Harmonics in Power System
Harmonics in Power System
Harmonics in Power System
POWER SYSTEM
Introduction
What are harmonics.?
Classification of harmonics
Causes and effects.
Types of equipments that generates harmonics.?
Problem caused by harmonics.
Harmonic migration measures
Conclusion
CONTENTS
www.forumelectrical.com
Various methodologies and techniques were proposed to
improve the power quality.
INTRODUCTION
www.forumelectrical.com
“Harmonics” is the term which means waves having frequencies of
integer multiples of one another.
It can be given as: fh= n*fundamental frequency
www.forumelectrical.com
If a system has the fundamental frequency as 60Hz then its 2nd and 3rd harmonic would
have frequencies of 120Hz and 180Hz respectively.
Figure 2 shows a fundamental with 70 % third order and 50 % fifth order harmonics
added.
In practice, most distorted waveforms will be much more complex than this
example, containing many more harmonics.
www.forumelectrical.com
Harmonics which are nothing but distorted waveforms have two
types namely voltage and current harmonics.
The orders of harmonics and symmetrical components, these are
two concepts which are used commonly to describe harmonics.
Regarding the harmonics, words odd and even harmonics are used
usually but the term triplen harmonics is not much known.
CLASSIFICATION OF
HARMONICS
www.forumelectrical.com
Generally, representation of harmonic components is given with equation:
POWER
QUALITY
Total Harmonic INDICES
Distortion Current (THDi) This value can be calculated
by taking the ratio of THC to the Fundamental current. It can be
given as:
UNDER HARMONIC
DISTORTION
Where 𝐼1= fundamental current
www.forumelectrical.com
Total Harmonic Distortion of Voltage (THDv) It shows the total magnitude
of the distortion in voltage. It can be calculated by calculating ratio of distorted
or harmonic voltage to the non-harmonic or fundamental voltage.
Total Demand Distortion (TDD) This concept is used widely used in North
America regarding harmonics. It is the ratio of harmonic current to the full load
fundamental current
www.forumelectrical.com
SOURCES OF HARMONIC DISTORTION
Static Compensators: Compensator which are controlled by Thyristor will produce near
about 1% of the 11th harmonic current.
Power Converters Rectifiers. Hence the dc current is almost constant and then converter
starts acting as a harmonic voltage source on the dc side where as the harmonics current
source on the ac side.
Rotating Machines In the rotating machines, harmonic currents can be produced due to
asymmetries in the winding pattern.
Electric Arc Furnace As the arc feed material varies, the harmonics rise up and their
value cannot be predicted certainly
Switched Mode Power Supplies (SMPS) SMPS unit draws current pulses contain large
amount of harmonics of third and above higher order harmonics.
www.forumelectrical.com
Harmonic currents and voltages cause many problems in electrical
installations, including
*Three phase
TYPES loads
OF EQUIPMENTS THAT
1.Variable speed drives
GENERATES
2. Large UPS units
HARMONICS
www.forumelectrical.com
SWITCHED MODE POWER SUPPLIES
Electronic lighting ballasts have become popular in recent years claiming improved
efficiency
Their great disadvantage is that they generate harmonics in the supply current
www.forumelectrical.com
In general are usually based on the three-phase bridge, also
known as the six-pulse bridge .
The six pulse bridge produces harmonics at 6n +/- 1 .
The magnitude of each harmonic is the reciprocal of the
harmonic number .
www.forumelectrical.com
There are several common problem areas caused by harmonics: -
PROBLEMS CAUSED BY
HARMONICS
www.forumelectrical.com
2.Second effect concerns the triple-N harmonics
NUISANCE TRIPPING OF CIRCUIT BREAKER
Nuisance tripping can occur in the presence of harmonics for two reasons .
*Firstly, the RCCB, being an electromechanical device, may not sum the higher
frequency components correctly
*Secondly, the equipment that generates harmonics also generates switching noise
*The situation is easily overcome by providing more circuits, each supplying fewer
loads
EFFECTS ON TRANSFORMERS
www.forumelectrical.com
Skin effect is normally ignored because it has very little effect
at power supply frequencies but above about 350 Hz.
