NetSure+731+CK2-Y3-Y4 V1.0 100 20221212 SM
NetSure+731+CK2-Y3-Y4 V1.0 100 20221212 SM
NetSure+731+CK2-Y3-Y4 V1.0 100 20221212 SM
Power System
User Manual
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
TABLE OF CONTENTS
Admonishments Used in this Document .............................................................................................................................. v
Important Safety Instructions .................................................................................................................................................vi
Static Warning ..............................................................................................................................................................................ix
1 Overview.....................................................................................................................................................................................1
1.1 Composition and Configuration .......................................................................................................................................................................................................................1
1.2 Features ..................................................................................................................................................................................................................................................................................1
1.3 Operating Principle...................................................................................................................................................................................................................................................... 2
1.4 Functions .............................................................................................................................................................................................................................................................................. 2
1.4.1 Lightning and Surge Protection ............................................................................................................................................................................................... 3
1.4.2 LLVD and BLVD ......................................................................................................................................................................................................................................4
1.4.3 Fault Alarm and Protection ...........................................................................................................................................................................................................4
1.4.4 AC and DC Distribution .................................................................................................................................................................................................................... 5
1.4.5 Earthing Design........................................................................................................................................................................................................................................ 5
2 Installation Instruction ......................................................................................................................................................... 7
2.1 Safety Regulations ....................................................................................................................................................................................................................................................... 7
2.2 Preparation.......................................................................................................................................................................................................................................................................... 7
2.3 Mechanical Installation ............................................................................................................................................................................................................................................8
2.3.1 Fixing the Power Cabinet ................................................................................................................................................................................................................8
2.3.2 Installing Rectifiers ................................................................................................................................................................................................................................9
2.4 Electrical Installation ............................................................................................................................................................................................................................................... 10
2.4.1 Connecting Power Cables ........................................................................................................................................................................................................... 10
2.4.2 Connecting Signal Cables............................................................................................................................................................................................................ 16
3 Testing ..................................................................................................................................................................................... 19
3.1 Installation Check and Startup ...................................................................................................................................................................................................................... 19
3.2 Basic Settings ............................................................................................................................................................................................................................................................... 20
3.3 Alarm Check and System Operation Status Check .................................................................................................................................................................. 20
3.4 Final Steps .........................................................................................................................................................................................................................................................................21
4 Use of the Controller.......................................................................................................................................................... 22
4.1 Operation Panel ........................................................................................................................................................................................................................................................... 22
4.2 Main Screens .................................................................................................................................................................................................................................................................. 22
4.2.1 System Information Screen ........................................................................................................................................................................................................ 23
4.2.2 Password Confirmation Screen .............................................................................................................................................................................................. 23
4.2.3 MAINMENU Screen .......................................................................................................................................................................................................................... 24
4.2.4 Status Screen ......................................................................................................................................................................................................................................... 24
4.2.5 Settings Screen ..................................................................................................................................................................................................................................... 25
4.2.6 Maintenance Screen ......................................................................................................................................................................................................................... 25
4.2.7 Energy Saving Screen .....................................................................................................................................................................................................................26
4.2.8 Fast Settings Screen ........................................................................................................................................................................................................................26
4.3 Querying System Main Information .......................................................................................................................................................................................................... 27
4.3.1 DC, System State, Battery State and Battery Management Mode Information ........................................................................ 27
4.3.2 Saving State, Rectifier Output Power and Time from Next BC ................................................................................................................ 27
4.3.3 Battery Information ............................................................................................................................................................................................................................28
4.3.4 AC Voltage Information .................................................................................................................................................................................................................28
4.3.5 System Temperature Information ........................................................................................................................................................................................28
4.4 Querying Rectifier Information ......................................................................................................................................................................................................................28
4.5 Querying Alarms Information ..........................................................................................................................................................................................................................29
iii
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
iv
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
DANGER! Warns of a hazard the reader will be exposed to that will likely result
in death or serious injury if not avoided. (ANSI, OSHA)
WARNING! Warns of a potential hazard the reader may be exposed to that could result
in death or serious injury if not avoided. This admonition is not used for situations that
pose a risk only to equipment, software, data, or service. (ANSI)
CAUTION! Warns of a potential hazard the reader may be exposed to that could
result in minor or moderate injury if not avoided. (ANSI, OSHA) This admonition is not
used for situations that pose a risk only to equipment, data, or service, even if such
use appears to be permitted in some of the applicable standards. (OSHA)
ALERT! Alerts the reader to an action that must be avoided in order to protect
equipment, software, data, or service. (ISO)
ALERT! Alerts the reader to an action that must be performed in order to prevent
equipment damage, software corruption, data loss, or service interruption. (ISO)
v
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
General Safety
DANGER! YOU MUST FOLLOW APPROVED SAFETY PROCEDURES.
Performing the following procedures may expose you to hazards. These procedures should be performed by qualified
technicians familiar with the hazards associated with this type of equipment. These hazards may include shock, energy,
and/or burns. To avoid these hazards:
c) Prior to contacting any uninsulated surface or termination, use a voltmeter to verify that no voltage or the
expected voltage is present. Check for voltage with both AC and DC voltmeters prior to making contact.
e) Use certified and well maintained insulated tools. Use double insulated tools appropriately rated for the work
to be performed.
Voltages
AC Input Voltages
DANGER! This system operates from AC input voltage capable of producing fatal electrical shock. AC input power must
be completely disconnected from the branch circuits wiring used to provide power to the system before any AC electrical
connections are made. Follow local lockout/tagout procedures to ensure upstream branch circuit breakers remain de-
energized during installation. DO NOT apply AC input power to the system until all electrical connections have been
completed and checked.
DANGER! Follow local lockout/tagout procedures to ensure DC branch circuit protection devices remain de-energized
during installation at loads, as required.
vi
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Battery
Refer to the battery manufacturer documentation for specific battery safety instructions. The following are general guidelines.
WARNING! Special safety precautions are required for procedures involving handling, installing, and servicing batteries.
Observe all battery safety precautions in this manual and in the battery instruction manual. These precautions should be
followed implicitly at all times.
WARNING! A battery can present a risk of electrical shock and high short circuit current. Servicing of batteries should
be performed or supervised only by properly trained and qualified personnel knowledgeable about batteries and the
required precautions.
Follow the recommended PPE requirements per the SDS for the battery to be used.
Batteries are an energy source that can produce high amounts of electrical current.
Eye protection should be worn to prevent injury from accidental electrical arcs.
Use certified and well maintained insulated tools. Use double insulated tools appropriately rated for the work to be
performed. Ensure that wrenches with more than one working end have only one end exposed.
Verify that no current will flow when the battery is connected or disconnected by opening battery disconnects (if
available) or adjusting the system to match battery voltage.
Risk of explosion if battery is replaced with an incorrect type or if polarity is reversed. Recommended to replace
batteries with the same manufacturer and type, or equivalent.
Dispose of used batteries according to the instructions provided with the batteries. Do not dispose of batteries in a
fire. They may explode.
Batteries may generate explosive gases during normal operation. Systems containing batteries should never be
installed in an airtight room or space. Only install in a ventilated environment.
Batteries may contain sulfuric acid. If battery acid enters your eye, immediately flush your eye with running cold
water for at least 15 minutes. Get medical attention immediately. If battery acid contacts skin or clothing, wash
immediately with soap and water.
ALERT! Performing maintenance and/or troubleshooting procedures may interrupt power to the loads, if battery reserve
is not sufficient.
vii
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Only authorized and properly trained personnel should be allowed to install, inspect, operate, or maintain the equipment.
Do not work on LIVE parts. If required to work or operate live parts, obtain appropriate Energized Work Permits as
required by the local authority, per NFPA 70E “Standard for Electrical Safety in the Workplace”.
Hazardous Voltage
DANGER! HAZARD OF ELECTRICAL SHOCK.
More than one disconnect may be required to de-energize the system before servicing.
NOTE! When performing any step in procedures that requires removal of existing hardware, retain all hardware for use in
subsequent steps, unless otherwise directed.
viii
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Static Warning
This equipment contains static sensitive components. The warnings listed below must be observed to prevent damage to
these components. Disregarding any of these warnings may result in personal injury or damage to the equipment.
2. Before touching any equipment containing static sensitive components, discharge all static electricity from
yourself by wearing a wrist strap grounded through a one megohm resistor. Some wrist straps have a built-in one
megohm resistor; no external resistor is necessary. Read and follow wrist strap manufacturer’s instructions outlining
use of a specific wrist strap.
3. Do not touch traces or components on equipment containing static sensitive components. Handle equipment
containing static sensitive components only by the edges that do not have connector pads.
4. After removing equipment containing static sensitive components, place the equipment only on static
dissipative surfaces such as conductive foam or ESD bag. Do not use ordinary Styrofoam or ordinary plastic.
5. Store and ship equipment containing static sensitive components only in static shielding containers.
6. If necessary to repair equipment containing static sensitive components, wear an appropriately grounded wrist
strap, work on a conductive surface, use a grounded soldering iron, and use grounded test equipment.
ix
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
x
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
1 Overview
This chapter introduces composition and configuration, features, operating principle and functions of the power system.
The ‘power system’ in this manual refers to the NetSure 731 CK2-Y3/Y4 power system.
Configuration
The configuration of NetSure 731 CK2-Y3/Y4 power system is listed in Table 1.1.
Configuration
Item
NetSure 731 CK2-Y3 NetSure 731 CK2-Y4
1.2 Features
The rectifier uses the active Power Factor Compensation (PFC) technology, raising the power factor to 0.99.
The power system has wide AC input voltage range of 85V ~ 305V (rectifier single phase input voltage).
The rectifier uses soft switching technology, raising the efficiency up to 96%.
The safety regulations of the rectifier are designed according to UL, CE certification of the rectifier, and NEBS standards.
The rectifier is hot pluggable. It takes less than 1 minute to replace a rectifier.
The rectifier has input overvoltage protection. The overvoltage protection point is set to 307.5V, which can be
automatically restored.
The rectifier has two optional over-voltage protection methods: hardware protection and software protection. The latter
one also has two optional modes: lock-out at the first over-voltage and lock-out at the second over-voltage.
1
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
The controller has perfect battery management. The management functions include the LLVD, BLVD, temperature
compensation, auto voltage regulation, stepless current limiting, battery capacity calculation, on-line battery test and
other functions.
The M530S controller can save up to 5000 pieces of historical alarm records and 5000 pieces of history data records.
The M530S controller can save 10 sets of battery test data records.
The power system has network design. Providing multiple communication ports (such as RS485, USB, Ethernet and
CAN), which enables flexible networking and remote monitoring.
The power system has perfect lightning protection at both AC side and DC side.
The power system has complete fault protection and fault alarm functions.
Using centralized monitoring mode, the controller manages the AC distribution unit and DC distribution unit. It also receives the
operating data of the rectifiers and controls them accordingly through CAN mode. The controller can be connected to a local
computer using the RS485 port and can be connected to the monitoring center through connecting a modem or other
transmission resources (such as official channels) to realize the centralized monitoring and networking of the power system.
