Central Battery Systems

Table of Content
General Presentation Single Phase Systems Three Phase Systems Optional Features User Interface and Display What to consider when requesting a Central System? 3&4 5&6 7&8 9 10 11

Choosing the right system


There are a variety of ways in which back-up power can be provided. However, even though certain methods are suitable for critical applications, they may not necessarily be suitable for Emergency Lighting.
This is because an Emergency Lighting system has unique load characteristics. And since Emergency Lighting is a critical life-safety installation, it is vital that a Central Battery System is designed with these load characteristics in mind. EMEX Power central inverter systems are specically designed to provide emergency power for emergency lighting systems in a power failure.

In choosing the right AC system to support emergency lighting it is important to consider the following questions:
Overload performance
Is the system able to start the full load without the mains supply present. How does the system perform in a total power failure (ie is the system able to start the load without the bypass supply being available)?

General information on UPS systems:


Recharge period
UPS systems which are designed primarily for computer back-up generally offer short run times, 5 or 10 minutes. The long run times required for emergency lighting call for more powerful chargers to recharge the larger bank of batteries needed in the time prescribed by CSA.

Repeat duty
CSA141-10 requires a central battery system to fully recharge within 24 hours. Is the charger able to recharge the batteries quickly (80% in 14 hours or 100% after 24 hours)?

Overload performance
An emergency lighting load will impose large in-rush currents when starting lamps from cold. However, UPS systems are often designed to shut down at only 125% overload and revert to the incoming supply. During a total power failure situation, this could result in total failure of the emergency lighting system. Furthermore, a UPS may fail to clear a breaker on a lighting circuit, meaning that a single short circuit fault could result in loss of the entire emergency lighting supply.

Energy consumption and heat dissipation


Is the inverter and charger permanently running, shortening the battery life, generating heat, wasting energy and shortening component life? Are cooling fans running continuously, generating noise?

Maintenance
Is the system easy to service and maintain? Is the system designed in a modular format, or would the failure of even a minor component require the whole system to be shut down and stripped for repair?.

Energy consumption and battery life


Most UPS systems operate in the on-line mode, whereby the inverter runs constantly to supply the load, and power is taken from the battery with the charger running constantly. This places an excessive ripple on the battery (contrary to the advice given by most battery manufacturers). Also, the system is constantly generating heat which has a further detrimental effect on battery life. There are energy costs and heat generation issues must be addressed when running an on-line system.

www.emergi-lite.com

EMEX Power - Modular AC Central Battery System


SYSTEM DESIGN
The EMEX Power inverter and charger modules utilize solid state electronics of the highest reliability to provide a rugged, easy to maintain system with exceptional performance for emergency lighting use. The system has been designed solely for emergency lighting, and not modied from other less essential power supply requirements. As such, the system has exceptional overload performance without the need to over-specify the rating of the inverter to ensure faults can be cleared. Each module has input and output protection and each module measures and limits its own current. Alarms and status indications are provided on the front panel display, which provides clear and concise information, rather than a long list of parameters, which may be confusing.

True Sine Waveform


Using a solid-state, pulse width modulation (PWM) inverter the systems produce pure sinusoidal output waveform with less than 5% Total Harmonic Distortion (THD) for linear loads.

Reliability
The product is third generation inverter technology. LVD (Low Voltage Disconnect) circuitry eliminates excessive battery drain after long power outages.

Batteries
Automatic restart and recharge upon restoration of utility.

Approvals
Letter of attestation from CSA (Electrical) Designed and tested to CSA 141-10

SERIES HIGHLIGHTS
Performance
The EMEX-Power Systems work with lighting loads to provide full light output for minimum 30 min. It is designed to support incandescent, uorescent and LED loads. It will power these loads at cold starts for all normally off circuits or normally on circuits.

Applications
EMEX-Power Systems can be used in almost every type of building, especially in architecturally sensitive applications or when maintenance costs and testing of individual unit equipment becomes signicant. Our systems are designed to work with power factor corrected as well as the most recent T5 and T5-HO electronic ballasts.

