618ti PDF
618ti PDF
618ti PDF
Standard
Section
Inquiry #
Reply
618 618
General 2.1
618-I-01/08 Reciprocating compressors differ from the machines you reference in that they are isolated from their piping by pulsation bottles or vessels. These latter vessels, through their mass and support system, absorb much of the loads from the piping. You are correct, there are no nozzle load limits specified in API 618; however, 2.1.11 makes it the joint responsibility of the user and vendor for the machine to perform satisfactorily. Section 2.6.2.2 defines the coordinate system for applied nozzle loads and requires the manufacturer to furnish allowable loads. It is recommended the user consult the manufacturer for guidance. Yes, it is the intent of this standard to provide equipment (including auxiliaries) that has been designed to provide 3 years of uninterrupted operation, without annual maintenance. It is realized that there are some services where that objective is easily attainable and others where it is more difficult. The system design is a very important criterion in meeting this objective. Note that this is a design requirement. Manufacturers may choose to recommend reduced maintenance intervals dependant upon the proposed operating conditions.
In API 610, 617, 611 and 612, there are some sections about the allowable forces and moments acting at the nozzles of the pump, turbines, and compressors. Normally, these are based on the specifications of NEMA SM23 with adding some factor, but in API 618, we didn't find any words about that. So, please tell me which standard will be adapted and where we can get it. Our LPEC is a petrochemical engineering corporation and imported some reciprocating compressors ACC to API 618 we can't find any standard.
618
2.1.1
618-I-02/03
Background: As we all know horizontal reciprocating compressors are fitted with rider rings on the piston, which are likely to be worn out with continuous operation. Hence compressor manufacturers recommend a yearly maintenance to replace these parts. Since 2.1.1 calls for "an expected uninterrupted operation of at least 3 years", my question to you is, that whether such 3 years continuous operation is really possible or not, OR, this clause neglects the downtime required for the annual maintenance. Question: Does API 618 insist, that the compressor be designed for three years of maintenance free operation?
API Standard 618 - Reciprocating Compressors for Petroleum, Chemical, and Gas Industry Services
Last Update: June 8, 2011
Standard 618
Section 2.2.4
Inquiry # 618-I-03/04
Question Background: We have experienced some failures in compressor crossheads due to inadequate lubrication, and some manufacturers perceive that API requirements for load reversals are only minimum requirements, and hence meeting them would not guarantee that lubrication is adequate. Their standpoint is that API 618 does not state that the compressor has to be designed to run at this minimum requirement, simply that the criteria should be met. The same requirement existed on the 3rd edition of API 618, and my understanding is that it will be kept unchanged on the forthcoming 5th edition. Section 2.4.4 requires that the duration of the load reversal at the crosshead pin shall not be less than 15 degrees of crank angle, and that the magnitude of the peak combined reversed load shall be at least 3% of the actual combined load in the opposite direction.
Reply
Question: Is it the intent of API 618 that this amount of load reversal be Reply 1: The API 618 Task Force is unable to respond to this question enough to ensure correct lubrication of the crosshead assembly? at this time. This information is currently under consideration by the task force and will appear in the next edition once specific guidance has been developed. Question 2: If the manufacturer's design requires a larger load reversal Reply 2: See Reply 1. to ensure proper lubrication, should this be considered a deviation to 2.4.4? 618 4th Ed. June 1995 2.5.1 Regarding Section 2.5.1: Does this Section require that a detailed lateral study of the compressor crankshaft be carried out, or is it sufficient that the study only include the drive system? This Section was intended to have a primary focus on the drive train of the compressor, since, in most cases, the lateral stiffness of the crankshaft is very high and the lateral frequencies are typically well above the operating speed range. Consequently, a detailed lateral study of the crankshaft would not normally be necessary, or expected. The report of such a study would not normally be necessary, or expected. The report of such a study should contain a statement indicating that a detailed lateral study of the crankshaft was not performed and the reasons. Any studies performed by the manufacturer or similar equipment should be cited as a means of substantiating the statement. If a lateral critical speed was expected to be below, within, or close to, the operating speed range, then a detailed laterals study of the crankshaft would be necessary.