1.4 Functions
Functions of the power system include:
AC and DC distribution
2
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
整流模块
5m~10m
交流输入 交流 直流
配电 整流模块 配电
单元 单元 -48V输出
DC
I/B II/C 防雷器
防雷器 整流模块
防雷器
电池组
监控模块 1、2
RS232
注:I,II,III级是IEC标准的分类方法 RJ11
Modem PSTN
B,C,D级是德国VDE标准的分类方法
RJ11 远程后台监控
防雷器
The power system is equipped with a Class II/C SPD. Meanwhile, each rectifier of the system has perfect lightning protection
circuit. The system can withstand simulated lightning surge currents of 20kA at 8/20μs five times, and 40kA at 8/20μs once. To
prevent higher lightning strikes from damaging the equipment, it is recommended to install a higher protective Class I/B SPD in
the cable inlet of the equipment room (lightning surge current is at least 60kA, refer to YD/T5098-2005 Signal station lightning
protection and grounding engineering design standard).
To prevent lightning strikes at the DC side from damaging the equipment, an effective lightning protection device is provided,
which can withstand simulated lightning surge currents of 20kA at 8/20μs five times. To prevent conductive lightning strike from
damaging the modem port of the controller, the power system provides lightning protection (optional) for the modem port. The
SPD can withstand a 5kA lightning surge current at 8/20μs and a 4kV lightning surge voltage at 10/700μs.
3
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
By equipping with a Class II/C SPD at AC side and SPD at DC side, the power system has perfect lighting protection at both AC
side and DC side. To achieve better lightning protection at AC side, it is recommended to mount a Class I/B SPD, lightning surge
current is at least 60kA. The Class I/B SPD should be purchased by the user. Refer to YD/T5098-2005 Signal station lightning
protection and grounding engineering design standard for the detailed technical rules. The Class I/B SPD installation is shown in
Figure 1.2.
Figure 1.2 Diagram of Class I/B SPD mounting & system earthing
Powersystem
Power supply
system
5m ~ 10m
A Lever
Level 2
Class
Class-C
(Class
B SPD C)
C SPD
SPD
N
SPD earth
PE --
System earth bar
-48Vdc
240Vdc
240Vdc
48Vdc
First 1
Lever
Level DC earth
lever
Lever 1 SPD
Class-B
Class-B
(Class B)
(Class
SPDB)
SPD +
+
SPD earth
DC earth cable
Protective earth
Protective earth cable
User earth bar
The Class I/B SPD should be purchased and mounted by the user. If condition permits, it is recommended that the cable length
between the Class I/B SPD and the power system meet the following rules: if a voltage limiting type SPD is used, then the cable
length should be longer or equal than 5m; if a switching type SPD is used, then the cable length should be longer or equal than
10m. The cable between the Class I/B SPD and the input terminals of the AC distribution unit of the power system should be
routed indoors to avoid direct lightning strike. The output cable CSA of the Class I/B SPD and the grounding cable CSA should
not be less than 16mm2. For the cable length, the shorter the better.
The power system has lighting protection at DC side, which can meet YD/T5098 requirements. There’s no need to design lighting
protection at DC side.
4
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
The AC input uses 3-pole MCB and has short circuit and over-current protection.
See Table 1.2 for the functions of the AC input and output interfaces of the power system.
Interface Functions
Output load branch has short circuit and over-current protections, and branch capacity can be adjusted according to
user requirements.
Battery input uses fuse which has functions like short circuit, over-current protection, alarm and fault status detection.
See Table 1.3 for the functions of the DC input and output interfaces of the power system.
Interface Functions
Earth
Application range Basis
resistance
Integrated building, international telecom bureau, tandem station, SPC switching office above 10000
< 1Ω YDJ20-88 Provisional technical
lines, toll office above 2000 lines
regulations of computerized
< 3Ω SPC switching office above 2000 lines and below 10000 lines, toll office below 2000 routes telephone switching equipment
5
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Earth
Application range Basis
resistance
SPC switching office with less than 2000 lines, optical cable terminal station, carrier wave repeating installation and design
< 5Ω
station, earth station, microwave junction center, mobile communication machine station
< 10Ω Microwave relay station, optical cable relay station, small-sized earth station YD/T5098-2005 Signal station
lightning protection and grounding
< 20Ω Microwave passive relay station engineering design standard
Suitable for those whose earth resistance rate is less than 100Ω·m, SPD earth in the interface
< 10Ω
between electric cable and aerial electric line
GB/T 50064-2014 Design
Suitable for those whose earth resistance rate is 100-500Ω·m, SPD earth in the interface between specification of overvoltage
< 15Ω
electric cable and aerial electric line protection and insulation
coordination of AC electrical device
Suitable for those whose earth resistance rate is 501-1000Ω·m, SPD earth in the interface between
< 20Ω
electric cable and aerial electric line
6
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
2 Installation Instruction
This chapter introduces the installation and cable connection. Before installation, please read through safety regulations, and then
follow this instruction to carry out the installation and connection step by step.
1. Only adequately trained personnel with satisfactory knowledge of the power system shall carry out the installation. The safety
rules before the contents and local safety rules in force shall be adhered to during the installation.
2. All external circuits below -48V and connected to the power system must comply with the requirements of SELV as defined in
IEC 62368.
3. Make sure that the power (mains and battery) to the power system is cut off before any operations can be carried out within
the cabinet.
4. The power system shall be kept locked and placed in a locked room. The key keeper should be the one responsible for the
power system.
5. The wiring of the power distribution cables should be arranged carefully so that the cables are kept away from the maintenance
personnel.
2.2 Preparation
Unpacking inspection
The equipment should be unpacked and inspected after it arrives at the installation site. The inspection shall be done by
representatives of both the user and Vertiv Tech Co., Ltd.
To inspect the equipment, you should open the packing case, take out the packing list and check against the packing list that the
equipment is correct and complete. Make sure that the equipment is delivered intact.
NOTE! 1. When delivered with the cabinet, the rectifier should be placed at the bottom of the cabinet subrack.
2. If the system needs to configure fuse extractor, it should be strapped at the bottom of the cabinet subrack.
Cable preparation
The cable should be selected in accordance with relevant industry standards.
It is recommended to use the RVVZ cables as AC cables. The cable should reach at least 70°C temperature durability. Select the
AC cable CSA according to Table 2.1.
The CSA of DC cable depends on the current flowing through the cable, the allowable voltage drop and load peak current. The
recommended load peak current is 1/2 to 2/3 of MCB or fuse capacity.
7
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Select the battery cable CSA according to Table 2.2. Select the load cable CSA according to Table 2.3.
Battery fuse Max. battery Max. cable length (allowable Max. cable Max. cable length (volt drop:
Min. cable CSA
rated current current voltage drop: 0.5V) CSA 0.5V, with max. CSA)
M6 screw: 8 ≤ 50mm2
The CSA of the system grounding cable should be the same as that of the largest power distribution cable and not less than
35mm2. The grounding terminal of the grounding busbar is M8 screw.
8
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Determine the installation position of the power cabinet in the equipment room according to Figure 2.1 (NetSure 731 CK2 is a
600mm deep cabinet).
According to the dimensions in Figure 2.2, mark the specific positions of the center points of the installation holes on the floor of
the equipment room. Drill a 70mm deep installation hole at the marked point with a Φ14 drill bit. Remove dust from holes. Put the
expansion pipe into the hole.
Move the cabinet to the installation position. Align the installation holes on the cabinet with those dug on the floor. Screw the
expansion bolt down into the expansion pipe in the floor.
9
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
1. After loosening the handle fixing screw on the front panel of the rectifier, pull the handle screw with your fingers (as shown in
Figure 2.3) to pull out the handle.
2. Put the rectifier into the rectifier slot. Slowly push the rectifier in until it stops. Close the handle of the rectifier and tighten the
fixing screws. The rectifier will be locked to the cabinet.
10
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
The cable entry and exit methods of the standard cabinet are top entry and top exit. Please bind the incoming and outgoing
cables according to the position of the binding bars inside the side wall of the cabinet. Please refer to Figure 2.4 for wiring.
11
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Figure 2.5 NetSure 731 CK2-Y3 wiring terminal diagram (rear view)
12
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Connecting AC cables
1. Connect the AC input phase cables to the AC input MCB, the positions as shown in Figure 2.6. Figure 2.6 shows the 2-route
mains input MCB configuration.
2. If the power system is configured with AC output MCB, connect the AC output cables to the AC output MCB, and connect the
AC output neutral line to the neutral busbar, as shown in Figure 2.5 and Figure 2.6.
Connect the negative load cable to the upper terminal of the load MCB or load fuse. Connect the positive load cable to the DC
positive busbar, as shown in Figure 2.6. The specifications of the positive busbar connection screw are Φ12mm, Φ10mm, Φ8mm
and Φ6mm. Please connect the load cable according to the priority load and non-priority load labels.
13
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Battery fuse
Controller
14
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Battery fuse
Controller
AC output MCB
1. Connect one end of the negative battery cable to the upper terminal of the battery fuse. Connect one end of the positive
battery cable to the DC output positive busbar. The specification of the positive busbar connection screw is Φ10mm.
2. Crimp the OT terminals to the unconnected ends of the two battery cables, completely wrap the exposed metal part of the OT
terminals with insulating tape, place them next to the negative and positive terminals of the battery respectively, and when the
DC power distribution is initially adjusted, connect the battery cables to the battery.
15
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
The interfaces of the controller are shown in Figure 2.9. The functions of the interfaces are listed in Table 2.4.
3, 6, 9 NC
J6, J7 2, 5, 8 COM 5 pairs of dry contact alarm output
1, 4, 7 NO
1 RS485+
2 RS485-
J3 RS485 interface
3 RS485+
4 RS485-
1 12V+
J8, J9, J10 2 TEMP Battery temperature sensor interface
3 PGND
Installation procedures:
Put the temperature probe in the battery room where best represents the ambient temperature of the battery temperature, far
away from other heat-generating equipment. When batteries are placed outside the cabinet, the temperature probe shall not be
replaced inside the cabinet.
16
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Installing modem
Modem is suitable for those who have purchased the modem remote monitoring system by themselves.
The following expounds the modem installation and connection, taking e-TEK TD-5648DCII modem for example.
Lead the cable ties through the modem fixing holes at the top of the cabinet. Use the cable ties to fix the modem on the top of
the cabinet, as shown in Figure 2.10.
Cable tie
Modem
The input and output interfaces of the modem are shown in Figure 2.11.
POWER
RS-232 LINE PHONE
2) Use a power cable to connect the positive and negative power terminals (silkscreen: POWER) of the modem to the DC positive
busbar and negative busbar (below the battery fuse) of the power system respectively.
3) Use a communication cable to connect the communication interface of the modem (DB25 female, silkscreen: RS-232) to the J6
interface (DB9 male) of the controller.
NOTE! During system testing, set the parameter ‘Modem’ of the controller to ‘Y’.
17
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
18
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
3 Testing
This chapter introduces the testing procedures after installation. The corresponding safety rules shall be adhered to in the test.
