PowerLogic ION7550 / ION7650


Energy and power quality meter
Installation Guide

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

Danger
This symbol indicates the presence of dangerous voltage within and outside the product enclosure that may constitute a risk of electric shock, serious injury or death to persons if proper precautions are not followed.

Caution
This symbol alerts the user to the presence of hazards that may cause minor or moderate injury to persons, damage to property or damage to the device itself, if proper precautions are not followed.

Note
This symbol directs the users attention to important installation, operating and maintenance instructions.

Installation Considerations
Installation and maintenance of the PowerLogic ION7550 / ION7650 meter should only be performed by qualified, competent personnel that have appropriate training and experience with high voltage and current devices. The meter must be installed in accordance with all local and national electrical codes.

DANGER
Failure to observe the following instructions will result in severe injury or death. During normal operation of the ION7550 / ION7650 meter, hazardous voltages are present on its ter-

minal strips, and throughout the connected potential transformer (PT), current transformer (CT), digital (status) input, control power and external I/O circuits. PT and CT secondary circuits are capable of generating lethal voltages and currents with their primary circuit energized. Follow standard safety precautions while performing any installation or service work (i.e. removing PT fuses, shorting CT secondaries, etc.). The terminal strips on the meter base should not be user-accessible after installation. The ION7550 / ION7650 meter is designed to be used as a permanently installed device. All electrical connections to the meter must be installed with a permanent connection method (screw-type mechanical connection). The ION7550 / ION7650 meter chassis ground must be permanently connected to the switchgear earth ground. Do not use digital output devices for primary protection functions. These include applications where the devices perform energy limiting functions or provide protection of people from injury. Do not use the ION7550 / ION7650 in situations where failure of the devices can cause injury or death, or cause sufficient energy to be released that can start a fire. The meter can be used for secondary protection functions. Do not HIPOT/Dielectric test the digital (status) inputs, digital outputs, or communications terminals. Refer to the label on the ION7550 / ION7650 meter for the maximum voltage level the device can withstand.

CAUTION
Observe the following instructions, or permanent damage to the meter may occur. The ION7550 / ION7650 meter offers a range of hardware options that affect input ratings. The

ION7550 / ION7650 meters serial number label lists all equipped options. Applying current levels incompatible with the current inputs will permanently damage the meter. This document provides installation instructions applicable to each hardware option. The ION7550 / ION7650 meters chassis ground must be permanently connected to the switchgear earth ground for the noise and surge protection circuitry to function correctly. Failure to do so will void the warranty. Terminal screw torque: Barrier-type (current, voltage, and relay terminal screws: 1.35 Nm (1.00 ft-lbf) max. Captured-wire type (digital inputs/outputs, communications, power supply: 0.90 Nm (0.66 ft.lbf) max.

2008 Schneider Electric. All rights reserved.

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

FCC Notice
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. The Ringer Equivalence Number (REN) for the ION7550 / ION7650 optional internal modem is 0.6. Connection to the ION7550 / ION7650 internal modem should be made via an FCC Part 68 compliant telephone cord (not supplied). The ION7550 / ION7650 cannot be used on a public coin phone service or party line services.

Network Compatibility Notice for the Internal Modem


The internal modem in meters equipped with this option is compatible with the telephone systems of most countries in the world. Use in some countries may require modification of the internal modems initialization strings. If problems using the modem on your phone system occur, please contact Schneider Electric Technical Support.

Standards Compliance

CSA: Certified to CAN/ Certified to CSA C22.2 No.1010-1 UL 3111


Made by Power Measurement Ltd. PowerLogic, ION, ION Enterprise, MeterM@il, WebMeter and Modbus are either trademarks or registered trademarks of Schneider Electric. Covered by one or more of the following patents: U.S. Patent No's 7010438, 7006934, 6990395, 6988182, 6988025, 6983211, 6961641, 6957158, 6944555, 6871150, 6853978, 6825776, 6813571, 6798191, 6798190, 6792364, 6792337, 6751562, 6745138, 6737855, 6694270, 6687627, 6671654, 6671635, 6615147, 6611922, 6611773, 6563697, 6493644, 6397155, 6236949, 6186842, 6185508, 6000034, 5995911, 5828576, 5736847, 5650936, D505087, D459259, D458863, D443541, D439535, D435471, D432934, D429655, D427533.

