NDLS-ROOF / PLATFORM GUTTER SIZE -A1

1.0 GUTTER SIZE CALCULATION

Considering depth of the gutter to be 2 times of width (h = 2w)

Area of rectangle=(h x w) 2w x w
2
Area of the rectangular shape gutter(A) 2 w

WETTED PERIMETER (P)=2h + w 5 w


Hydraullic Radius ( R ) = A / P 0.4000 w
(2/3) 0.67
R 0.5427 w
Slope of the gutter(S) 400
S 0.003
(1/2)
S 0.050
MANNING COEFFICIENT NO. 0.013
0.67 0.5 3 2.67
Discharge Q=(AxR xS )/0.013 in m /sec 4.1748 w Eq.1

3
Maximum rate of run off Q=CxIxA/3600x1000 in m /sec
Where
C=Coefficient 0.9
I=Intensity of rainfall 50 mm/hr (235.5 mm per 24 hour)
2
A=Area of the roof 11000 m

Q=(0.90x9.8x11000)/3600x1000
0.1375 Eq.2

Equatting rate of run off and discharge from the gutter i.e Eq.1 and Eq.2

2.67
w 0.03293609 m
w 0.2784973 m

Width of the gutter 0.2784973 m

Depth of the gutter 0.5569946 m

Hence width of gutter = 278.4972989 mm say as 300 mm


height of the gutter= 556.9945978 mm say as 560 mm

Note : Width & Height of Gutter is come According to Above Calculation, But that can be vary according to Space availabilty Etc.
NDLS-Diameter of downtake pipes from roof Gutter.-A1
FACTORS
Sl.No. Factors Representation Unit Value
1 Total Roof Area RA sqm 11000
2 Diameter of downtake pipes d mm 150
3 Intensity of rainfall I mm/hour 50

For rain water pipe of other material, the roof area shall be multiplied by (0.013/Coefficient of roughness of surface of that
material)
4 AS PER NBC PART -9 CLAUSE NO. 4.5.11.6.8

RA = 0.084 X d5/2/I

Where,
A) d = diameter of pipe in mm = 150 mm
B) I = intensity of rain fall, mm/hr = 50 mm/hr
= considered 50 mm/hr.
C) RA = roof area, m2
=roof area that contain per down take
a) pipe for discharge (for full flow condition ) 462.95 M2
=
=for safe design consideration roof area that contain per down take
b) pipe for discharge (for 90% of flow condition ) = 416.66 M2

D) Total terrace area. = 11000 M2


Total no. of down take pipe (150 mm) required for rain water discharge
from roof drainage system = 26 nos.
(for 90% of flow condition )
NDLS-ROOF / PLATFORM GUTTER SIZE -A2
1.0 GUTTER SIZE CALCULATION

Considering depth of the gutter to be 2 times of width (h = 2w)

Area of rectangle=(h x w) 2w x w
2
Area of the rectangular shape gutter(A) 2 w

WETTED PERIMETER (P)=2h + w 5 w


Hydraullic Radius ( R ) = A / P 0.4000 w
(2/3) 0.67
R 0.5427 w
Slope of the gutter(S) 400
S 0.003
(1/2)
S 0.050
MANNING COEFFICIENT NO. 0.013
0.67 0.5 3 2.67
Discharge Q=(AxR xS )/0.013 in m /sec 4.1748 w Eq.1

3
Maximum rate of run off Q=CxIxA/3600x1000 in m /sec
Where
C=Coefficient 0.9
I=Intensity of rainfall 50 mm/hr (235.5 mm per 24 hour)
2
A=Area of the roof 11000 m

Q=(0.90x50x11000)/3600x1000
0.1375 Eq.2

Equatting rate of run off and discharge from the gutter i.e Eq.1 and Eq.2

2.67
w 0.03293609 m
w 0.2784973 m

Width of the gutter 0.2784973 m

Depth of the gutter 0.5569946 m

Hence width of gutter = 278.4972989 mm say as 300 mm


height of the gutter= 556.9945978 mm say as 560 mm

Note : Width & Height of Gutter is come According to Above Calculation, But that can be vary according to Space availabilty Etc.
NDLS-Diameter of downtake pipes from roof Gutter.-A2
FACTORS
Sl.No. Factors Representation Unit Value
1 Total Roof Area RA sqm 11000
2 Diameter of downtake pipes d mm 150
3 Intensity of rainfall I mm/hour 50

