PMT Hps Ep03 320 400 v1 c300
PMT Hps Ep03 320 400 v1 c300
PMT Hps Ep03 320 400 v1 c300
Specification
EP03-320-400
Release 400
July 2010, Version 1
Experion C300 Controller Specification, EP03-320-400, V.1, July 2010 2
Table of Contents
1. Product Introduction....................................................................................................... 3
1.1. Experion System ................................................................................................... 3
1.2. Architecture Overview ........................................................................................... 3
1.3. Experion C300 Controller Overview ..................................................................... 3
2. Specifications ................................................................................................................. 4
2.1. C300 Controller Hardware .................................................................................... 4
2.2. C300 Controller Specifications.............................................................................. 4
2.3. Supported Function Blocks ................................................................................... 6
3. Model Numbers ............................................................................................................. 9
Revision History
Revision Date Description
1. Product Introduction
Introduced in Experion PKS R400, the C300 Controller now supports Custom Algorigthm Blocks. Custom Algorithm Blocks
are similar in purpose and structure to the standard function blocks that are distributed with Control Builder. However, CABs
have user-defined algorithms and data structures. For more information, see the CAB spec sheet, EP03-350-400.
Experion C300 Controller Specification, EP03-320-400, V.1, July 2010 4
2. Specifications
Power requirement 24 V (provided through power bars by the Series C power system)
Agency Approvals
Specification Limit
Vibration Frequency 10 to 60 Hz
Acceleration 0.5 g max
Displacement 0.1 Inch
Mechanical Shock Acceleration 5 g max
Duration 30 msec maximum
Barometric Pressure
Altitude -300 to +3000 m
EMI 15 V/M External to cabinet with doors closed
Harsh Environment (ANSI/ISA- CC- model number designation support the harsh environment or G3 level
S71.04-1985 corrosion standard)
Module Removal and Insertion Supported
Under Power
Supported I/O Types Series A (Serial interface, Pulse Input, ProfiBus and DeviceNet interface),
Series C and PMIO in any combination
Supported I/O Links 2 I/O Links, each I/O Link configurable for either PM or Series C I/O.
Supported Number of IO Modules 64 I/O Units (see system specification for further detail)
Supported Number of IO Modules 64 I/O Units (see system specification for further detail)
Control Capacity
Controller Communication
Experion C300 Controller Specification, EP03-320-400, V.1, July 2010 6
Specification Limit
Modulo X OR X
Multiply X PULSE X
Negate X QOR X
Power X ROL X
Rolling Average X ROR X
Round X RS X
Square Root X RTRIG X
Subtract X SEL X
Truncate X SELREAL X
Discrete Logic SHL X
2oo3 (2 out of 3 voting) X SHR X
AND X SR X
CHECKBAD X STARTSIGNAL X
CHECKBOOL X TRIG X
CHGEXEC X WATCHDOG X
CONTACTMON X XOR X
DELAY X Sequential Control Functions
EQ (Compare Equal) X Step X
FTRIG (Falling Edge Trigger) X Transition X
GE (Compare Greater than or Synchronize X
X
Equal)
Handler X
GT (Compare Greater Than) X
Phase X
LE (Compare Less than or
X Container Block Types
Equal)
LIMIT X Control Module X
LT X Sequential Control Module X
MAX X Recipe Control Module X
MAXPULSE X Unit Control Module X
MIN X IO Related
nOON X PCDI X
NOR X PLC Data Exchange X
NOT X AB Drive Interface
JagXtreme
Q.Impact
Calculation Block Types
AGA X
VCONE X
Experion C300 Controller Specification, EP03-320-400, V.1, July 2010 9
3. Model Numbers
Model Number Description
This document contains Honeywell proprietary information. It is published for the sole usage of Honeywell Process Solutions’
customers and prospective customers worldwide. Information contained herein is to be used solely for the purpose submitted,
and no part of this document or its contents shall be reproduced, published, or disclosed to a third party without the express
permission of Honeywell International Inc.
While this information is presented in good faith and believed to be accurate, Honeywell disclaims the implied warranties of
merchantability and fitness for a particular purpose and makes no express warranties except as may be stated in its written
agreement with and for its customer.
In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and
specifications in this document are subject to change without notice.