FEATURES
Self-Diagnostic/Self-Testing
Programmable monthly and annual self-testing. Proven self-diagnostic with information stored in separate memory logs for Test, Event and Alarm. Microprocessor monitoring and control.

BENEFITS
Compliance with NFPA101
The self-testing meets the requirements of NFPA and UL. User programmable time of testing. Test results, events or alarms can be downloaded from history logs. Load monitoring. Reduced testing/service time.

Low heat dissipation


Very low heat loss in standby operating mode (see specications for exact values). Convection cooling in normal mode with forced air during emergency and recharge mode. Battery cabinets: convection cooling only.

Less air-conditioning
Reduced costs for air-conditioning required to ensure the optimum operating temperature when compared with equivalent systems that dissipate much more heat. Higher reliability of fans and electronic components.

Versatile Installation
Modular design, easy front access freestanding cabinets, fasten together when more than one cabinet is required. Optional seismic kit available. All wiring provided is pre-cut and terminated, along with the necessary hardware for proper installation.

Easy to install
Quick installation and connection through exible cable entries and fast access terminal blocks. Low MTTR (<30 min.) due to modular design, quick disconnect means and frontal access.

Complete Protection
Battery circuit breakers are standard. Modular standard systems offer overload capacity, short-circuit protection, current- limiting, low-battery disconnect and brownout protection as standard.

Reduced damage risks


The full protection of the system will eliminate damage created by external events and will increase lifetime of the electronics and the batteries.

Thermal Performance
Bonded oversized heat sinks for maximum thermal performance. Cooling fans are energized only in inverter and recharge modes.

Increased MTBF
Increased reliability and reduced preventative maintenance. No air lters needed.

Monitoring and Control


User friendly programmable interface with LCD display provides full metering values, easy program and control functions and a wide range of visual and audible alarms.

Easy maintenance
Diagnostics, troubleshooting, preventative maintenance and service are made easier by using the front panel display or the history logs.

EMEX Central Battery Systems IPS SINGLE PHASE SERIES


Interruptible emergency lighting inverter system 3KVA 15KVA Features:
PWM/Power Mosfet technology Self-testing/Self-diagnostic User programmable with password protection User programmable variable time delay Optional 100% normally Off output RS485 MODBUS RTU communication port Micro-processor controlled 30, 60, 90, 120 minutes run times Summary alarm form C dry contact Generator compatibility Electronic and magnetic ballast compatible Automatic event, test and alarm log LCD display Maintenance free standard batteries Forced air cooling during emergency and recharge mode only Off when on standby

For all fluorescent/incandescent/LED loads

ELECTRICAL/MECHANICAL CHARACTERISTICS for 30 minutes back-up time


Efc. Power at full rating load KVA/KW %
3.0 6.0 9.0 12.0 15.0 98% 98% 98% 98% 98%

Max. input current (A)(1)


120V 42 67 92 117 142 240V 21 33 46 58 71 277V 18 29 40 51 61 347V 14 23 32 40 49

Heat loss in normal mode (BTU/hr)


546 546 546 546 546

Batt. VDC
120 120 120 120 120

Batt. ADC
34 68 101 135 168

No. of batt.(1)
10 20 10 20 20

IPS cabinet dimensions


W 30 30 30 30 30 H 71 71 71 77 77 D 27 27 27 27 27

No. of batt. cab.


(1)(2)

Batt. cabinet dimensions


W NA NA NA 30 30 H NA NA NA 77 77 D NA NA NA 27 27

IPS Cabinet weight kg(1)


240 290 340 390 440

Batt. cabinet weight kg (empty)(1)


NA NA NA 140 140

Battery weight kg(1)


105 210 372 550 550

Total system weight kg(1)


345 500 712 1080 1130

NA NA NA 1 1

1- For 30 min. discharge time. For other discharge times, consult factory. 2- Batteries are installed in the IPS cabinet for 3 to 9.0KVA systems, for 30 minutes only.

