AUTOMATIC CONTROL SWITCH-BOARD FOR DIESEL ENGINE

TYPE NF-1100
Made to start and protect a DIESEL engine.
INTSTRUCTION AND USER MANUAL

Complete with
automatic battery charger

INSTRUMENTS:

- battery voltmeter
- total hour meter
- partial hour meter
- starting counter
- starting failures counter
- fuel level
indicator
- tachometer

For the description of operation and the technical programming


see manuals DCA-109.

FUNCTIONS:

• SETTING WITH BRIDGES (JUMPERS) TO OBTAIN MOTOR START AND STOP IN


AUTOMATIC MODE USING THE CALL CONTACTS (PRESSURE GAUGES OR MIN/MAX
FLOATS OR MAINS RELAYS)

• Automatic faults surveillance with messages on the display.


• Texts in 6 languages: Italian, English, French, German, Spanish and Portuguese.
• Remote control (starting and stop).
• Glow plugs preheating management or engine heating cooling.
• Clock for programming the starting or the stopping of the engine.
• Preventive maintenances warning.
• Programmable weekly selftest.
• Available fully programmable input for anomaly.
• Possibility of starting the engine when the charge of the battery is low.
• Anomaly historical record (Including data from the last 100 occurred anomalies).

ELCOS SRL - Parma - NF-1100 - EN 1


NF-1100 TECHNICAL DATA

SWITCH-BOARD CONFORMING WITH STANDARDS 17-13/1; EN 60439-1


BATTERY SUPPLY 12 Vdc (16 Vdc max) or
24 VDC (32VDC MAX)
MAXIMUM LOAD DELIVERY 1A (12VDC) 200 mA (24VDC)
SELFCONSUMPTION WITH ENGINE BY MAINS FAUL 20mA
STATIONARY
SELFCONSUMPTION WITH ENGINE STATIO- 185mA a 12V 110mA a 24V
NARY AND PRESSED EMERGENCY BUTTON
SINGLE PHASE MAINS SUPPLY 230 VAC ± 10% 10A MAX 50 ÷ 60 Hz

(6) ACCELERATOR OR PREHEATING 3W


(15) STARTING 3W
(17) STOPPING 7W
(19) STARTING AND RUNNING ENGINE 3W
(70) GENERAL ALARM 3W

HEATER OUTPUT 230 VAC MAX 1500 W


TEMPERATURE RANGE -10 ÷ +50°C
RELATIVE HUMIDITY 50% A 40°C
MAX ALTITUDE 1000 mt a.s.l.
NOMINAL INSULATION VOLTAGE (TERMINALS 230V
AT MAINS VOLTAGE)
NOMINAL INSULATION VOLTAGE (TERMINALS 32 V
AT BATTERY VOLTAGE)
INSULATION CLASS CLASS I
WALL INSTALLATION CONDITIONS FOR EXTERNAL USE
DEGREE OF PROTECTION IP 54
WEIGHT 2,8 Kg
DIMENSIONS (LxHxD) mm 235X315X125

2 ELCOS SRL - Parma - NF-1100 - EN


NOTES

ELCOS SRL - Parma - NF-1100 - EN 3


4 ELCOS SRL - Parma - NF-1100 - EN
SETTING WITH BRIDGES (JUMPERS) TO OBTAIN MOTOR START AND STOP IN AUTOMATIC MODE
USING THE CALL CONTACTS (PRESSURE GAUGES OR MIN/MAX FLOATS OR MAINS RELAYS)

THE STOP DUE TO FAULTS IS ALWAYS ACTIVE (IT DOES NOT DEPEND ON THE SETTING USING JUMPERS)

START AND STOP ARE THE ENGINE STARTS: THE ENGINE STOPS: JUMPERS
FUNCTIONS
CONTROLLED BY:
One call contact On the closing of the call By moving the functions selec- 3-7
contact tor to the OFF or MAN position 9-10
On the opening of the call 3-7
“ “ “ “ “ “ contact FACTORY
SETTINGS
Two min and max call contacts. On the closing of the minimum On the opening of the 3-4
call contact maximum call contact 9-10

Two min and max call con- For mains fault and closing of On the opening of the 3-5
tacts and mains current relay the minimum call contact maximum call contact or when 4-6
the mains is restored 9-10

For mains fault or on the On the opening of the 3-4


closing of the minimum call maximum call contact or when 5-7
“ “ “ contact the mains is restored and the 6-9
min. call contact is opened
3-4
“ “ “ On the opening of the 5-7
“ “ “ maximum call contact 6-8
9-10

WIRING DIAGRAMS FOR THE CARD TYPE SEA 1100


Make bridges (JUMPERS) to obtain the required operation
DIAGRAM FUNCTION N° 1 DIAGRAM FUNCTION N° 2 SDIAGRAM FUNCTION N° 3
THE CONTROL PANEL IS PRE-SET

