Introduction To Power System Protection & Relays
Introduction To Power System Protection & Relays
GOPALA KRISHNA
ADE/400KV/APTRANSCO
Power Systems Protection -Introduction
Power Systems Protection -Introduction
Switching Substation
Distribution Substation
Power Systems Protection -Introduction
Code numbers
Used to denote
Protections
On a SLD
Power Systems Protection -Introduction
Inputs
Outputs
Current CTs
Voltage PTs
Trip Contact
Frequency PTs
Power CTs + PTs
Power Systems Protection -Introduction
1.3 or
3.0 sec
1.4 10
I/Is
LS
Power Systems Protection -Introduction
1.3 or
3.0 sec
50 msec
1.4 6 10
I/Is
LS HS
Power Systems Protection -Introduction
Very Inverse 1.5 sec 13.50 4.50 2.70 1.93 1.50 0.96 0.71
Extremely Inverse 26.66 5.33 2.28 1.27 0.81 0.36 0.20
Power Systems Protection -Introduction
NEXT MODIFICATION :
SEMI NUMERIC RELAYS
IN THIS SOME FUNCTIONS ARE CAN BE PROGRAMMABLE AND
INTERFACE THROUGH PC. SOME ICs ARE HAVING THE FACILITY
TO INTERACT THROUGH COMMUNICATION PORT. IT IS SOME
WHAT MODIFICATION TO IC BASED RELAYS. IN THIS SOME
FUNCTION CAN BE ENABLED AND DISABLED, BASED ON THE
REQUIREMENT.
4 ND GENERATION
MICROPROCESSOR BASED NUMERICAL RELAYS
¾ IN THIS ALL OF THE FUNCTIONS ARE BROUGHT ON
ONE IC. THE FOURTH GENERATION PROCESSOR-
BASED RELAYS, DO HAVE THE WATCHDOG FEATURE,
WHICH FACILITATES THE CHECKING OF POWER
SUPPLY FAILS, CLOCK FREQUENCIES, AND OTHER
PATTERNS. MOST OF THESE RELAYS HAVE AUTO TEST
FEATURES WHICH TEST THE ELECTRONIC CIRCUIT
FUNCTIONS AT REGULAR INTERVALS &
AUTOMATICALLY.
MICROPROCESSOR BASED RELAYS
¾ FILTERING TECHNIQUES
1960s
¾ A FEW CONCEPTS WERE PROPOSED
1980s
¾ MAJOR MANUFACTURERS LIKE ABB, GE, GEC , TOSHIBA,
SIEMENS START DESIGN & SALES OF BROAD RANGE OF
PRODUCTS FOR POWER SYSTEM PROTECTION
¾ MICROPROCESSOR IMPROVES PERFORMANCE SPECS FOR
OPERATION IN INDUSTRIAL ENVIRONMENT
¾ MANY PLC BASED SYSTEMS ARE COMMISSIONED IN INDIA BY
L&T, SIEMENS, ECIL ETC.
¾ MANY ELECTRICITY BOARDS & PROCESS PLANTS IN INDIA
START USING MICROPROCESSOR BASED INSTRUMENTS
ACCURACY 1% 5% / 7.5%
BURDEN < 0.5 VA > 5 VA
SETTING RANGES WIDE LIMITED
MULTI FUNCTIONALITY YES NO
SIZE SMALL LARGE
FIELD PROGRAMMABILITY YES NO
PARAMETER DISPLAY YES NO
SYSTEM FLEXILBILITY YES NO
CO-ORDINATION TOOLS MANY TWO
COMMUNICATION YES NO
REMOTE CONTROL YES NO
SPECIAL ALGORITHMS MANY LIMITED
SPECIAL PROTECTIONS YES NO
SELF DIAGNOSTICS YES NO
DIS-ADVANTAGES OF NUMERIC RELAYS
SOFTWARE INTENSIVE
OBSOLESENCE RATE
SERIAL NATURE
PROTECTION ALGORITHM
MEASUREMENMT METHOD
ANALOG D RAM
INPUT S
SU-SYSTEM P ROM
MICRO EPROM
PROCESSOR FLASH
DIGITAL
INPUT
SUB-SYSTEM DIGITAL
OUTPUT
SUB-SYSTEM
SURGE ANALOG
CT SUPPRESSION FILTER
A/D MICRO
MUX
CONVERTER PROCESSOR
SURGE ANALOG
PT SUPPRESSION FILTER
MICROPROCESSORS Vs MICRO CONTROLERS
Address Register
Address Register
C C
O O
N Data Register N Data Register
T T
R Arithmetic Logic R Arithmetic Logic
O Unit O Unit
L L
Accumulator Accumulator
ROM Timers
I/O RAM Counters
EPROM UART
RELAY HARDWARE
16 / 32 BIT
PC
MODEM
IRIG-B
RE/CC
¾ Example:
1. LINE PROTECTION,
2. TRANSFORMER PROTECTION,
3. BUSBAR PROTECTION,
4. GENERATOR PROTECTION
5. MOTOR PROTECTION
6. REACTOR PROTECTION
7. CAPACITOR PROTECTION
4 ND GENERATION
¾ 2ND DEVELOPMENT:
SOFTWARE DEVELOPMENT IS SOME GROUP BASED
RELAYS i.e SOME PROTECTION FUNCTIONS ARE
TAKEN IN TO ONE FLATFORM AND PROVIDED
COMMON SOFTWARE.
