ABB

ROUTINE TEST REPORT


MEDIUM VOLTAGE SWITCHGEAR
Project no : X18155111
Project name : SQM SEUL
Substation : 33 kV SUBSTATION
Panel No : A01

Type : UNIGEAR Type ZS2


Serial number : 1YTU180155X1101
Rated voltage : 36kV
Service voltage : 33kV
Rated current : 2000A
Rated frequency : 60Hz
Rated short-time withstand current : 25ka,3s
Rated peak withstand current : 62,5kA
Year of production : 2018

The switchgear complies with the tests required according to IEC Publication 62271-1
and IEC Publication 62271-200 corresponding clauses as follows

TESTS:

1. Design and visual checks acc.to IEC 62271-1 clause 7.5


Conclusion : Satisfactory

2. Power frequency voltage withstand tests on the main circuit acc.to IEC 62271-200 clause 7.1
Test value : 70kV,1min
Conclusion : Satisfactory

3. Dielectric tests on auxiliary and control circuits acc.to IEC 62271-1 clause 7.2.4
Test value : 1kV, 50Hz, 1 sec.
Conclusion : Satisfactory

4. Mechanical operation tests acc.to IEC 62271-200 clause 7.102


a. Verification of interlocking - 5 times
b. Verification of proper function of switching device - 5 times
c. Verification of proper function of withdrawable parts - 5 times
Conclusion : Satisfactory

5. Functional tests acc.to IEC 62271-1 clause 7.2.2 and test of auxiliary devices acc.to IEC 62271-200 clause 7.104
Conclusion : Satisfactory

6. Verification of protection against electrical shock acc.to IEC 62271-1 clause 7.2.3
Conclusion : Satisfactory

7. Inspection of auxiliary and control circuits and verification of conformitiy to the circuit diagrams and wiring
diagrams acc.to IEC 62271-1 clause 7.2.1
The wiring conforms with the diagram No: 1YTU180155X1151
Conclusion : Satisfactory

Dilovası, 10.10.2018

App. By EPMV , Test Department

ABB ABB ELEKTRİK SANAYİİ A.Ş.


Dilovasi Organize Sanayi Bolgesi 4.Kisim
D4009 Sok. No:11 Kocaeli Turkey

Form No: 1YTFR014-0


ABB
ROUTINE TEST REPORT
MEDIUM VOLTAGE SWITCHGEAR
Project no : X18155111
Project name : SQM SEUL
Substation : 33 kV SUBSTATION
Panel No : A02

Type : UNIGEAR Type ZS2


Serial number : 1YTU180155X1102
Rated voltage : 36kV
Service voltage : 33kV
Rated current : 1250A
Rated frequency : 60Hz
Rated short-time withstand current : 25ka,3s
Rated peak withstand current : 62,5kA
Year of production : 2018

The switchgear complies with the tests required according to IEC Publication 62271-1
and IEC Publication 62271-200 corresponding clauses as follows

TESTS:

1. Design and visual checks acc.to IEC 62271-1 clause 7.5


Conclusion : Satisfactory

2. Power frequency voltage withstand tests on the main circuit acc.to IEC 62271-200 clause 7.1
Test value : 70kV,1min
Conclusion : Satisfactory

3. Dielectric tests on auxiliary and control circuits acc.to IEC 62271-1 clause 7.2.4
Test value : 1kV, 50Hz, 1 sec.
Conclusion : Satisfactory

4. Mechanical operation tests acc.to IEC 62271-200 clause 7.102


a. Verification of interlocking - 5 times
b. Verification of proper function of switching device - 5 times
c. Verification of proper function of withdrawable parts - 5 times
Conclusion : Satisfactory

5. Functional tests acc.to IEC 62271-1 clause 7.2.2 and test of auxiliary devices acc.to IEC 62271-200 clause 7.104
Conclusion : Satisfactory

6. Verification of protection against electrical shock acc.to IEC 62271-1 clause 7.2.3
Conclusion : Satisfactory

7. Inspection of auxiliary and control circuits and verification of conformitiy to the circuit diagrams and wiring
diagrams acc.to IEC 62271-1 clause 7.2.1
The wiring conforms with the diagram No: 1YTU180155X1152
Conclusion : Satisfactory

Dilovası, 10.10.2018

App. By EPMV , Test Department

ABB ABB ELEKTRİK SANAYİİ A.Ş.


