “ERR” message and flashing of the sensor symbol
on the display.
Repeat calibration!
• The instrument is automatically switched to hold during calibration (factory setting).
• After calibration, the system jumps back to the measuring mode. During the hold dwell period
the hold symbol is displayed.
The slope calibration of the oxygen sensor COS61 will be performed in air or in air saturated water.
The calibration of the zero point will be performed in nitrogen or in oxygen-free water (water
enriched with zero solution). The sensor identifies unassisted the slope calibration (75 ... 140 %SAT)
and the calibration of the zero point (0 ... 10 %SAT). No further selection is necessary. These limits
are valid for the three types of calibration "air", "water" and "ref".
Endress+Hauser 67
Commissioning Liquisys M COM223/253
Function group
C Calibration oxygen C Calibration settings.
CALIBRATION
CALIBRAT
Air (1)
C1 (1) Calibration in air H2O (2) Air C1 Calibration in air is only possible if air
temperature is ≥-5 °C (≥23 °F).
Ref (3)
Cal.Mode
C112
Calibration status is
displayed
o.k.
E xxx
o.k. C112 If the calibration status is not o.k., see
chapter "System error messages".
Status
68 Endress+Hauser
Liquisys M COM223/253 Commissioning
Air (1)
C1 (2)
Calibration in
air-saturated water
H2O (2) H2O C1
Ref (3)
Cal.Mode
C122
Calibration status is
displayed
o. k.
Exxx
o.k. C122 If the calibration status is not o.k., see
chapter "System error messages".
Status
Endress+Hauser 69
Commissioning Liquisys M COM223/253
mg/l
C131 Enter calibration value Current value 10.00 C131 Minimum value is 0.2 mg/l
Real PV
%
C132 Slope is displayed
100.0 %
75.0 ... 140 %
100.0 C132
Slope
C133
Calibration status is
displayed
o.k.
Exxx
o.k. C133 If the calibration status is not o.k., see
chapter "System error messages".
Status
70 Endress+Hauser
Liquisys M COM223/253 Maintenance
7 Maintenance
Take all the necessary measures in time to guarantee the operational safety and reliability of the
entire measuring system.
Maintenance work at the transmitter comprises:
• Calibration (see "Calibration" section)
• Cleaning of assembly and sensor
• Cable and connection check
# Warning!
• When carrying out all work on the device, please observe any possible effects on the process
control or the process itself.
• When removing the sensor during maintenance or calibration, please consider potential hazards
due to pressure, high temperatures and contamination.
• Make sure the device is de-energised before you open it.
If work must be carried out when the device is live, this may only be performed by an electrical
technician!
• Switching contacts can be fed by separate circuits. These circuits must also be de-energised before
work on the terminals is performed.
Caution ESD!
• Electronic components are sensitive to electrostatic discharge. Personal protective measures such
as discharging at the PE beforehand or permanent grounding with a wrist strap are required.
• For your own safety, use only genuine spare parts. With genuine spare parts, the function,
accuracy and reliability are also guaranteed after repair.
! Note!
If you have any queries, please contact your local Sales Office.
" Caution!
For cleaning purposes, never use:
• Concentrated mineral acids or alkalis
• Benzyl alcohol
• Methylene chloride
• High-pressure steam
Endress+Hauser 71
Maintenance Liquisys M COM223/253
∞ (open) 0 mg O2/l
With 1.9 MΩ and a temperature equivalent resistance of 9.0 ... 9.2 mg O2/l
37.3 kΩ after calibration
Test procedure
1. Connect the O2 equivalent resistance (e. g. decade resistor) to terminals 90 and 91.
2. Connect the temperature equivalent resistance (e. g. decade resistor) to terminals 11 and 12.
3. Air pressure measurement:
The air pressure measured can be checked in field S11 (absolute air pressure). There is no air
pressure compensation for the DX version. Use the location altitude setting to compensate for
the air pressure influence.
72 Endress+Hauser
Liquisys M COM223/253 Maintenance
COS31 BA285/07/en
COS41 BA284/07/en
COS61 BA387/07/en
COS71 BA286/07/en
Endress+Hauser 73
Maintenance Liquisys M COM223/253
! Note!
If the function test explained in the previous chapter is performed on a junction box instead of the
instrument, the junction box, terminals and connnecting line to the instrument are automatically
included in the test.
COS31, COS61 and COS71 sensors work with a digital interface and therefore are not sensitive to
electrical faults and shunting by humidity. Nevertheless, follow the recommendations mentioned
above.