For rain water pipe of other material, the roof area shall be multiplied by (0.013/Coefficient of roughness of surface of that
material)
4 AS PER NBC PART -9 CLAUSE NO. 4.5.11.6.8

RA = 0.084 X d5/2/I

Where,
A) d = diameter of pipe in mm = 150 mm
B) I = intensity of rain fall, mm/hr = 50 mm/hr
= considered50 mm/hr.
C) RA = roof area, m2
=roof area that contain per down take
a) pipe for discharge (for full flow condition ) 462.95 M2
=
=for safe design consideration roof area that contain per down take
b) pipe for discharge (for 90% of flow condition ) = 416.66 M2

D) Total terrace area. = 11000 M2


Total no. of down take pipe (150 mm) required for rain water discharge
from roof drainage system = 26 nos.
(for 90% of flow condition )
NDLS-ROOF / PLATFORM GUTTER SIZE -A3
1.0 GUTTER SIZE CALCULATION

Considering depth of the gutter to be 2 times of width (h = 2w)

Area of rectangle=(h x w) 2w x w
2
Area of the rectangular shape gutter(A) 2 w

WETTED PERIMETER (P)=2h + w 5 w


Hydraullic Radius ( R ) = A / P 0.4000 w
(2/3) 0.67
R 0.5427 w
Slope of the gutter(S) 400
S 0.003
(1/2)
S 0.050
MANNING COEFFICIENT NO. 0.013
0.67 0.5 3 2.67
Discharge Q=(AxR xS )/0.013 in m /sec 4.1748 w Eq.1

3
Maximum rate of run off Q=CxIxA/3600x1000 in m /sec
Where
C=Coefficient 0.9
I=Intensity of rainfall 50 mm/hr
2
A=Area of the roof 6500 m

Q=(0.90x9.8x6500)/3600x1000
0.08125 Eq.2

Equatting rate of run off and discharge from the gutter i.e Eq.1 and Eq.2

2.67
w 0.01946223 m
w 0.22869054 m

Width of the gutter 0.22869054 m

Depth of the gutter 0.45738109 m

Hence width of gutter = 228.6905427 mm say as 250 mm


height of the gutter= 457.3810854 mm say as 500 mm

Note : Width & Height of Gutter is come According to Above Calculation, But that can be vary according to Space availabilty Etc.
NDLS-Diameter of downtake pipes from roof Gutter.-A3
FACTORS
Sl.No. Factors Representation Unit Value
1 Total Roof Area RA sqm 6500
2 Diameter of downtake pipes d mm 150
3 Intensity of rainfall I mm/hour 50

For rain water pipe of other material, the roof area shall be multiplied by (0.013/Coefficient of roughness of surface of that
material)
4 AS PER NBC PART -9 CLAUSE NO. 4.5.11.6.8

RA = 0.084 X d5/2/I

Where,
A) d = diameter of pipe in mm = 150 mm
B) I = intensity of rain fall, mm/hr = 50 mm/hr
= considered 50 mm/hr.
C) RA = roof area, m2
=roof area that contain per down take
a) pipe for discharge (for full flow condition ) 462.95 M2
=
=for safe design consideration roof area that contain per down take
b) pipe for discharge (for 90% of flow condition ) = 416.66 M2

D) Total terrace area. = 6500 M2


Total no. of down take pipe (150 mm) required for rain water discharge
from roof drainage system = 16 nos.
(for 90% of flow condition )
NDLS-ROOF / PLATFORM GUTTER SIZE -A4
1.0 GUTTER SIZE CALCULATION

Considering depth of the gutter to be 2 times of width (h = 2w)

