Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Type TA Class 10: Thermal Overload Relays

Download as pdf or txt
Download as pdf or txt
You are on page 1of 18

Thermal overload relays Type TA Class 10

Th Ov erm e a re rloa l lay d s

Description
Available for starter construction with A Line contactors and separate panel mounting Designed for close couple mounting Separate base mounting available for all overload relays Class 10 adjustable overload relays are standard with all ABB Line starters Reset can also be adjusted to function as a stop button Screwdriver guide holes All terminal screws are available from the front UL File No: E48139 CSA File No: LR98336 Trip indication Remote trip and reset option available Single phase and phase unbalance protection Isolated alarm circuit (N.O.) contact Ambient compensation: -25C to +55C (-13oF to +131oF) Manual test Manual or automatic reset Factory calibrated and tested Wide adjustment range

Tripping classes of the thermal overload relays


Standard classes in IEC 947-4-1 are classes: 10 A, 10, 20, 30. The tripping class indicates according to IEC 947-4-1 the maximum tripping time in seconds under specied conditions of test at 7.2 times the setting current and species tripping and non tripping times for 1.5 and 7.2 times the setting current. Mostly used class is 10 A.

Abstract from IEC 947-4-1


Tripping class 10 A 10 20 30

Max. tripping time at 1.5 x setting current (warm state) Tripping time at 7.2 x setting current (cold state) At 1.05 x setting current

(s)

120

240

480

720

(s)

2 10

4 10

6 20

9 30

no tripping

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb-control.com

2.1
1SXU 000 023 C0201

al m d r a e Th erlo s v O elay r

Description

TA thermal overload relays are used with A Line contactors for the protection of motors having a nominal voltage of up to 600VAC max per UL/CSA (690VAC and 800VDC per IEC).

Construction and function


General Thermal O/L relays and their accessories meet UL, CSA and most other important international standards (IEC), European standards (EN) and the most important national standards (DIN-VDE, NFC-UTE, BS, etc.). They meet the certication and approval directives required throughout the world. Thermal overload relays are 3 pole. The motor current ows through their bimetals (1 per phase) which are indirectly heated. Under the effect of the heating, the bimetals bend, cause the relay to trip and the position of the auxiliary contacts to change. The relay setting range is graduated in amps. In compliance with international and national standards, the setting current is the motor nominal current and not the tripping current (no tripping at 1.05 x setting current, tripping at 1.2 times setting current). The tripping curves (cold or warm starting, 3 phases and 2 phases) are shown on page 2.14. The relays are built to be self protecting in the event of an overload until the short circuit protection device is activated.

Product range
Standard relays: Types: TA25DU, TA42DU, TA75DU, TA80DU, TA110DU, TA200DU and TA450DU TA25 to TA110 and TA200 are directly connected in the motor circuit. TA450DU relays are fed through a linear type transformer Special construction Thermal overload relays with different certications and approvals. Relays for protection EEx e motors.

Terminals L1, L3, L5

Manual test

Manual or automatic reset Frame size TA....DU Trip indication light Tripping contact (95, 96) Amp setting range

Signaling contact, (97, 98)

Terminals T1, T2, T3

2.2
1SXU 000 023 C0201

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb-control.com

Description

Th Ov erm e a re rloa l lay d s

Application Technical data


All the relays have: Free tripping: the resetting button, even if held in, does not prevent tripping of the thermal overload relay in the event of a fault. Temperature compensation Phase failure protection according to IEC 947-4-1: Within the limits of the setting range, a reduced tripping time, and thus improved motor protection, is obrtained in case of a phase failure. Tripping class: 10A, for TA relays Test functions and resetting: see table below. Auxiliary contacts The relays have two built in auxiliary contacts: NC marked 95-96; NO marked 97-98. Both contacts are physically separate and can thus be used for 2 different circuits (control circuit and indication circuit).

Function of TA25DU TA450DU thermal O/L relays


Resetting Contacts Effect of blue button indexed on R (RESET ONLY) Resetting 95-96 Relay tripped Manual Yes Closed when the button is pressed Open when the button is pressed Yes Closed when the button is released Open when the button is pressed No No effect No Open when the button is pressed Closed when the button is released No effect Open {95-96 97-98 Closed Automatic No Relay not tripped Closed { 95-96 97-98 Open

Both manual and automatic No

TA25DU

No effect

No effect

97-98 Effect of blue button indexed on R/O (RESET/OFF) Resetting 95-96 97-98

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb-control.com

2.3
1SXU 000 023 C0201

2
Types

al m d r a e Th erlo s v O elay r

Selection guide TA25DU TA80DU

TA25DU

TA42DU

TA75DU

TA80DU

Main characteristics
Construction
3 pole with ambient temperature variation compensation. Protection against single phase operation. Built in auxiliary contacts: 1N.O. + 1N.C.