API Standard 618 - Reciprocating Compressors for Petroleum, Chemical, and Gas Industry Services
Last Update: June 8, 2011
Standard 618
Section 2.5.2
Inquiry #
Question According to 2.5.2 of API Standard 618, "except for the belt driven units, the vendor shall provide a torsional analysis of the complete drive train. Torsional natural frequencies of the driver-compressor system (including couplings and any gear unit) shall be avoided within 10 percent of any operating shaft speed and within 5 percent of any other multiple of operating shaft speed in the rotating system up to and including the tenth multiple. For motor-driven compressors, torsional natural frequencies shall be separated from the first and second multiples of the electrical power frequency by the same separation margins." Is the required distance in % a + or - (Amplitude) or Peak to Peak declaration? Regarding Section 2.5.3: Does this Section require that a detailed lateral study of the compressor crankshaft be carried out, or is it sufficient that the separate study only include the quill shaft system? Referring to Section 2.6.2.6, when specified, the running bore of the cylinder shall be coated with tetrafluoroethylene (TFE). The method of application shall be agreed on by the user and the vendor. Please provide some references for process gas compressors using such coating, and the benefits and features of this coating.
Reply We do not understand the reference to amplitude or Peak to Peak. Torsional natural frequencies shall be avoided: in the range of 90% (100 - 10) of any operating shaft speed; and, in the range of 955 (100 5) of a multiple of operating shaft speed to 105% (100 + 5) of that multiple operating shaft speed. Please refer to API 684 for a detailed discussion on torsional analysis.
618
2.5.3
This Section only requires an analysis of the low-speed quill shafting and coupling.
618
2.6.2.6
There are two known methods of applying such a coating. One is to spray the liner with an aerosol containing tetrafluoroethylene, and the other is to burnish the liner with solid tetrafluoroethylene. Some purchasers believe that this coating shortens the break-in period of a non-lubricated compressor cylinder and reduces that initial wear on the piston rings and rider bands. It is for this reason that the process is a "when specified" requirement, with the method to be agreed upon by the user and the vendor. The oil temperature control valve in the lubricating oil cooling system, as illustrated in Figure G-5 is required by Section 2.12.5 to be steel. The temperature control valve in the jacket water cooling system, as illustrated in Figure G-1, Plan D, is required by Section 3.7.1.12.8 to be steel. Reply 1: This requirement refers to the minimum design pressure.
618
2.12
Are the thermostatic valve bodies in the cooling circuit required to be cast steel or is cast iron acceptable?
618
2.12.3.4
618-I-01/04
Question 1: Section 2.12.3.4 states: The rated pressure for the frame lubrication system shall be a gauge pressure of 10 bar (150 psi) minimum. Please clarify whether 10 bar is the recommended design pressure or the normal operating pressure. Question 2: What is the significance of specifying 10 bar when the normal operating pressure in lube oil systems of various compressor manufacturers is a maximum of 5 bar? Question 3: Does the bullet () in 2.12.3.2 apply only to the purchaser specifying the type of driver for the lube oil system?
Reply 3: Yes.
API Standard 618 - Reciprocating Compressors for Petroleum, Chemical, and Gas Industry Services
Last Update: June 8, 2011
Standard 618
Section 2.13.3.1
Inquiry #
Question Referring to Section 2.13.3.1 of API Standard 618, are the bonnets of heat exchangers in the cooling circuit required to be cast steel or is cast iron acceptable?
Reply For the heat exchangers in the lubricating oil cooling system, 2.13.3.1 requires the oil-pressure containing components to be steel. There are no specific materials requirements in API Standard 618 for the water pressure containing components. Where the purchaser does not specify specific materials requirements on the data sheet, then, in accordance with 2.14.1.1, the manufacturer's standard materials of construction are acceptable. Yes, Sections 2.14.3.5.1 through 2.14.3.5.4 pertain to testing for all castings.