2008 Schneider Electric. All rights reserved.

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

PowerLogic ION7550 / ION7650 Models


Integrated Display Model
Comes with front optical port.

TRAN (transducer) Model


The TRAN model has no display.

Available Options
Option
Form Factor

Current Inputs
Standard

COM
Standard (RS-232,

I/O
Standard (8 digital

Security
Standard1 RMANSI2

ION7550

Integ. Display TRAN 5 MB memory 10 MB memory Up to 256 sampling rate

(5 Amp)

RS-485, optical)

1 Amp

Power Supply
Standard Low Voltage

Ethernet RJ45 Ethernet Fiber Modem

DC

inputs, 3 Form C relays, 4 Form A outputs) Extra 8 digital inputs Four 0-1mA analog inputs Four 0-20 mA analog inputs Four -1 to 1mA analog outputs Four 0-20 mA analog outputs

Model

Form Factor

Current Inputs

COM
Same as

I/O
Same as ION7550

Security
Same as

ION7650

Integ. Display Same as ION7550 TRAN 5 MB memory Power Supply 10 MB memory Same as Up to 512 ION7550 sampling rate (standard) 1024 sampling rate (optional) EN50160 compliance IEC61000-4-30 Class A compliance

ION7550

ION7550

Notes
1 2

Standard = password protected, no locking or sealing. RMANSI = ANSI C12.16 approved revenue meter; meets ANSI C12.20 class 0.2 accuracy standards.

2008 Schneider Electric. All rights reserved.

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

Before You Begin


Before installing the meter, familiarize yourself with the steps in this guide and read the safety precautions presented on the Installation Considerations page.

DANGER
Do not power up the meter until the current and voltage wiring is completed.

Recommended Tools

Phillips screwdriver Precision flat-head screwdriver Wire cutters / stripper

Meter Overview
Meter Front Meter Back
Voltage and Current Inputs

Digital Inputs

Analog Inputs

Analog Outputs

Softkeys
ESC

Button

I/O Expansion Card

Optical Port

Power Supply

Communications Card

Ground Terminal

Operational LEDs

Navigation Buttons

PROG/SELECT

Button

Form C Digital Outputs

Digital Inputs

Form A Digital Outputs

Front Panel Button Functions


PROG

PROG/SELECT: Press the PROG/SELECT (program or select) button to enter Setup mode. In Setup mode, press the PROG/SELECT button to accept changes. ESC:

ESC

Press the ESC (Escape) button to return to a higher menu or discontinue a configuration change.

NAVIGATION:

Press the UP / DOWN arrow buttons to highlight menu items, or increment / decrement numbers. Press the LEFT or RIGHT arrow buttons to move to an adjacent digit.

SOFTKEY: Press a SOFTKEY button to select the parameter that you want to configure from the sub-menus.

2008 Schneider Electric. All rights reserved.

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

Unit Dimensions
Basic Model Rear View

Basic Model Front View

Basic Model Side View

2008 Schneider Electric. All rights reserved.

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

Step 1: Mount the Meter


Environmental Specifications
Mounting Location Operating Range Display Operating Range Storage Range Relative Humidity Range Indoor use -20 to +70C (-4 to +158F) Standard Power Supply -20 to +50C (-4 to +122F) Low Voltage DC Power Supply No formation of ice -20 to +70C (-4 to +158F) -40 to +85C (-40 to +185F) 5 to 95% non-condensing

Meter Battery Considerations


The meters battery life expectancy depends on both temperature and the amount of time the meter is without power. For typical installations, the battery should last 20 years or more. If the meter is not powered, the battery will last a minimum of 7 years at room temperature.