74 Endress+Hauser
Liquisys M COM223/253 Accessories
8 Accessories
8.1 Sensors
• Oxymax W COS31
oxygen sensor for drinking water and wastewater measurements, SS 1.4571 , potentiostatic
amperometric principle
ordering acc. to product structure, see Technical Information (TI285/07/en)
• Oxymax W COS41
oxygen sensor for drinking water and wastewater measurements, POM, amperometric principle
ordering acc. to product structure, see Technical Information (TI284/07/en)
• Oxymax W COS61
optical oxygen sensor for drinking water and wastewater measurements, SS 1.4571, fluorescence
quenching principle
ordering acc. to product structure, see Technical Information (TI387/07/en)
• Oxymax W COS71
oxygen sensor for trace measurement, SS 1.4571, potentiostatic amperometric principle
ordering acc. to product structure, see Technical Information (TI286/07/en)
Endress+Hauser 75
Accessories Liquisys M COM223/253
270 / 10.63
320 / 12.60
300 / 11.81
mm / inch
C07-CYY101xx-00-06-00-en-001.eps
60 x 60 /
2.36 x 2.36
120 /
4.72
mm/inch
C07-CYY102xx-00-06-00-en-002.eps
76 Endress+Hauser
Liquisys M COM223/253 Accessories
• Kit for mounting of field housing on horizontal or vertical pipes (Ø max. 60 mm (2.36"))
order no. 50086842
90 / 3.54
Ø max. 60 / 2.36
70 / 2.76
1.18
30 /
Ø8/
0.31
M6
70 / 2.76
90 / 3.54
60 / 2.36
Ø8/
Ø 6 / 0.24 0.31
70 / 2.76
90 / 3.54
mm / inch
C07-CxM2x3xx-00-06-00-en-001.eps
8.4 Assemblies
• Flow assembly COA250
for sensor installation in pipe lines, PVC;
ordering acc. to product structure (Technical Information TI111C/07/en)
• Flow assembly COA260
for plate or wall mounting, for oxygen trace measurements;
ordering acc. to product structure (Technical Information TI310C/07/en)
• Retractable assembly Cleanfit COA451
manually driven retractable assembly, stainless steel, with ball valve, for oxygen sensors;
ordering acc. to product structure (Technical Information TI368C/07/en)
• Immersion assembly COA110
for sensor immersion in the basin, PVC pipe resp. PUR floating body with SS 1.4571 (AISI 316Ti)
immersion tube;
Ordering acc. to product structure (see Technical Information TI035C/07/en)
• Immersion assembly Dipfit W CYA611
for sensor immersion in basins, open channels and tanks, PVC;
Ordering acc. to product structure (Technical Information TI166C/07/en)
• Immersion assembly CYY105
for sensor immersion in basins, SS 1.4404 (AISI 316L) pipe, SS 1.4571 (AISI 316Ti) fitting;
Ordering acc. to product structure (Technical Information TI092C/07/en)
• Basin rim holder CYY106
for sensor immersion in basins, SS 1.4301 (AISI 304);
Order no. CYY106-A
• Immersion assembly holder CYH101
for pH, ORP, oxygen, conductivity assemblies and for oxygen and turbidity sensors;
Ordering acc. to product structure (Technical Information TI092C/07/en)
Endress+Hauser 77
Accessories Liquisys M COM223/253
8.6 Optoscope
• Optoscope
Interface between transmitter and PC / laptop for service purposes.
The Windows software "Scopeware" required for the PC or laptop is supplied with the Optoscope.
The Optoscope is supplied in a sturdy plastic case with all the accessories required.
Order no. 51500650
78 Endress+Hauser
Liquisys M COM223/253 Trouble-shooting
9 Trouble-shooting
Error Display Tests and/or remedial measures Alarm contact Error current Autom. cleaning
no. start
E001 EEPROM memory error 1. Switch device off and then on again. Yes No — —1
2. Load device software compatible with the
hardware (with optoscope, see "Optoscope
Instrument not calibrated, calibration service tool" section).
data invalid, no user data, user data
3. Load measurement-parameter specific device
E002 invalid (EEPROM error), instrument Yes No — —1
software.
software not suitable to hardware
(controller) 4. If the error persists, send in the device for repair
to your local service organisation or replace the
device.
E008 Sensor or sensor connection faulty Check sensor and sensor connection (Service). Yes No — —
E020 Signal range of sensor undershot Check medium and sensor. Yes No — —
E022 Signal range of sensor exceeded Check medium and sensor. Yes No — —
E044 During calibration sensor unstable Check sensor and recalibrate. Yes No No
E059 Below temperature measuring range Check measurement, control and connections. Yes No No
Endress+Hauser 79
Trouble-shooting Liquisys M COM223/253
Error Display Tests and/or remedial measures Alarm contact Error current Autom. cleaning
no. start
E065 Below current output range 2 Check measured value and current assignment. Yes No No
E171 Flow in main stream too low or zero Restore flow. Yes No No
Switch-off limit for current input Check process variables at sending measuring
E172 Yes No No
exceeded instrument. Change range assignment if necessary.