618
2.14.3.5
618-I-01/07
Are production tests on castings as described in 2.14.3.5.1 through 2.14.3.5.4 applicable to all casting pieces for reciprocating compressors, or only for pressure-containing castings? Referring to Section 3.1.2.2 of API Standard 618, which of the following applies: (1) The specified motor reserve of 10 percent applies to the design phase and when measured during actual operation the reserve measured may be less than 10 percent in accordance with the tolerances for power (3 percent maximum, as per point 2.1.13 of API 618) and the measuring instruments (as per Acceptance and Performance test)., or (2) The motor reserve of 10 percent has to be available in the full amount at any time. Section 3.1.2.6 says, For induction-motor-compressor installations, motor current variations shall not exceed 40 percent of the full load current". Assuming, for instance, that the full load current of the motor is 100, should the current variations be between 60A and 140A or between 80A and 120A?
618
3.1.2.2
This Section allows for the selection of a driver of the appropriate rating during the design phase. The 110 percent applies at the design phase. Please also refer to the last Section of Appendix B.
618
3.1.2.6
618-I-01/02
The method for determining the actual limits of current variation is described in the NEMA Standard MG 1 Section 20.82 which requires that the "maximum value" of the stator current be measured by oscillograph or similar instrument (not by ammeter) and is assumed as 1.41 times the rated full-load current. The maximum current variation is limited to 40 percent of this "maximum value". Consequently the minimum value of the current variation (measured by oscillograph or similar instrument) is the "maximum value" minus 40 percent. Section 3.7.1.12.21 is correct. Table 5 will be corrected in the next edition of API 618.
618
4th Ed. - 3.7.1.12.21 June 1995 4th Ed. June 1995 3.9
618-I-01/02
Compressor tubing is mandated to be seamless stainless steel in Section 3.7.1.12.21 but Table 5 allows either stainless or carbon steel. Which one is correct?
618
618-I-02/01
618
3.9.1
618-I-02/05
A method for calculation of peak to peak pulsation levels in the Section 3.9 of API 618 discusses pulsation dampers. There are two pulsation bottles is not addressed by API 618 4th Edition. equations to calculate the suction and discharge bottle volumes. Equation 7 is given to calculate the peak-to-peak pulsation level in a line. I want to calculate the peak-to-peak value of the bottle themselves. What equation is available? Yes. Section 3.9.1, refers to selected piping configurations as being a possible pulsation suppression device. If a pulsation suppression device is remotely mounted from the compressor flange and requires additional interconnecting piping, is this interconnecting piping included in the pressure drop calculation?
API Standard 618 - Reciprocating Compressors for Petroleum, Chemical, and Gas Industry Services
Last Update: June 8, 2011
Standard 618
Section 3.9.2
Inquiry #
Question Referring to section 3.9.2.2.2 of API Standard 618, for Design Approach 1 and for initial commercial sizing, pulsation suppression devices shall have minimum suction surge volume and minimum discharge surge volume (not taking into account liquid collection chambers), as determined from Equation 2 and 3. In SI units, VS = 8.1 PD(KTs/M)1/4 and Vs is greater than or equal to Vd. And in customary units, Vs is greater than or equal to 0.028 cubic meter, Vs = 7 PD (KTs/M)1/4, and Vs is greater than or equal to one cubic foot. Where VS = minimum required suction surge volume, in cubic meters (cubic feet); K = isenotropic compression exponent at average operating pressure and temperature; TS = absolute suction temperature, in Kelvin (degrees Rankine); M = molecular weight; and PD = total net displaced volume per revolution of all compressor cylinders to be manifolded in the surge volume, in cubic meters per revolution (cubic feet per revolution). Is PD the sum of the volumes of the head end plus the crank end side of the cylinders or is it simply the piston area multiplied by the stroke (swept volume as used in API 11P)?
Reply PD is the net displace volume at each end of each cylinder manifolded to the surge volume. The net displaced volume allows for the volume occupied by the rod in the crank end. This committee cannot comment on the content of API 11P.
618
3.9.2
I require clarification on the use of the equations listed under Section 3.9.2.2 of API 618, dealing with the design of pulsation and vibration control requirements (4th Edition, June 1995). Sections 3.9.2.2.3 through 3.9.2.7 provide formulae to predict peak-to-peak pulsation levels that are acceptable. However, these peak-to-peak values do not appear anywhere in other equations covering the sizing of the pulsation suppression devices. Hence, there appears to be no influence of peak levels on device sizing, which seem counter-intuitive. The same can be said for Appendices N and O. Can you please provide clarifications on this observation? Thank you. 618-I-01/01 In equation 3.9.2.2.2 of API 618, does PD for a double-acting cylinder two times the swept volume? For example, if the cylinder is 9.5" in diameter with a 5" stroke is PD 0.205 ft3 or 0.410 ft3?