Integrated Display Model


1. 2. Fit the meter into the DIN standard 192 cutout (186 mm by 186 mm). Slide the four brackets into their slots on the back of the meter and secure using the four Phillips head screws. Do not overtighten.
Screw

DIN 192 Cutout

Bracket

Step 2: Wire the Ground Terminal


Connect the terminal to a good earth ground with a 2.1 mm2 (14 AWG) wire. Ensure that the terminal nut is tightened down securely onto the ground wire. Do not use metal door hinges as a grounding point.

2008 Schneider Electric. All rights reserved.

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

Step 3: Wire the Digital I/O and Analog I/O


Form C Digital Outputs: Mechanical Relays R1 - R3
Internal Form C Mechanical Relay

R11 R12

R13

R11 R12 R13 R21

Type Contacts Wire Connector Voltage Rating Rated Load @ Rated Voltage Max. Voltage MOV Protection Max. Load @ Max. Voltage Turn-On Time Isolation Turn-Off Time Lifetime Update time

Form C (R1, R2, R3) K (common), Y (NO), Z (NC) Use wiring that is appropriate for the application Ring or split ring connector 250 VAC / 30 VDC Resistive: 10 A (AC/DC) Inductive (PF=0.4): 7.5 A (AC) / 5 A (DC) 380 VAC / 125 VDC between K and NO/NC 300 V max. between NO and NC 3 A (AC) / 0.2 A (DC) 15 ms max. 5,000 VAC for 60 s 5 ms max. No load = 10,000,000 operations Rated voltage and load = 100,000 operations cycle or 1 s NO K NC
Mechanical relays should always be protected by external fuses

Meter

Alarm Lamp

Load

External Supply

Form A Digital Outputs: Solid State Relays D1 - D4


Type
Internal Form A Solid State Relay

Form A (D1, D2, D3, D4) 1.3 to 0.1 mm2 (16 to 28 AWG) Continuous or pulse 30 VDC 80 mA per channel Optically isolated; max. 5,000 V RMS isolation (UL-E91231) cycle or 1 s Meter

Wire Signal Type Max. Load Voltage Max. Load Current Isolation

D1
D3 - +

DIGITAL OUTPUTS

D3

D2

D1

+
1.8 Wh

External Supply 30VDC max D4 output is factory-configured to pulse once every 1.8 Wh for Class 20 meters, or once every 0.18 Wh for Class 2 meters (for calibration testing purposes).
2008 Schneider Electric. All rights reserved. 9

External Relays

D4 - +

D2 - +

+
D1 - +

Scan Time

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

Digital Inputs: S1 - S8
DIGITAL INPUTS
S C O M S S 8 7 S 6 S S 5 4 S 3 S 2 S 1

Type Application Wire Min. Pulse Width Max. Pulse Rate Timing Resolution Updated Isolation to Ground Max. External Voltage

Self-excited (internal 30 VDC supply) Dry contact sensing, or with external excitation 1.3 to 0.1 mm2 (16 to 28 AWG) 1 ms 20 pulses per second 1 ms cycle (after timing resolution) max. 200 VDC for 10s 130 VDC continuous External Excitation Meter
_
S7

Internal Excitation Meter


_
S7

_
+
S8

_
+
S8

30 VDC +
SCOM

Opticallycoupled switch

30 VDC + +

SCOM

Opticallycoupled switch

External Supply

130 VDC max

Digital Inputs (Meter Ordering Option): DI1 - DI8


Type Application Wire Min. Pulse Width Max. Pulse Rate Timing Resolution Updated Isolation to Ground Max. External Voltage Self excited (internal 30 VDC supply) Dry contact sensing, or with external excitation 1.3 to 0.1 mm2 (16 to 28 AWG) 20 ms 25 pulses per second 2 ms cycle (after timing resolution) 750 VDC 50 VDC continuous External Excitation Meter

Internal Excitation Meter

Opticallycoupled switch

Opticallycoupled switch

External Supply

50 VDC max

10

2008 Schneider Electric. All rights reserved.

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

Analog Inputs (Meter Ordering Option): AI1 to AI4


Type Wire
+ -

Captured wire connector 1.3 to 0.1 mm2 (16 to 28 AWG) DC current 0 to 20 mA (scalable 4-20 mA) or 0 to 1 mA 24 (0-20 mA option) or 475 (0-1 mA option) +/ 0.3% of full scale 1s 750 V max 400 k (channel/channel) Meter
+ AI1

AI3

Signal Type Available Options Input Impedance Accuracy Update Rate Isolation to Ground Isolation Impedance

AI4

AI3

AI2 AI1

Thermocoupler

mV

mA

Voltage-toCurrent Transducer

Example application: temperature sensing

NOTE
Do not connect the analog inputs of the I/O card to the analog outputs on the same I/O card.

