Ficha Tecnica de FC150X-C
Ficha Tecnica de FC150X-C
Ficha Tecnica de FC150X-C
Powered by CUMMINS
— 50Hz Manufacture
Powers PRP(1) ESP(2) Prime Brand
Voltage (V) KW KVA KW KVA Amps Model TAL-A44-H (60HZ)
380/220 108 135 120 150 205.1 Series LSA TAL STD(3) S STD(3) STD(3)
(3)STD:Standard Alternator.
TIDE Power reserves the right to change the design or specifications without notice and without any obligation or liability.
Fuel system
Injection system BYC PB DIRECT INJECTION
Governor type Electronic
Maximum restriction at lift pump 13.6kPa
Maximum fuel inlet temperature 40℃
Top drain flow
Standard reference Conditions (constant for all loads) 30 liters/h
Note: Standard reference condition 25°C[77°F] air inlet temp, 1000m(328ft) A.S.L
30%
relative humidity. Fuel consumption data with diesel fuel with specific gravity of
0.85 and
conforming to BS 2869: 1998, Class A2
■ Optional configuration
Controller Photos
Standard Supply × × ● ○
Viewable Parameters
Phase Voltage × 3 3 3
Current Instrumentation ● ● ●
Frequency ● ● ● ●
Active Power × ● ● ●
Reactive Power × ● ● ●
Apparent Power × ● ● ●
Power Factor × ● ● ●
Electric Energy Metering × ● ● ●
Generator Protection
Abnormal Voltage ● ● ● ●
Over-current Warning × ● ● ●
Over current Protection ● ● ● ●
Over Frequency Protection ● ● ● ●
Short Circuit Protection MCCB / ● MCCB / ● MCCB / ● MCCB / ●
Engine Figure
Oil Pressure ● ● ● ●
Water Temperature ● ● ● ●
Fuel Meter / Fuel Sensor ●/○ ●/○ ●/○ ●/○
Speed ● ● ● ●
Battery Voltage ● ● ● ●
Runing hours ● ● ● ●
Engine Protection
Low Oil Pressure Warning × ● ● ●
Low Oil Pressure Protection ● ● ● ●
High Temperature Warning × ● ● ●
High Temperature Protection ● ● ● ●
Overspeed Warning × ● ● ●
Overspeed Protection × ● ● ●
Alternator Charger ● ● ● ●
Functions
Remote Start ● ● ● ●
AMF (Auto Main Failure) ● ● ● ●
Service Indicate × × ● ●
Fault History ● ● ● ●
Gen-Gen Synchronising × × × ●
Gen-Mains Synchronising × × × ●
Remark: ● Standard Supply ○ Available as Optional × Not Available
■ Automatic Transfer Switch A.T.S - 4 Poles
Tide Power offers not only a changeover switch but also an integrated mains
detection and switch system for your 24 Hour Power Protection. The system
enables automatic start-up and operation of the generating set in the event of a
mains power failure, overvoltage or loss of a mains automatic re-transfer once it
come back.
System Advantages
▪ Automatically transfer and re-transfer load from main power to gen-power without
operator intervention.operation(Both automatic and manual).
▪ ATS Controller (AMF function), seamless integration with AMF25
▪ Available from 32 – 4000A, better protection for 4 pole switch.
▪ Available in standard, bypass isolation and service-entrance configurations.
▪ Configurable in open, closed and programmed transition operating modes.
▪ Designed to interface seamlessly with TIDE POWER generators and switchgear.
▪ Drip proof IP42 enclosure.
▪ Easy installation: wall-mounted & floor standing
▪ Comes fully loaded with the technology to do the job.
Warranty