1) If this error occurs, there is no possibility of starting a cleaning session (field F8 not applicable with this error).
80 Endress+Hauser
Liquisys M COM223/253 Trouble-shooting
Error Possible cause Tests and / or remedial measures Equipment, spare parts, personnel
Sensor defective – Test with new sensor. Sensor type acc. to instrument version.
– Instrument test with sensor diagram. Sensor simulation see chapter "Maintenance
– Sensor current test. of the entire measuring point".
Value indicated 0.0
Sensor extension line interrupted Check junction boxes and line. Sensor simulation see chapter "Maintenance
of the entire measuring point".
Instrument input defective Replace modul MKO1 (DX/DS). See spare parts list.
Replace modul MKO5 (WX/WS).
Membrane soiled Clean sensor membrane. See instructions for COSxx. Heavily soiled
media: use spray cleaning.
Incorrect air pressure measurement Check pressure value in field S11. Only with version WX/WS/DS.
sea level: approx. 1013 hPa. Caution: display value = absolute
Value indicated too small / 500 m above sea level: approx. 950 hPa. atmospheric pressure.
sensor can probably not be Electrolyte used up or soiled Replace electrolyte. See instructions for COSxx.
calibrated
Flow rate too low Check installation conditions, move sensor
to area with optimal flow conditions.
Polarisation incomplete After sensor commissioning (also after Polarisation is complete when the measured
interruption to operation) wait for value is stable, max. approx. 60 minutes.
polarisation time.
Incorrect air pressure measurement Check pressure value in field S11. Only with version WX/WS/DS.
sea level: approx. 1013 hPa. Caution: display value = absolute
500 m above sea level: approx. 950 hPa. atmospheric pressure.
Air cushion under membrane Install new membrane cap. For procedures and spare parts ordering see
Value indicated too high /
instructions for COSxx.
sensor can probably not be
calibrated Anode coating worn off (silver Sensor regeneration at factory. Normal anode colour is brownish.
coloured)
"S" membrane on standard sensor Install correct membrane cap. "S" membrane cap recognisable by white
colour (COS31). With COS31
self-recognition of S version.
Simulation with sensor Incorrect sensor voltage Required sensor voltage 6.5 ... 8.5 VDC. See chapter "Function, simulation and test
incorrect with COS31 and COS71".
Fixed incorrect measured Impermissible instrument operating Switch instrument off and back on. EMC problem: check line routing. If problem
value state (no response to key actuation) persists, check for possible sources of
interference.
Endress+Hauser 81
Trouble-shooting Liquisys M COM223/253
Error Possible cause Tests and / or remedial measures Equipment, spare parts, personnel
Incorrect sensor connection Verify connections using connection Connection diagram in chapter "Electrical
diagram. connection".
Measuring cable defective Check cable for interruption/short circuit/ Ohmmeter or on-site simulation.
Incorrect temperature value shunt.
Temp. probe in sensor defective Measure resistance value in sensor (red and Ohmmeter / values see chapter "Simulation
brown sensor lines) only possible with temperature sensor".
COS41.
Faults on measuring cable Connect cable screening according to See chapter "Wiring".
circuit diagram.
Faults on signal output line Check line routing, possibly route line Separate signal output, measuring input and
separately. power supply lines.
Measured value variations
Irregular flow/turbulences/large air Select a better installation site or calm Measured value damping see field A5.
bubbles turbulences.
Possibly use large measured value damping
factor.
Controller or timer cannot No relay module available Install module LSR1-2 or LSR1-4.
be activated
Controller in "Manual/On" mode Set controller to "Manual/Off" or "Auto". Keyboard, REL and AUTO keys.
Controller/limit contact Dropout delay setting too long Shorten dropout delay. See field R2xx.
works continuously
Control loop interruption Check measured value, current output,
actuators, chemical supply.
Line open or short-circuited Disconnect line and measure directly on mA meter 0–20 mA.
No O2 current output signal instrument.
Current output table not Value interval too small Select practical intervals.
accepted
Instrument does not have 2nd current Refer to nameplate for variant; change Module LSCH-x2,
No temperature output output LSCH-x1 module if necessary. see chapter "Spare parts".
signal
Instrument with PROFIBUS PA PA instrument has no current output!
Plus package functions not Plus package not enabled (enable with – When upgrading instrument with Plus For a detailed description, see chapter
available code that depends on serial number and package: code received from E+H ⇒ "Replacement of central module".
is received from E+H with order of enter.
extension package) – After replacing defective LSCH/LSCP
module: first enter instrument serial
number (s. nameplate) manually, then
enter code.
82 Endress+Hauser
Liquisys M COM223/253 Trouble-shooting
Error Possible cause Tests and / or remedial measures Equipment, spare parts, personnel
Line interferences
Several devices set to same address Set addresses correctly. Communication not possible with several
devices set to same address.