Ordering Information(1)
Series
E= Series

System Voltage
1= 120-120 input-output 2= 240-240/120 3= 277-277 4= 347-347 A= 3 B= 6 C= 9 D= 12 E= 15*

KVA/KW

Run Time
3= 30 minutes 6= 60 minutes 9= 90 minutes 12= 120 minutes

External Circuit Breaker


B= no breakers N= normally on F= normally off Quantity 1 to ** Specify Quantity AMP 10,15,20,25 .

Options
A= fast recovery charge B= remote meter panel C= remote alarm panel D= ethernet port E= output trip alarm F= NEXUS system interface G= inverter on dry contact H= normally off output (specify capacity) I= extended battery warranty* J= external maintenance bypass K= seismic mounting bracket L= drip shield
*Consult your sales representative.

# 5 to Z ( other voltages available )

*Min. 240Vac in/out

Example :N1020 **

Example: E1A3N1020

www.emergi-lite.com

EMEX Central Battery Systems IPS SINGLE PHASE SERIES


SYSTEM SPECIFICATIONS
General
Design Control Metering Communications
Stand-by. PWM inverter type utilizing Power Mosfet technology with 500ms transfer time. Microprocessor controlled, 4 x 20-character display with touch pad controls & functions Input & Output Voltage, Battery Voltage, Battery & Output Current, Output VA, Temperature RS-485 MODBUS RTU Port (DB-9)

CABINETS
Modular design, freestanding NEMA type 1 steel cabinets powder coated for corrosion and scratch resistance. Front access design through hinged lockable doors requires only 42 front, 2 back and side clearance and 12 top clearance without drip shield. Top conduit entry Gland Plate.

INVERTER
Using Power Mosfet/PWM technology the inverter converts DC voltage supplied by the batteries to AC voltage of a precise stabilized amplitude and frequency, suitable for most sophisticated electrical equipment. True sinusoidal output waveform with very low distortion (less than 5% for linear loads). Overload capability of 120% continuous, 150% for 1 minute and 200% for 10 seconds.

Electrical Input
Voltage Input Frequency
120, 240, 277, 347VAC 1-phase 2-wire +10% / -15%. 60Hz

CHARGER
Fully automatic, temperature compensated, charger recharges fully discharged batteries in maximum 24 hours at nominal AC input voltage. AC input current limiting and over-voltage protection included.

Electrical Output
Voltage Dynamic Voltage Harmonic Distortion Output Frequency Load Power Factor Inverter Overload Protection Crest Factor
120, 240, 277 or 347VAC 1-phase 2-wire. +/-2% for +/-25% load step change, +/-3% for a 50% load step change, recovery within 3 cycles <5% THD for linear load 60Hz +/- 2Hz during emergency mode 0.7 lag to 0.9 lead 120% continious, 150% for 1 minute and 200% for 10 seconds Optional External Distribution Circuit Breaker 3

BATTERY
System is provided standard with 10 year, maintenance free, sealed valve regulated, lead calcium batteries. 20 years life sealed lead calcium available. 30, 60, 90 & 120 min. standard discharge time at full load under normal operating temperature (20C to 25C). Low Voltage Disconnect protection included. No special ventilation required.

SUPERVISION
Automatic self tests consist of a 2-minute monthly, 1/3 discharge at 6 months and full annual discharge. The front-mounted control panel includes, a 4-line 20-character LCD display with a keypad to control and monitor the operation of the system. This allows the operator to easily watch system functions as they occur and check on virtually any aspect of the systems operation. Standard RS485 MODBUS RTU diagnostic interface.