Analog Outputs (Meter Ordering Option): AO1 to AO4


Type Wire
OUT COM

Captured wire connector 1.3 to 0.1 mm2 (16 to 28 AWG) DC current 0 to 20 mA (scalable 4-20 mA) or -1 to 1 mA (scalable 0-1 mA) 500 (0-20 mA option) or 10 k (-1 to 1 mA option) +/ 0.30% of full scale cycle or 1 s min. 1 cycle for measurement + cycle for ION + 1 s delay for hardware 750 V Meter

AO3

Signal Type Available Options Driving Capability

AO4 A03 A02 AO1

Accuracy Update Rate Latency Isolation to Ground

Analog Meter

OUT

AO1
COM

Example application: driving an analog meter with the DC current output

NOTE
Do not connect the analog outputs of the I/O card to the analog inputs on the same I/O card.

2008 Schneider Electric. All rights reserved.

11

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

Step 4: Wire the Voltage and Current Inputs


V1 V2 V3 V4 Vref I11 I12 I21 I22 I31 I32 I41 I42
3~ CURRENT INPUTS

I51 I52

3~ VOLTAGE INPUTS

Voltage Inputs
Connector Type Wire Gauge Rated Inputs Fault Capture Overload Dielectric Withstand Input Impedance Ring or split ring connector 3.3 to 2.1 mm2 (12 to 14 AWG) 347 V L-N RMS /600 V L-L RMS 1200 V L-N peak 1500 VAC RMS continuous 2500 VAC RMS at 60 Hz for 60 s 5 M/phase (phase - Vref)

Current Inputs: Class 20 Current Inputs (5A Option)


Connector Type Wire Gauge Input Rating Starting Current Fault Capture Max. Voltage Overload Dielectric Withstand Burden Impedance Ring or split ring connector 5.3 to 3.3 mm2 (10 to 12 AWG): Use 8.4 mm2 (8 AWG) for 10-20 A applications 5 A, 10 A, and/or 20 A RMS 0.005 A RMS 70 A peak 600 V RMS (CAT III IEC61010-1) 500 A RMS for 1 s, non-recurring 2500 VAC RMS at 60 Hz for 60 s 0.05 VA per phase (at 5 A) 0.002 per phase

Current Inputs: Class 2 Current Inputs (1A Option)


Connector Type Wire Gauge Input Rating Starting Current Fault Capture Max. Voltage Overload Dielectric Withstand Burden Impedance Ring or split ring connector 5.3 to 3.3 mm2 (10 to 12 AWG) 1 A, 2 A, 5 A, and/or 10 A RMS 0.001 A RMS 17.5 A peak 600 V RMS (CAT III IEC61010-1) 50 A RMS for 1s, non-recurring 2500 VAC RMS at 60 Hz for 60 s 0.015 VA per phase (at 1 A) 0.015 per phase

NOTE
The appropriate Volts Mode setting is included with each wiring diagram. Refer to Step 8 to learn how to configure Volts Mode on the meter.