During operation, parts of this equipment carry hazardous voltage. Misoperation can result in severe or fatal injuries and property
damage. Before the test, check the equipment to ensure the proper earthing. Installation check must be done before testing.
Then the batteries can be charged for the first time.
Make sure that the AC input MCBs, rectifier MCBs and load MCBs are switched off. Make sure that all the devices are properly
installed.
Check the power system step by step according to the following listed items.
Installation check
Check item OK Comments
Check all the models of MCBs, fuses and cables are correct
Check that the grounding of the power system is correct and reliable, and the connection of input and output cables is correct and
reliable
Check whether the number and connections of the cells are correct; check the polarity of the battery string is correct
Make sure all the connections are solid and reliable
Make sure all the communication cables and alarm cables are connected to the controller. Check that the temperature sensor, if any,
has been installed
Startup preparations
Check item OK Comments
Make sure that all the MCBs are switched off and all the fuses are removed
Measure the AC input voltage. Make sure the input voltage is within the allowable range Umin=___V
Check that at least one section of the short-circuited copper bar in battery string circuit is not connected before installation,
prevent short circuits caused by shorting the positive and negative poles
Connect and install the last unconnected battery in all battery strings
Measure each battery connection point with a voltmeter and make sure that the battery polarity is right. For a lead-acid battery
with 24 cells, the voltmeter should read 2.0V ~ 2.1V/cell or 48V ~ 51V/battery. If the voltage reading of a cell is below 2.0V, the cell Umin=___V
must be replaced
Check with an ohmmeter to confirm that there is no short circuit between the positive busbar and negative busbar of the DC
output or between the positive pole and the negative pole of the battery (note that all rectifiers are pulled out before
measurement, and restored after measurement)
Startup
Check item OK Comments
Switch on the AC input MCB. Switch on one rectifier input MCB. The green indicator on the rectifier will be on and the fan will
start running. After a delay, the controller shows that the output voltage is 53.5V
Check busbar polarity and system voltage with a voltmeter. The difference between the measured value and displayed value
should be less than ±0.3V
Turn on and off each rectifier in the power system in sequence by switching on and switching off the rectifier input MCBs.
Measure the output voltage of the rectifiers
19
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Select the main menu Settings (password: 1) Battery Settings Batt. Selection submenu. Set the ‘Mode’ parameter to
‘Manual’, and then return to the submenus under the Settings menu to set the parameters (unless otherwise specified). Refer to
4.7 Setting System Parameters for detailed controller parameter setting method.
The system type has been set before the product leaves the factory, check whether the setting is consistent with the actual
system (the system type is NetSure 731 CK2: 48V/SET)
Set the controller according to the number of actually connected battery strings. Default: 2
Set the controller according to the total capacity of the actually connected battery strings. Default: 200Ah
Configure the temperature coefficient according to the battery manufacturer’s requirement. Setting range: 0mV/°C ~
500mV/°C. Default: 72mV/°C. (if no temperature sensor is installed, do not set this parameter)
Set the charging current limit. Setting range: 0.1C10 ~ 0.25C10. Default: 0.1C10
Set the controller according to the voltage suggested by the battery supplier
Floating Charge (FC) voltage range: 42V ~ Boost Charge (BC) voltage. Default: 53.5V
BC voltage range: FC voltage ~ 58V. Default: 56.4V
For batteries that do not need BC, set the BC voltage to FC voltage plus 0.1V
Measure the battery voltage with a multimeter and record it. Enter Main menu Maintenance (password: 1) RectTrim
submenu. Set the output voltage of the rectifier to the actual voltage of the battery. Insert the battery fuse. Set the output
voltage of the rectifier to 53.5V
Enter the Batt. Selection submenu. Set the ‘Mode’ parameter to ‘Auto’
Pull out one rectifier. The ‘Rect N Com Failure’ alarm should be triggered. Insert the rectifier again. The alarm should
disappear. Repeat the same procedures on other rectifiers
Remove battery fuse 1. The ‘Batt1 Failure’ alarm should be triggered. Put on the fuse. The alarm should be cleared. Repeat the
same procedures on battery fuse 2
Disconnect one of the DC output branches connected to the load. The alarm ‘Load Fuse N Failure’ should be triggered.
Connect the branch, and the alarm should disappear. Repeat the same procedures on the other load branches
Disconnect all battery fuses. Keep only one rectifier in operation. Through the controller, adjust the rectifier FC voltage to
make it lower than the alarm point. The alarm ‘DC Voltage Low’ should be triggered
Pull out the varistor of the AC SPD. The ‘SPD fault’ alarm should be triggered. Insert the varistor, the alarm should be cleared
Note: When the preceding alarms are generated, the controller will give alarms after approximately 3s. For querying the alarm information in the controller,
please refer to 4.5 Querying Alarms Information
20
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
The controller should be able to display the DC voltage. The difference between the displayed and measured DC voltage should be
less than ±0.3V
The controller should display the battery current. The difference between the displayed and measured battery current should be less
than 1%
Check the number of the rectifiers displayed on the controller. The number should be consistent with the actual installed quantity
Check that any rectifier voltage, current, and current limit value displayed on the controller are consistent with the set value and the
actual value
For the power system configured with a temperature sensor, the battery and ambient temperature displayed on the controller should
be normal. Hold the probe of the temperature sensor with your hand and the displayed temperatures should change
Make sure that materials irrelevant to the equipment have been all removed
Fill in the installation report and hand it over to the user
Fill in the parameter table at the cabinet door
If any defect is found in the power system, inform the contract manager.
If repairing is needed, please fill in the FAILURE REPORT and send the report together with the defective unit to the repairing
center for fault analysis.
21
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
For factory parameter setting and operation menu structure of the controller, refer to 10 Parameter Setting of the Controller and
11 Menu Structure of the Controller.
LCD
液晶显示屏
Run indicator
运行指示灯 ESC
Alarm indicator
告警指示灯 Functional keys
操作键
Critical紧急告警指示灯
alarm indicator ENT
The description of the indicators on the operation panel is given in Table 4.1.
The controller uses a 128 × 64 LCD, and a keypad with four functional keys (listed in Table 4.2). The interface language is
Chinese/English optional and shows 8 × 4 Chinese characters. The interface is easy to use, and the controller is easy to be
removed and replaced.
ESC Escape Return to the upper level menu. When an audible alarm is generated, press this key to silence it
Enter the lower level menu or confirm the menu operation. When changing or inputting parameters, press this key to get into
ENT ENT
editing state. After any change is made, press this key to validate the change
▲ Up
Shift among parallel menus. For a character string, these two keys can be used to change values. After the selection, press the
ENT key to confirm
▼ Down
Left In value setting interface, these two keys can be used to change values. These two keys can move the cursor when one screen
Right requires character string to be input
NOTE! The contents of the screens given in this manual are just examples. For different configurations, models and
system states, the actual contents of the screens may be different from this manual.
22
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
The system information screen displays the main information, which is displayed on five screens. You can press ▲ or ▼
repeatedly to display different system information screens. The first system information screen has 7-level contrast (the contrast
can be adjusted only in the first system information screen), and you can press or to adjust the contrast. The first system
information screen is shown in Figure 4.2.
2009-3-23
浮充
53.5V 125A
自动 正常
2. At the main menu screen, press the ESC key to return to the first system information screen.
3. If no operation is conducted on the controller keypad for eight minutes, the screen will automatically return to the first system
information screen. The time of that return will be recorded automatically and can be queried through the host.
4. At any one of the system information screen, pressing the ESC key returns to the first system information screen.
At the first system information screen, pressing the ENT key enters the product information screen, as shown in Figure 4.3. The
product information screen displays the monitoring model, software version and runtime. At the product information screen,
pressing the ESC key returns to the first system information screen.
5. At the system information screen, press and hold the ESC and ENT keys simultaneously for several seconds, the controller will
be reset, and then the system will restart.
Login:
Password:
1. When inputting the password, press the ENT key to get into editing state, press ▲ or ▼ to move the cursor, and press or
to modify numbers. After the input, press the ENT key to confirm.
2. If the password is correct, the next screen will appear. Otherwise, the system will prompt ‘Password Incorrect’.
23
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
3. During this operation, pressing the ESC key returns to the main menu screen.
4. The controller has three password levels: user level password (default: 1), engineer level password (default: 2) and administrator
level password (default: 640275).
Once you input the correct password, you never need to input the password again during the operation. If the interval between
two adjacent operations is more than four minutes, the system will prompt you to input the password again. If you want to operate
senior settings, you need to input higher level password.
MAINMENU
Energy Saving
Status
Fast Settings
Settings
Maintenance
1. At any one of the system information screen, press the ENT key to enter the MAINMENU screen.
2. At any sub-menu of the MAINMENU screen, press the ESC key repeatedly to return to the higher-level menu, and ultimately
return to the MAINMENU screen.
3. Select the required sub-menu through pressing ▲ or ▼. The selected sub-menu is shown by cursor, then press the ENT key
to enter the corresponding sub-menu.
DCEM Status
Day Energy
Statistic
1. At the MAINMENU screen, press ▲ or ▼ to select the ‘Status’ menu and press the ENT key to enter the Status screen.
2. At any sub-menu of the Status screen, press the ESC key repeatedly to return to the higher-level menu, and ultimately return to
the Status screen.
3. Select the required sub-menu through pressing ▲ or ▼. The selected sub-menu is shown by cursor, then press the ENT key
to enter the corresponding sub-menu.
24
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Settings
DC
DG Settings
Settings
DG Ctrl
Rect Set
Settings
Sys Settings
DG Settings
1. At the MAINMENU screen, press ▲ or ▼ to select the ‘Settings’ menu and press the ENT key to display the password
confirmation screen.
2. Input the correct password and press the ENT key to enter the Settings screen. Press ▲ or ▼ to select the operation screen
you need.
At the Settings screen, different password levels have different authorities. See Table 4.3 for the default password and authority.
Password
Operation authority Default password
level
User The authority to browse operation information, control output and change general parameters 1
All the user’s authorities, plus operation authorities such as changing system type and changing energy saving
Engineer 2
parameter
All the engineer’s authorities, plus operation authorities such as resetting system, resetting password, modifying
Administrator 640275
password and accessing serial port download mode
Once you input the correct password, you never need to enter the password again during the operation. If the interval between
adjacent operations is more than four minutes, the system will prompt you to input the password again. If you want to operate
senior settings, you need to input higher level password.
25
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
After the ‘Sys Mode’ is changed from ‘Auto’ to ‘Manual’, you can press ▲ or ▼ to enter the Maintenance screen, as shown in
Figure 4.9.
If some sampling values of the system enter the special range (for example, DC busbar in under-voltage state), the ‘Sys Mode’
may automatically switch to ‘Auto’, resulting in the controller returns to the MAINMENU screen without continually controlling the
output. It is a normal phenomenon.
1. At the MAINMENU screen, press ▲ or ▼ to select the ‘Energy Saving’ menu and press the ENT key to display the password
confirmation screen.
2. Input the correct password and press the ENT key to enter the Energy Saving screen. Press ▲ or ▼ to select the parameters
you need.
1. At the MAINMENU screen, press ▲ or ▼ to select ‘Fast Settings’ menu and press the ENT key to display the password
confirmation screen.