Environmental Conditions
Storage/Transport
32F to 104F (0C to 40C) without batteries 68F to 86F (20C to 30C) with batteries(1) System operates safely from 32F to 104F (0C to 40C) but optimum operation is between 68 F and 77F (20C to 25C). Battery performance can be affected by temperature. <10,000 feet (above sea level) without de-rating 0 to 95% non-condensing 45 dBA at 1m from surface in emergency mode

ALARMS
Battery High/Low, Low Voltage Disconnect, Battery Disconnect, Maintained Lamp Off, Charger Fail, Supply From Battery, System Inhibit, Circuit Breaker Trip, Module Breaker Trip, Inverter Undervoltage, Inverter Overvoltage, Output Overcurrent, Hi Temp, Over Temp, Unit in Bypass, Inverter Frequency Control Failed, Processor Reset.

Operating Temperature

Altitude Relative Humidity Audible Noise

OPTIONAL FEATURES
External Output Circuit Breakers, Output Trip Alarms, Extended Battery Warranty, 12 Hours Fast Recharge, External Maintenance Bypass Switch, Remote Meter Panel, Ethernet Port, NEXUS System Interface. Dripshield, Remote Alarm Panel, Normally Off Output, Seismic Mounting Brackets, Dry Contact Relay.

(1) - max. 3 months at 77F-86F (25C-30C)

Single Line Diagram

FACTORY START-UP
Includes one additional year of warranty. See warranty conditions.

WARRANTY
(full limited warranty conditions available upon request)

Limited manufacturer warranty is one-year, parts and labor, for system electronics. Battery warranty is one year full plus 9 years pro-rata for a total of 10 years, under normal operating conditions. System must be put in service within 6 months from ship date in order to validate warranty. Consult factory for other battery types.

EMEX Central Battery Systems IPS THREE PHASE SERIES


Interruptible emergency lighting inverter system 4.5KVA 54KVA Features:
PWM/Power Mosfet technology Self-testing/Self-diagnostic User programmable with password protection User programmable variable time delay Optional 100% normally Off output RS485 MODBUS RTU communication port Micro-processor controlled 30, 60, 90, 120 minutes run times Summary alarm form C dry contact Generator compatibility Electronic and magnetic ballast compatible Automatic event, test and alarm log LCD display Maintenance free standard batteries Forced air cooling during emergency and recharge modes only Off when on standby

For all fluorescent/incandescent/LED loads

ELECTRICAL/MECHANICAL CHARACTERISTICS for 30 minutes back-up time


Max. input Heat loss IPS cabinet Batt. cabinet Batt. cabinet Power Efc. current (A)(1) No. of dimensions No. of dimensions No. of 30 dimensions rating in normal Batt. Batt. No. of at full IPS 20 batt. batt. cab. VDC ADC batt.(1) KVA/ mode (1)(2) load % 208/ 480/ 600/ cab. (1)(2) W H D cab.(1)(2) W H D W H D KW 120V 277V 347V (BTU/hr)
4.5 9.0 13.5 18.0 22.5 27.0 31.5 36.0 40.5 45.0 49.5 54.0 98% 98% 98% 98% 98% 98% 98% 98% 98% 98% 98% 98% 29 42 54 67 79 92 104 117 129 142 NA NA 13 18 23 29 34 40 45 51 56 61 67 73 10 14 19 23 27 32 36 40 45 49 53 58 546 546 546 546 546 1092 1092 1092 1092 1092 1092 1638 120 120 120 120 120 120 120 120 120 120 120 120 50 101 151 202 252 303 353 403 454 504 555 605 20 10 20 20 30 30 30 40 40 50 50 60 1 1 1 1 1 1 2 2 2 2 2 2 30 30 30 30 30 30 30 30 30 30 30 30 71 71 77 77 77 77 77 77 77 77 77 77 27 27 27 27 27 27 27 27 27 27 27 27 NA NA 1 1 NA NA 1 NA 2 1 1 NA NA NA 30 30 NA NA 30 NA 30 30 30 NA NA NA 77 77 NA NA 77 NA 77 77 77 NA NA NA 27 27 NA NA 27 NA 27 27 27 NA NA NA NA NA 1 1 NA 1 NA 1 1 2 NA NA NA NA 30 30 NA 30 NA 30 30 30 NA NA NA NA 71 77 NA 77 NA 77 77 77 NA NA NA NA 30 30 NA 30 30 30 30 30