Resetting Setting ranges

Convertible: Number from to 18 0.1 0.16A 24 32A 3 18 25A 29 42A

Manual to Automatic 6 18 25A 60 80A 4 29 42A 60 80A

Mounted with contactors


Mounting kit
Types of contactors for combined mounting A/AE/AL9 A/AE/AL12 A/AE/AL16 A/AE/AL26 A/AE/AL30 A/AE/AL40 No kit is required for mounting thermal O/L relays below contactors

A/AE30 A/AE40 A/AE/AF50 A/AE/AF63 A/AE/AF75 A/AE/AF95 A/AE/AF110

Mounted separately (i.e. separate from contactor)


Separate mounting kit DB25 DB80

Accessories
Tripping coil Resetting coil Terminal shroud Function markers DS25-A DR25-A Terminals protected against direct contact (without the addition of terminal shrouds) BA5-50

2.4
1SXU 000 023 C0201

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb-control.com

Selection guide TA110DU TA450DU

Th Ov erm e a re rloa l lay d s

Types Main characteristics


Construction

TA110DU

TA200DU

TA450DU

3 pole with ambient temperature variation compensation. Protection against single phase operation. Built in auxiliary contacts: 1N.O. + 1N.C.
1 2 3 4 5 6 R
95 97

96

98

Resetting Setting ranges

Convertible: manual to automatic Number from to A A 2 65 90 80 110 6 65 90 150 200 3 130 185 220 310

Mounted with contactors


Mounting kit
Types of contactors for combined mounting No kit is required for mounting thermal O/L relays See page 2.7.

A/AE/AF95 A/AE/AF110 A/AF145 A/AF185

A/AF210 + DT450/A300 A/AF260 + DT450/A300 A/AF300 + DT450/A300

Mounted separately (i.e. separate from contactor)


Separate mounting kit DB200 No kit required for separate mounting of thermal O/L relays

Accessories
Tripping coil Resetting coil Terminal shroud Function markers 1 LT200 BA5-50 LT450

1 Terminals protected against direct contact (without the addition of terminal shrouds)

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb-control.com

2.5
1SXU 000 023 C0201

al m d r a e Th erlo s v O elay r

TA25 - TA450 Class 10 for Contactors A9 A/AF300


For contactor Setting range A Sufx Code Catalog number List price

TA25DU

A/AE/AL9 A/AE/AL40

0.1 0.16 0.25 0.4 0.63 1.0 1.3 1.7 2.2 2.8 3.5 4.5 6.0 7.5 10 13 18 24

0.16 0.25 0.4 0.63 1.0 1.4 1.8 2.4 3.1 4.0 5.0 6.5 8.5 11 14 19 25 32

A B C D E F G H J K L M N P Q R S T A B C A B C D E F C D E F A B A B C D E F A B C

TA25DU0.16 TA25DU0.25 TA25DU0.4 TA25DU0.63 TA25DU1.0 TA25DU1.4 TA25DU1.8 TA25DU2.4 TA25DU3.1 TA25DU4.0 TA25DU5.0 TA25DU6.5 TA25DU8.5 TA25DU11 TA25DU14 TA25DU19 TA25DU25 TA25DU32 TA42DU25 TA42DU32 TA42DU42 TA75DU25 TA75DU32 TA75DU42 TA75DU52 TA75DU63 TA75DU80 TA80DU42 TA80DU52 TA80DU63 TA80DU80 TA110DU90 TA110DU110 TA200DU90 TA200DU110 TA200DU135 TA200DU150 TA200DU175 TA200DU200 TA450DU185 1 TA450DU235 TA450DU310

