Ce 36 Be
Ce 36 Be
Ce 36 Be
CE-36(BE)
UL AWM 2464
Characteristics Radar Chart
Heat resistance
5
4
Cable carrier Oil resistance
resistance 3
2 Features
1 ■ Global-standard cables designed to CE&UL・cUL&GOST-R
0 ■ Oil resistance/Heat resistance (105℃)/Flexibility
left/right
Noise
bending
resistance
resistance
Application
■ Internal/external cable connection to electrical equipment
45°left/right vibration
Twist resistance ■ Cable connection under oil environment
resistance
Technical Data
CE UL・cUL
Voltage Rating 300/300V 300V
Temperature Rating 70℃ 80℃
Test Voltage AC2000V・15min AC3000V・1min
Flame Resistance VDE0482 Teil 265-2-1 VW-1, FT1
Applicable Standard VDE0281-13 UL 758 AWM Style 2464 CAN/CSA-C22.2 No210.2
Electrical Characteristics
Nominal Cross-Sectional Number of Cores Allowable Current(A)
Item
Area(Ý)(AWG) 2∼51 2 3 4 5 7 8 9 11 13 17 21 25 31 41 51
0.5 (20) 34.3 11 11 10 9 8 7 7 6 6 5 5 5 4 4 4
Insulation Resistance
(20℃) 0.5(20)∼2.5(14) 10
MΩÜ or above
●Thecable designed with its number of cores of 3 or more as indicated in the above table contains one core of 2.5Ý (14AWG) (50/0.25) green/yellow grounding conductor.
●The conductor resistance of the 2.5Ý (14AWG) green/yellow grounding conductor is 7.98Ω/km or less at 20℃.
●The insulation resistance of the 2.5Ý (14AWG) green/yellow grounding conductor is 10 MΩkm or more at 20℃.
●Allowable Current (A) for the cable is based on calculation under aerial one-cable installation at ambient temper-
ature of 30℃, not representing a guaranteed value.
Allowable current for the cable at ambient temperature above 30℃ is to be determined by multiplying the current
value by the appropriate current reduction factor specified in the following table for the ambient temperature.
●The Allowable current values are those calculated by JCS197, but not guaranteed.
( For details on Allowable current of the cable when used in Europe, refer to the applicable standard
− IEC60364-5 (Electrical installation of building − Part 5: Selection and erection of electrical equip-
ment − Section 523: Current-carrying capacities in wiring system).
)
JCS197… Japanese Electric Wire and Cable Makers’Association’
s Standard“Allowable Current for Cabtyre Cable”
95
Core Identification
Core identification system
●Green/yellow: Yellow straight lines on green (in green/yellow color ratio of 60/40)
Cable Construction
Item Configuration
Conductor Soft annealed stranded copper
Insulator Heat resistant PVC
Conductor stranding Circular
Core wrapping tape Tape wrap around cores if their number is 4 or more
Sheath Oil resistant/heat resistant PVC (light gray)
CE-36(BE)
■Example: 8 core (7 core (2.5Ý)14AWG + 1 core (2.5Ý)14AWG) cable
Soft annealed stranded copper conductor Oil resistant/heat resistant PVC sheath
2.5Ý grounding conductor
2 1
CE-362(BE)KURAMO 300/500V
CE-36(BE)KURAMO-K VDE Reg.-Nr. 7898 300/300V
KURAMO E162205 AWM STYLE 2587 Ⅰ/Ⅱ A/B 90C 600V VW-1 FT1
KURAMO E162205-K AWM STYLE 2464 Ⅰ A 80C 300V VW-1 FT1 GOST-R LF
54 3
Tape
Heat resistant PVC insulator
table contains one core of 2.5Ý (14AWG) (50/0.25) green/yellow grounding conductor.
※ indicates specifications for custom order production.
UL AWM
NFPA79
NFPA70
CE
CCCcUL/CSA
GOST-R
96