FROM THIS INBUILT FACILITY OF EVENT RECORDER
AND DISTURBANCE RECORDER IS DEVELOPED.
¾ Example:
ABB: 1. REX 5xx SERIES FLATFORM
2. REX 316 SERIES FLATFORM
3. REX 670 SERIES FLATFORM
4. RED 500 SERIES FLATFORM
5. RED 600 SERIES FLATFORM
4 ND GENERATION
¾ 3RD DEVELOPMENT:
UNIVERSAL SOFTWARE FOR ALL TYPES OF RELAYS
FOR PARTICULAR MANUFACTURER. i.e. ONE
SOFTWARE ONE MANUFACTURER.
¾ Example:
1. SIEMENS: SIPROTEC SERIES – DIGSI
2. GE MULTILIN: ENERVISTA
3. AREVA : MICOM S1
4 ND GENERATION
¾ 4TH DEVELOPMENT:
UNIVERSAL HARDWARE FOR ALL TYPES OF RELAYS
FOR PARTICULAR MANUFACTURER. ONE HARDWARE
FOR ONE MANUFACTURER.
BUT IT IS MODULAR DESIGN.
RELAY IS COMMON HARDWARE BASED ON
PROTECTION FUNCTION, PARTICULAR CARD IS
ADDED.
¾ Example:
1. GE MULTILIN: UR SERIES & SR SERIES
4 ND GENERATION
¾ 5TH DEVELOPMENT:
EACH MANUFACTURER ADOPTING THEIR
PROPERITIERY BASED PROTOCOL FOR
COMMUNICATION, INTERFACING, NETWORKING AND
AUTOMATION. SOME UTILTIES ARE REQUESTED
MANUFACTURERS TO SUIT THEIR ADOPTED
PROTOCOL.
¾ Example:
1. UCA – Utility communication architecture
2. LON
3. SPA
4. PROFIBUS
5. MODBUS
6. DNP
7. FIELDBUS
8. MVB
9. IEC 60870
4 ND GENERATION
¾ 6TH DEVELOPMENT:
BASED ON THE EXPERIENCE WITH DIFFERENT
PROTOCOLS, NEED FOR UNIFORMITY AND KNOW –
HOW FOR GLOBAL CONSIDERATION
ONE WORLD
ONE TECHNOLOGY
ONE STANDARD
A UNIVERSAL PROTOCOL FOR COMMUNICATION,
INTERFACING AND NETWORKING IS DEVELOPED.
ALL MANUFACTURERS ARE FORM A GROUP AND
PROTOCOLS ARE STANDARDIZED. ANY RELAY CAN BE
COMMUNICATED FOR COMMON COMMUNICATION
PROTOCOL, i.e INTEROPERATABULITY. THIS IS
SPECIAL FOR AUTOMATION OF STATIONS.
Example:
1. IEC 61850
BENIFITS OF UNIVERSAL PROTOCOL
One Protocol ETHERNET & TCP/IP
¾ for all the needs in the substation ¾Adopted worldwide
¾Scalable technology
¾ flexible configuration
¾Common use of infrastructure
¾ no gateways required