The equations you cite do not predict pulsation levels. They provide limitations on pulsation levels. The actual pulsation levels for a given system are determined by an acoustical analysis per 3.9.3.6, or in the case of a design approach one, the pulsation suppression devices are sized by the vendor using 3.9.2.2.2 which experience has shown to give reasonable results within its applicable limits. Pulsation suppression devices are sized and configured to result in pulsation levels below prescribed limits. The characteristics of the devices are used in the computer model which predicts pulsation levels.
618
3.9.2.2.2
PD in this equation is defined as the total net displaced volume per revolution of all compressor cylinders to be manifold in the surge volume. In the case cited in the inquiry, if the double acting cylinder is the only cylinder manifold to the Pulsation Suppression Device in question, PD would include the displacement volume from both sides of the piston.
API Standard 618 - Reciprocating Compressors for Petroleum, Chemical, and Gas Industry Services
Last Update: June 8, 2011
Standard 618
Section 3.9.2.2.2
Inquiry # 618-I-01/01
Question
Reply
What pulsation level in % peak-to-peak is to be expected using 3.9.2.2.2 It is assumed that by suction tank and discharge tank you mean the pulsation suppression vessels (bottles). API 618 does not address for the suction tank? What about the discharge tank? peak-to-peak pulsation inside pressure pulsation devices. The maximum allowable peak to peak pulsation levels at the cylinder flange resulting from the utilization of the equations in Section 3.9.2.2 would be 7% of average absolute line pressure or that percentage determined by Equation (4) in Section 3.9.2.2.3 whichever is lower. The maximum allowable line side peak to peak pulsation levels would be limited to the values determined by Equation (7), Section 3.9.2.5. These equations should be valid for both suction and discharge Pulsation Suppression Devices.
618
3.9.2.2.4
618-I-02/05
618
3.9.3.13
Section 3.9.2.2.4 states the maximum allowable pressure drop across a pulsation suppression device. For multiple pulsation suppression devices, no recommended limit is stated in excess of that defined by Equation 5, can be designed while still conforming to allowable levels for each suppression device. Is there a recommended total pressure drop limit that can be applied for a suction or discharge system for a single stage? Are studded pad-type inspection openings as allowed in Section 3.9.13 considered flanged branch connections when determining the reinforcement required?
Multiple pulsation suppression devices in series are not covered by the standard. API can only provide interpretations of the requirements that appear in the standard.
No.
API Standard 618 - Reciprocating Compressors for Petroleum, Chemical, and Gas Industry Services
Last Update: June 8, 2011
Standard 618
Section 3.9.3.5
Inquiry # 618-01/05
Question Background: We have new pulsation bottles that are being fabricated and stamped as ASME pressure vessels. The compressors fall within the scope of the API 618, so I am trying to make sure the bottles comply with the additional requirements in API 618 with regard to the flanged branch connections (nozzles) in 3.9.3.5. Question 1: For sake of discussion, we have a shell with a nominal thickness of 2.000 in. We are attaching a 6 in. nozzle to the shell made Reply 1: Yes of 6 in. pipe (OD = 6.625 in.). The nozzle will be an insert type (it is inserted into the shell wall versus an abutting type). From the above requirement, it appears that the cut-away area for nozzle reinforcement would be calculated as 2 in. nominal shell thickness times 6.625 in. cutout diameter (for the 6 in. nozzle), resulting in a cut-away area of 13.25 in2. Normally, the A-required in the ASME Code is calculated using the tr of the shell (or head). Thus, the above requirement appears to require 100% area replacement of the nominal shell (head) thickness no matter what tr calculates out to be. Do you agree with my interpretation of this? Question 2: Does the term connection wall in 3.9.3.5 mean just the nozzle neck, or does it also include the shell wall. In other words, does this mean that the A-required (cut-away area) as calculated above must be completely replaced by added reinforcement material (repad and welds), and that you can not take reinforcement credit for excess thickness in the nozzle neck (connection wall) and possibly no credit for excess shell thickness? Referring to Section 3.9.2.7 of API 618, when calculating the maximum allowable peak-to-peak level of individual pulsation components (P1%) according to Equation 8 for pressure less than 3.5 bar, is the actual value of the component allowed calculated as a percentage of 3.5 bar, or as a percentage of the actual absolute line pressure?