Skin effect will become significant, causing additional loss
and heating.
Multiple cable cores or laminated busbars can be used to help
overcome this problem.
PROBLEMS CAUSED BY HARMONIC
VOLTAGES
Because the supply has source impedance, harmonic load
currents give rise to harmonic voltage distortion on the voltage
waveform .
SKIN EFFECT
www.forumelectrical.com
Harmonic voltage distortion causes increased eddy current
losses in motors in the same way as in transformers.
Additional losses arise due to the generation of harmonic
fields in the stator.
Where harmonic voltage distortion is present motors should be
de-rated to take account of the additional losses.
INDUCTION MOTORS
www.forumelectrical.com
When a harmonic current is drawn from the supply it gives
rise to a harmonic voltage drop.
Which proportional to the source impedance at the point of
common coupling (PCC) and the current.
Since the supply network is generally inductive, the source
impedance is higher at higher frequencies.
The voltage at the PCC is already distorted by the
harmonic currents drawn by other consumers and by the
distortion inherent in transformers, and each consumer
makes an additional contribution.
www.forumelectrical.com
Harmonic mitigation measures are required to:
Passive filters,
Isolation and harmonic reduction transformers
And active solutions
HARMONIC MITIGATION
METHODS
www.forumelectrical.com
Passive filters are used to provide a low impedance path for harmonic currents so
that they flow in the filter and not the supply .
The filter may be designed for a single harmonic or for a broad band depending on
requirements.
This harmonic voltage appears across the supply on the load side.
www.forumelectrical.com
Triple-N currents circulate in the delta windings of transformers, are a
problem for transformer manufacturers and specifiers .
The extra load has to be taken into account – it is beneficial to systems
designers because it isolates triple-N harmonics from the supply.
ISOLATION TRANSFORMERS
www.forumelectrical.com
Virtually all modern electrical and electronic equipment involves
some form of power control and so is a non-linear load.
Each
CONCLUSION
successful strategy to prevent future problems will be a
combination of good design practice, the right electrical equipment,
and good maintenance.
www.forumelectrical.com
Harmonics in Your Electric System, A White Paper of Eaton Corporation.
Douglas Andrews, Martin T. Bishop, John F. Witte,(May-June 1996), Harmonic
Measurements, Analysis, and Power Factor Correction in a Modern Steel
Manufacturing Facility, IEEE Transactions on Industry Applications, Vol. 32, No. 3.
Masoud Karimi-Ghartemani, and M. Reza Iravani,( January 2005), Measurement of
Harmonics/Interharmonics of Time-Varying Frequencies, IEEE Transactions On
Power Delivery, Vol. 20, No.3.
David M. McNamara, Alireza K. Ziarani, Thomas H. Ortmeyer(January 2007), A
New Technique of Measurement of Nonstationary Harmonics, IEEE Transactions
On Power Delivery, Vol. 22, No.1
Weicheng XIE, Xia YANG, (2010), A Power Harmonic Measurement System
Based on Wavelet Packet Transform and ARM9, IEEE.
Gary W. Chang, Senior Member, IEEE and Cheng-I Chen, (2010), Measurement
REFERENCES
Techniques for Stationary and Time-Varying Harmonics, IEEE
Hsiung Cheng Lin, (February 2012),Power Harmonics and Interharmonics
Measurement Using Recursive Group-Harmonic Power Minimizing Algorithm,
IEEE Transactions On Industrial Electronics, Vol. 59, No.2
www.forumelectrical.com
Dobinson, L. G. "Closer Accord on Harmonics", Electronics and Power, 15
May, 1975, pp 567 - 572.
ANSVIEEE Std 100-1 988, "Standard Dictionary of Electrical and Electronics
Terms", ISBN: 1-55937-000-9, The Institute of Electrical and Electronics
Engineers, Inc.
IEEE Std 519-1992, IEEE Recommended Practices and Requirements for
Harmonic Control in Electric Power Systems.
Limits for Harmonics in the United Kingdom Electricity Supply System, G.93,
' September 1976, Classification C.
www.forumelectrical.com
THANK YOU
www.forumelectrical.com