No or incorrect DD/DLL
Incorrect baud rate setting for segment For further information, see
coupler in DPV-1 server BA 209C/07/en "PROFIBUS PA/DP - Field
No PROFIBUS®
Incorrect station (master) addressed or communication with Liquisys M
communication
duplicate address CxM223/253".
Line problems
(too long, cross section too small; not
shielded, screen not grounded, wires
not twisted)
Endress+Hauser 83
Trouble-shooting Liquisys M COM223/253
Error Possible cause Tests and/or remedial measures Execution, tools, spare parts
No line voltage Check whether line voltage is present. Electrical technician/e.g. multimeter
User
Compare actual line voltage and nameplate
Supply voltage wrong/too low (data for energy supply company or
data.
multimeter)
Device or module in device not COM223: reinstall module. Perform with the aid of the installation
correctly mounted COM253: reinstall display module. drawings in the "Spare parts" section.
Display is on but
Poss. EMC problem: if this persists, check
– No change in display Operating system in unpermitted mode Switch device off and then on again.
the installation.
and/or
– Device cannot be Replace LSCxx module.
operated Only in emergency, with alcohol and glass
Conductive rubber soiled Clean conductive rubber and printed
fibre brush
– Missing pixels in display conductor.
Contact pressure too low Lay paper strips in frame. Only in emergency, better: replace LSCxx.
Voltage wrong/too high Compare line voltage and nameplate data. User, electrical technician
Device gets hot
Power unit defective Replace power unit. Diagnosis only by Endress+Hauser Service
84 Endress+Hauser
Liquisys M COM223/253 Trouble-shooting
Error Possible cause Tests and/or remedial measures Execution, tools, spare parts
No function of additional COM253: ribbon cable item 320 loose Check ribbon cable seating, renew cable if
See "Spare parts" section.
relay or defective required.
Additional functions (Plus Replacement modules LSCH or LSCP In the case of LSCH/LSCP with SNR 0000,
package and/or have the device serial number 0000 a device serial number can be entered
For a detailed description, see "Replacing
Chemoclean) missing after when they leave the factory. The Plus once in fields E114 to E116.
central module" section.
LSCH/LSCP module package or Chemoclean are not enabled Then enter the release code for the Plus
replaced on leaving the factory. package and/or Chemoclean.
Bus problem Remove some devices and repeat the test. Contact Endress+Hauser Service.
No sensor data in E151 ... For COS3 and compatible sensors, no data
Analog sensor connected
E159 exchange possible
Endress+Hauser 85
Trouble-shooting Liquisys M COM223/253
" Caution!
Please note the effects on the process if the device is taken out of service!
! Note!
Please refer to the following diagram for the item numbers.
1. Disconnect the terminal block (item 424 b) from the rear of the device to de-energise the
device.
2. Then remove the terminal blocks (item 424 a and poss. 430) from the rear of the device. Now
you can disassemble the device.
3. Press in the latches of the end frame (item 340) and remove the frame from the rear.
4. Release the special screw (item 400) by turning it counter-clockwise.
5. Remove the entire electronics block from the housing. The modules are only mechanically
connected and can be easily separated:
– Simply remove the processor/display module from the front.
– Pull out the brackets of the rear plate (item 320) slightly.
– Now you can remove the side modules.
6. Remove the O2 transmitter (item 250/260) as follows:
– Using fine side-cutting pliers, nip off the heads of the synthetic distance holders.
– Then remove the module from above.
Assembly is the reverse of the disassembly sequence. Tighten the special screw hand-tight without
a tool.
86 Endress+Hauser
Liquisys M COM223/253 Trouble-shooting
424a
424b
340
400
250/260
10/20
40-90
C
320
330
310
430
290/300
10
30
30
A
230 V
B 115 V
100 V
C07-COM223xx-09-06-00-xx-001.eps
Endress+Hauser 87
Trouble-shooting Liquisys M COM223/253
310, 320, Housing mechanical parts Rear plate, side panel, end frame, 51501076
340, 400 special screw
424a, 424b Terminal strip set Complete terminal strip set, 51501204
Standard + HART / DX + DS standard + HART
424a, 424b Terminal strip set Complete terminal strip set, 51502127
PROFIBUS PA / DX + DS PROFIBUS PA
424a, 424b Terminal strip set Complete terminal strip set, 51502492
PROFIBUS DP / DX + DS PROFIBUS DP
88 Endress+Hauser
Liquisys M COM223/253 Trouble-shooting
" Caution!
Please note the effects on the process if the device is taken out of service!
! Note!
Please refer to the following diagram for the item numbers.