2. Input the correct password and press the ENT key to enter the Fast Settings screen. Press ▲ or ▼ to select the parameters
you need.
26
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
At the Fast Settings screen, you can set the system type and battery capacity, as listed in Table 4.4.
24V/100
24V/300
24V/500 When the controller is shipped with the power system, the system type of the controller has been
24V/1000 set according to the actual situation, and the user does not need to change it. When replacing a
new controller, the new controller needs to be set according to the actual power system type
24V/SET NetSure 731
System type After changing the system type, the controller will automatically restart, and all other parameters
48V/100 CK2: 48V/SET
inside the controller will become the default values of the corresponding system type. The user
48V/300 needs to change some parameters according to the system configured battery and other
48V/500 equipment requirements
48V/1000
48V/SET
The sum of the battery capacity connected to the shunt. Users should set according to the actual
Battery capacity 50Ah ~ 5000Ah 500Ah
battery configuration
2009-3-23
浮充
53.5V 125A
自动 正常
The date and time are alternately displayed every two seconds. The system state contains ‘Normal’ and ‘Alarm’. The battery
management mode includes ‘Auto’ and ‘Manual’. The battery state includes float charge, temperature compensation, boost
charge, cyclic boost charge, test, short test and time test.
4.3.2 Saving State, Rectifier Output Power and Time from Next BC
At the first system information screen, press ▼ to enter the following screen shown in Figure 4.13.
Figure 4.13 Information screen of saving state, rectifier output power and time from next BC
The first row displays the percentage of the output power and rated power of the rectifier. The last two rows display the boost
charge prompt information, which provides the time for next battery cyclic boost charge according to the battery state.
27
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
‘Batt 1’ and ‘Batt 2’ represent the current that flowed through battery shunt 1 and battery shunt 2. If there are many battery shunts,
groups of battery information will be displayed; if groups of batteries are connected to one shunt, the displayed current is the
total current of them; if the ‘Shunt Coeff’ of one battery group is set to ‘N’, the corresponding battery information will not be
displayed.
Batt.Temp:
25°
C
Amb.Temp:
25 °
C
If the temperature sensor is not connected or is faulty, the system will prompt ‘---’. Meanwhile, the alarm information screen will be
displayed. If the monitoring unit bans boost charge and no temperature sensor is configured, this screen will not appear.
The rectifier information includes the rectifier serial number, output voltage, output current, current limit, input voltage, AC and
DC states, AC power limit and temperature power limit.
28
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
At the Status screen shown in Figure 4.6, press ▲ or ▼ to select the ‘Rectifiers’ menu, and press the ENT key to enter the screen
shown in Figure 4.17.
The information of every rectifier is displayed in three screens. Press ▲ or ▼ to scroll to the three information screens. Press
or to query other rectifiers’ information.
At most 30 pieces of rectifier information can be displayed in the controller. When selecting one rectifier, the run indicator of the
corresponding rectifier will blink. If the rectifier communication is interrupted, the information will be displayed in high light.
At the Status screen shown in Figure 4.6, press ▲ or ▼ to select ‘Active Alarm’ menu and press the ENT key to enter it.
If there is an active alarm, the screen shown in Figure 4.18 will appear.
Alarm 1/5
Manual Mode
Observation
071213 14:27:50
The previous screen includes the alarm serial number/alarm total number, alarm name, alarm level and alarm time. The alarm
generating time determines the sequence it is displayed, with the latest alarm displayed first. Press ▲ or ▼ to view all active
alarms. The active alarms may be displayed in the controller are given in Table 4.5.
When querying the rectifier alarms, the status indicator of the corresponding rectifier will blink.
Alarm
No. Alarm Description
type
1 Rect AC Fails
2 Rect Over Temp
3 Rect Fault
4 Rectifier Rect Protect Reported by rectifiers
5 Rect Fan Fails
6 Rect Derated
7 Rect Not Respond
29
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Alarm
No. Alarm Description
type
30
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Alarm
No. Alarm Description
type
8 Battery Batt Charge Over The battery charging current is higher than the setting of over-current point
1 Self Detect Fail Controller hardware self-test failure
2 Manual Mode The system mode is set to ‘Manual’
The actual output voltage is different from both the measured DC bus voltage and the voltage reported by
3 Monitoring Volt Discrepancy
the rectifier to controller. The error is bigger than 1V
4 Maintain Alarm Time to maintain the system
5 Alarm Block Alarm block function is enabled
1) If there is no history alarm, the system cannot access the History Alarm screen.
2) If the active alarm is cleared, the alarm will automatically switch to the history alarm.
3) If there is an active alarm, the screen shown in Figure 4.19 will appear.
199 ID2067000584
Rect1 Fault
071213 14:27:50
071213 17:30:05
If it shows the rectifier alarm information, then the first row of Figure 4.19 will show the last 10 numbers of the alarm rectifier ID.
At most 200 history alarms and 512 history events can be recorded in EEPROM, through Flash, the history alarm records can be
expanded to 1000 and above, and the history data to 6000 and above.
3. At any History Alarm screen, press the ESC key repeatedly to return to the higher-level menu, and ultimately return to the first
system information screen.
4.6 Maintenance
NOTE! Be careful! BLVD operations may result in load power interruption.
1. At the MAINMENU screen, press ▲ or ▼ to select the ‘Maintenance’ menu. Press the ENT key, the system will prompt you to
input the password. After inputting the correct password, the management mode screen shown in Figure 4.20 will appear.
31
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
2. After changing the ‘Sys Mode’ from ‘Auto’ to ‘Manual’, press ▲ or ▼ to enter the Maintenance screen, as shown in Figure 4.21.
3. Press or to select the needed operation and press the ENT key to confirm. The screen pops up the corresponding
prompt. If the system satisfies control situation, press the ENT key to make the control become valid, otherwise, the controller will
prompt you that the control is disabled. Press the ESC key to cancel. The control contents are given below.
1) Start: The option includes ‘FC’, ‘BC’ and ‘Test’. After selecting the Start option, press or to select the needed operation. If
there is an AC power-off alarm, or the busbar under-voltage, the boost charge and battery test control will not be executed by the
system. No battery test control can be conducted when the rectifier communication is interrupted. After the battery test, the
battery management mode will be changed from ‘Manual’ to ‘Auto’ automatically.
2) Batt: The option includes ‘ReConnect’ and ‘DisCon’. If there is a battery fuse alarm, the battery operations will be invalid.
4) RectTrim: Range: 42V ~ 58V. The control voltage value of this parameter cannot exceed the over-voltage alarm point;
otherwise, the parameter will be invalid.
4. Press the ESC key to ultimately return to the MAINMENU screen, and then change the ‘Sys Mode’ from ‘Manual’ to ‘Auto’. After
this operation, press the ESC key to return to the system information screen.
32
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Alarm Type:
Load Fuse Alarm
Level: Critical
Out Relay: N
Press ▲ or ▼ to move the cursor to the option needs to be modified and press or to select the corresponding content, and
then press the ENT key to confirm the modification.
The controller classifies the alarms into four types: critical alarm, major alarm, observation alarm and no alarm.
Critical alarm, major alarm: These two types of alarms have strong impact on the system performance. Whenever these alarms are
generated, you are supposed to handle them immediately. The alarm indicators will be on and audible alarm will be generated.
Observation alarm: When this type of alarm is generated, the system maintains normal DC output for a while. If the alarm occurs
during watch time, it should be handled immediately. If the alarm occurs during non-watch-time, handle it when the watch time
begins. The alarm indicators will be on when an observation alarm occurs.
The alarm and its default value of the controller are listed in Table 4.6.
Related
No. Alarm Description Alarm level Related relay
parameter
33
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Related
No. Alarm Description Alarm level Related relay
parameter
34
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Related
No. Alarm Description Alarm level Related relay
parameter
Alarm Control
Voice Sign: Open
Clear: Hist Alarm
‘Voice Sign’ option includes: open, off, 3min, 10min, 1h, and 4h. You can set it according to your requirement.
‘Clear: History’ option includes: history alarm, rectifier lost, test, short test, energy-saving failure, maintain, communication failure,
and battery record. If you press the ENT key, the corresponding alarm information saved in the controller will be cleared.
DI settings
DI settings only have an impact on user-defined DI alarm. At the Alarm Settings screen, press ▲ or ▼ to select the ‘DI Settings’
menu and press the ENT key to enter the screen shown in Figure 4.25.
Press ▲ or ▼ to select the needed option, press or to select the parameter value and press the ENT key to confirm. Press
▲ or ▼ to modify the number and letter of DI name on the third line after pressing the ENT key to confirm, and press or to
move the cursor left or right, then input # to end. Finally, press the ENT key to confirm.
35
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
When there are DI alarms, this parameter shows the alarm name you have actually
DI Name Figures or letters, 10 at most Digital Alarm
defined
Active Open, Close Open Close: alarm in close state; Open: alarm in open state
At the Settings screen shown in Figure 4.7, press ▲ or ▼ to select the ‘Bat Settings’ menu, and press the ENT key to enter the
screen shown in Figure 4.26.
Bat. Settings
Basic Setting
LVD Settings
Charge
The battery parameters include ‘Basic Setting’, ‘LVD Settings’, ‘Charge’, ‘Battery Test’, ‘Temp. Comp’ and ‘Power Split’. The
methods for setting the battery parameters are given in the following sections.
Basic parameters
1. At the Bat Settings screen, press ▲ or ▼ to select the ‘Basic Setting’ menu and press the ENT key to enter the screen shown
in Figure 4.27.
2. Press ▲ or ▼ to select one screen or one of the parameters and press or to select the parameter value. Then press the
ENT key to confirm. The controller will automatically save the setting value.
36
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Bat. Shunt 2 Y, N Y You should set this parameter according to the actual configuration
Shunt Coeff -Current 1A ~ 2000A 500A
You can set the shunt parameter according to the system adopted shunt
Shunt Coeff -Volt 1mV ~ 500mV 25mV
Symmetry DI, None, Op1, Op2, Op3, Op4 None /
Symm Alarm 0.2V ~ 1.0V 0.5V /
LVD parameters
At the Bat Settings screen, press ▲ or ▼ to select the ‘LVD Setting’ menu and press the ENT key to enter the screen shown in
Figure 4.28.
Press ▲ or ▼ to select the parameter you need and press or to select the parameter value. Then press the ENT key to
confirm.
LVD1 means the controller receives power supply from the battery upon AC power-off, and the power supply system will switch
off the non-priority load automatically. In this way, the battery remaining capacity can sustain the priority load longer.
LVD2 means the controller generates LVD1 upon AC power-off and battery under-voltage, and the power supply system will
switch off the battery automatically. In this way, the battery over-discharge can be avoided.
The controller is based on the battery voltage to estimate whether executing the LVD function. The value description of the LVD
parameters is listed in Table 4.9.
LVD1 Volt 44.0V Select the battery voltage, when the battery voltage is lower than the preset LVD1 Volt, the load will be
40V ~ 60V
LVD2 Volt 43.2V disconnected, and so does the battery when the battery voltage is lower than the preset LVD2 Volt
37
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Charge parameters
At the Bat Settings screen, press ▲ or ▼ to select the ‘Charge’ menu and press the ENT key to enter the screen shown in Figure
4.29.
