Lmo14 Series
Lmo14 Series
ro
7 130
The LMO14..., LMO24..., LMO44... and this Data Sheet are intended for use by
OEMs which integrate the burner controls in their products.
Use, features
Use The LMO... are designed for the startup and supervision of 1- or 2-stage forced draft oil
burners in intermittent operation. Yellow-burning flames are supervised with photo
resistive detectors QRB..., blue-burning flames with blue-flame detectors QRC...
In terms of housing dimensions, electrical connections and flame detectors, the LMO...
are identical with the LOA... oil burner controls.
CC1N7130en
Building Technologies Division
22.08.2013 Infrastructure & Cities Sector
Warning notes
To avoid injury to persons, damage to property or the environment, the following
warning notes must be observed!
x All activities (mounting, installation and service work, etc.) must be performed by
qualified staff
x Before making any wiring changes in the connection area, completely isolate the
plant from mains supply (all-polar disconnection). Ensure that the plant cannot be
inadvertently switched on again and that it is indeed dead. If not observed, there is
a risk of electric shock hazard
x Ensure protection against electric shock hazard by providing adequate protection
for the burner control’s connection terminals. If this is not observed, there is a risk
of electric shock
x Each time work has been carried out (mounting, installation, service work, etc.),
check to ensure that wiring is in an orderly state and make the safety checks as
described in «Commissioning notes». If not observed, there is a risk of
impairment of safety functions and of electric shock hazard
x Press the lockout reset button / operation button or the AGK20… lockout reset
button extension only manually (applying a force of no more than 10 N) without
using any tools or pointed objects. If not observed, there is a risk of impairment
of safety functions and of electric shock hazard
x Fall or shock can adversely affect the safety functions. Such units must not be put
into operation, even if they do not exhibit any damage. If not observed, there is a
risk of impairment of safety functions and of electric shock hazard
x When replacing LOA26... or LOA36..., any ARK21... remote lockout reset module
ARK21... or similar modules fitted in the burner or boiler must be removed. If not observed,
there is a risk of impairment of safety functions
Mounting notes
x Ensure that the relevant national safety regulations are complied with
Installation notes
x Always run the high-voltage ignition cables separately while observing the greatest
possible distances to the unit and to other cables
x Install switches, fuses, earthing, etc., in compliance with local regulations
x Ensure that the maximum permissible amperages will not be exceeded (refer to
«Technical data»)
x Do not feed external mains voltage to the control outputs of the unit. When testing
the components controlled by the burner control (fuel valves, etc.), the LMO... may
never be plugged in
x Do not mix up live and neutral conductors
2/13
Service notes
x Use the KF8885 / KF8833 / KF8840 service adapters for short periods of time only
Life cycle
Burner controls has a designed lifetime* of 250,000 burner startup cycles which, under
normal operating conditions in heating mode, correspond to approx. 10 years of usage
(starting from the production date given on the type field).
The designed lifetime is based on use of the burner controls according to the
manufacturer’s Data Sheet. After reaching the designed lifetime in terms of the number
of burner startup cycles, or the respective time of usage, the burner control is to be
replaced by authorized personnel.
* The designed lifetime is not the warranty time specified in the Terms of Delivery
Disposal notes
The unit contains electrical and electronic components and must not be disposed of
together with domestic waste.
Local and currently valid legislation must be observed.
3/13
Indication and - Multicolor indication of operational status and fault status messages
diagnostics - Transmission of operational status and fault status messages and detailed service
information via additional OCI400 interface and ACS400 / ACS410 PC software
Type summary
4/13
Connection accessories for small burner controls refer to Data Sheet N7201
- Plug-in base AGK11...
- Cable holders AGK65..., AGK66
Flame detectors
- Photo resistive detectors QRB1... refer to Data Sheet N7714
- Blue-flame detectors QRC1... refer to Data Sheet N7716
5/13
Attention!
Condensation, formation of ice and ingress of water are not permitted! If this is
not observed, there is a risk of loss of safety functions and a risk of electric
shock.
6/13
Flame supervision with Detector current Perm. detector Possible detector current
QRB... or QRC... required current with flame
(with flame) (without flame) (typically)
QRB... ¹) Min. 45 µA Max. 5.5 µA 100 µA
QRC... ¹) Min. 45 µA Max. 5.5 µA 70 µA
¹) The values given in the table above only apply under the following conditions:
- Mains voltage depending on execution AC 120 V or AC 230 V
- Ambient temperature 23 °C
7/13
Undervoltage x Safety shutdown from the operating position takes place should mains voltage drop
below about AC 165 V (UN = AC 230 V) or AC 75 V (UN = AC 120 V)
x Restart is initiated when mains voltage exceeds about AC 175 V (UN = AC 230 V)
or AC 95 V (UN = AC 120 V)
Time supervision If the oil preheater’s release contact does not close within 10 minutes, the burner control
oil preheater will initiate lockout.
Controlled intermittent After no more than 24 hours of continuous operation, the burner control will initiate
operation automatic controlled shutdown followed by a restart.
Control sequence in If lockout occurs, the outputs for the fuel valves, the burner motor and the ignition
the event of fault equipment will immediately be deactivated (<1 second). In the event of lockout, the
LMO... remains locked and the red signal lamp (LED) will light up. The burner control can
immediately be reset. This state is also maintained in the case of mains failure.