$ 63

A/AE30 A/AE40
TA42DU

18 25 22 32 29 42 18 22 29 36 45 60 29 36 45 60 25 32 42 52 63 80 42 52 63 80

78

A/AE/AF50 A/AE/AF75

102

135

A/AE/AF95 A/AE/AF110

65 90 80 110
TA75DU

165 165

65 90 80 110 A/AF145 A/AF185 100 110 130 150 135 150 175 200

225

A/AF210 A/AF300

130 185 165 235 220 310

488

AF400 AF750

See electronic overloads, pages 2.21

TA80DU

TA110DU

1 TA450 overloads require mounting kits for installation.

2.6
1SXU 000 023 C0201

Discount schedule TAA TA25 Discount schedule TBA TA42, TA75 Discount schedule TCA TA80, TA110, TA200, TA450

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb-control.com

Accessories

Th Ov erm e a re rloa l lay d s

2
List price

Separate mounting kits


For O/L relays Amps Catalog number

TA25DU TA25DU TA42DU, TA75DU, TA80DU TA110DU, TA200DU

0.1 24 18 100

25 32 80 200

DB25/25A DB25/32A DB80 DB200

$ 30 38 45 60

Flat pin terminal blocks


DB25/25A Mounting on: Catalog number List price

TA25DU relay DB25/25A or DB25/32A

LC30-T LC26-B1

$6

Terminal block AWG #8 cable


Mounting on: Catalog number List price

TA25DU (25A or less) or DB25/25A

DX25

$ 15

DB80

LC terminal blocks can be used to convert standard connections into Faston connections: 2 x 6.3mm or 4 x 2.8mm per pole. The connections are protected against accidental contact. The LC30-T has a terminal block for the 3 power terminals and a second for the 4 auxiliary terminals of a TA25DU thermal O/L relay. The LC26-B1 has two identical terminal blocks each for 3 power terminals. This block allows the power terminals to be mounted with two DB25 kits or a TA25DU thermal O/L relay and DB25 kit assembly. NOTE: According to DIN 46429 part 1 and NFC 20-120 the max. capacity of a Faston connection is 25 A.

Mounting kit for TA450 overload relay


For contactor Catalog number List price

DB200

A145 A185 A210 A300

DT450/A185 DT450/A300

$ 225

Terminal shrouds for contactors and overload relays


Contactor Overload relay Catalog number List price

A9 A16 A26 A40 A30 A40 A50 A75 A95 A110


LC26-B1

TA25DU TA42DU TA75DU TA80DU TA110DU TA200DU Load side of TA200DU

Included Included Included Included LT185-AY LT200A185

$ 10 50

A145 A185 A145 A185

Terminal lug kits


Wire range For overloads Catalog number List price

6 250MCM 4 400MCM (2) 4 500MCM

TA110DU, TA200DU TA450DU185 TA450DU310

EHTK210 ATK300HK ATK300/2HK

$ 90 78 120

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb-control.com

Discount schedule ABA A-contactor accessories Discount schedule TAA TA25 Discount schedule TBA TA42, TA75 Discount schedule TCA TA80, TA110, TA200, TA450

2.7
1SXU 000 023 C0201

al m d r a e Th erlo s v O elay r

Accessories

Remote tripping coils


U voltage at 50/60 Hz Catalog number 1 List price

DS25-A remote tripping coil 24V 48V 110V 220/380V 500V DS25-A remote resetting coil 24V 48V 110V 220/380V 500V DR25-A-24 DR25-A-48 DR25-A-110 DR25-A-220/380 DR25-A-500 DS25-A-24 DS25-A-48 DS25-A-110 DS25-A-220/380 DS25-A-500

$ 60

DS25A

Application
The DS25-A coil is used for remote electrical tripping of the TA25 DU thermal O/L relay and is connected to the relay's normally closed 95-96 auxiliary contact. The DR 25-A coil is used for remote electrical resetting of the TA25DU thermal O/L relay which is adjusted for Manual resetting; it is connected to the relays normally open 97-98 auxiliary contact. The coils are not designed for continuous duty. Impulse duration: 0.2 to 0.35 s. Set the button to Man (Manual resetting). Mounting: clipped on to TA25DU thermal O/L relay.