Reply
Reply 2: Yes.
618
3.9.3.5
The maximum allowable peak-to-peak level of individual pulsation component is calculated as a percentage of 3.5 bar. For low pressure applications, the concern is the forces generated by the pulsations, not the actual level of the pulsation. At very low pressures the forces become small even for large pulsations. It is intended that the application of the rules be simplified at low pressures by flattening out the allowable level pulsation at pressures below 3.5 bar.
618
3.9.3.5
Referring to Section 3.9.3.5 of API 618, which "connection wall" is being The "connection wall" being referred to is the flanged connection wall, referred to: both flanged connection wall and the shell/head wall, or jut not the shell or head wall. the flanged connection wall?
API Standard 618 - Reciprocating Compressors for Petroleum, Chemical, and Gas Industry Services
Last Update: June 8, 2011
Standard 618
Section 3.9.3.5
Inquiry #
Question What method of design calculations of the connections are used to satisfy both ASME Section VIII, Division 1, and API 618?
Reply This Section of API 618 requires a reinforcing pad of an area equal to the area of metal cutaway from the shell. Extra area in the branch connection wall, such as through the use of heavy wall nozzles, is not to be counted. Detailed reinforcement calculations in accordance with ASME Section VIII, Division 1 or 2, except as modified by API 618, satisfy the requirements. Pulsation suppression devices operate in a pulsating, vibration-rich environment. Deflection in the shell or head wall from external loads is a concern. The API 618 modification is intended to add stiffness to the vessel at branch connections which may transmit external loads. The capacity of the compressor purchased to API Standard 618 is based on the inlet mass flow.
618
4.1.9
According to Section 1.4.9 and Appendix B of API Standard 618, "the inlet volume is the flow rate determined at the conditions of pressure, temperature, compressibility, and gas compression - including moisture - at the compressor inlet flange. To determine the inlet volume flow, allowance must be made for pressure drop across pulsation suppression devices and for interstage liquid knockout." Does the capacity of a compressor purchased to API 618 relate to the mass flow at the inlet of the compressor? This is larger than, and in conflict with, ISO 1217 Section 3.4.1 and ISO 8012 Section 5.4.1, which relate to the volume flow delivered to the discharge. 618-I-01/03 I have a question regarding Appendix N & O of API 618. In both these sections equations are given to solve pulsation problems in piping systems. In both sections an input of the equation is compressor speed in rpm. I believe this should not be rpm, but should be compression strokes per minute. Rpm would work for a 1 cylinder machine, but what about more than 1 pulses per/revolution.
618
The guidelines in Appendix N include compensation for multiple cylinders along with the rpm. Refer to the equation in Section N 2.3. The guidelines in Appendix O are based on a single cylinder per acoustic filter. Sizing of acoustic filters applicable to multiple cylinders is not addressed. Refer to the equation in Section O 2.1.
For instance a three cylinder machine should use 3X rpm, not rpm as is With respect to the three throw example that you mentioned, a three throw machine may not have a third order component, depending on stated. the compressor arrangement. Can you please clarify this for me? 618 5th 618 8.3.2.2 618-2010-1 Heat Exchangers like Intercooler, Aftercooler and Oilcooler Does this means that we have to prepare a helium gas leak test at maximum allowable working pressure for heat exchangers, too? In the item 6.2.1 it is stated that for fasteners of diameter equal to or greater than 24 mm shall be of the constant 3 mm pitch series. Are the piston rods thread affected? Or should be not considered as fasteners? No.
The requirements listed in 6.2.1 do not apply to the piston rod threads
5th
6.2.1
618-2011-1