Area of rectangle=(h x w) 2w x w
2
Area of the rectangular shape gutter(A) 2 w

WETTED PERIMETER (P)=2h + w 5 w


Hydraullic Radius ( R ) = A / P 0.4000 w
(2/3) 0.67
R 0.5427 w
Slope of the gutter(S) 400
S 0.003
(1/2)
S 0.050
MANNING COEFFICIENT NO. 0.013
0.67 0.5 3 2.67
Discharge Q=(AxR xS )/0.013 in m /sec 4.1748 w Eq.1

3
Maximum rate of run off Q=CxIxA/3600x1000 in m /sec
Where
C=Coefficient 0.9
I=Intensity of rainfall 50 mm/hr (235.5 mm per 24 hour)
2
A=Area of the roof 17500 m

Q=(0.90x50x17500)/3600x1000
0.21875 Eq.2

Equatting rate of run off and discharge from the gutter i.e Eq.1 and Eq.2

2.67
w 0.05239832 m
w 0.3313932 m

Width of the gutter 0.3313932 m

Depth of the gutter 0.6627864 m

Hence width of gutter = 331.3932021 mm say as 350 mm


height of the gutter= 662.7864042 mm say as 700 mm

Note : Width & Height of Gutter is come According to Above Calculation, But that can be vary according to Space availabilty Etc.
NDLS-Diameter of downtake pipes from roof Gutter.-A4
FACTORS
Sl.No. Factors Representation Unit Value
1 Total Roof Area RA sqm 17500
2 Diameter of downtake pipes d mm 150
3 Intensity of rainfall I mm/hour 9.8

For rain water pipe of other material, the roof area shall be multiplied by (0.013/Coefficient of roughness of surface of that
material)
4 AS PER NBC PART -9 CLAUSE NO. 4.5.11.6.8

RA = 0.084 X d5/2/I

Where,
A) d = diameter of pipe in mm = 150 mm
B) I = intensity of rain fall, mm/hr = 50 mm/hr
= considered 50mm/hr.
C) RA = roof area, m2
=roof area that contain per down take
a) pipe for discharge (for full flow condition ) 462.95 M2
=
=for safe design consideration roof area that contain per down take
b) pipe for discharge (for 90% of flow condition ) = 416.66 M2

D) Total terrace area. = 17500 M2


Total no. of down take pipe (150 mm) required for rain water discharge
from roof drainage system = 42 nos.
(for 90% of flow condition )
NDLS-ROOF / PLATFORM GUTTER SIZE -A5
1.0 GUTTER SIZE CALCULATION

Considering depth of the gutter to be 2 times of width (h = 2w)

Area of rectangle=(h x w) 2w x w
2
Area of the rectangular shape gutter(A) 2 w

WETTED PERIMETER (P)=2h + w 5 w


Hydraullic Radius ( R ) = A / P 0.4000 w
(2/3) 0.67
R 0.5427 w
Slope of the gutter(S) 400
S 0.003
(1/2)
S 0.050
MANNING COEFFICIENT NO. 0.013
0.67 0.5 3 2.67
Discharge Q=(AxR xS )/0.013 in m /sec 4.1748 w Eq.1

3
Maximum rate of run off Q=CxIxA/3600x1000 in m /sec
Where
C=Coefficient 0.9
I=Intensity of rainfall 50 mm/hr
2
A=Area of the roof 17500 m

Q=(0.90x50x17500)/3600x1000
0.21875 Eq.2

Equatting rate of run off and discharge from the gutter i.e Eq.1 and Eq.2

2.67
w 0.05239832 m
w 0.3313932 m

Width of the gutter 0.3313932 m

Depth of the gutter 0.6627864 m

Hence width of gutter = 331.3932021 mm say as 350 mm


height of the gutter= 662.7864042 mm say as 700 mm

Note : Width & Height of Gutter is come According to Above Calculation, But that can be vary according to Space availabilty Etc.
NDLS-Diameter of downtake pipes from roof Gutter.-A5
FACTORS
Sl.No. Factors Representation Unit Value
1 Total Roof Area RA sqm 17500
2 Diameter of downtake pipes d mm 150
3 Intensity of rainfall I mm/hour 50