To dismantle the field instrument you need the following tools:
• Standard set of screwdrivers
• Torx-screwdriver size TX 20
Proceed as follows:
1. Open and remove the cover of the connection compartment (item 420).
2. Disconnect the mains terminal (item 470) to de-energise the device.
3. Open the display cover (item 410) and loosen the ribbon cables (item 310/320) on the side of
the central module (item 40 ... 90).
4. To remove the central module (item 40), loosen the screw in the display cover (item 450 b).
5. Proceed as follows to remove the electronics box (item 330):
– Release the screws in the housing base (item 450 a) with two revolutions.
– Then push the entire box backwards and remove it from above.
– Make sure that module locks do not open!
– Loosen the ribbon cables (item 310/320).
– Bend the module locks out and remove the modules.
6. To remove the docking module (item 340), remove the screws in the housing base
(item 450 c) and remove the entire module from above.
7. Proceed as follows to remove the O2 transmitter (item 250/260):
– Using fine side-cutting pliers, nip off the heads of the synthetic distance sleeves.
– Then remove the module from above.
To assemble, carefully push the modules into the trolley tracks of the electronics box and let them
engage in the side box noses.
! Note!
• Incorrect mounting is not possible. Modules inserted in the electronics box incorrectly are not
operable since the ribbon cables cannot be connected.
• Make sure the cover seals are intact to guarantee IP 65 ingress protection.
Endress+Hauser 89
Trouble-shooting Liquisys M COM223/253
A
B
10
30
C
410
230 V
370
D 115 V
460b 100 V
40-90
450b
330
450a
310/320
400
460a
250/260
430
420
10/20
290/300
490
340
450c
480
470
C07-COM253xx-09-06-00-xx-001.eps
90 Endress+Hauser
Liquisys M COM223/253 Trouble-shooting
The exploded drawing contains the components and spare parts of the field device. You can take
the spare parts and the corresponding order number from the following section using the item
numbers.
Endress+Hauser 91
Trouble-shooting Liquisys M COM223/253
! Note!
Generally, when a central module has been replaced, all data which can be changed are set to the
factory setting.
Proceed as described below if a central module is replaced:
1. If possible, note the customised settings of the device, such as:
– Calibration data
– Current assignment, main parameter and temperature
– Relay function selections
– Limit value/controller settings
– Cleaning settings
– Monitoring functions
– Interface parameters
2. Disassemble the device as explained in the "Dismantling the panel-mounted instrument" or
"Dismantling the field instrument" section.
3. Use the part number on the central module to check whether the new module has the same
part number as the previous module.
4. Assemble the device with the new module.
5. Start up the device again and check the basic functions (e.g. measured value and temperature
display, operation via keyboard).
6. Enter the serial number:
– Read the serial number (“ser-no.”) off the nameplate of the device.
– Enter this number in the fields E115 (year, one-digit), E116 (month, one-digit), E117 (cons.
number, four-digit).
– In the field E118, the complete number is displayed again so you can check it is correct.
" Caution!
You can only enter the serial number for modules fresh from the factory with the serial
number 0000. This can only be done once! For this reason, make sure the number entered
is correct before you confirm with ENTER!
Entry of an incorrect code will prevent the additional functions from being enabled. An
incorrect serial number can only be corrected at the factory!
Press ENTER to confirm the serial number or cancel the entry to enter the number again.
7. If available, enter the release codes for the Plus Package and/or Chemoclean in the "Service"
menu.
8. Check the Plus Package release (e.g. by opening the function group CHECK / Code P) or the
Chemoclean function.
9. Make the customer device settings again.
9.6 Return
If the transmitter has to be repaired, please return it cleaned to the sales centre responsible.
Please use the original packaging, if possible.
9.7 Disposal
The device contains electronic components and must therefore be disposed of in accordance with
regulations on the disposal of electronic waste.
Please observe local regulations.