12

2008 Schneider Electric. All rights reserved.

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

4-Wire Wye, 3-Element, Direct Connection Diagram


Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source

4-Wire Wye, 3-Element, 3 PTs Connection Diagram


Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source

4-Wire Wye, 2-Element, 2 PTs Connection


Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source

2008 Schneider Electric. All rights reserved.

LINE
347 V L-N / 600 V L-L max. VOLTS MODE = 4W-Wye

I4 Optional

LOAD LOAD

LINE LINE

I4 Optional

Use PTs for voltages over 347 V L-N / 600 V L-L. Wye (Star) wiring for PT primaries and secondaries. VOLTS MODE = 4W-Wye

I4 Optional

Phase B voltage (V2) displayed by meter is derived from phase A and phase C, not measured. V2 will display a value even if no voltage is present on Phase B. V2 values are only accurate for balanced loads. VOLTS MODE = 3W-Wye

LOAD

13

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

3-Wire Solid-Grounded Wye, 3-Element, Direct Connection


LOAD LINE
A B C

Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source

When the common or star point of a 3-wire Wye system is grounded, the meter may be connected directly without using PTs, provided that the phase voltages are within the meters range. VOLTS MODE = 4W-Wye

3-Wire Delta, 2-Element, Direct Connection


Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source

LOAD

3-Wire Delta, 2-Element 2 PTs & 2 CTs


A B C

LINE LINE

2A
Do not connect

3A

V1

V2 V3 V4 Vref I11 I12 I21 I22 I31 I32 I41 I42 I51 I52

L / + N/-

600 V L-L max. VOLTS MODE = Delta

Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source

LOAD

2A

3A

V1

V2 V3 V4 Vref I11 I12 I21 I22 I31 I32 I41 I42 I51 I52

L / + N/-

Use PTs for voltages over 600 V L-L. VOLTS MODE = Delta

14

2008 Schneider Electric. All rights reserved.

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

3-Wire Delta, 2-Element, 2 PTs & 3 CTs


A B C

Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source

LOAD

Single Phase Connection Diagram


Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source

Using Potential Transformers


System Mode Wye Voltage Range 120 V L-N or 208 V L-L 277 V L-N or 480 V L-L 347 V L-N or 600 V L-L over 347 V L-N or 600 V L-L 120 V L-N or 240 V L-L 277 V L-N or 554 V L-L over 277 V L-N or 554 V L-L up to 600 V L-L over 600 V L-L no no no yes no no yes no yes Requires PTs

Single Phase Delta

2008 Schneider Electric. All rights reserved.

LINE

2A

3A

V1

V2 V3 V4 Vref I11 I12 I21 I22 I31 I32 I41 I42 I51 I52

L / + N/-

Use PTs for voltages over 600 V L-L VOLTS MODE = Delta

LINE

I4 Optional

277 V L-N / 554 V L-L max. Use PTs for higher voltages. VOLTS MODE = Single

LOAD

15

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

Step 5: Wire the Communications


RS-232 Connections (COM1)
DB9 Null Modem Wiring Diagram

DTE (computer)

DTE (meter)

Null modem cable pinout Pin 3 - Transmit Data - Pin 2 Pin 2 - Receive Data - Pin 3 Pin 7 - Request to Send- Pin 8 Pin 8 - Clear to Send- Pin 7 Pin 5 - Signal Ground- Pin 5 Pin 6 - Data Set Ready- Pin 4 Pin 4 - Data Terminal Ready- Pin 6

Specification Connector Type Wire Maximum Cable Length Data Rate Isolation Duplex Compliance

Meter Connected to Computer

Meter Connected to External Modem

DB9 female end for mating with male connector on the meter Null modem RS-232 cable Straight-through RS-232 cable 15.2 m (50 ft) 300 115,200 bps Optical Full ANSI/IEEE C37.90.1-2002 surge withstand and fast transient tests

RS-485 Connections (COM1 and COM2)


SH + RS-485 Shield (electrically connected to chassis ground) RS-485 Data Minus RS-485 Data Plus Captured wire Shielded twisted pair RS-485 cable, 0.33 mm2 (22 AWG) or larger 1219 m (4000 ft) total for entire bus 300 115,200 bps 32 Optical Half ANSI/IEEE C37.90.1-2002 surge withstand and fast transient tests

Connector Type Wire Maximum Cable Length Data Rate Maximum Devices (per bus) Isolation Duplex
Connect SH at one end only

Compliance

Infrared Connections (COM4)


Interface Location Data Rate Duplex ANSI C12.18 Type II optical port Front of meter 1,200 19,200 bps Half

16

2008 Schneider Electric. All rights reserved.

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

Ethernet Connections (if equipped)