Total IPS

Cabinet weight kg(1)(2)


265 340 415 540 615 690 905 1030 1105 1180 1255 1380

Total batt. Battery cabinet weight weight kg kg(1) (empty)(1)


NA NA 140 140 165 165 140 165 280 305 305 330 210 372 550 744 825 1116 1116 1488 1488 1860 1860 2232

Total system weight kg(1)


475 712 1105 1424 1605 1971 2161 2683 2873 3345 3420 3942

1- For 30 min. discharge time. For other discharge times, consult factory. 2- Batteries are installed in the IPS cabinet for 1.5 to 9.0KVA systems, for 30 minutes only.

Ordering Information(1)
Series
EIII= Series

System Voltage
1= 120-208 4 wire 2= 277/480 3= 347/600 A= 4.5 B= 9 C= 13.5 D= 18 E= 22.5 F= 27 G= 31.5 H= 36 I=40.5 J= 45* K= 49.5* L= 54*

KVA/KW

Run Time
3= 30 minutes 6= 60 minutes 9= 90 minutes 12= 120 minutes

External Circuit Breaker


B= no breakers N= normally on F= normally off Quantity 1 to ** Specify Quantity AMP 10,15,20,25 .

Options
A= fast recovery charge B= remote meter panel C= remote alarm panel D= ethernet port E= output trip alarm F= NEXUS system interface G= inverter on dry contact H= normally off output (specify capacity) I= extended battery warranty* J= external maintenance bypass K= seismic mounting bracket L= drip shield

# 4 to Z ( other voltages available )

** For 120/208Vac in/out, 120 mins. runtime not available. *Min. 277/480Vac in/out

Example :N1020 **

*Consult your sales representative.

Example: EIII1A3N1020

www.emergi-lite.com

EMEX Central Battery Systems IPS THREE PHASE SERIES


SYSTEM SPECIFICATIONS
General
Design Control Metering Communications
Stand-by. PWM inverter type utilizing Power Mosfet technology with 500ms transfer time. Microprocessor controlled, 4 x 20-character display with touch pad controls & functions Input & Output Voltage, Battery Voltage, Battery & Output Current, Output VA, Temperature RS-485 MODBUS RTU Port (DB-9)

CABINETS
Modular design, freestanding NEMA type 1 steel cabinets powder coated for corrosion and scratch resistance. Front access design through hinged lockable doors requires only 42 front, 2 back and side clearance and 12 top clearance without drip shield. Top conduit entry Gland Plate.

INVERTER
Using Power Mosfet/PWM technology the inverter converts DC voltage supplied by the batteries to AC voltage of a precise stabilized amplitude and frequency, suitable for most sophisticated electrical equipment. True sinusoidal output waveform with very low distortion (less than 5% for linear loads). Overload capability of 120% continuous, 150% for 1 minute and 200% for 10 seconds.

Electrical Input
Voltage Input Frequency
120/208, 277/480, 347/600VAC 3-phase 4-wire +10% / -15%. 60Hz

CHARGER
Fully automatic, temperature compensated, charger recharges fully discharged batteries in maximum 24 hours at nominal AC input voltage. AC input current limiting and over-voltage protection included.

Electrical Output
Voltage Dynamic Voltage Harmonic Distortion Output Frequency Load Power Factor Inverter Overload Protection Crest Factor
120/208, 277/480, 347/600VAC 3-phase 4-wire. +/-2% for +/-25% load step change, +/-3% for a 50% load step change, recovery within 3 cycles <5% THD for linear load 60Hz +/- 2Hz during emergency mode 0.7 lag to 0.9 lead 120% continuous, 150% for 1 minute and 200% for 10 seconds Optional External Distribution Circuit Breaker 3

BATTERY
System is provided standard with 10 year, maintenance free, sealed valve regulated, lead calcium batteries. 20 years life sealed lead calcium available. 30, 60, 90 & 120 min. standard discharge time at full load under normal operating temperature (20C to 25C). Low Voltage Disconnect protection included. No special ventilation required.