Cause Response
Mains failure Restart
Voltage has fallen below the undervoltage Safety shutdown, followed by restart
threshold
Extraneous light during prepurge time (t1), 5 Lockout at the end of prepurge time (t1)
s before fuel valve (BV1) release
Extraneous light during waiting time (tw) Prevention of startup, lockout after 40
seconds at the latest
No flame at the end of safety time (TSA) Lockout at the end of safety time (TSA), blink
code 2
Loss of flame during operation Max. 3 repetitions, followed by lockout
Oil preheater’s release contact does not Lockout
close within 10 minutes
Resetting the When lockout occurs, the burner control can immediately be reset. To do this, press the
burner control lockout reset button for about 1 second (<3 seconds). The LMO... can only be reset when
all contacts in the line are closed and when there is no undervoltage.
Ignition program with If the flame is lost during safety time (TSA), the burner will be reignited, but only until the
LMO14.113x2 and end of safety time (TSA). This means that several ignition attempts can be made during
LMO24.113x2 safety time (TSA) (see Control sequence).
Limitation of repetitions If the flame is lost during operation, a maximum of 3 repetitions can be made. If the
flame is lost for the fourth time during operation, the burner will initiate lockout. The
repetition count is restarted each time controlled switching on by control thermostat or
pressurestat (R) takes place.
8/13
7130z05/0700
EK the burner control and for activating / deactivating the diagnostic
functions.
Red The multicolor signal lamp (LED) in the lockout reset button is the key
7130z06e/0700
Yellow indicating element for both visual diagnostics and interface diagnostics.
Green
LED
Both «EK» and LED are located under the transparent cover of the lockout reset
button.
Visual diagnostics:
In normal operation, the different operating states are indicated in the form of color
codes according to the color code table given below.
Operational status During startup, status indication takes place according to the following table:
indication
Color code table for multicolor signal lamp (LED)
Status Color code Color
Waiting time «tw», other waiting states ........................................ Off
Oil preheater on z........................................ Yellow
Ignition phase, ignition controlled zzzzzz Flashing yellow
Operation, flame o.k. ........................................ Green
Operation, flame not o.k. Flashing green
Extraneous light on burner startup SSSSS Green-red
Undervoltage zSzSzSzSz Yellow-red
Fault, alarm S....................................... Red
Error code output (refer to «Error code S S S S Flashing red
table») S
Interface diagnostics S S S S S S S S Red flicker light
9/13
OCI400
Lockout position Lockout position Lockout position
Visual diagnostics Interface diagnostics
Flashing PC / analyzer
On
Reset
EK EK EK
7130z04e/0602
Error code table
>3s xxxx xxxx
xxxx xxxx
>3s <3s
xxxx xxxx
xxxx xxxx
xxxx xxxx
xxxx xxxx
During the time the cause of fault is diagnosed, the control outputs are deactivated
burner remains shut down.
The diagnostics of the cause of fault is quit and the burner switched on again by
resetting the burner control. Press the lockout reset button for about 1 second (<3
seconds).
10/13
R A´ A B C D
W 1
EK1 µC1 µC control µC2
SB tw
LED OH 8
K1 K2 FSV
OW 3
K3
M 3
1 2 10 8 3 6 7 4 5 9 11 12
kbr
BV1 4
SB
t1 t3n
8 3
Z 6
R QRB
OW EK2 t3 TSA
11
W OH FS
AL 12
N QRC Only with LMO14.113C2: re-ignition
Si 1 bl sw t3n t3n
L M Z BV1 br Z 6
N
7130a01e/0700 11
FS
7130d02e/1207 12
R A´ A B C D
µC control µC2 W 1
EK1 µC1
SB tw
LED OH 8
K2
K1 FSV OW 3
K3 t1´
K4 M 3
t1
1 2 10 8 3 6 7 4 5 9 11 12 BV1
kbr 4
SB t4
8 3 BV2 5
R QRB t3 t3n
OW EK2
Z 6
W OH BV2 TSA
AL 11
FS
N QRC 12
Si 1 bl sw
Only with LMO24.113C2: re-ignition
L M Z BV1 br t3n t3n
N Z 6
7130a04e/0908
11
FS
7130d03e/1207 12
R A´ A B C D
µC control W 1
EK1 µC1 µC2
SB tw
LED OH 8
K2
K1 FSV OW 3
K3 t1´
M 3
K4 t1
1 2 10 8 3 6 7 4 5 9 11 12 BV1 4
kbr
t4
SB
8 3 BV2 5
R t3 t3n
QRB
OW EK2 Z 6
W TSA
OH BV2 11
AL FS
N 7130d05/1105 12
QRC
Si 1 bl sw
L M Z BV1 br
N
7130a04e/0908
11/13
AL Alarm device
BV... Fuel valve
EK1 Lockout reset button
EK2 Remote lockout reset button
FS Flame signal
FSV Flame signal amplifier
K... Contacts of control relay
kbr Cable link (required only when no oil preheater is used)
LED 3-color signal lamp
M Burner motor
OW Release contact of oil preheater
OH Oil preheater
QRB... Photo resistive flame detector
QRC... Blue-flame detector
bl = blue, br = brown, sw = black
R Control thermostat or pressurestat
SB Safety limit thermostat
Si External primary fuse
W Limit thermostat or pressure switch
Z Ignition transformer
Control signals
Required input signals
Perm. input signals
µC1 Microcontroller 1
µC2 Microcontroller 2
12/13
LMO...
5,2
22
53,9
7130m04/1004
9
Plug-in base AGK11...
88 41,6
91
47,2
62,5
AGK20...
7,44
7130m05/0904