92 Endress+Hauser
Liquisys M COM223/253 Technical data
10 Technical data
10.1 Input
COS31:
– Oxygen concentration 0 ... 20 / 0 ... 60 mg/l
– Oxygen saturation index 0 ... 200 / 0 ... 600 % SAT
– Oxygen partial pressure 0 ... 400 / 0 ... 1200 hPa
COS41/61:
– Oxygen concentration 0 ... 20 mg/l
– Oxygen saturation index 0 ... 200 % SAT
– Oxygen partial pressure 0 ... 400 hPa
COS71:
– Oxygen concentration 0 ... 20 mg/l
– Oxygen saturation index 0 ... 200 % SAT
– Oxygen partial pressure 0 ... 400 hPa
10.2 Output
COS31:
– Oxygen concentration ∆ 0.2 ... ∆ 20 / ∆ 0.6 ... ∆ 60 mg/l
– Oxygen saturation index ∆ 2 ... ∆ 200 / ∆ 6 ... ∆ 600 % SAT
– Oxygen partial pressure ∆ 4 .... ∆ 400 / ∆ 12 ... ∆ 1200 hPa
COS41/61:
– Oxygen concentration ∆ 0.2 ... ∆ 20 mg/l
– Oxygen saturation index ∆ 2 ... ∆ 200 % SAT
– Oxygen partial pressure ∆ 4 .... ∆ 400 hPa
COS71:
– Oxygen concentration ∆ 0.02 ... ∆ 20 mg/l
– Oxygen saturation index ∆ 0.2 ... ∆ 200 % SAT
– Oxygen partial pressure ∆ 0.4 ... ∆ 400 hPa
Temperature: ∆ 7 ... ∆ 70 °C
Endress+Hauser 93
Technical data Liquisys M COM223/253
94 Endress+Hauser
Liquisys M COM223/253 Technical data
Temperature: 0.1 °C
1
Maximum measured error Display
– Oxygen: max. 0.5 % of measuring range
– Temperature: max. 1.0 % of measuring range
Signal output
– Oxygen: max. 0.75 % of measuring range
– Temperature: max. 1.25 % of measuring range
Slope adjustment range COS31: 75 ... 140 % (nominal 290 nA, in air, 20 °C (68 °F),
1013 hPa)
10.5 Environment
Ambient temperature range -10 ... +55 C (+14 ... +131 °F)
Ambient temperature limits –20 ... +60 C (-4 ... +140 °F)
Electromagnetic compatibility Interference emission and interference immunity as per EN 61326: 1997 / A1:
1998
Overvoltage protection As per EN For outputs, binary inputs and current input
61000-4-5:1995
Field device: IP 65
Endress+Hauser 95
Technical data Liquisys M COM223/253
10.7 Documentation
96 Endress+Hauser
Liquisys M COM223/253 Technical data
Endress+Hauser 97
Appendix Liquisys M COM223/253
11 Appendix
Operating matrix COM223/253 - DX/DS with COS41 - WX/WS with COS61
Entry of Slope is Calibration status Store calibration
calibration value displayed is displayed results
Countdown
H2O = water 600 s --> 0 s o.k. Exxx yes; no; new
C1 (2) C121 C122 C123
Countdown
CALIBRATION 600 s --> 0 s
on air o.k. Exxx yes; no; new
C C1 (1) C111 C112 C113
Edit: Read:
Code 22 any code Temperature display Temperature display Measured value Measured value
MEAS. VAL. DISPLAY
with in °F suppressed in mg/l in % Sat
TEMPERATURE
DISPLAY 1st error is displayed Other errors are
in °C displayed
Edit: Read: (if present) (up to max. 10 errors)
Code 22 any code
Entry of Entry of measured
Selection of
operating mode
Selection of
display unit * altitude value damping
------------
1 (no damping)
SETUP 1 mg/l % SAT hPa mg/l ppm ppb 0m 0 ... 4000 m 1 ... 60
A A1 A2 A3 A4 A5
Controller switch-off Delay for controller Delay for controller Switch-off limit value Switch-off direction
by current input switch-off by current switch-on by current for current input for current input
input input
Off; Input 0 s 0 ... 2000 s 0 s 0 ... 2000 s 50% 0 ... 100% Low; High
CURRENT INPUT
Z Z1 Z2 Z3 Z4 Z5
Entry of
simulation value
current value
sim = Simulation 0 ... 22.00 mA
O3 (2) O321
Selection of Alarm delay Setting of lower Setting of upper Selection of process monitoring
alarm threshold alarm threshold alarm threshold off; AC; CC monitoring
monitoring 0 min (s) 0.00 mg/l; 0...19 mg/l 20.00 mg/l; 1...20 mg/l limit (AC):
Off; Low; High; 0 ... 2000 min (s) 0.0%SAT; 0...190%SAT 200.0%SAT;10...200%SAT AC+CC ±0.1 mg/l ±1 % SAT
CHECK Lo+Hi=low and high (depends on F2) 0 hPa; 0... 380 hPa 400 hPa; 20...400hPa
±2 hPa (in 1 h)
P P1 P2 P3 P4 P5
C07-COM2x3xx-13-06-00-en-001.eps
98 Endress+Hauser
Liquisys M COM223/253 Appendix
Selection of
measuring range
20 mg/l 60 mg/l
200%Sat 600% Sat
400 hPa 1200 hPa
A6
O313
Endress+Hauser 99
Appendix Liquisys M COM223/253
C07-COM2x3xx-13-06-00-en-003.eps
100 Endress+Hauser
Liquisys M COM223/253 Appendix
C07-COM2x3xx-13-06-00-en-004.eps
Endress+Hauser 101
Appendix Liquisys M COM223/253
Countdown
H2O = water 600 s --> 0 s o.k. Exxx yes; no; new
C1 (2) C121 C122 C123
Countdown
CALIBRATION 600 s --> 0 s
on air o.k. Exxx yes; no; new
C C1 (1) C111 C112 C113
Edit: Read:
Code 22 any code Temperature display Temperature display Measured value Measured value
MEAS. VAL. DISPLAY
with in °F suppressed in mg/l in % Sat
TEMPERATURE
DISPLAY 1st error is displayed Other errors are
in °C displayed
Edit: Read: (if present) (up to max. 10 errors)
Code 22 any code
Selection of Selection of Automatic Entry of Entry of measured
operating mode display unit pressure altitude value damping
compensation
1 (no damping)
SETUP 1 mg/l % SAT hPa mg/l ppm ppb Off; On 0m 0 ... 4000 m 1 ... 60
A A1 A2 A3 A4
* A5
Controller switch-off Delay for controller Delay for controller Switch-off limit value Switch-off direction
by current input switch-off by current switch-on by current for current input for current input
input input
Off; Input 0 s 0 ... 2000 s 0 s 0 ... 2000 s 50% 0 ... 100% Low High
CURRENT INPUT