Cyc Boost:
Boost Limit Time:
-Enable: Yes
-Period: 2400h 1080min
-Time: 720min
Press ▲ or ▼ to select the parameter you need and press or to select the parameter value. Then press the ENT key to
confirm. The value description of the charge parameters is listed in Table 4.10.
Factory
Parameter Range Value description
setting
During the BC state, to ensure the system safety, the controller will forcefully control
BoostLimitTime 60min ~ 2880min 1080min
the system to enter the FC state, if the BC time reaches the ‘BoostLimitTime’
Select Y to enable this function
DG Chg Limit -Enable Y, N N
Select N to disable this function
DG Chg Limit -Current 0.050C10 ~ 0.080C10 0.100C10 The battery charge limit upon DG running
38
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Charge current
Constant BC smaller than
time-up Constant 'Const Boost
BC Current'
2. Press ▲ or ▼ to select one screen or one of the parameters and press or to select the parameter value. Then press the
ENT key to confirm and save.
The controller can do battery test, and record 10 groups of battery test data (accessible only through the host). The battery test
has to be started manually, and the controller will adjust the rectifier output voltage to the setting value of the ‘End Test Volt’,
then the battery discharge will begin. The controller will stop the battery test if the battery voltage reaches the ‘End Test Volt’, or
the discharge time reaches the ‘End Test Time’, or the battery capacity reaches the ‘End Test Cap’. Afterwards, it will restore the
rectifier output voltage to the normal FC voltage, begin the battery charge and switch the system to battery auto-management.
39
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Meanwhile, the test start time-voltage, end time-voltage and battery remaining capacity will be recorded. The records can be
queried through the host. During the battery test, if abnormalities occur, the controller will stop the battery test automatically. See
Table 4.11 for battery test parameter settings.
Factory
Parameter Range Value description
setting
10-01-00:00
Short Test -Enable Y, N N Whether using the short test function
Short Test -Alarm 1A ~ 100A 10A The short test is used for discharge test comparation of two groups of batteries. The
inspection for the battery feature is valuable when one battery is not discharged for a long
time
Short Test -Period 24h ~ 8760h 720h If the battery is not discharged within the ‘ShortTest Period’, the controller will start a short
test, whose operation time is set by the parameter ‘ShortTest Time’. By the end of the test, if
the difference in the discharge currents of batteries is bigger than the ‘Short Test Alarm’, the
Short Test -Time 1min ~ 60min 5min battery discharge abnormal alarm will be generated
The stable test is conducted with constant battery discharge current. To execute the stable
Stable Test -Enable Y, N N test, the present load current should be bigger than the current value set by stable test. The
stable test is suitable for bigger load and relative stable load current, otherwise, do not exercise
it. The current value is set through the parameter ‘Stable Test Current’. If the parameter
Stable Test -Current 0A ~ 9999A 9999A ‘StableTest Enable’ is set to ‘Y’, the test will be started once the battery satisfies the test
condition
40
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
2. Press ▲ or ▼ to select the parameter and press or to select the parameter value. Then press the ENT key to confirm.
The value description of the temperature compensation parameters is listed in Table 4.12.
Center Temp 10°C ~ 40°C 25°C FC voltage derated value = (Batt Temp – ‘Center Temp’) * Temp Coeff
Upon alarms such as rectifier communication interruption, DC over/undervoltage or
battery fuse alarm, the controller will not do temperature compensation to the battery
Coeff 0mV/°C ~ 500mV/°C 72mV/°C FC voltage
Batt T H2 50°C When the detected battery temperature is higher than Batt T H2/Batt T H1, the
Batt T H1 50°C controller will generate an alarm
-40°C ~ +100°C
The controller will generate an alarm when the detected battery temperature is lower
Batt T L1 0°C
than Batt T L1
4.7.3 AC Settings
At the Settings screen shown in Figure 4.7, press ▲ or ▼ to select the ‘AC Settings’ menu, and press the ENT key to enter the
screen shown in Figure 4.34.
Press ▲ or ▼ to select the parameter you need and press or to select the parameter value. Then press the ENT key to
confirm. The value description of the AC parameters is listed in Table 4.13.
The controller will generate an AC over-voltage alarm when the AC input voltage is higher than the
Over Volt 50V ~ 300V 280V
setting value
The controller will generate an AC low-voltage alarm when the AC input voltage is lower than the
Low Volt 50V ~ 300V 180V
setting value
Under Volt 50V ~ 300V 80V Set it according to the actual requirement
Set it according to the AC input mode of AC sampling board. Choose ‘N’ if the AC sampling board is
AC In Y, N N
not configured
AC PH 1-PH, 3-PH 1-PH Set it according to the actual requirement
CT Coeff 10 ~ 10000 100 Set it according to AC sampling board parameter
41
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
4.7.4 DC Settings
At the Settings screen shown in Figure 4.7, press ▲ or ▼ to select the ‘DC Settings’ menu, and press the ENT key to enter the
screen shown in Figure 4.35.
Press ▲ or ▼ to select the parameter you need and press or to select the parameter value. Then press the ENT key to
confirm.
OverVolt2 58.5V The DC OverVolt2 alarm will be generated when the system DC voltage is higher than the setting value
OverVolt1 58.5V The DC OverVolt1 alarm will be generated when the system DC voltage is higher than the setting value
40V ~ 60V
LowVolt1 48.0V The DC LowVolt1 alarm will be generated when the system DC voltage is lower than the setting value
LowVolt2 48.0V The DC LowVolt2 alarm will be generated when the system DC voltage is lower than the setting value
Press ▲ or ▼ to select the parameter you need and press or to select the parameter value. Then press the ENT key to
confirm.
Y: The controller will prompt you to set the rectifier position after the rectifier and controller are powered
Position En Y, N N on
N: You do not need to set the rectifier position
The rectifier over-voltage alarm will be generated when the rectifier output voltage is higher than the
HVSD 56V ~ 59V 58.0V
setting value
‘Default V’ output occurs when rectifier communication is interrupted. This setting value must be lower
Default V 48V ~ 58V 53.5V
than the ‘HVSD’ voltage value
Walk-in On Y, N N
It means the rectifier voltage will rise from 0V to the ‘Default V’ value after the ‘Walk-in T’ value
Walk-in T 8s ~ 128s 8s
42
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
The controller can set the DC-DC interval start of the system rectifiers. Start time = rectifier address *
Interval T 0s ~ 10s 0s
interval
The controller can set the rectifier to ‘Over Volt En’, meanwhile, the rectifier can start forcibly. The
AC OverV
Y, N N controller will automatically set the rectifier with least address to have this function. If the rectifier always
On
exceeds the normal voltage for 60s, the function will be canceled automatically
ACCurrLim 1A ~ 50A 30A The controller limits the input current of the rectifier within the AC current limiting range
Press ▲ or ▼ to select the parameter you need and press or to select the parameter value. Then press the ENT key to
confirm.
If the ‘Reset Para’ is set to ‘Y’, press the ENT key will pop up the screen shown in Figure 4.39.
Confirm:
ENT Continue
ESC Quit
43
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Press the ESC key to cancel the resetting. Press the ENT key to execute the resetting. At this time, all the parameters will return
to the default value. It is recommended to execute system resetting when the controller cannot work normally through the
method of powering off or restoration.
If the ‘Reset PWD’ is set to ‘Y’, the password of the controller will be reset to the factory default password after pressing the ENT
key.
Press ▲ or ▼ to select the parameter you need and press or to select the parameter value. Then press ENT to confirm.
Press ▲ or ▼ to select the parameter you need, press or to select the parameter value. Then press the ENT key to confirm.
The value description of the communication parameters is listed in Table 4.18.
Address 1 ~ 254 1 The addresses of power systems that are at the same monitored office should be different
44
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
BaudRate 1200bps ~ 9600bps 9600bps Make sure that the baud rates of both sending and receiving parties are the same
IP/Subnet/Gate / / Set them according to the actual condition
4.7.9 DG Settings
At the Settings screen shown in Figure 4.7, press ▲ or ▼ to select the ‘DG Settings’ menu, then press the ENT key to enter the
password confirmation screen. After inputting the correct password, the screens shown in Figure 4.41 are displayed.
Press ▲ or ▼ to select the parameter you need and press or to select the parameter value. Then press the ENT key to
confirm.
AC Power
Grid, DG, Grid+DG Grid System power supply mode, ‘Grid’ by default
Mode
DG Cap 5.0KVA ~ 100.0KVA 12.5KVA Set it according to actual DG capacity
Dry contact input of DG running state, users can set the DG state by referring to DI settings in
4.7.1 Alarm Settings. For example, if you set ‘DG’ In to ‘DI2’ and the ‘Active’ to ‘Close’, then the DI2
DG In None, DI1 ~ DI8 None
input close represents the DG start running, while the DI2 input open means the DG is not
started
DG Relay None, 1 ~ 8 None Output dry contact signal of DG start/stop, ‘None’ by default, the hardware state is settable
Press ▲ or ▼ to select the parameter you need and press or to select the parameter value. Then press the ENT key to
confirm.
45
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Start DG
Volt 13.2V ~ 60.0V 47.3V Start DG when the battery voltage is lower than the setting value
Y: The system will determine whether start DG according to battery remaining capacity
BattCap En Y, N N
N: The system will not judge the battery capacity
When the ‘BattCap En’ is set to ‘Y’, and the current battery remaining capacity is lower than the
BattCap 10% ~ 95% 50%
‘BattCap’, the DG will be started
Stop DG
Volt En Y, N N When set to ‘Y’, the system will judge whether start DG according to battery voltage
Volt 40.0V ~ 54.0V 53.5V When the battery voltage rises to ‘Volt’ and meets the delay condition, stop the DG
BattCur En Y, N N When set to ‘Y’, the system will judge whether stop DG according to battery charge current
When ‘BattCur En’ is set to ‘Y’, and the battery charge current decreases to ‘Curr’ and meet the
Curr 0.010C ~ 0.060C 0.010C
delay condition, stop the DG
Time En Y, N N When set to ‘Y’, the system will judge whether stop DG according to the setting time
Time 10min ~ 1440min 300min When ‘Time En’ is set to ‘Y’, and the ‘Time’ is reached, stop the DG
Y: The system will determine whether stop DG according to battery remaining capacity
BattCap En Y, N N
N: The system will not judge the battery capacity
When the ‘BattCap En’ is set to ‘Y’, and the current battery remaining capacity is lower than the
BattCap 50% ~ 100% 95%
‘BattCap’, stop the DG
When the battery charge current decrease to the stop DG condition, or the battery voltage rises
Delay 0min ~ 255min 10min
to stop DG condition, and meet the delay time continuously, the DG will be actually stopped
DG Run Time
Max 30min ~ 2880min 1440min After the DG is started, and continuously running to the max. run time, the DG will be stopped
After the DG is started, when meets the stop condition, but the continuous run time doesn’t
Min 5min ~ 720min 10min reach the min. run time, then the DG will keep start state and until reaching the min. run time, will
the DG be stopped
Press ▲ or ▼ to select the parameter you need and press the ENT key to confirm. The value description of the DCEM
parameters is listed in Table 4.21.