SUPERVISION
Automatic self tests consist of a 2-minute monthly, 1/3 discharge at 6 months and full annual discharge. The front-mounted control panel includes, a 4-line 20-character LCD display with keypad to control and monitor the operation of the system. This allows the operator to easily watch system functions as they occur and check on virtually any aspect of the systems operation. Standard RS485 MODBUS RTU diagnostic interface.

Environmental Conditions
Storage/Transport
32F to 104F (0C to 40C) without batteries 68F to 86F (20C to 30C) with batteries(1) System operates safely from 32F to 104F (0C to 40C) but optimum operation is between 68 F and 77F (20C to 25C). Battery performance can be affected by temperature. <10,000 feet (above sea level) without de-rating 0 to 95% non-condensing 45 dBA at 1m from surface in emergency mode

ALARMS
Battery High/Low, Low Voltage Disconnect, Battery Disconnect, Maintained Lamp Off, Charger Fail, Supply From Battery, System Inhibit, Circuit Breaker Trip, Module Breaker Trip, Inverter Undervoltage, Inverter Overvoltage, Output Overcurrent, Hi Temp, Over Temp, Unit in Bypass, Inverter Frequency Control Failed, Processor Reset.

Operating Temperature

Altitude Relative Humidity Audible Noise

OPTIONAL FEATURES
External Output Circuit Breakers, Output Trip Alarms, Extended Battery Warranty, 12 Hours Fast Recharge, External Maintenance Bypass Switch, Remote Meter Panel, Ethernet Port, NEXUS System Interface. Dripshield, Remote Alarm Panel, Normally Off Output, Seismic Mounting Brackets, Dry Contact Relay.

(1) - max. 3 months at 77F-86F (25C-30C)

Single Line Diagram

FACTORY START-UP
Includes one additional year of warranty. See warranty conditions.

WARRANTY
(full limited warranty conditions available upon request)

Limited manufacturer warranty is one-year, parts and labor, for system electronics. Battery warranty is one year full plus 9 years pro-rata for a total of 10 years, under normal operating conditions. System must be put in service within 6 months from ship date in order to validate warranty. Consult factory for other battery types.

Systems Options -DETAILS(-A) 12 Hour Fast Recharge


Battery charger upgrade option which decreases the time required to recharge a fully discharged battery to a fully charged state. The normal 24 hour recharge time is reduced to a 12 hour period.

(-H) Normally Off Output


This output circuit is dedicated for the emergency only equipment. Emergency only equipment operates during power outages and when the system is on battery back up. This option leaves the normally off load circuits off during normal utility power conditions.

(-B) Remote Meter Panel


The panel allows monitoring of parameters and control from remote locations up to 150 feet away from the inverter system. Also, the remote panel provides a complete touch pad interface allowing the user to monitor, control and program the inverter system.

(-I) Extended Battery Warranty


Extends battery warranty from 10 years pro-rated to 20 years pro-rated.

(-J) External Maintenance Bypass Switch


The external maintenance bypass switch is mounted in a 20H x 16W x 9D NEMA 1 separate enclosure, used to completely isolate the inverter system from the connected load and AC utility input. This option allows the system to be safely powered down for maintenance or service.

(-C) Remote Summary Alarm Panel


Wall mountable box provides visual and audible alarms with silence switch. The panel consists of LED indicators and built in audible alarm and may be located up to 1,000 feet away from the inverter system.

(-K) Seismic Mounting Kit


The seismic mounting kit option is designed to prevent system movement during seismic events. Heavy duty brackets are provided to secure system cabinetry to your surfaces.

(-D) Ethernet Port


Interface to ethernet network. Provides status information and allows system management via internet browser.

(-E) Output Trip Alarm


System triggers an alarm when any output breaker trips.

(-L) Drip Shield


Hood cover to protect the enclosure against falling water from sprinkler systems.

(-F) NEXUS System Interface


Allows remote monitoring of the system from a server (wireless or cabled communication).