For rain water pipe of other material, the roof area shall be multiplied by (0.013/Coefficient of roughness of surface of that
material)
4 AS PER NBC PART -9 CLAUSE NO. 4.5.11.6.8

RA = 0.084 X d5/2/I

Where,
A) d = diameter of pipe in mm = 150 mm
B) I = intensity of rain fall, mm/hr = 10 mm/hr
= considered 50 mm/hr
C) RA = roof area, m2
=roof area that contain per down take
a) pipe for discharge (for full flow condition ) 2314.77 M2
=
=for safe design consideration roof area that contain per down take
b) pipe for discharge (for 90% of flow condition ) = 2083.29 M2

D) Total terrace area. = 17500 M2


Total no. of down take pipe (150 mm) required for rain water discharge
from roof drainage system = 8 nos.
(for 90% of flow condition )
NDLS-ROOF / PLATFORM GUTTER SIZE -A6
1.0 GUTTER SIZE CALCULATION

Considering depth of the gutter to be 2 times of width (h = 2w)

Area of rectangle=(h x w) 2w x w
2
Area of the rectangular shape gutter(A) 2 w

WETTED PERIMETER (P)=2h + w 5 w


Hydraullic Radius ( R ) = A / P 0.4000 w
(2/3) 0.67
R 0.5427 w
Slope of the gutter(S) 400
S 0.003
(1/2)
S 0.050
MANNING COEFFICIENT NO. 0.013
0.67 0.5 3 2.67
Discharge Q=(AxR xS )/0.013 in m /sec 4.1748 w Eq.1

3
Maximum rate of run off Q=CxIxA/3600x1000 in m /sec
Where
C=Coefficient 0.9
I=Intensity of rainfall 50 mm/hr
2
A=Area of the roof 10000 m

Q=(0.90x50x5000)/3600x1000
0.125 Eq.2

Equatting rate of run off and discharge from the gutter i.e Eq.1 and Eq.2

2.67
w 0.0299419 m
w 0.26873121 m

Width of the gutter 0.26873121 m

Depth of the gutter 0.53746242 m

Hence width of gutter = 268.7312109 mm say as 300 mm


height of the gutter= 537.4624218 mm say as 550 mm

Note : Width & Height of Gutter is come According to Above Calculation, But that can be vary according to Space availabilty Etc.
NDLS-Diameter of downtake pipes from roof Gutter.-A6
FACTORS
Sl.No. Factors Representation Unit Value
1 Total Roof Area RA sqm 10000
2 Diameter of downtake pipes d mm 150
3 Intensity of rainfall I mm/hour 50

For rain water pipe of other material, the roof area shall be multiplied by (0.013/Coefficient of roughness of surface of that
material)
4 AS PER NBC PART -9 CLAUSE NO. 4.5.11.6.8

RA = 0.084 X d5/2/I

Where,
A) d = diameter of pipe in mm = 150 mm
B) I = intensity of rain fall, mm/hr = 50 mm/hr
= considered 50 mm/hr.
C) RA = roof area, m2
=roof area that contain per down take
a) pipe for discharge (for full flow condition ) 462.95 M2
=
=for safe design consideration roof area that contain per down take
b) pipe for discharge (for 90% of flow condition ) = 416.66 M2

D) Total terrace area. = 10000 M2


Total no. of down take pipe (150 mm) required for rain water discharge
from roof drainage system = 24 nos.
(for 90% of flow condition )
NDLS-ROOF / PLATFORM GUTTER SIZE
1.0 GUTTER SIZE CALCULATION

Considering depth of the gutter to be 2 times of width (h = 2w)

Area of rectangle=(h x w) 2w x w
2
Area of the rectangular shape gutter(A) 2 w

WETTED PERIMETER (P)=2h + w 5 w


Hydraullic Radius ( R ) = A / P 0.4000 w
(2/3) 0.67
R 0.5427 w
Slope of the gutter(S) 400
S 0.003
(1/2)
S 0.050
MANNING COEFFICIENT NO. 0.013
0.67 0.5 3 2.67
Discharge Q=(AxR xS )/0.013 in m /sec 4.1748 w Eq.1