DR25A

Installation diagrams
For connection of DS25-A to TA25DU relay For connection of DR25-A to TA25DU relay

L1 STOP
21 22

START OL
13 14 A1

L2/N

L1 STOP
21 22

START OL
13 14 A1

L2/N

A2

95

96

A2

95

96

M
13 14

M
13 14

OVERLOAD TRIP
E1 E2

OVERLOAD RESET

OL
97 98 E1 E2

OL TRIPPING COIL L1 OFF HAND


23 13

OL RESETTING COIL L2/N L1 OFF HAND


23 13

AUTO
24 14 A1

OL

AUTO
24 14 A1

L2/N OL

A2

95

96

A2

95

96

OVERLOAD TRIP
E1 E2

OVERLOAD RESET

OL
97 98 E1 E2

OL TRIPPING COIL
1 Cannot be used with TA42, TA75, or TA200 overload relays.

OL RESETTING COIL

2.8
1SXU 000 023 C0201

Discount schedule TAA TA25

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb-control.com

Technical data TA25DU TA450DU


Switching frequency:
Intermittent duty
(ops/h) 140

Th Ov erm e a re rloa l lay d s

To avoid untimely tripping, TA and T thermal O/L relays have been designed to withstand roughly 15 switching operations per hour with an approximately equal distribution between working and rest cycles. In these conditions, the motor starting time must not exceed 1 second and the starting current must be lower than or equal to 6 times the motor In. For intermittent operations, the diagram opposite species relay operating limits. Example: Motor starting time: 1 sec. 40 % 60 ops./h according to diagram Load factor: Switching frequency:

ta = s 0.5

120

Switching frequency

100 80 60 40 20 0 0

ta

1s

ta

=1

ta =

.5s

For a higher number of operations and for load variations (e.g. frequent starting and braking), it is advisable to use CUSTORAPID protection. For motors subject to particularly severe operating conditions (e.g. locked rotor) it is advisable to use protection combined with a thermal O/L relay and the CUSTORAPID system.

3s

ta = 3.5 s
20 40 60 Closing time 80 100(%)

Protection of motors with long starting time


See electronic overload relay section, pages 2.21 - 2.32.

Mounting position
On a support at an angle of 30 in relation to the vertical plane (standard position). Other mounting positions possible, except mounting on a horizontal plane (in this case the tripping mechanism would be located above the bimetals).

Switching frequency in relation to load factor. ta: motor starting time.

Special version for EEx e motors


[s] 40

Consult factory.

Tripping limits at ambient temperatures varying by + 20C


Ambient temperature compensation
Thermal O/L relays are compensated against ambient temperature variations by a compensation bimetal which is sensitive to the ambient temperature.
Multiple of the setting current
1.5 1.4 1.3 1.2 1.1 1.0 0.9 -20 -10 0 10 20 30 Ambient temperature 40 50 No tripping Tripping Ambient temperature compensation limits according to IEC 947-4-1

20 11 10 6 4 3 2

Tripping time

Thermal O/L relays are designed to operate between 5 C and +40 C in compliance with standard IEC 947-4-1. For a wider range of 25 C to +55 C consult the graph opposite. Example: tripping at 25 C. Tripping takes place before 1.5 times the setting current. Resetting: TA25DU TA450 DU thermal O/L relays have convertible manual/automatic resetting. Delivery: in manual resetting mode.

1 3 7 7.4 Multiple of the setting current 4 5 6 8

TA thermal O/L relay cold-state tripping characteristics

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb-control.com

2.9
1SXU 000 023 C0201

2
Types

al m d r a e Th erlo s v O elay r

Technical data TA25DU TA80DU


TA25DU TA42DU TA75DU TA80DU

Standards: (international, European) Rated insulation voltage Ui according to IEC 947-4-1 Rated impulse withstand voltage Uimp according to IEC 947-4-1 Permissible ambient temperature for storage for operation Climatic withstand DIN 50017 Mounting positions V kV

IEC 947-4-1, EN 60947-4-1 690 6

C C

40 to +70 25 to +55 with temperature compensation (maximum values: see page 2.9) Humidity in alternate climate KFW, 30 cycles On a support at an angle of 30 in relation to the vertical plane (standard position). Other positions possible except mounting on a horizontal plane (in this case the tripping mechanism would be located above the bimetals).

