RM st60
RM st60
RM st60
Model RM-ST60
P.O. Box 330607 Ft. Worth, TX 76163 Phone: 817.483.8497 Fax: 817.572.2242
www.sinetamer.com
The SineTamer RM series of units blends outstanding high-energy impulse suppression with excellent ring-wave transient protection. This durable device is intended for general purpose and sensitive/critical load applications. The RM-ST60 is typically installed at small service entrances up to 400 amps, distribution and subdistribution panels. Compact size and non-metallic enclosure design also allow it to be installed directly inside electrical panels and individual equipment disconnects. The internal installation provides the absolute shortest possible lead length and optimum performance. The RM-ST60 is extremely effective in limiting internally generated transients and is an absolute must on panels feeding office locations and/or microprocessor based equipment. This economical device has features that are not available in devices costing many times its price. Its compact size makes installation a breeze. Maintenance Free operation and 15 Year Unlimited Free Replacement Warranty provide peace of mind.
GENERAL
Description: Parallel connected, transient voltage surge suppressor device utilizing both high-energy handling and sine-wave tracking circuitry for virtual elimination of impulse and ring wave type transients. (actively tracking the AC sine wave) Designed for use at ANSI/IEEE Categories C, B and A with susceptibility up to medium exposure levels. Designed to protect sensitive/critical loads fed from distribution panels, branch panels and/or individual equipment panels. 15 Years Unlimited Free Replacement nd Listed to UL1449 2 Edition (Feb. 9, 2007 Rev.) by CSA, an NRTL, CSA MC#214804, UL1283 and CE Compliant, ISO 9001:2000, ANSI C62.72-2007
Application:
MECHANICAL
Enclosure: Mounting: Connection Method: Shipping Weight: High strength ABS Plastic, NEMA 4 rated enclosure. 3/4 conduit fitting (internally threaded) and external mounting feet. #10 stranded wire. 6 lbs
ELECTRICAL
Circuit Design: Parallel connected, internally fused, hybrid design incorporating all mode protection, and utilizing our encapsulated design to provide improved durability. All suppression circuits are encapsulated in our exclusive compound to assure long component life and complete protection from the environment and/or vibration. L-N, L-L (Normal Mode), and L-G, N-G (Common Mode). (Seven discrete modes) 50-60Hz constant <1 nanosecond 30dB Max. from 1kHz to 10MHz Up to 3.5 uF Max. Super Bright LED, 1 per phase, normally on. External and internal (see installation instructions for details). Component Level Thermal and Board Level Current Fusing 200 kAIC when installed according to installation instructions
Protection Modes: Input Power Frequency: Response Time: EMI/RFI Noise Attenuation: Capacitance: Circuit Diagnostics: Circuit Interrupt: Fusing: kAIC Rating:
Because we are constantly seeking to improve our products, specifications are subject to change at any time.
2008 ECS International Inc. Specification Last Changed 07/06 RM-ST60.doc
Top View
8.87
9.37 5.00
3.00
3.37
Model
Circuit Type
MCOV
Mode
RM-ST60-1P1
120V, Single (2 wire + ground) 120/240V, Split (3 wire + ground) 120/208V, 3Y (4 wire + ground) 240V, Single (2 wire + ground) 277/480V, 3Y 220/380V, 3Y (4 wire + ground) 240V, 3 (3 wire + ground) 380V, 3 480V, 3 (3 wire + ground)
RM -ST60-1S1
RM-ST60-3Y1
RM -ST60-1P2
150 L-N 150 L-G 150 N-G 300 L-L 150 L-N 150 L-G 150 N-G 300 L-L 150 L-N 150 L-G 150 N-G 320 L-N 320 L-G 320 N-G 550 L-L 320 L-N 320 L-G 320 N-G 320 L-L 320 L-G 550 L-L 550 L-G
20,000 / 40,000
20,000 / 40,000
20,000 / 40,000
20,000 / 40,000
RM -ST60-3Y2
20,000 / 40,000
RM -ST60-3N2 RM -ST60-3N4
L-N L-G N-G L-L L-N L-G N-G L-L L-N L-G N-G L-N L-G N-G L-L L-N L-G N-G L-L L-G L-L L-G
Let-Through Voltage Test Environment: Positive Polarity. Time base=1ms. All voltages are peak (10%). Surge voltages are measured from the insertion point of surge on the sine wave to the peak of the surge. All tests are Dynamic (voltage applied) except N-G which is static (no voltage applied). All tests were performed with 6 inches of lead length outside the device enclosure which simulates actual as installed performance. Single-pulse, surge current testing for all modes at rated currents, is in compliance with NEMA LS 1-1992. Single-pulse, surge current capacities of 200,000 amps or less are determined by single-unit testing of all components within each mode. Present industry test equipment limitations require testing of individual components or sub-assemblies within a mode for single-pulse, surge current capacities over 200,000 amps.
Because we are constantly seeking to improve our products, specifications are subject to change at any time.
2008 ECS International Inc. Specification Last Changed 07/06 RM-ST60.doc