3
Maximum rate of run off Q=CxIxA/3600x1000 in m /sec
Where
C=Coefficient 0.9
I=Intensity of rainfall 9.8 mm/hr (235.5 mm per 24 hour)
2
A=Area of the roof 70000 m

Q=(0.90x9.8x70000)/3600x1000
0.1715 Eq.2

Equatting rate of run off and discharge from the gutter i.e Eq.1 and Eq.2

2.67
w 0.04108029 m
w 0.30252523 m

Width of the gutter 0.30252523 m

Depth of the gutter 0.60505046 m

Hence width of gutter = 302.5252277 mm say as 350 mm


height of the gutter= 605.0504553 mm say as 650 mm

Note : Width & Height of Gutter is come According to Above Calculation, But that can be vary according to Space availabilty Etc.
NDLS-Diameter of downtake pipes from roof Gutter.
FACTORS
Sl.No. Factors Representation Unit Value
1 Total Roof Area RA sqm 70000
2 Diameter of downtake pipes d mm 100
3 Intensity of rainfall I mm/hour 9.8

For rain water pipe of other material, the roof area shall be multiplied by (0.013/Coefficient of roughness of surface of that
material)
4 AS PER NBC PART -9 CLAUSE NO. 4.5.11.6.8

RA = 0.084 X d5/2/I

Where,
A) d = diameter of pipe in mm = 100 mm
B) I = intensity of rain fall, mm/hr = 9.8 mm/hr
= considered 9.8 mm/hr.(235.5mm in 24 hours)
C) RA = roof area, m2
=roof area that contain per down take
a) pipe for discharge (for full flow condition ) 857.14 M2
=
=for safe design consideration roof area that contain per down take
b) pipe for discharge (for 90% of flow condition ) = 771.43 M2

D) Total terrace area. = 70000 M2


Total no. of down take pipe (100 mm) required for rain water discharge
from roof drainage system = 91 nos.
(for 90% of flow condition )
NDLS-Diameter of downtake pipes from roof Gutter.-A4
FACTORS
Sl.No. Factors Representation Unit Value
1 Total Roof Area RA sqm 10000
2 Diameter of downtake pipes d mm 100
3 Intensity of rainfall I mm/hour 9.8

For rain water pipe of other material, the roof area shall be multiplied by (0.013/Coefficient of roughness of surface of that
material)
4 AS PER NBC PART -9 CLAUSE NO. 4.5.11.6.8

RA = 0.084 X d5/2/I

Where,
A) d = diameter of pipe in mm = 100 mm
B) I = intensity of rain fall, mm/hr = 9.8 mm/hr
= considered 9.8 mm/hr.(235.5mm in 24 hours)
C) RA = roof area, m2
=roof area that contain per down take
a) pipe for discharge (for full flow condition ) 857.14 M2
=
=for safe design consideration roof area that contain per down take
b) pipe for discharge (for 90% of flow condition ) = 771.43 M2

D) Total terrace area. = 10000 M2


Total no. of down take pipe (100 mm) required for rain water discharge
from roof drainage system = 13 nos.
(for 90% of flow condition )
NDLS-ROOF / PLATFORM GUTTER SIZE -A4
1.0 GUTTER SIZE CALCULATION

Considering depth of the gutter to be 2 times of width (h = 2w)

Area of rectangle=(h x w) 2w x w
2
Area of the rectangular shape gutter(A) 2 w

WETTED PERIMETER (P)=2h + w 5 w


Hydraullic Radius ( R ) = A / P 0.4000 w
(2/3) 0.67
R 0.5427 w
Slope of the gutter(S) 400
S 0.003
(1/2)
S 0.050
MANNING COEFFICIENT NO. 0.013
0.67 0.5 3 2.67
Discharge Q=(AxR xS )/0.013 in m /sec 4.1748 w Eq.1

3
Maximum rate of run off Q=CxIxA/3600x1000 in m /sec
Where
C=Coefficient 0.9
I=Intensity of rainfall 9.8 mm/hr (235.5 mm per 24 hour)
2
A=Area of the roof 10000 m