(-G) Inverter On Dry Contacts


Form C dry contacts that will change state when the system transfers to battery.

www.emergi-lite.com

10

User Interface & Display Functions


Meter & Reading Functions Menu
AC Voltage Output AC Current Ouput Normally On AC Current Output Normally Off Battery Voltage Battery Charging Current Battery Discharging Current KVA Total Output Cabinet Internal Temperature Inverter Frequency Real Time Clock Time Delay Monthly Test Result Half Year Test Result Annual Test Result Event Log Reading

Service Menu Functions


Passkeyword protected Set Battery Voltage & Current Ranges Set System Voltage & Current Ranges Set System Phase Set Normally OFF Load Set Language Set Real Time Clock & Calendar Set Time Delay Function Set Manual Test Duration Set Self Test Sequence Set Buzzer Function

Administration Menu Functions


Passkeyword protected Read/Set Serial Number Read/Set Manufacturing Date Read/Set Installation Date Read Firmware Version Read/Clear Battery Elapse Time Read/Clear Total Power Failures Read/Clear Total Alarms Clear Event Log Enter Calibration Routine

Alarm and Events


Event Logging (1000) Type Date & Hour Transfer Mode Standby Load Off Stop Mode Lock-Out Mode Forced Transfer Battery Volt Battery Disconnect Mains Out Of Range Manual Test Monthly Test Half Year Test Yearly Test Modbus Transfer NEXUS Transfer

System Testing
EMEX Central Battery Systems provide manual and automatic test functions. Manual test can be activated any time using the test key provided on the control panel. Manual testing will do a programmable fixed test time and can be aborted any time by pushing again on the test key. Automatic test and diagnostic is done following an annual sequence. Every month a quick diagnostic test of 2 minutes is performed. At the 6 month mark, a 1/3 timed discharge test is done, and at the 12 month, a full discharge, down to LVD is performed. Pass/Fail and discharge time are registered in the event log. Test time and date is programmed using the Service Menu.

11

Central System Request Data


1) Input voltage
Single phase Three phase Three phase (2 wire + ground) (4 wire + ground, Y) (3 wire + ground, ) 120VAC 120/208VAC 208VAC 208VAC 277/480V 480VAC 240VAC 347/600VAC 600VAC 277VAC 347VAC

2) Output voltage
Single phase Single phase Three phase (2 wire + ground) (3 wire + ground) (4 wire + ground, Y) 120VAC 120/240VAC 120/208VAC 208VAC 120/277V 277/480VAC 347/600VAC 277VAC 347VAC

3) System capacity
KVA rating: a) Please consider total power consumption of the complete xture, not just the lamp wattage b) Even if the systems can run with 100% load, it is recommended as standard practice to use a system with a capacity at least 20% over maximum connected load

4) Runtime
30 minutes Other 60 minutes 90 minutes 120 minutes

5) Type of loads
Incandescent Others Fluorescent L.E.D.

6) Mode of operation
Normally ON (24/7) Normally OFF (emergency only)

7) output circuit breakers


# of CB # of CB Amps Amps # of poles # of poles Normally On Normally On Normally Off Normally Off Trip alarm Trip alarm

8) Options (refer to available options for each system type)


(-A) 12 Hour Fast Recharge (-B) Remote Meter Panel (-C) Remote Summary Alarm Panel (-D) Ethernet Port (-E) Output Trip Alarm (-F) NEXUS System Interface

(-G) Inverter On Dry Contacts (-H) Normally Off Output (-I) Extended Battery Warranty (-J) External Maintenance Bypass Switch (-K) Seismic Mounting Kit (-L) Drip Shield

www.emergi-lite.com

All information and specifications contained in this catalogue are subject to change due to engineer design, errors and omissions. Illustrations and diagrams within this catalogue may vary from actual products. 2011 Thomas&Betts Limited. All rights reserved. Printed in Canada. 06/11/000. Order No.: EL/EMEXCATALOGUE-E