Z Z1 Z2 Z3 Z4 Z5
Entry of
simulation value
current value
sim = Simulation 0 ... 22.00 mA
O3 (2) O321
Selection of Alarm delay Setting of lower Setting of upper Selection of process monitoring
alarm threshold alarm threshold alarm threshold off; AC; CC monitoring
monitoring 0 min (s) 0.00 mg/l; 0...59 mg/l 20.00 mg/l; 1...60 mg/l limit (AC):
Off; Low; High; 0 ... 2000 min (s) 0.0%SAT; 0...590%SAT 200.0%SAT;10...600%SAT AC+CC ±0.1 mg/l ±1 % SAT
CHECK Lo+Hi=low and high (depends on F2) 0 hPa; 0...1180 hPa 400 hPa; 20...1200hPa
±2 hPa (in 1 h)
P P1 P2 P3 P4 P5
C07-COM2x3xx-13-06-00-en-005.eps
102 Endress+Hauser
Liquisys M COM223/253 Appendix
Selection of
measuring range
20 mg/l 60 mg/l
200%Sat 600% Sat
400 hPa 1200 hPa
A6
O313
Endress+Hauser 103
Appendix Liquisys M COM223/253
C07-COM2x3xx-13-06-00-en-007.eps
104 Endress+Hauser
Liquisys M COM223/253 Appendix
Entry of Entry of Entry of Number of Setting of interval Setting of minimum Number of cleaning
pre-rinse time cleaning time post-rinse time repeat cycles between 2 cleaning pause time cycles without
cycles cleaning agent
(pause time)
30 s 0 ... 999 s 10 s 0 ... 999 s 30 s 0 ... 999 s 0 0 ... 5 360 min 1...7200 min 120 min 1...3600 min 0 0 ... 9
R253 R254 R255 R256 R257 R258 R259
Entry of integral Entry of derivative Selection of Selection Entry of pulse Entry of pulse Entry of minimum Entry of
action time Tn action time Tv control characteristics interval frequency on time ton basic load
(0.0=no I component) (0.0=no Ien = pulse length
D component) inv = invers freq = pulse frequency 120 min-1
0.0 s 0.0...999.9 min 0.0 s 0.0...999.9 min dir = direct curr = current output 10.0 s 0.5...999.9 s 60 ... 180 min-1 0.3 s 0.1 ... 5.0 s 0% 0 ... 40%
R234 R235 R236 R237 R238 R239 R2310 R2311
Entry of SW upgrade Entry of SW upgrade Display of Display of Reset instrument Perform instrument Display of absolute
release code release code order number serial number to default values test air pressure
(Plus package) Chemoclean
0000 0000 ... 9999 0000 0000 ... 9999 no; sens; factory no; display
S2 S6 S7 S8 S9 S10 S11
C07-COM2x3xx-13-06-00-en-008.eps
Endress+Hauser 105
Appendix Liquisys M COM223/253
Countdown
H2O = water 600 s --> 0 s o.k. Exxx yes; no; new
C1 (2) C121 C122 C123
Countdown
CALIBRATION 600 s --> 0 s
on air o.k. Exxx yes; no; new
C C1 (1) C111 C112 C113
Edit: Read:
Code 22 any code Temperature display Temperature display Measured value Measured value
MEAS. VAL. DISPLAY
with in °F suppressed in mg/l in % Sat
TEMPERATURE
DISPLAY 1st error is displayed Other errors are
in °C displayed
Edit: Read: (if present) (up to max. 10 errors)
Code 22 any code
Selection of Selection of Automatic pressure Entry of Entry of measured
operating mode display unit compensation altitude value damping
1 (no damping)
SETUP 1 mg/l % SAT hPa mg/l ppm ppb Off; On 0m 0 ... 4000 m 1 ... 60
A A1 A2 A3 A4
* A5
Controller switch-off Delay for controller Delay for controller Switch-off limit value Switch-off direction
by current input switch-off by current switch-on by current for current input for current input
input input
Off; Input 0 s 0 ... 2000 s 0 s 0 ... 2000 s 50% 0 ... 100% Low; High
CURRENT INPUT
Z Z1 Z2 Z3 Z4 Z5
Entry of
simulation value
current value
sim = Simulation 0 ... 22.00 mA
O3 (2) O321
Selection of Alarm delay Setting of lower Setting of upper Selection of process monitoring
alarm threshold alarm threshold alarm threshold off; AC; CC monitoring
monitoring 0 min (s) 0.000 mg/l; 0...19 mg/l 20.000 mg/l; 1...20 mg/l limit (AC):
Off; Low; High; 0 ... 2000 min (s) 0.0%SAT; 0...190%SAT 200.0%SAT;10...200%SAT AC+CC ±0.1 mg/l ±1 % SAT
CHECK Lo+Hi=low and high (depends on F2) 0 hPa; 0... 380 hPa 400 hPa; 20...400hPa
±2 hPa (in 1 h)
P P1 P2 P3 P4 P5
C07-COM2x3xx-13-06-00-en-009.eps
106 Endress+Hauser
Liquisys M COM223/253 Appendix
Selection of
measuring range
20 mg/l 60 mg/l
200%Sat 600% Sat
400 hPa 1200 hPa
A6
O313
Endress+Hauser 107
Appendix Liquisys M COM223/253
C07-CON2x3xx-13-06-00-en-011.eps
108 Endress+Hauser
Liquisys M COM223/253 Appendix
C07-COM2x3xx-13-06-00-en-012.eps
Endress+Hauser 109
Liquisys M COM223/253
Index
A I
Access codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Icons
Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Electrical. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Alarm contact. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Safety symbols. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Alarm threshold monitoring . . . . . . . . . . . . . . . . . . . . . . . 50 Immersion assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Appendix Incoming acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Operating matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98 Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Automatic mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5, 9–10, 12
Instrument specific errors . . . . . . . . . . . . . . . . . . . . . . . . . 84
C Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 K
Checking Key assignment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 L