Shock withstand at nominal Ie Critical direction of shocks A1, A2 Resistance to vibrations (1 mm, 50 Hz) Mounting on contactor separate with DB - kit

shock duration ms

15

multiples of g multiples of g

12 8 Latching below the contactor, screw xing on main terminals Using screws: 2 x M4 or 35 mm EN 50022 TA25DU setting ranges: from 0.1-0.16A 24-32 A to 18-25A M4 M5 2 x 1.5 - 6 2 x 1.5 - 4 1 x 10 2 x 0.75- 6

Terminals and cross-sectional areas for main conductors (motor side) screw terminal with cable clamp via tunnel connector at type for lug or bar conductor cross-sectional area rigid solid or rigid stranded exible with cable end recommended bars Terminals and cross-sectional area for auxiliary conductors screw terminal (screw size) with cable clamp conductor cross-sectional area rigid solid or rigid stranded exible with cable end Degree of protection

A1

A2

M6

M6 1 x 2.5 - 35 or 2 x 2.5 x 16 1 x 2.5 - 25 or 2 x 2.5 x 10

M6

mm2 mm2 mm

M 3.5 2 x mm2 2 x mm2 0.75 - 4 0.75 - 2.5 All the terminals are protected against direct contact according to VDE 0106/Part. 100. (without additional terminal shrouds) All the terminals are protected against direct direct contact according to VDE0106/part 100 (with additional terminal shrouds for the main terminals

Pole Technical Characteristics


Types Number of poles Setting ranges Tripping class according to IEC 947-4-1, EN 60947-1 Rated operational frequencies Max. switching frequency without untimely tripping Resistance per phase in m and heat dissipation in W Hz TA25 DU TA42 DU TA75 DU TA80 DU 3 see page 2.6 10 A 0 - 400 Up to 15 starts/h or 60 starts/h with 40 % on-load factor when neither the starting current of 6 x In nor the starting time 1 s are exceeded. see page 2.13 50/60 TA10 DU TA200 DU TA450 DU

2.10
1SXU 000 023 C0201

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb-control.com

Technical data TA110DU TA450DU


Types
Standards: (international, European) Rated insulation voltage Ui according to IEC 947-4-1 Rated impulse withstand voltage Uimp according to IEC 947-4-1 Permissible ambient temperature for storage for operation Climatic withstand DIN 50017 Mounting positions V kV 690 6

Th Ov erm e a re rloa l lay d s


TA200DU
IEC 947-4-1, EN 60947-4-1 1000 8

TA110DU

TA450DU

C C

40 to +70 25 to +55 with temperature compensation (maximum values: see page 2.9) Humidity in alternate climate KFW, 30 cycles On a support at an angle of 30 in relation to the vertical plane (standard position). Other positions possible except mounting on a horizontal plane (in this case the tripping mechanism would be located above the bimetals).

Shock withstand at nominal Ie Critical direction of shocks A1, A2 Resistance to vibrations (1 mm, 50 Hz) Mounting on contactor separate with DB - kit

shock duration ms

15

multiples of g multiples of g 4 x M5 screws

12 8

Terminals and cross-sectional areas for main conductors (motor side) screw terminal with cable clamp via tunnel connector at type for lug or bar conductor cross-sectional area rigid solid or rigid stranded exible with cable end recommended bars Terminals and cross-sectional area for auxiliary conductors screw terminal (screw size) with cable clamp conductor cross-sectional area rigid solid or rigid stranded exible with cable end Degree of protection

A1

A2

HC, M8 16 35 16 35 12 x 3

M10 25 120 25 95 20 x 4

M10 2 x 240 2 x 240 20 x 4...5

mm2 mm2 mm

M 3.5 2 x mm2 2 x mm2 0.75 - 4 0.75 - 2.5 All the terminals are protected against direct contact according to VDE 0106/Part. 100. (with additional terminal shrouds)

Technical characteristics of auxiliary contacts for thermal O/L relays: TA25DU to TA450DU
Auxiliary contacts Terminal marking Rated operational voltage Ue Conventional thermal current (in free air) Ith Rated operational current Ie, AC-15 up to 240 V up to 440 V up to 500 V Rated operational current Ie DC-13 up to 250 V Protection against short circuits gG (gl) fuses (according to IEC 269) S 271/S 281circuit-breaker Maximum potential difference between N.C. and N.O. auxiliary contacts VAC A A A A A A A VAC VDC normally closed N.C. 95-96 500 10 3.0 1.9 1.0 0.12 10 k3 500 440 normally open N.O. 97-98 500 6 1.5 0.95 0.75 0.04 6 k1 500 440

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb-control.com

2.11
1SXU 000 023 C0201

al m d r a e Th erlo s v O elay r

Technical data Motor protection; Choice of protective device

Motor Protection general


It is very important to choose an adequate protective device for the safety of the motor during operation and for its durability. The efciency of protection methods varies according to the application. The overview below will help you to choose. There is no general rule and we are available to advise you for special applications and especially in the case of difcult starting.

