Aquedut Design
Aquedut Design
Aquedut Design
STRUCTURE
Example:
Design one aqueduct 1.5m wide and 1m deep. The aqueduct is
expected to carry water with a maximum depth of flow of High of
water = 0.7m
Wide of aqueduct = 1.5m
Span of aqueduct = 9m
Unite weight of concrete = 2400kg/m3
Unite weight of soil in bed of wash = 1600kg/m3
Yield stress of steel or fy = 2500 kg/cm2
Compression strength of Concrete fc = 250kg/cm2
Design of Aqueduct
A
B
A
B
Design of Aqueduct
Design of Aqueduct
2-Design of Beam
Step 1 : Wide of beam
span 900
wide 30 cm
30 30
Step 2 : Calculatio n of Loads
DL
weight of slab 0.75 0.15 2400 270kg/m, weight of beam 0 . 3 1 . 15 2400 828 kg / m
Total DL 1098 kg / m
LL :
weight of water 0 . 7 0 . 75 1000 525 kg / m ,
Factor load 1 . 7 LL 1 . 4 DL 1 . 7 525 1 . 4 1098 2429 . 7 kg / m
Step3 : Mide Span Moment
wl 2 2429 . 7 9 9
Mu 24600 . 7 kg m
8 8
Step4 : Reinforcem ent
Mu 24600 . 7 10 1000
As 1286 . 3 mm 2
fy ( 0 . 85 d ) 0 . 9 250 0 . 85 1000
As 12 . 86 cm 2
Design of Aqueduct
Design of Aqueduct
3-Design of Bracket
Step 1 : Calculation of loads
DL
1 - weight of aqueduct
slab 2.1 0.15 9 2400 6804kg , wall 1 0.3 2 9 2400 12960kg
2 - weight of bracket :
0.3 2.6 0.6 2400 1123.2kg
0.25 2 0.6 1.15 2400 720kg
0.7 0.3 0.6 2400 302.4kg
0.25 0.3
2 0.6 2400 410.4kg
2
Total 22320kg 22.32ton
L.L 1.5 0.7 9 100 9450kg
Design of Aqueduct
Factor load 1.4 DL 1.7 L.L 1.4 22.32 1.7 9.45 47.31ton
4-Design of Column
Step 1 : Loads
D.L 22 .32 ton , L.L 9.45ton
Total load 473 KN
lef 11m
assume 1% of steel
c 5 N / mm 2 , s 130 N / mm 2
P c ( A 0.01 A) c 0.01 A 473000 6 .25 A
A 75680 D 310 mm
lef 11000
36 12 so it is long column
D 310
Step2 : Calculatio n of P
P lef 36
P C r 1.25 C r 1.25 C r 0 .5
Cr 48 D 48
Design of Aqueduct
P 473000
P 946000 6 . 25 A A 151360 mm 2
Cr 0 .5
D 440 mm D 500 mm
Step 3 : Calcuation of Steel :
D 2 3 . 14 500 2
As 0 . 01 A 0 . 01 0 . 01 1962 . 5 mm 2 20 cm 2
4 4
Use 10 16mm
Design of Aqueduct
B B
Design of Aqueduct
Design of Footing
1 - Loads
D . L 22 . 32 Ton W of Column 22 . 32 5 . 2 27 . 5 Ton
L . L 9 . 45 Ton
f ' c 200 kg / cm 2
fy 2500 kg / cm 2
q ul of Soil Assume 1 . 5 kg / cm 2
d 0 . 64 cm h 0 . 64 0 . 06 0 . 7 m
b check for one way shear : -
2.1
X ( 0 . 225 d )
2
X 1 . 05 0 . 225 d x 0 . 825 d
fy
129 . 92 { 2 . 1 ( 0 . 825 d )} V ul 0
V ul 129 . 92 {1 . 7325 2 . 1 d } 225 . 1 272 . 8 d
V ul 225 . 1 272 . 8 d
V n1 2 f 'c
bd 0 . 85 2 . 1 d
f ' c 200 kg / cm 2 2857 . 14 psi 2 2857 . 14 106 . 9 psi 736 . 83 kpa
225 . 1 272 . 8 d
736 . 83 225 . 1 272 . 8 d 736 . 83 ( 0 . 85 2 . 1 d )
0 . 85 2 . 1 d
225 . 1 272 . 8 d 1315 . 24 d
d 14 cm
So, select d 0.64m cover 70cm
Design of Aqueduct
2 2
As 7 .16
act 0 .00053
bd 210 64
14 14
min 0 .0056
fy 2500
act min So, use min
As min min b d 0 .0056 2 .1 0 .64 75 cm 2
75
No. of bar 23 .8 24 20 mm
(2) 2
4
Design of Aqueduct
Use 5 16mm
Check the developmen t length
db 16
L d1 0 . 25 fy 0 . 25 250 223 . 6 mm 23 cm
'
f c 20
L d 2 0 . 04 ( 250 ) 16 160 mm 16 cm
L d 3 8 in 200 mm 20 cm
Use 23cm
Design of Aqueduct
B B
Design of Aqueduct
Design of Aqueduct
Design of Aqueduct