10BASE-T / 100BASE-TX
Pin 1: Transmit Data + Pin 2: Transmit Data Pin 3: Receive Data + Pin 6: Receive Data -

Wire Type Connector Type Maximum Length

High quality Category 5 or 6 unshielded twisted pair cable RJ45 modular 100 m (328 ft) IEEE 802.3 10/100BASE-T for 10/100 Mbps base band CSMA/CD Type LANs Data Rate 10/100 Mbps Isolation Transformer isolated to 1500 V RMS Max. Connections Allowed 4 simultaneous (32 via Modbus TCP/IP)

100BASE-FX (Fiber)
62.5/125 or 50/125 micrometer multimode fiber optic cable Connector Type SC 2000 m (6562 ft) full duplex Maximum Length 400 m (1312 ft) half duplex Data Rate 100 Mbps Isolation Optical Wire Type

SC type fiber cable

Ethernet TCP/IP Service Ports


Protocol ION Modbus RTU Modbus TCP EtherGate (COM1) EtherGate (COM2) DNP TCP SMTP Port 7700 7701 502 7801 7802 20,000 25 (configurable)

Only one EtherGate connection per port is allowed at a time

Internal Modem Connection (COM3 if equipped)


Pin 3: Ring Pin 4: Tip

Connector Type Wire Type Data Rate Error Correction Data Compression

RJ11 FCC Part 68 compliant telephone cord (two male RJ11 ends) 300 bps 56 kbps V.42 LAPM, MNP 2-4, V.44 V.42 bis/MNP 5

2008 Schneider Electric. All rights reserved.

17

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

Step 6: Wire the Power Supply


Specification Type Standard Power Supply Captured wire connector 3.3-2.1 mm2 (12-14 AWG) 2.1-0.8 mm2 (14-18 AWG) Low Voltage DC

G L+ N_

Wire Rated Inputs

85-240 VAC 10%(47-63 Hz), 20-60 VDC 10% or 110-300 VDC 10% Dielectric Withstand 2500 VAC RMS at 60 Hz for 60s Burden 35 VA max. (15 VA typical) 18 W max. (12 W typical) Ride-through 100 ms (6 cycles at 60 Hz) min. None

Step 7: Power Up the Meter


1. 2. 3. Ensure the ground wire is securely connected on both ends. Ensure the meters power supply voltage is within the allowed range. Power up the meter.

Step 8: Set Up the Meter Using the Front Panel


The following Setup screens are available for meter configuration via the front panel:
BASIC SETUP COM1 SETUP COM2 SETUP COM3 SETUP COM4 SETUP NETWORK SETUP PQ SETUP FORMAT SETUP DISPLAY SETUP TIME SETUP SECURITY SETUP METER RESETS

Use the PROG/SELECT, ESC, softkeys and arrow buttons to configure settings. The following example shows Volts Mode setup using the meter front panel.

Press Press Press

Press Press

Press PROG/SELECT to enter Setup Mode from Display Mode.

Press

Use arrow buttons to move up and down in list. Press PROG/SELECT to select Basic Setup.

Use arrow buttons to move up and down in list. Press PROG/SELECT to select PT/CT Setup.

Press Mode softkey. Use arrow buttons to move up and down in list. Press PROG/SELECT to select Delta.

18

2008 Schneider Electric. All rights reserved.

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

Password
A password is required for all front panel configuration changes and to enter the Security Setup menu. The password is set to 0 (zero) in the factory. The front panel only prompts you for the meter password once, before you make your first configuration change. You can disable the password via the Security Setup menu.

Selecting the Front Panel Language


Meters are shipped with English as the default front panel language. To select another language: 1. 2. Press PROG/SELECT and the right arrow buttons, hold for two seconds then release. Scroll through the language list and select the language you want.

3.

Press PROG/SELECT to confirm.

You can also access this setting via the Display Setup menu.

NOTE
The meter only communicates to software in English.