Dilovasi Organize Sanayi Bolgesi 4.Kisim
D4009 Sok. No:11 Kocaeli Turkey

Form No: 1YTFR014-0


ABB
ROUTINE TEST REPORT
MEDIUM VOLTAGE SWITCHGEAR
Project no : X18155111
Project name : SQM SEUL
Substation : 33 kV SUBSTATION
Panel No : A03

Type : UNIGEAR Type ZS2


Serial number : 1YTU180155X1103
Rated voltage : 36kV
Service voltage : 33kV
Rated current : 1250A
Rated frequency : 60Hz
Rated short-time withstand current : 25ka,3s
Rated peak withstand current : 62,5kA
Year of production : 2018

The switchgear complies with the tests required according to IEC Publication 62271-1
and IEC Publication 62271-200 corresponding clauses as follows

TESTS:

1. Design and visual checks acc.to IEC 62271-1 clause 7.5


Conclusion : Satisfactory

2. Power frequency voltage withstand tests on the main circuit acc.to IEC 62271-200 clause 7.1
Test value : 70kV,1min
Conclusion : Satisfactory

3. Dielectric tests on auxiliary and control circuits acc.to IEC 62271-1 clause 7.2.4
Test value : 1kV, 50Hz, 1 sec.
Conclusion : Satisfactory

4. Mechanical operation tests acc.to IEC 62271-200 clause 7.102


a. Verification of interlocking - 5 times
b. Verification of proper function of switching device - 5 times
c. Verification of proper function of withdrawable parts - 5 times
Conclusion : Satisfactory

5. Functional tests acc.to IEC 62271-1 clause 7.2.2 and test of auxiliary devices acc.to IEC 62271-200 clause 7.104
Conclusion : Satisfactory

6. Verification of protection against electrical shock acc.to IEC 62271-1 clause 7.2.3
Conclusion : Satisfactory

7. Inspection of auxiliary and control circuits and verification of conformitiy to the circuit diagrams and wiring
diagrams acc.to IEC 62271-1 clause 7.2.1
The wiring conforms with the diagram No: 1YTU180155X1152
Conclusion : Satisfactory

Dilovası, 10.10.2018

App. By EPMV , Test Department

ABB ABB ELEKTRİK SANAYİİ A.Ş.


Dilovasi Organize Sanayi Bolgesi 4.Kisim
D4009 Sok. No:11 Kocaeli Turkey

Form No: 1YTFR014-0


ABB
ROUTINE TEST REPORT
MEDIUM VOLTAGE SWITCHGEAR
Project no : X18155111
Project name : SQM SEUL
Substation : 33 kV SUBSTATION
Panel No : A04

Type : UNIGEAR Type ZS2


Serial number : 1YTU180155X1104
Rated voltage : 36kV
Service voltage : 33kV
Rated current : 1250A
Rated frequency : 60Hz
Rated short-time withstand current : 25ka,3s
Rated peak withstand current : 62,5kA
Year of production : 2018

The switchgear complies with the tests required according to IEC Publication 62271-1
and IEC Publication 62271-200 corresponding clauses as follows

TESTS:

1. Design and visual checks acc.to IEC 62271-1 clause 7.5


Conclusion : Satisfactory

2. Power frequency voltage withstand tests on the main circuit acc.to IEC 62271-200 clause 7.1
Test value : 70kV,1min
Conclusion : Satisfactory

3. Dielectric tests on auxiliary and control circuits acc.to IEC 62271-1 clause 7.2.4
Test value : 1kV, 50Hz, 1 sec.
Conclusion : Satisfactory

4. Mechanical operation tests acc.to IEC 62271-200 clause 7.102


a. Verification of interlocking - 5 times
b. Verification of proper function of switching device - 5 times
c. Verification of proper function of withdrawable parts - 5 times
Conclusion : Satisfactory

5. Functional tests acc.to IEC 62271-1 clause 7.2.2 and test of auxiliary devices acc.to IEC 62271-200 clause 7.104
Conclusion : Satisfactory

6. Verification of protection against electrical shock acc.to IEC 62271-1 clause 7.2.3
Conclusion : Satisfactory

7. Inspection of auxiliary and control circuits and verification of conformitiy to the circuit diagrams and wiring
diagrams acc.to IEC 62271-1 clause 7.2.1
The wiring conforms with the diagram No: 1YTU180155X1152
Conclusion : Satisfactory

Dilovası, 10.10.2018

App. By EPMV , Test Department

ABB ABB ELEKTRİK SANAYİİ A.Ş.


Dilovasi Organize Sanayi Bolgesi 4.Kisim
D4009 Sok. No:11 Kocaeli Turkey

Form No: 1YTFR014-0