DCEM1
-Sh1 Curr 10A ~ 1000A 1000A Current of DCEM1 shunt1
-Sh1 Volt 10mV ~ 100mV 25mV Voltage of DCEM1 shunt1
46
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Press ▲ or ▼ to select the parameter you need, press or to select the parameter value. Then press the ENT key to confirm.
The value description of the DC converter parameters is listed in Table 4.22.
47
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
User 1 settings: at the screen shown in Figure 4.45, press ▲ or ▼ to select the user parameter needs to be set, and press ENT
key to enter the screen shown in Figure 4.46.
The setting screen for User 2, User 3 and User 4 are similar, please refer to User 1 settings screen for your reference.
Factory
Parameter Range Value description
setting
User settings
User 1 settings
User Name CTCC, CUCC, CMCC, Other Other Name of User 1, ‘Other’ by default
LVD Time 3min ~ 2880min 300min LVD time of User 1
LVD Shunt Y, N Y Whether User 1 has shunt
Shunt Coeff-Curr 1A ~ 2000A 100A Shunt current coefficient of User 1, used with voltage coefficient
Shunt Coeff-Volt 1mV ~ 500mV 75mV Shunt voltage coefficient of User 1, used with current coefficient
User 2 settings
User Name CTCC, CUCC, CMCC, Other Other Name of User 2, ‘Other’ by default
LVD Time 3min ~ 2880min 300min LVD time of User 2
LVD Shunt Y, N Y Whether User 2 has shunt
Shunt Coeff-Curr 1A ~ 2000A 100A Shunt current coefficient of User 2, used with voltage coefficient
Shunt Coeff-Volt 1mV ~ 500mV 75mV Shunt voltage coefficient of User 2, used with current coefficient
User 3 settings
User Name CTCC, CUCC, CMCC, Other Other Name of User 3, ‘Other’ by default
LVD Time 3min ~ 2880min 300min LVD time of User 3
LVD Shunt Y, N Y Whether User 3 has shunt
Shunt Coeff-Curr 1A ~ 2000A 100A Shunt current coefficient of User 3, used with voltage coefficient
Shunt Coeff-Volt 1mV ~ 500mV 75mV Shunt voltage coefficient of User 3, used with current coefficient
User 4 settings
User Name CTCC, CUCC, CMCC, Other Other Name of User 4, ‘Other’ by default
48
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Factory
Parameter Range Value description
setting
Press ▲ or ▼ to select the parameter you need, press or to select the parameter value. Then press the ENT key to confirm.
The value description of the DCEM parameters is listed in Table 4.24.
CFG Settings
Fan Num Y, N N The fan number controlled
Temp SRC Temp1, Temp2, Temp3 Temp2 The fan is controlled according to the temperature of selected test object
Fan Mode Exch, Force Exch Fan working mode
MNG Settings
Select ‘Y’ to start the fan test, then estimate the fan status, abnormity will
Fan Test Y, N N generate an alarm; the setting value will automatically return to ‘N’ after the
test is finished
ACOff Fan Stop Y, N Y Whether the fan is operating upon AC power-off
When the temperature of fan 1 is lower than the preseted value, the fan will
Fan Group1-TempofLow 20°C ~ 45°C 40°C run at low speed; when the temperature is higher than the preseted value,
the fan will speed up with the rise of temperature
When the temperature of fan 1 reaches the preset value, the fan will run at
Fan Group1-TempofFull 45°C ~ 80°C 50°C
full speed
Fan Group1-LowSpeed 25% ~ 60% 25% Fan 1 runs at low speed
Fan Group1-HighSpeed 25% ~ 100% 60% Fan 1 runs at high speed
When the temperature of fan 2 is lower than the preseted value, the fan will
Fan Group2-TempofLow 20°C ~ 45°C 40°C run at low speed; when the temperature is higher than the preseted value,
the fan will speed up with the rise of temperature
When the temperature of fan 2 reaches the preset value, the fan will run at
Fan Group2-TempofFull 45°C ~ 80°C 50°C
full speed
Fan Group2-LowSpeed 25% ~ 60% 25% Fan 2 runs at low speed
Fan Group2-HighSpeed 25% ~ 100% 60% Fan 2 runs at high speed
49
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
If you want the system to operate in energy saving mode, set ‘Save Enable’ to ‘Y’, otherwise, set it to ‘N’. Set ‘Cyc Period’ according
to the actual instance. The energy saving operating principle of the system is described below.
1. Operating principle
In energy saving mode, the controller will switch off some rectifiers, the power-on rectifiers will be charged with all loads. Each
power-on rectifier works on the best efficiency to improve utilization ratio of the rectifier and save energy consumption. After
certain time (that is, ‘Cyc Period’ shown in Figure 4.48), the power-off rectifiers will work, and meanwhile, the power-on rectifiers
will stop work. Two states circulate, to make sure that the working hours of the rectifiers in the system approach. If the battery
current and load current change, the controller will switch off some power-on rectifiers or switch on some power-off rectifiers,
according to the actual condition. In any case, the system guarantees at least one rectifier to work.
2. Prerequisite
If the battery is configured and the load current has no instant shock, the system will operate in energy saving mode, that is, ‘Save
Enable’ is set to ‘Y’.
3. Advantage
Balancing working hours of the rectifiers to prolong the life of the rectifier.
In shutdown state, preventing rectifiers from being damaged by AC inrush to reduce lightning fault.
Switch on all the rectifiers when the busbar voltage is faulty (DC over-voltage or under-voltage).
Switch on all the rectifiers when a rectifier alarm (communication interruption) is generated.
Switch on all the rectifiers automatically when the system has no controller or the communication between the rectifier
and the controller is interrupted.
Delay implementation when the rectifier receives shutdown command, immediately execute when the rectifier receives
startup order.
The value description of the energy saving parameters is listed in Table 4.25.
Save Enable Y, N N It can be set to ‘Y’ only when the battery is configured and the load current without instant shock
Time of rectifier is in power-on state and power-off state, it can be set according to the actual
Cyc Period* 1h ~ 8760h 48h
requirement
50
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Rect Work 30% ~ 90% 90% Output capacity percentage. More rectifiers will start to work when larger than this setting percentage
Rect Limit 1 ~ 30 1 Minimum number of the rectifier in energy saving state
Note*: Cyc Period, Rect Work and Rect Limit are available only when ‘Save Enable’ is set to ‘Y’
System Type:
48V/SET
Capacity: 500AH
At the Fast Settings screen, you can set the system type and battery capacity, as listed in Table 4.26.
48V/100 The system type of the controller has been set according to the actual instance before
48V/300 the controller is delivered with power supply system. You do not need to change the value
except that the controller needs to be replaced with a new one
System Type 48V/500 48V/300
After changing the type, the controller will restart and other parameters will resume the
48V/1000 default. You need to reset and change some parameters according to the battery and
48V/SET equipment configured with the system
The capacity of the total batteries connected with each shunt. You should set this
Capacity 20Ah ~ 5000Ah 500Ah
parameter according to the actual battery configuration
51
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Power indicator off No alarm Change the position of the abnormal rectifier and
Auxiliary power source failure normal rectifier, if the abnormal rectifier does not
work, replace the rectifier
Remove any object that may be blocking a fan
Fan rotor blocked
rotor
Remove any object that may be blocking the inlet
Rectifier over-temperature Ventilation blocked
or outlet
Ambient temperature too high or Lower the ambient temperature; relocate the heat
rectifier inlet too close to a heat source source
Check whether the communication of the rectifier
Protection indicator on is normal, if no, check whether the communication
Rectifier load sharing imbalance
cable connection is normal, if the connection is
abnormal, replace the faulty rectifier
Rectifier protection Change the position of the abnormal rectifier and
PFC output over/under voltage
normal rectifier, if the abnormal rectifier does not
protection
work, replace the rectifier
Correct the AC input voltage to within the
AC input out the normal range
acceptable range
Rectifier communication Communication failure between Check whether the communication cable
Protection indicator flashing
failure controller and rectifier connection is normal
Pull out the rectifier and restart, if overvoltage
Rectifier overvoltage
persists, replace the rectifier
Rectifier failure
Two or more rectifiers have the same ID
Contact Vertiv for repair
in one system
Fault indicator on
Check whether the communication of the rectifier
System current sharing is normal, if no, check whether the communication
Rectifier severe load sharing imbalance
imbalance cable connection is normal, if the connection is
abnormal, replace the faulty rectifier
Fault indicator flashing Faulty rectifier fan Faulty rectifier fan Replace the fan
52
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Rear panel
There are AC input socket and DC output socket on the rear panel of the rectifier, as shown in Figure 5.2.
J1 Rectifier 1 AC input
J2 Rectifier 2 AC input
J3 Rectifier 3 AC input
AC input socket J4 Rectifier 4 AC input
J5 Rectifier 5 AC input
J6 Rectifier 6 AC input
PE Rectifier AC earthing
J11 ~ J16 Negative pole of the DC output
J21 ~ J26 Positive pole of the DC output
DC output socket
J7 CAN/matching resistance
J8 Matching resistance/CAN
Active load-sharing
When the loads (60 rectifiers at most) range from 10% to 100%, rectifiers in the same cabinet can perform load sharing, and
maintain the average current difference of the rectifiers within ±2A. Current sharing condition: 220V input, 53.5V output, loads
range from 10% to 100%.
53
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Output power vs. Input voltage at Temp≤ 35℃ and Vo≥ 48V
120.0%
% of output power
100.0%
80.0%
60.0%
40.0%
20.0%
0.0%
0 40 80 120 160 200 240 280 320
Input voltage (Vac)
Output characteristics
The relationship between output voltage and current is listed in Table 5.4.
54
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
120
100
% of output power
80
60
40
20
0
-40 -20 0 20 40 60 80
Temperature (℃ )
Fan control
When the input voltage is in the normal range, the in-built processor will regulate the fan speed (stepless regulation) according to
the internal temperature and output power of the rectifier. For example, the fan speed increases with the rectifier temperature or
the output power. The rectifier can be set to full speed through the corresponding controller.
When the input voltage exceeds 305Vac, the yellow indicator will be on, and the rectifier will stop working. When the input voltage
returns to the normal range, the rectifier will automatically work in normal state.
The rectifier will report the event to the controller when overvoltage protection occurs.
Once the output voltage reaches software protection point, the rectifier will shut down and hold that state. It requires manual
resetting to restore the operation.
When the output voltage reaches the software protection point, the rectifier will shut down, and restart automatically after 5
seconds. If the overvoltage happens again within a set time (default: 5min. Configurable through controller), the rectifier will shut
55
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
down and hold that state. It requires manual resetting to restore the operation. If the output current is less than 10 percent of the
rated output current, the rectifier will not shut down.
Manual resetting: Resetting can be done manually through the controller, or by removing the rectifier from system.
NOTE! If the output current is less than 10 percent of the rated output current, the rectifier will not shut down.