Protective devices and efciency


Protection in relation to current:
Fuses Protective relay with phase fault protection

Protection in relation to temperature:


Motor protection via CUSTORAPID thermistor Motor protection via SPEM electronic relay

SPEM M 3~ M 3~ M 3~ M 3~

Causes of dangerous overloads for the motor windings


1 Overload with current 1.2 times the nominal current 2 S1-S8 nominal duties according to IEC 34-I 3 Operation with starting, braking, reversal in operating direction 4 Operation with starting rate at > 15 cycles/hour 5 Locked rotor 6 Overloads due to phase failure 7 Network undervoltage or overvoltage 8 Fluctuation of network frequency 9 Ambient temperature too high 10 Overheating due to external cause (i.e. overheating of bearings) 11 Motor cooling disturbed 12 13 for motors with special rotor Undercurrent protection on drop in load Protection of asymmetry: wrong phase direction rotation or asymmetrical load Earth fault protection Automatic disconnection for auxiliary load fault

14 15

Note: Fuses

Protection efciency:
unsuitable very average efciency perfectly efcient

Fuses do not protect motors against overloads. They are only used to protect installations and lines against short circuits. To ensure efcient protection of a motor against short circuits, it is advisable to use aM type fuses in association with thermal OLR relays. For the selection of fuses or circuit-breakers, refer to the indications given in this catalogue concerning contactors on the one hand and thermal O/L relays on the other. In general, fuse protection for direct-on-line starting must be sized as follows: aM fuses: choose the fuse rating immediately above the full load value of the motor current. gG (gI) fuses: determine the fuse rating immediately above the motor current value and choose the next highest fuse rating.

2.12
1SXU 000 023 C0201

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb-control.com

Technical data Resistance and Joule losses per phase Short circuit protection
Resistance and Joule losses per phase, short circuit protection
Setting range current from to A A Resistance per phase m Joule losses per phase at max. setting W Setting range current from to A A Resistance per phase m

Th Ov erm e a re rloa l lay d s

Joule losses per phase at max. setting W

TA25DU 0.1 0.16 0.25 0.4 0.63 1.0 1.3 1.7 2.2 2.8 3.5 4.5 6.0 7.5 10 13 18 24

0.16 0.25 0.4 0.63 1.0 1.4 1.8 2.4 3.1 4.0 5.0 6.5 8.5 11 14 19 25 32

85850 85150 13750 5370 2190 1120 670 383 229 137 87.5 61 30.4 18.2 11.2 6.3 4.7 3.2 5.5 2.89 1.84 5.5 2.89 1.84 1.3 0.936 0.615 1.84 1.3 0.936 0.615

2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.3 2.9 3.3 3.43 2.91 3.24 3.43 2.91 3.24 3.51 3.72 3.94 3.24 3.51 3.72 3.94

TA110DU 80 TA200DU 100 110 130 150

110 135 150 175 200

0.378 0.318 0.255 0.214 0.182

3.78 5.79 5.74 6.55 7.28 2.5 2.5 2.5

TA450DU 130 185 165 235 220 310

TA42DU 18 25 22 32 29 42 TA75DU 18 22 29 36 45 60 TA80DU 29 36 45 60 25 32 42 52 63 80 42 52 63 80

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb-control.com

2.13
1SXU 000 023 C0201

al m d r a e Th erlo s v O elay r

Technical data Tripping curves

TA25DU

TA75DU

TA110DU/SU

TA450DU

TA-DU thermal O/L relays are 3-pole with manual or automatic resetting mode selection. The resetting button can also be used for stopping. Built-in auxiliary contacts are physically separate and, consequently, can be used in different circuits (control circuit/indication circuit). Each relay is temperature compensated and ensures phase failure protection. Protective relays up to size TA75DU are protected against direct contact via the front face. Terminal shrouds are available for TA200DU to TA450DU size relays. The connecting terminals are delivered in open position with (+,-) pozidriv screws and screwdriver guidance. It is advisable to tighten unused terminal screws.