CALL
(MAXIMUM)
WITH THIS FUNCTION

CALL
CALL CALL (MINIMUM)

DIAGRAM FUNCTION N° 4 DIAGRAM FUNCTION N° 5 DIAGRAM FUNCTION N° 6

MAINS MAINS RELAY


MAINS RELAY
RELAY (EXCITED
(EXCITED WITH MAINS
(EXCITED CALL WITH
CALL
WITH CALL ON)
(MAXIMUM) (MAXIMUM) MAINS ON) (MAXIMUM)
MAINS ON)

CALL CALL
(MINIMUM) CALL (MINIMUM)
(MINIMUM)

TERMINAL 67 TERMINAL 1 TERMINAL 30 NEGATIVE, ENGINE STARTING JUMPERS


NEGATIVE WITH UNIT IN AUTOMATIC POSITIVE TERMINAL 30 WITHOUT SIGNAL, ENGINE STOPPING

ELCOS SRL - Parma - NF-1100 - EN 5


COMPONENTS LIST

DESCRIPTION TYPE CODE MANUFACTURER QUANTITY


ELCOS
BOX GW44209 70493130 GEWISS 1
300X220x120
CONTROL UNIT DCA-109 00242293 1
CARD SEA-1100 12V 40026548 ELCOS 1
“ 24V 40026549
BATTERY CBS-010 12V 00010101 1
CHARGER CBS-010 24V 00010102

FUSE HOLDERS 10,3X38 70450833 2


FUSES OF 10,3X38 WIMEX 2
VARIOUS TYPES
TERMINALS CBC4 70421784 CABUR 3
CBC2 70421782 4

6 ELCOS SRL - Parma - NF-1100 - EN


NOTICES
Used only to check and command a diesel engine. Maintains the charge of the start battery.
It has been designed on a wall.

Warning: Components carrying dangerous voltage levels


Only assigned and suitably trained personnel are allowed access to the panel. No maintenance operations
are permitted unless the plant is disconnected from the mains and the battery. As an additional safety
measure, the plant phases should be short-circuited and earthed.
Not withstanding the above, only assigned and trained personnel can perform the following
operations with the plant on:
- make a visual inspection of the control unit, the connections and their markings;
- measure the voltage and/or current values;
- programming of the functions.
These interventions, however, must be performed using equipment which ensures appropriate
levels of electrical protection.

Warning:
Adhere closely to the following advice
- When making connections always follow the instructions and the Wiring Diagram on pages 4-5.
- Any interventions on the unit must be performed with the motor stationary and terminal 50 of the
starting motor disconnected.
- Check that the consumption of the connected equipment are compatible with the described
technical characteristics.
- Install in such a way that there is always adequate heat disposal.
- Always install under other equipment which produces or spreads heat.
- Handle and connect without mechanically stressing the electronic board.
- Make sure that no copper conductor cuttings or other waste material fall inside the control panel.

THIS SWITCH-BOARD IS NOT SUITABLE FOR OPERATING IN THE FOLLOWING CONDITIONS:


- Where the environmental temperature is outside the limits indicated in the technical data.
- Where the air pressure and temperature variations are so rapid as to produce exceptional condensation.
- Where there are high levels of pollution caused by dust, smoke, vapour, salts and corrosive or
radioactive particles.
- Where there are high levels or heat from radiation caused by the sun, ovens or the like.
- Where attacks from mould or small animals are possible.
- Where there is the risk of fire or explosions.
- Where the control panel can receive strong vibrations or knocks.

ELECTROMAGNETIC COMPATIBILITY
This control unit functions correctly only if inserted in plants which conform with the CE marking standards; it meets
the exemption requirements of the standard EN61326-1 but it cannot be excluded that malfunctions could occur in
extreme cases due to particular situations.
The installer has the task of checking that the disturbance levels are within the requirements of the standards.

CONDUCTION AND MAINTENANCE


The following maintenance operations should be performed every week:
- check that the indicators function;
- check the condition of the batteries;
- check that the conductors are tight, check the condition of the terminals.

UNLESS WE MAKE A WRITTEN DECLARATION STATING THE CONTRARY, THIS CONTROL UNIT IS
NOT SUITABLE FOR USE AS A CRITICAL COMPONENT IN EQUIPMENT OR PLANTS RESPONSIBLE
FOR KEEPING PERSONS OR OTHER LIVING BEINGS ALIVE.

YOUR ELECTRICAL TECHNICIAN CAN ASK ANY QUESTIONS ABOUT


THIS CONTROL UNIT BY TELEPHONING OUR TECHNICIAN
ELCOS SRL - Parma - NF-1100 - EN 7
ORDERING DATA

Type NF-1100 12V Code 00022141


“ NF-1100 24V “ 00022142

SUPPLIED ACCESSORIES

GEWISS MOUNTING BRACKET KIT Code 40750688

8 ELCOS SRL - Parma - NF-1100 - EN