2. Overvoltage hardware protection: When the output voltage (unadjustable) reaches the hardware protection point (58.5V ~
60V), the rectifier will shut down, and restart automatically after 5 seconds. If the overvoltage happens again within a set time
(default: 5min. Configurable through controller), the rectifier will shut down and hold that state. It requires manual resetting to
restore the operation.
Overtemperature protection
Power limiting based on temperature
Each rectifier monitors the working temperature of the power-switching circuit. No matter in what reason (for instance, high
ambient temperature or fan fault) the temperature increase +35°C, the rectifier will not power off. But it will limit the maximum
power output, and then turn into the power limiting status to guarantee the power-switching circuit temperature is in the setting
range. The operation at temperature from +35°C to +70°C will minimize the output power. When the temperature dropped to
about +35°C, the full power will restore.
WARNING! 1. The continuous running rated full power output temperature of the rectifier reaches up to +35°C full power.
The operation at the temperature from +35°C to +70°C will minimize the output power. The operation at temperature
above +70°C is abnormal, the running is temporary.
2. Temporary running at abnormal temperature: The continuous running time for temporary running in one day cannot
exceed 8 hours, in one year cannot exceed 15 days (that is, it cannot exceed 120 hours in one year, the frequency cannot
exceed 15 days).
Communication failure
The yellow indicator on the rectifier panel will flash when the rectifier experiences a communication failure. To protect the battery,
when the rectifier communication failure occurs, the rectifier output voltage will automatically adjust to 53.5V (default value,
configurable through controller). The yellow indicator on the rectifier panel will be normal when the rectifier communication is
restored. Auto-recovery is enabled upon the clearing of the corresponding fault.
The failure information will be reported to the associated system controller and the controller will process the failure accordingly.
Monitoring function
There’s a built-in digital signal processor in the rectifier. The processor monitors and controls the rectifier operation, and
communicates with the controller in real time through the CAN bus. Table 5.5 lists the exchanged commands and information
between the rectifier and controller.
56
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Input voltage, output voltage, output current, current limiting setting, temperature, overvoltage setting,
power on/off status, fault alarm (overvoltage shutdown, fan fault), protection information (input voltage
Controller information reported by the rectifier protection, internal busbar voltage protection, high temperature protection), high temperature derating,
input derating, input power failure, output current not sharing, address, code, date, software version,
hardware version
Operating temperature -5°C ~ 40°C (derating is necessary above 35°C, startup in -40°C)
Relative humidity ≤ 95%, non-condensing
Environmental
Altitude ≤ 2000m, derating is necessary above 2,000m
Cooling mode Forced cooling
Input system 1-phase 3-wire
Voltage range 85Vac ~ 305Vac
Rated voltage 200Vac ~ 240Vac
Max. static voltage upon no operation 415Vac
AC input Input current < 22A
Impact current upon startup < 31A
Input impact current < 150% steady state input peak current
Allowable grid frequency 45Hz ~ 65Hz
Rated grid frequency 50Hz/60Hz
Voltage range 42V ~ 58V
DC current 0A ~ 62.5A
Total regulation ≤ ±0.6%
DC output
Load regulation ≤ ±0.5%
Voltage regulation ≤ ±0.1%
Startup impact range ≤ ±1%
Dimension 43.6mm (H) × 85.1mm (W) × 330mm (D)
Mechanical parameters
Weight ≤ 3kg
57
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
6 Troubleshooting
This chapter describes the handling of alarms, as well as the preventive maintenance of the power system during system daily
operation.
The maintenance personnel must have adequate knowledge about the power system.
NOTE! 1. The maintenance must be conducted under the guidance of related safety regulations.
2. Only the trained personnel with adequate knowledge about the power system can maintain the inner part of the
cabinet.
If the failure does not last long, the battery will power the load. If the cause is unknown or the failure lasts too long, a diesel
1 Mains Failure generator is needed. Before using the generator power to supply the power system, it is suggested to run the generator five
minutes to minimize the impact on the power system
Check if the AC over-voltage value is too low. If yes, change the value
2 AC Voltage High A mild over-voltage does not affect the system operation. However, the rectifier will stop operation when the mains voltage
is more than 530V. If the mains voltage is above the AC over-voltage value, the mains grid should be improved
Check if the AC Under- voltage point is too high. If yes, change the value
3 AC Voltage Low When the mains voltage is lower than 304V, the output power of the rectifiers will be derated. And if lower than 260V, the
rectifiers will stop working. If the mains voltage is under the AC under-voltage value, the mains grid should be improved
4 SPD failure Check the SPD condition. If the SPD is damaged, replace it
Check the DC over-voltage value through the controller. If the set value is inappropriate, correct it. Otherwise, find out the
rectifier that has caused the alarm:
1. Ensure that the batteries can operate normally
5 DC Volt High
2. Switch off the AC input of all rectifiers
3. Power on the rectifiers one by one
4. If the over-voltage protection is triggered when a certain rectifier is powered on, that rectifier is the faulty one. Replace it
1. Check if the alarm is caused by mains failure, if yes, disconnect some loads to prolong the operation of the whole system
2. Check the DC under-voltage value set through the controller. If the set value is inappropriate, correct it
6 DC Volt Low 3. Check if any rectifier is inoperative or has no output current. If yes, replace it
4. Check if the total load current exceeds the total rectifier current during float charge. If yes, disconnect some loads or add
more rectifiers to make the total rectifier current bigger than 120% of the total load current with one redundant rectifier
Load Fuse Alarm, Batt Check if the corresponding MCB is switched off. If the MCB is open, find out the fault and remove it. Otherwise, the alarm
7
Fuse Alarm circuit is faulty. Please contact Vertiv
1. Check if there is mains failure, and the battery voltage is lower than the value of ‘LVD2’
8 LVD2
2. Check whether the battery is disconnected from the system manually
58
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
The methods to handle the fault of the rectifier are listed in Table 6.3.
59
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Red indicator
Rect Fan Fails Fan fault Replace the fan
flashing
Rectifier replacement
Other than a rectifier fan replacement, no attempt should be made to troubleshoot or repair individual components on any
rectifier. Apply the product according to the rated power of the product. If the module unit inserted in the system fails, please
return to the manufacturer for repair. You should take the following procedures when a rectifier is faulty.
1. Performing this procedure may activate external system alarms. Do one of the following. If possible, disable these alarms. If
these alarms cannot be easily disabled, notify the appropriate personnel to disregard any future alarms associated with this
system.
2. On the module being replaced, loosen the screw that is located on the module handle. (Turn the screw several turns
counterclockwise to loosen.) Pivot the handle 90 degrees to the open position.
3. Grasp the handle and pull firmly to remove the module from the shelf.
4. On the replacement module, loosen the screw that is located on the module handle. (Turn the screw several turns
counterclockwise to loosen.) Pivot the handle 90 degrees to the open position.
5. Place the module into the mounting position in the shelf, and with the handle still in the open position, push the module
completely into the shelf.
6. Push the handle into the front panel of the module. This will lock the module securely in the shelf. Tighten the screw on the
handle.
8. Enable the external system alarms or notify appropriate personnel that this procedure is finished.
9. Ensure that there are no local or remote alarms active on the system.
60
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
1. Loosen the three fixing screws on the controller to remove the cover plate, as shown in Figure 6.2.
LCD
2. Estimate fault causes according to the indicator status of the PCB board, as listed in Table 6.4.
61
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
The indicators and terminals of the PCB board are shown in Figure 6.3. The function of terminals is described in Table 2.4.
3. Wrap the DI/DO cable terminals with insulating tape. To prevent short circuit, keep the disconnected terminals and cables
insulated from components of the power system and the PCB.
4. Remove the fixing screws of the PCB and replace the PCB. Note that the screwdriver should be prevented from touching the
bare parts of the signal cables to prevent short circuit.
5. Connect the signal cables in reverse sequence, that is, reconnect signal cables other than J8, J10 terminal cables and DI/DO
cables.
6. Check the cable connections. If the connections are correct, reconnect J8 terminal. If the watchdog indicator flashes and power
indicator is on, the PCB works normally.
7. Check the voltages of J10 terminal with a multimeter. Make sure that it outputs low voltage. Connect J10 terminal.
8. Set the parameters of the controller according to 4.7 Setting System Parameters.
2. Unplug the terminal tape cable connected the LCD and screen.
3. Replace the LCD. Restore the J3 terminal tape cable connected the LCD and screen. Pay attention not to short the LCD with
the power system or the PCB.
4. Check the voltages of J10 terminal with a multimeter. Make sure that it outputs low voltage.
62
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Rated voltage Rated current Temperature rise Rated loss power Weight
Model Breaking capacity
(DC) (V) (A) (K) (W) (kg)
4
6
10
16
20
25
32
40
50
63
80
100
RT302-00 80 ≤ 70 ≤ 30 ≤ 0.23 25KA
125
160
200
224
250
300
315
355
400
425
500
600
63
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
NOTE! 1. When the number of solar modules is less than the full configuration, the dummy plate should be installed in
time.
2. It is not allowed to connect the positive and negative poles of the 1-route solar system to the positive and negative
poles of the 2-route solar modules respectively.
3. For the specific methods of installing and commissioning HSS48100/XMX-1 1U solar subrack, please refer to
HSS4850/XMX-1, HSS48100/XMX-1 1U Solar Subrack User Manual delivered with the package.
64
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Connect the output cable of the solar subrack to the corresponding position of the power system, as shown in Figure 7.2.
The rear panel of the solar subrack provides two signal interfaces: lightning protection alarm terminal and CAN communication
terminal, as shown in Figure 7.3.
A A amplified
Wiring method
The HSS48100/XMX-1 1U solar subrack has no controller, and its CAN communication terminals need to be connected to the
CAN terminals of the rectifier subrack of the power system (unplug the matching resistor at the end of the power system, and
connect the CAN interfaces of the rectifier subrack to the CAN communication terminals of the solar subrack).
65
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
The lightning protection signal cables of the solar subrack need to be connected to the M530S controller, as shown in Figure 7.4
(pins J5-3 and J5-4 of the controller).
Figure 7.4 Connecting lightning protection signal cables of the solar subrack
Wiring steps
1. Remove the terminal baffle plate on the rear panel of the solar subrack.
2. Loosen the captive screws by hand and pull the terminal base out about 20mm.
3. Put the lightning protection signal cables and the CAN communication cables into the terminals and install the captive screws
with a slotted screwdriver, as shown in Figure 7.5.
松不脱螺钉(2颗)
连接防雷信号电缆 连接CAN信号电缆
4. After the lightning protection signal cables and the CAN communication cables are connected, push the terminal base firmly
inward, and after pushing it in place, tighten the captive screws by hand.
Setting
1. MAIN MENU Settings Sys Settings Sys Work Mode AC + Solar.
66
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
3. MAIN MENU Settings Bat. Settings Rect FC (Lead-acid battery: cell float charge mark × 24; lithium battery: refer to
lithium battery string float charge setting).
4. MAIN MENU Settings Bat. Settings Rect BC (Lead-acid battery: cell boost charge mark × 24; lithium battery: refer to
lithium battery string boost charge setting).