Thermal O/L relay tripping curves


TA25DU
(tripping class 10A)
120 100 80 60 40 20 10 8 6

TA42DU, TA75DU and TA80DU


(tripping class 10A)
120 100 80 60 40 20 10 8 6

TA110DU
(tripping class 10A)
120 100 80 60 40 20 10 8 6

from cold state

Minutes

Minutes

Minutes

4 2 1 40 20

4 2

4 2 1 40 20

Tripping time

Tripping time

2 Phases
1 40 20

Tripping time

from cold state

from cold state 2 Phases 3 Phases

2 Phases

3 Phases 2 Phases

3 Phases

Seconds

Seconds

10 8 6 4 2

2 Phases 3 Phases

10 8 6 4 2

Seconds

3 Phases

10 8 6 4 2

3 Phases

2 Phases

from warm state


1 0.8 1 1.2 1.5 2 3 4 5 6 7 8 9 10 1 0.8 1 1.2

from warm state

from warm state


1 1.5 2 3 4 5 6 7 8 9 10 0.8 1 1.2 1.5 2 3 4 5 6 7 8 9 10

Tripping current in multiples of the setting current

Tripping current in multiples of the setting current

Tripping current in multiples of the setting current

TA200DU
(tripping class 10A)
120 100 80 60 40 20 10 8 6
from cold state

TA450DU
(tripping class 10A)
120 100 80 60 40 20 10 8 6 4 minutes

4
Minutes

from cold state


2 2 Phase 1 40 20 3 Phase

2 Phases

1 40 20
Seconds

3 Phases

Triping time

Tripping time

2 Phases

seconds

10 8 6 4 2 1 0.8 1 1.2 1.5 2 3 4 5 6 7 8 9 10


3 Phases

10 8 6 4 2 1 0.8

2 Phase

3 Phase from warm state

from warm state

1 1.2

1.5

6 7 8 9 10

Tripping current in multiples of the setting current

Tripping current as multiple of setting current

2.14
1SXU 000 023 C0201

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb-control.com

Approximate dimensions T25DU TA42DU


00.00
00.00

Inches
[Millimeters]

Th Ov erm e a re rloa l lay d s

TA25DU
0.51
13

3.70
94

3.15
80

TA25DU32 only

0.24
6

1.73
44

3.70
94

TA25DU & DB25


4.25
108

1.73
44

0.24
6

0.35
6

1.38
35

0.51
13

3.31
84

1.88
48

0.17
4.2

TA25DU & DB25/32


1.73
44

4.25
108

0.24
6

0.35
6

1.38
35

0.51
13

4.41
112

1.88
48

0.17
4.2

TA42DU
0.51
13

3.54
90

0.24
6

2.13
54

4.35
110.5

TA42DU / TA75DU & DB80


5.03
127.7

2.36
60

0.24
6

1.97
50

0.51
13

3.86
98

2.95
75

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb-control.com

2.15
1SXU 000 023 C0201

2
TA75DU TA80DU

al m d r a e Th erlo s v O elay r

Approximate dimensions TA75DU TA200DU


00.00
00.00

Inches
[Millimeters]

0.51
13

3.99
93

0.24
6

2.13
54

4.35
110.5

2.85
72.3

TOUCH SAFE COVER 0.47


12.0

1.18
30.0

0.47
12.0

3.77
95.7

12.5

0.50 2 - M4 Mtg. Slots

2.12
54.0

4.37
111.0

TA110DU

TOUCH SAFE COVER

1.48
37.5

0.24
6.0

5.44
138.1

2.52
64.0

6 - 0.21 HOLES

.61
15.5

3.14
80.0

0.24
6.0

120.1

4.73

0.07
1.7

1.98
50.2

TA200DU

2.16
1SXU 000 023 C0201

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb-control.com

Approximate dimensions TA450DU


00.00
00.00

Inches
[Millimeters]

Th Ov erm e a re rloa l lay d s

TA450DU
0.18
4.5

0.24
6.0

2.99
76.0

0.2 DIA.
5.0 DIA.

6.62
168.0

2.17 0.96
24.5
2 4 6

55.0

0.82
21.0

1.11
28.3

7.60
193.0

2.28
58.0

2.28
58.0

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb-control.com

2.17
1SXU 000 023 C0201

al m d r a e Th erlo s v O elay r

Notes

2.18
1SXU 000 023 C0201

Low Voltage Products & Systems


ABB Inc. 888-385-1221 www.abb-control.com

You might also like