Q=(0.90x9.8x10000)/3600x1000
0.0245 Eq.2

Equatting rate of run off and discharge from the gutter i.e Eq.1 and Eq.2

2.67
w 0.00586861 m
w 0.14596391 m

Width of the gutter 0.14596391 m

Depth of the gutter 0.29192781 m

Hence width of gutter = 145.963906 mm say as 200 mm


height of the gutter= 291.927812 mm say as 300 mm

Note : Width & Height of Gutter is come According to Above Calculation, But that can be vary according to Space availabilty Etc.
NDLS-Diameter of downtake pipes from roof Gutter.-A3
FACTORS
Sl.No. Factors Representation Unit Value
1 Total Roof Area RA sqm 35000
2 Diameter of downtake pipes d mm 100
3 Intensity of rainfall I mm/hour 9.8

For rain water pipe of other material, the roof area shall be multiplied by (0.013/Coefficient of roughness of surface of that
material)
4 AS PER NBC PART -9 CLAUSE NO. 4.5.11.6.8

RA = 0.084 X d5/2/I

Where,
A) d = diameter of pipe in mm = 100 mm
B) I = intensity of rain fall, mm/hr = 9.8 mm/hr
= considered 9.8 mm/hr.(235.5mm in 24 hours)
C) RA = roof area, m2
=roof area that contain per down take
a) pipe for discharge (for full flow condition ) 857.14 M2
=
=for safe design consideration roof area that contain per down take
b) pipe for discharge (for 90% of flow condition ) = 771.43 M2

D) Total terrace area. = 35000 M2


Total no. of down take pipe (100 mm) required for rain water discharge
from roof drainage system = 45 nos.
(for 90% of flow condition )
NDLS-ROOF / PLATFORM GUTTER SIZE -A3
1.0 GUTTER SIZE CALCULATION

Considering depth of the gutter to be 2 times of width (h = 2w)

Area of rectangle=(h x w) 2w x w
2
Area of the rectangular shape gutter(A) 2 w

WETTED PERIMETER (P)=2h + w 5 w


Hydraullic Radius ( R ) = A / P 0.4000 w
(2/3) 0.67
R 0.5427 w
Slope of the gutter(S) 400
S 0.003
(1/2)
S 0.050
MANNING COEFFICIENT NO. 0.013
0.67 0.5 3 2.67
Discharge Q=(AxR xS )/0.013 in m /sec 4.1748 w Eq.1

3
Maximum rate of run off Q=CxIxA/3600x1000 in m /sec
Where
C=Coefficient 0.9
I=Intensity of rainfall 9.8 mm/hr (235.5 mm per 24 hour)
2
A=Area of the roof 35000 m

Q=(0.90x9.8x35000)/3600x1000
0.08575 Eq.2

Equatting rate of run off and discharge from the gutter i.e Eq.1 and Eq.2

2.67
w 0.02054014 m
w 0.23335455 m

Width of the gutter 0.23335455 m

Depth of the gutter 0.46670911 m

Hence width of gutter = 233.3545535 mm say as 250 mm


height of the gutter= 466.7091069 mm say as 500 mm

Note : Width & Height of Gutter is come According to Above Calculation, But that can be vary according to Space availabilty Etc.
NDLS-Diameter of downtake pipes from roof Gutter.-A2
FACTORS
Sl.No. Factors Representation Unit Value
1 Total Roof Area RA sqm 6500
2 Diameter of downtake pipes d mm 100
3 Intensity of rainfall I mm/hour 9.8

For rain water pipe of other material, the roof area shall be multiplied by (0.013/Coefficient of roughness of surface of that
material)
4 AS PER NBC PART -9 CLAUSE NO. 4.5.11.6.8

RA = 0.084 X d5/2/I

Where,
A) d = diameter of pipe in mm = 100 mm
B) I = intensity of rain fall, mm/hr = 9.8 mm/hr
= considered 9.8 mm/hr.(235.5mm in 24 hours)
C) RA = roof area, m2
=roof area that contain per down take
a) pipe for discharge (for full flow condition ) 857.14 M2
=
=for safe design consideration roof area that contain per down take
b) pipe for discharge (for 90% of flow condition ) = 771.43 M2