5. MAIN MENU Settings Bat. Settings Float (the settable float charge voltage of the solar subrack should be 0.5Vdc ~
0.7Vdc higher than float charge voltage of the rectifier).
6. MAIN MENU Settings Bat. Settings Boost (the settable boost charge voltage of the solar subrack should be 0.5Vdc ~
0.7Vdc higher than boost charge voltage of the rectifier).
7. MAIN MENU Settings Alarm Settings DI Settings, on the DI Settings screen, change the value of ‘DI No: 1’ to
‘MPPTspd1 Alarm’, and change the value of ‘Active’ to ‘Open’.
8. MAIN MENU Settings Alarm Settings Alarm Level, on the Alarm Type: 3/85 screen, change the value of ‘Level’ to ‘MA’.
9. MAIN MENU Settings Alarm Settings Alarm Level, on the Alarm Type: 58/85 screen, change the value of ‘Out Relay’
from 3 to ‘No’.
67
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
8 Technical Data
Table 8.1 Technical data
AC input alarm and AC input under-voltage recovery point Default: 190Vac ± 5Vac, 10Vac higher than the AC input under-voltage alarm point
protection AC input over-voltage protection point Default: 305Vac ± 5Vac, configurable through controller
AC input over-voltage protection recovery point 10Vac lower than the AC input over-voltage protection point
AC input under-voltage protection point Default: 80Vac ± 5Vac, configurable through controller
AC input under-voltage protection recovery point 15Vac higher than the AC input under-voltage protection point
DC output over-voltage alarm point Default: 58.5Vdc ± 0.2Vdc, configurable through controller
DC output over-voltage recovery point Default: 58.0Vdc ± 0.2Vdc, 0.5Vdc lower than the over-voltage alarm point
DC output under-voltage alarm point Default: 45.0Vdc ± 0.2Vdc, configurable through controller
DC output alarm and
DC output under-voltage recovery point Default: 45.5Vdc ± 0.2Vdc, 0.5Vdc higher than the under-voltage alarm point
protection
DC output over-voltage protection point Default: 44.0Vdc ± 0.2Vdc, configurable through controller
LLVD Default: 43.2Vdc ± 0.2Vdc, configurable through controller
BLVD Default: 58.5Vdc ± 0.2Vdc, configurable through controller
The rectifiers can work in parallel and share the current. The unbalance is better
Load sharing
than ±5% rated output current
Rectifier 176Vac input, rectifier outputs 100% power (3000W); when the input voltage is
Derate by input (at 45°C) between 85Vac and 176Vac, the rectifier adopts two linear power limit controls; input
below 80Vac, rectifier will shut down due to undervoltage
68
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Upon rectifier power-on, the output voltage increases slowly, and the rise time can
Slow output start function
be set
The rectifier fan speed can be set to be regulated automatically. It can also be set to
Fan speed can be set
full speed
The rectifier provides over-voltage hardware and software protection. The hardware
protection point is 59.5V ± 0.5V, and it requires manual resetting to restore
operation. The software protection point is between 56V and 59V (0.5V above
output voltage, 58.5V by default), and can be set through the controller
There are two software protection modes, which can be selected through the
software at the host:
1. Lock out at the first over-voltage
Once the output voltage reaches protection point, the rectifier will shut off and hold
Over-voltage protection
Rectifier that state. it requires manual resetting to restore the operation
2. Lock out at the second over-voltage
When the output voltage reaches the software protection point, the rectifier will shut
down, and restart automatically after 5 seconds. If the over-voltage happens again
within a set time (default: 5min. Configurable through controller), the rectifier will
shut off and hold that state. It requires manual resetting to restore the operation
Manual resetting: Resetting can be done manually through the controller, or by
removing the rectifier from system
The rectifier can be started at -40°C ambient temperature
Temperature below 45°C, rectifier outputs full power: 3000W
Temperature derating Linear power drop from 3000W to 2900W at 45°C ~ 55°C
55°C ~ 65°C, the linear derating from 2900W to 2250W
65°C ~ 70°C, the linear derating from 2250W to 0W
Conducted emission
Class A EN300386
Radiated emission
Immunity to EFT Level 4 EN/IEC 61000-4-4
EMC Immunity to ESD Level 3 EN/IEC 61000-4-2
Immunity to surges Level 4 EN/IEC 61000-4-5
Immunity to radiation Level 3 EN/IEC 61000-4-3
Immunity to conduction Level 3 EN/IEC 61000-4-6
The AC input side can withstand five times of simulated lightning current of 20kA at
8/20μs, for the positive and negative polarities respectively. It can withstand one
At AC side time of simulated lightning surge current of 40kA at 8/20μs, for the positive and
Lightning protection negative polarities respectively. The test interval is not smaller than 1 minute (each
features phase has at least two rectifiers)
The DC side can withstand five times of simulated lightning current of 20kA at
At DC side 8/20μs, for the positive and negative polarities respectively. The test interval is not
smaller than 1 minute (at least two rectifiers)
Safety Meet the criteria of EN 62368-1
Acoustic noise When the ambient temperature is 25°C, under full load, no more than 60dB (A)
At temperature of 25°C ± 5°C and relative humidity not bigger than 90%RH, apply a
Insulation resistance test voltage of 500Vdc. The insulation resistances between AC circuit and earth, DC
circuit and earth, and AC and DC circuits are all not less than 2MΩ
Remove the SPD, controller and rectifiers from the power system before the test
Others AC to DC circuits: 50Hz, 3000Vac or 4242Vdc
AC circuit to earth: 50Hz, 2500Vac or 3535Vdc
Insulation strength
DC circuit to earth: 50Hz, 1000Vac or 1414Vdc
For all the three tests above, there should be no breakdown or flashover within 1min,
with leakage current less than or equal to 10mA
MTTF > 100000hr
ROHS Compliant with R10 requirement
69
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
70
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
9 Engineering Diagram
Figure 9.1 NetSure 731 CK2-Y3 engineering diagram (unit: mm)
600
233
469 468
548 473
705
1132
2000
71
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Factory
Item Parameter Range Value description
setting
LVD1 Volt 44.0V Select battery voltage, when the battery voltage is lower
LVD than the preset LVD1 Volt, the load will be disconnected,
40V ~ 60V
and so does the battery when the battery voltage is lower
LVD2 Volt 43.2V than the preset LVD2 Volt
LVD1Time 300min Select battery discharge time, when the battery discharge
time reaches the preset LVD1Time, the load will be
3min ~ 600min
disconnected, and so does the battery when the battery
LVD2Time 600min voltage reaches the preset LVD2Time
Battery Float 53.5V Battery float charge voltage
42V ~ 58V Battery boost charge voltage, and the ‘Boost’ must be
Boost 56.4V
higher than the ‘Float’
Limit 0.100C10 ~ 0.250C10 0.100C10 Maximum battery charging current
Over 0.300C10 ~ 1.000C10 0.300C10 Battery charge over-current alarm point
Auto Boost -Enable Y, N Y Enable or disable this function
0.050C10 ~ The controller will control the system enter the BC state
Auto Boost -Current 0.060C10
0.080C10 when the battery capacity decreases to the value of ‘To
Boost Cap’, or when the charge current reaches the ‘To
Auto Boost -Cap 10% ~ 99% 80% Boost Current’. The charge voltage will be the Boost state
Charge Const Boost -Current 0.002C10 ~ 0.020C10 0.020C10 The system in BC state will enter the FC state when the
charge current decreases to the ‘Const Boost Current’
management value and after the ‘Const Boost Time’ value. The battery
Const Boost -Time 30min ~ 1440min 180min charge voltage then will be the Float state
Cyc Boost -Enable Y, N Y Enable or disable this function
Cyc Boost -Period 48h ~ 8760h 2400h The ‘Cyc Boost Period’ means the interval between the two
cyclic boost charge. The battery charging voltage is the
Cyc Boost -Time 30min ~ 2880min 720min preset ‘Boost’, and the time is the preset ‘Cyc Boost Time’
To ensure the system safety, the controller will forcefully
BoostLimitTime 60min ~ 2880min 1080min control the system to enter the FC state from the BC state,
if the boost charge time reaches the ‘BoostLimitTime’
DG Chg Limit -Enable Y, N N Whether using this function
0.050C10 ~
DG Chg Limit -Current 0.050C10 /
0.080C10
72
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Factory
Item Parameter Range Value description
setting
End Test -Volt 43.1V ~ 57.9V 45.2V The controller will stop the test if the battery voltage
reaches the ‘End Test Volt’, or the discharge time reaches
End Test -Time 5min ~ 1440min 300min
the ‘End Test Time’, or the battery capacity reaches the
End Test -Cap 0.01C10 ~ 0.95C10 0.70C10 ‘End Test Cap’
Short Test -Alarm 1A ~ 100A 10A If the battery is not discharged within the ‘Short Test
Period’, the controller will start a short test, whose
Short Test -Period 24h ~ 8760h 720h operation time is set by the parameter ‘Short Test Time’. By
the end of the test, if the difference in the discharge
currents of batteries is bigger than the ‘Short Test Alarm’,
Short Test -Time 1min ~ 60min 5min the battery charge abnormal alarm will be generated
Stable Test -Enable Y, N N Whether using the stable test function
Stable Test -Current 0A ~ 9999A 9999A Battery discharging current upon stable test
Battery FC voltage derated value = (Batt Temp – ‘Center Temp’) *
Center Temp 10°C ~ 40°C 25°C Temp Coeff
When an alarm such as rectifier communication
interruption, DC overvoltage or undervoltage, or battery
0mV/°C ~
Coeff 72mV/°C branch disconnection is detected, the controller will not do
500mV/°C
temperature compensation to the battery FC voltage
Temp1 Batt Temp
Temperature Amb Temp, None, Measure ambient temperature, battery temperature, or
coefficient Temp2 None
Batt Temp nothing
Temp3 None
Batt T H2 -40°C ~ +100°C 50°C When the detected battery temperature is higher than Batt
Batt T H1 -40°C ~ +100°C 50°C T H2 / Batt T H1, the controller will generate an alarm
73
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Factory
Item Parameter Range Value description
setting
Shunt Coeff -Current 1A ~ 5000A 500A They can be reset when the shunt options are ‘48V/SET’ in
DC
Shunt Coeff -Volt 1mV ~ 500mV 25mV the system with load shunt
74
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Factory
Item Parameter Range Value description
setting
75
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Factory
Item Parameter Range Value description
setting
76
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
Factory
Item Parameter Range Value description
setting
77
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
78
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
79
Vertiv™ NetSure™ 731 CK2-Y3/Y4 Power System User Manual
https://www.instagram.com/vertiv/
https://www.linkedin.com/company/vertiv/
https://www.twitter.com/vertiv/
Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2022 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv
Group Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective
owners. While every precaution has been taken to ensure accuracy and completeness here, Vertiv Group Corp. assumes no
responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions.
Specifications, rebates and other promotional offers are subject to change at Vertiv’s sole discretion upon notice.
NetSure 731 CK2-Y3/Y4 (BOM: 31014611) _REV1.0