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Limit contactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Chemoclean function . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Cleaning M
Transmitter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5, 36 Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 Connecting lines and junction boxes . . . . . . . . . . . . . . 74
Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Entire measuring point . . . . . . . . . . . . . . . . . . . . . . . . 71
Controller monitoring. . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Oxygen sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Controller replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . 92 Manual mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Current input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Measuring cable
Current outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Variant 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
D Mechanical construction. . . . . . . . . . . . . . . . . . . . . . . . . . 96
Declaration of conformity . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Menu structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Monitoring functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Diagnosis code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Dismantling N
Field instrument . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Panel mounted instrument . . . . . . . . . . . . . . . . . . . . . 86
Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
O
Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 Operating elements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96 Operating matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
E Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
E+H Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Electrical connection Operating concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Without Memosens . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Electrical icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
EMC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Optoscope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95 Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
F
Factory settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Field device connection . . . . . . . . . . . . . . . . . 18, 22, 25, 27
Flow assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Freezing of outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
H
Hold function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35, 64
110 Endress+Hauser
Liquisys M COM223/253
P
P controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
PD controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Performance characteristics . . . . . . . . . . . . . . . . . . . . . . . . 95
PI controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
PID controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Plus package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Post mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Process specific errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Product structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Q
Quick commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Quick setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Quick start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29, 38
R
Relay contact configuration . . . . . . . . . . . . . . . . . . . . . . . . 53
Replacement of controller . . . . . . . . . . . . . . . . . . . . . . . . . 92
Retractable assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 92
S
Safety icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Sensor activity monitoring . . . . . . . . . . . . . . . . . . . . . . . . . 50
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Setup 1 (oxygen) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Setup 2 (salinity and temperature) . . . . . . . . . . . . . . . . . . . 41
Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Switching on. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
System configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
System error messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
T
Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Test
Variant 1 (DX/DS). . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Variant 2 (WX/WS) . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Timer for cleaning function . . . . . . . . . . . . . . . . . . . . . . . . 57
Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Trouble-shooting
Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Instrument specific errors. . . . . . . . . . . . . . . . . . . . . . . 84
Process specific errors . . . . . . . . . . . . . . . . . . . . . . . . . 81
System error messages . . . . . . . . . . . . . . . . . . . . . . . . . 79
U
Use
designated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
W
Wall mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Endress+Hauser 111
www.endress.com/worldwide
BA199C/07/en/09.05
51500272
Printed in Germany / FM+SGML 6.0 / DT
51500272