D) Total terrace area. = 6500 M2


Total no. of down take pipe (100 mm) required for rain water discharge
from roof drainage system = 8 nos.
(for 90% of flow condition )
NDLS-ROOF / PLATFORM GUTTER SIZE -A2
1.0 GUTTER SIZE CALCULATION

Considering depth of the gutter to be 2 times of width (h = 2w)

Area of rectangle=(h x w) 2w x w
2
Area of the rectangular shape gutter(A) 2 w

WETTED PERIMETER (P)=2h + w 5 w


Hydraullic Radius ( R ) = A / P 0.4000 w
(2/3) 0.67
R 0.5427 w
Slope of the gutter(S) 400
S 0.003
(1/2)
S 0.050
MANNING COEFFICIENT NO. 0.013
0.67 0.5 3 2.67
Discharge Q=(AxR xS )/0.013 in m /sec 4.1748 w Eq.1

3
Maximum rate of run off Q=CxIxA/3600x1000 in m /sec
Where
C=Coefficient 0.9
I=Intensity of rainfall 9.8 mm/hr (235.5 mm per 24 hour)
2
A=Area of the roof 6500 m

Q=(0.90x9.8x6500)/3600x1000
0.015925 Eq.2

Equatting rate of run off and discharge from the gutter i.e Eq.1 and Eq.2

2.67
w 0.0038146 m
w 0.12421544 m

Width of the gutter 0.12421544 m

Depth of the gutter 0.24843087 m

Hence width of gutter = 124.2154373 mm say as 150 mm


height of the gutter= 248.4308746 mm say as 250 mm

Note : Width & Height of Gutter is come According to Above Calculation, But that can be vary according to Space availabilty Etc.
NDLS-Diameter of downtake pipes from roof Gutter.-A1
FACTORS
Sl.No. Factors Representation Unit Value
1 Total Roof Area RA sqm 22000
2 Diameter of downtake pipes d mm 100
3 Intensity of rainfall I mm/hour 9.8

For rain water pipe of other material, the roof area shall be multiplied by (0.013/Coefficient of roughness of surface of that
material)
4 AS PER NBC PART -9 CLAUSE NO. 4.5.11.6.8

RA = 0.084 X d5/2/I

Where,
A) d = diameter of pipe in mm = 100 mm
B) I = intensity of rain fall, mm/hr = 9.8 mm/hr
= considered 9.8 mm/hr.(235.5mm in 24 hours)
C) RA = roof area, m2
=roof area that contain per down take
a) pipe for discharge (for full flow condition ) 857.14 M2
=
=for safe design consideration roof area that contain per down take
b) pipe for discharge (for 90% of flow condition ) = 771.43 M2

D) Total terrace area. = 22000 M2


Total no. of down take pipe (100 mm) required for rain water discharge
from roof drainage system = 29 nos.
(for 90% of flow condition )
NDLS-ROOF / PLATFORM GUTTER SIZE -A1
1.0 GUTTER SIZE CALCULATION

Considering depth of the gutter to be 2 times of width (h = 2w)

Area of rectangle=(h x w) 2w x w
2
Area of the rectangular shape gutter(A) 2 w

WETTED PERIMETER (P)=2h + w 5 w


Hydraullic Radius ( R ) = A / P 0.4000 w
(2/3) 0.67
R 0.5427 w
Slope of the gutter(S) 400
S 0.003
(1/2)
S 0.050
MANNING COEFFICIENT NO. 0.013
0.67 0.5 3 2.67
Discharge Q=(AxR xS )/0.013 in m /sec 4.1748 w Eq.1

3
Maximum rate of run off Q=CxIxA/3600x1000 in m /sec
Where
C=Coefficient 0.9
I=Intensity of rainfall 9.8 mm/hr (235.5 mm per 24 hour)
2
A=Area of the roof 22000 m

