DSE 7510 Data Sheet
DSE 7510 Data Sheet
DSE 7510 Data Sheet
Highfield House
Hunmanby Industrial Estate
Hunmanby, North Yorkshire
YO14 0PH England
TELEPHONE
+44 (0)1723 890099
EMAIL
sales@deepseaplc.com
FACSIMILE
+44 (0)1723 893303
WEBSITE
www.deepseaplc.com
VAT No.316923457
TELEPHONE
+1 (815) 316 8706
EMAIL
sales@deepseausa.com
FACSIMILE
+1 (815) 316 8708
WEBSITE
www.deepseausa.com
PENDING
DEEP SEA ELECTRONICS PLC maintains a policy of continuous development and reserves the right to
change the details shown on this data sheet without prior notice. The contents are intended for guidance only.
This data sheet is printed on 9lives 55 Silk, which is produced with 55% recycled fibre
from both pre and post-consumer sources, together with 45% virgin ECF fibre.
055-065/01/10 (5)
DSEPOWER
SHARING
WITH
SIMPLICITY.
DSE7510
AUTO START CONTROL MODULE
SPECIFICATION
DC SUPPLY
8V to 35V continuous
CRANKING DROPOUTS
Able to survive 0V for 50mS, providing supply
was at least 10V before dropout and supply
recovers to 5V. This is achieved without the
need for internal batteries
MAXIMUM OPERATING CURRENT
460mA at 12V. 245mA at 24V
MAXIMUM STANDBY CURRENT
375mA at 12V. 200mA at 24V
ENVIRONMENTAL TESTING
STANDARDS
ELECTRO MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the
Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the
Industrial Environment
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment
TEMPERATURE
BS EN 60068-2-2
Test Ab to +70oC 60068-2-2 Hot
Test Ab to -30oC 60068-2-1 Cold
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes
5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn
HUMIDITY
BS 2011 part 2.1 60068-2-30
Test Cb Ob Cyclic
93% RH @ 40oC for 48 hours
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15gn in 11mS
OPERATION
The module is operated using the
front STOP/RESET, MANUAL, AUTO
and START push buttons. Three of
these push buttons include an LED
indicator. Additional push buttons
provide LCD display scroll, lamp test,
mute functionality and breaker control.
TYPICAL LOAD SHARE
APPLICATION
G1
G2
G3
LOAD
BUILT-IN FUNCTIONS
Alternator under/over volts
Alternator under/over frequency
Warning or shutdown on engine temperature, over/under speed, oil
pressure
Warning, shutdown or electrical trip on battery volts or over current
Shutdown or electrical trip on reverse power, phase rotation or short
circuit fault
Earth fault shutdown
Adjustable crank cycle/attempts
Full remote control and telemetry
9 configurable digital inputs
5 configurable and 2 fixed relay/FET outputs
System lock input
Load switching control push-button inputs
ROCOF/vector shift (mains/utility decoupling)
Negative phase sequence
Loss of excitation
PIN number
INSTRUMENTATION AND ALARMS
The DSE7510 module provides advanced metering and alarm functionality
via the LCD display. The information can be accessed using the display scroll
push buttons. The table below shows the instrumentation and alarm features
the module provides.
Generator Volts L1-N, L2-N, L3-N
Generator Volts L1-L2, L2-L3, L3-L1
Generator Amps L1, L2, L3
Generator Frequency Hz
Generator kVA L1, L2, L3, Total
Generator kW L1, L2, L3, Total
Generator pf L1, L2, L3, Average
Generator kVAr L1, L2, L3, Total
Generator kWh
Generator kVAh
Generator kVArh
Generator Phase Sequence
Synchroscope Display
Engine Speed RPM
Engine Oil Pressure
Engine Temperature
Plant Battery Volts
Charge Alternator Volts
Fuel Level
Generator Earth Current
Bus Volts (L-L&LN)
Bus Frequency (Hz)
Bus Phase Sequence
Engine Hours Run
Number of Start Attempts
Maintenance Display
Engine ECU diagnostics information via industry standard CAN interface
Enhanced metering via CAN when connected to an electronic engine
TELEMETRY
The module gives the user full
telemetry facilities when using the
optional communications software.
The module can be connected to a
PC using the DSE810 PC interface
or by using a suitable modem.
The PC software is Microsoft
Windows based. All access into
the module can be configured to
become password protected to
prevent unauthorised entry. The PC
software allows the module to be
controlled from a remote location.
COMMUNICATIONS
The DSE7510 has a number of
different communication capabilities:SMS Messaging
When the module detects an alarm
condition, it has the ability to send
an SMS message to a dedicated
mobile number, notifying an engineer
of the problem. (GSM Modem and
data enabled SIM Card required).
Remote Communications
When the module detects an
alarm condition, it dials out to a PC
notifying the user of the exact alarm
condition (modem required).
Building Management
The module has been designed to
be integrated with new and existing
building management systems.
SCADA/PC Software
The module has the ability to be
configured and monitored from a
remote PC, using the DSE810
interface.
EVENT LOG
The module includes a
comprehensive event log that
shows the 25 most recent alarm
conditions and the date and time
that they occurred.
This function assists the user when
fault finding and maintaining the
generating set.
EXPANSION MODULES
DSE123 Load Share Lines Interface
Module
DSE157 Relay Output Expansion
Module
DSE545 & DSE548 Remote
Annunciation Expansion Module
DSE130 Input Expansion Module
ELECTRONIC ENGINE
COMPATIBILITY
Cummins
Deutz
John Deere
MTU
Perkins
Scania
Volvo
Isuzu
Generic
Plus additional manufacturers
DSE7510
FROM
GENERATOR
AUTOMATIC MCCB
AUTOMATIC ACB
or CONTACTOR
3 or 4 POLE
P1
TO
LOAD
P2
L1
S1
S2
L2
L3
55
54
43
44
45
46
CT4
NS2
COM
U
L1
V
L2
W
L3
OIL PRESSURE
WATER TEMP
COMMON GROUND
CHG ALT
17
18
15
23
39
40
56
57
47
48
49
50
R
L1
S
L2
T
L3
OUTPUT C
MPU
33
SCR
31
32
MSC
BUS VOLTS
P810
MODULE 7510
157
3 OUTPUTS
GOVERNOR
10
34
CONNECT SCREEN AT
GENERATOR ONLY
68
67
66
65
64
63
62
61
O/P
B
60
AVR
35
36
ENGINE ECU
O/P
B
SCR
37
38
27
25
26
TO
GOVERNOR
TO
AVR
SCREEN EARTHED
AT THIS END ONLY
CONNECT SCREEN AT
GENERATOR ONLY
PLANT +VE
9 INPUTS
FUEL TEMP
CRANK
FUEL
UPTO32 AMPS
FUSE
22
-VE
+VE
BATTERY
24
CLOSE GEN
OUTPUT D
16
B
SCR
SCR
GEN VOLTS
42
GEN CURRENT
RS232
41
RS485
53
CT3
L3S1
CHARGE ALTERNATOR
52
CT1
CT2
L1S1 L2S1
MPU
TO ENGINE EARTH
51
2 AMP
FUSES
TO GEN SWITCHING
DEVICE CIRCUITRY
2 AMP
FUSES
RELATED MATERIALS
TITLE
DSE7510 Manual
DSE7510 Installation Instructions
DSE75xx PC Software Manual
DSE7520 Data Sheet
DSE7560 Data Sheet
02/2010 ISSUE 5
PART NOS
057-088
053-052
057-078
055-066
055-067
055-044
057-047
057-045/6
057-004
055-072