RAR Photocell

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

7 713

ISO 9001

Selenium Photocell RAR...


Detectors

The selenium photocell detectors are designed for use with burner controls, for
the supervision of oil flames.
They are used especially in connection with burner controls for the control and
supervision of large-capacity burners.

The RAR... and this Data Sheet are intended for use by OEMs which integrate the
flame detectors in their products!

Use

The RAR... flame detectors are used for the supervision of yellow-burning oil flames.

They are designed for use with the following types of burner controls: LAL..., LAE1...,
LOK16... and LAE10...

CC1N7713en
Siemens Building Technologies
09.10.2002 HVAC Products
Warning notes

To avoid injury to persons, damage to property or the environment, the following


warning notes should be observed!

Do not open, interfere with or modify the flame detector!

· Before performing any wiring changes in the connection area of the detector, com-
pletely isolate the equipment from the mains supply (all-polar disconnection)
· Ensure protection against electric shock hazard by providing adequate protection
for the connection terminals
· Check to ensure that wiring is in an orderly state and that the wires are firmly con-
nected
· Fall or shock can adversely affect the safety functions. Such flame detectors or
burner controls may not be put into operation, even if they do not exhibit any dam-
age

Mounting notes

· Ensure that the relevant national safety regulations are complied with
· The flame detector plugs into the burner (the detector’s clamp engages on the
burner’s light metal flange)

Installation notes

· Installation work must be carried out by qualified staff


· Always run the high-voltage ignition cables separate from the unit and other cables
while observing the greatest possible distances

Electrical connection of the flame detector

It is important to achieve practically disturbance- and loss-free signal transmission:


· Never run the detector cable together with other cables
– Line capacitance reduces the magnitude of the flame signal
– Use a separate cable
· Observe the permissible detector cable lengths (refer to «Type summary»)

Commissioning notes

· Commissioning work must be carried out by qualified staff


· The intensity of light radiation on site is checked by measuring the detector current

Measuring circuit 22 24 LAL2.../LAL3...


22 24 LOK16...
9 10 LAE10...
- + 14 13 LAE1...
M
7713v01/9512

A
-

+
RAR

Legend A Incidence of light


M Microammeter (DC), internal resistance 5,000 W

Measuring circuit for measuring the detector current. For the minimum detector currents
required, refer to the Data Sheet of the relevant burner control.

2/4

Siemens Building Technologies CC1N7713en


HVAC Products 09.10.2002
Service notes

· Maintenance work must be carried out by qualified staff


· Each time a unit has been replaced, check to ensure that wiring is in an orderly
state and that the wires are firmly connected

Disposal notes

The flame detector contains electrical and electronic components and may not be dis-
posed of together with household waste.
Local and currently valid legislation must be observed.

Mechanical design

- Housing made of dust-proof duroplast


- Photocell is under protective glass
- Flame detector can be supplied with or without flange and clamp (refer to «Type
summary»)

Type summary

Type reference Length of detector cable Flange and clamp


RAR7 Up to 20 m Without
RAR7(1) Up to 20 m With
RAR8 Up to 100 m Without
RAR8(1) Up to 100 m With

When ordering, please give the type reference according to «Type summary».

Accessories

Item Part number


Flange with radius 4 241 8855 0
Flange straight 4 241 8898 0
Clamp 4 199 8806 0

Technical data

General data Safety class I


Degree of protection IP 40
Mounting position optional
Weight approx. 85 g

Environmental Transport DIN EN 60 721-3-2


conditions Climatic conditions class 2K2
Mechanical conditions class 2M2
Temperature range -20...+60 °C
Humidity < 95 % r.h.
Operation DIN EN 60 721-3-3
Climatic conditions class 3K5
Mechanical conditions class 3M2
Temperature range -20...+60 °C
Humidity < 95 % r.h.

Condensation, formation of ice and ingress of water are not permitted!

3/4

Siemens Building Technologies CC1N7713en


HVAC Products 09.10.2002
Function

With this type of flame supervision, the radiation of oil flames in the visible band of the
light spectrum is used for generating the flame signal.
The light-sensitive element is a selenium photocell. When illuminated, it generates DC
voltage, causing a current to flow to the input of the flame signal amplifier. Hence, the
RAR... is an active detector.
The selenium photocell is insensitive to infrared radiation so that glowing firebrick in the
combustion chamber cannot produce a flame signal.

Dimensions

Dimensions in mm

130
10
49...73 2,5
30

M4
18
48
18

7713m01/0597
ø22,5
ø23

ã2002 Siemens Building Technologies


4/4 Subject to change!
Siemens Building Technologies CC1N7713en
HVAC Products 09.10.2002