Q=(0.90x9.8x22000)/3600x1000
0.0539 Eq.2

Equatting rate of run off and discharge from the gutter i.e Eq.1 and Eq.2

2.67
w 0.01291095 m
w 0.19610726 m

Width of the gutter 0.19610726 m

Depth of the gutter 0.39221452 m

Hence width of gutter = 196.1072599 mm say as 200 mm


height of the gutter= 392.2145199 mm say as 400 mm

Note : Width & Height of Gutter is come According to Above Calculation, But that can be vary according to Space availabilty Etc.
15

5M
M

HIG
HI
GH

HF
FR

RO
15

OM
M

MC
HI

CO
G

ON
GUTTER SIZE (mm)

NC
FR

C
350(W)X650(H)

OU

OU
O
M

RS

RS
CO

E
NC

E
O
UR
5

SE

SKYL
M
HI
GH

PE

IGHT
FR

O
OM

SL
CO

SLOPE
NC
OU
RS
E

GUTTER SIZE (mm)


350(W)X650(H)
SK
YL
IG
HT
15 M HIGH FROM CONCOURSE
10
235

E
OP
SL
5 M HIGH FROM CONCOURSE
E
CO URS
M CON
H FRO
HIG
20 M

344
00

EL
EV
45
391

AT
ED
RO
AD
PE
SLO

BE
LO
W
GUTTER SIZE (mm)
350(W)X650(H)
EL

05
306
EV
AT
ED
RO

55 ALUMINUM ROOFING AS /
592
AD

SPECIFICATIONS
AT
LV
L.
482

+9
.5M

SK
575

YL
.

IG
H
T

00
100
SL
O
PE RIDGE LINE

SK
SLOP

YL
IGH
E
25
219

T
SE
R
U
O
C
N
ELEVA

O
00
C
100

VAL
M
O
FR

LEY
TED RO

148

SE
235
IG
H

UR
GUTTER SIZE (mm)
LINE
ROOF 10000 M

1390

O
00
5
350(W)X650(H)

NC
AD

CO
00
100

OM
E
RS

RS

FR
U

U
10000

CO

GH
O
NC

HI
ON
GUTTER
H

CO

M
C

15
M
OM

RO
R
W

HF
HF

G
HIG

H I
M
5M

15 505
214
15

5M
M

HIG
HI
GH

HF
FR

RO
15

OM
M

MC
HI

CO
G

ON
GUTTER SIZE (mm)

NC
FR

C
200(W)X400(H)

OU

OU
O
M

RS

RS
CO

E
NC

E
O
UR
5

SE

SKYL
M
HI
GH

PE

IGHT
FR

A1

O
OM

SL
CO

SLOPE
NC
OU
RS
E

GUTTER SIZE (mm)


150(W)X250(H)
SK
YL
IG
HT
15 M HIGH FROM CONCOURSE
10
235

E
OP
SL
5 M HIGH FROM CONCOURSE
E
CO URS
M CON
H FRO
HIG
20 M

A2

344
00

EL
EV
45
391

AT
ED
RO
A4

AD
PE
SLO

BE
LO
W
GUTTER SIZE (mm)
200(W)X300(H)
EL

05
306
EV
AT
ED
RO

55 ALUMINUM ROOFING AS /
592
AD

SPECIFICATIONS
AT
LV
L.
482

+9
.5M

SK
575

YL
.

IG

A3
H
T

00
100
SL
O
PE RIDGE LINE

SK
SLOP

YL
IGH
E
25
219

T
SE
R
U
O
C
N
ELEVA

O
00
C
100

VAL
M
O
FR

LEY
TED RO

148

SE
235
IG
H

UR
GUTTER SIZE (mm)
LINE
10000 M

1390

O
00
5
250(W)X500(H)

NC
AD

CO
00
100

OM
E
RS

RS

FR
U

U
10000

CO

GH
O
NC

HI
ON

CO

M
C

15
M
OM

RO
R

HF
HF

G
HIG

H I
M
5M

15
ROOF

4 505
GUTTER 21
H

You might also like