2008 Schneider Electric. All rights reserved.

19

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

Front Panel Setup Menu Settings


The following table lists all settings that can be configured via the front panel. Menu Setting
VOLTS MODE PT PRIMARY PT SECONDARY CT PRIMARY CT SECONDARY V4 PRIMARY V4 SECONDARY I4 PRIMARY I4 SECONDARY I5 PRIMARY

Description

Range (Values)

Default
4W-WYE 120.00 120.00 5.00 5.00 120.00 120.00 5.00 5.00 5.00 5.00 120.00 120.00 Normal Normal Normal Normal Normal Normal Normal Normal Normal

The power systems configuration 4W-WYE, DELTA, 3W-WYE, WYE, DELTA, etc. SINGLE, DEMO The Potential Transformers primary 1 to 999,999.99 winding voltage rating The Potential Transformers secondary winding voltage rating The Current Transformers primary winding current rating The Current Transformers secondary winding current rating 1 to 999,999.99 1 to 999,999.99 1 to 999,999.99

The Potential Transformers primary 1 to 999,999.99 winding voltage rating on V4 The Potential Transformers secondary winding voltage rating on V4 The Current Transformers primary winding current rating on I4 The Current Transformers secondary winding current rating on I4 The Current Transformers primary winding current rating on I5 The Current Transformers secondary winding current rating on I5 1 to 999,999.99 1 to 999,999.99 1 to 999,999.99 1 to 999,999.99 1 to 999,999.99

BASIC SETUP

I5 SECONDARY V NOMINAL V4 NOMINAL Va POLARITY Vb POLARITY Vc POLARITY V4 POLARITY Ia POLARITY Ib POLARITY Ic POLARITY I4 POLARITY I5 POLARITY

The V1, V2 and V3 nominal voltage 1.000 to 999,999.000 used for harmonics calculations The V4 nominal voltage used for harmonics calculations The polarity of the Potential Transformer on Va The polarity of the Potential Transformer on Vb The polarity of the Potential Transformer on Vc The polarity of the Potential Transformer on V4 The polarity of the Current Transformer on Ia The polarity of the Current Transformer on Ib The polarity of the Current Transformer on Ic The polarity of the Current Transformer on I4 The polarity of the Current Transformer on I5 1.000 to 999,999.000 Normal or Inverted Normal or Inverted Normal or Inverted Normal or Inverted Normal or Inverted Normal or Inverted Normal or Inverted Normal or Inverted Normal or Inverted

CURRENT PROBE The type of current probes being TYPE used with the meter

Factory Default, User Defined 1, Factory or User Defined 2 Default

20

2008 Schneider Electric. All rights reserved.

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

Menu

Setting
PROTOCOL

Description
The communications protocol

Range (Values)

Default

ION, Modbus RTU, Modbus Master, DNP V3.00, ION GPS:Truetime/Datum,GPS: Arbiter, GPS:Arbiter-Vorne, Factory, Ethergate, ModemGate 3001, 1200, 2400, 4800, 9600, 19,200 19200, 38400, 57600, 115200 0 to 1 0.010 From serial number2 RS232 RTS + DELAY OFF ION 19,200 0.010 101

COM1 SETUP

BAUD RATE TRAN DELAY UNIT ID SERIAL PORT MODE

The data rate, in bits per second The transmit delay in seconds

Every meter on an RS-485 network 1 to 9999 must have a unique Unit ID number Parity and stop bits for the port Hardware mode for the port RS232 or RS485 RTS + DELAY or RTS/CTS ON or OFF See COM1 protocol 19200, 38400, 57600, 115200 0 to 1 3001, 1200, 2400, 4800, 9600,

8N1, 8N2, 8E1, 8E2, 8O1, 8O2 8N1

Specifies the handshake mode FLOW CONTROL when COM1 is set to RS232 RS485 BIAS PROTOCOL Turns on biasing when Mastering on the RS-485 bus The communications protocol The data rate, in bits per second The transmit delay in seconds

COM2 SETUP

BAUD RATE TRAN DELAY UNIT ID SERIAL PORT RS485 BIAS

Every meter on an RS-485 network 1 to 9999 must have a unique Unit ID number Parity and stop bits for the port Turns on biasing when Mastering on the RS-485 bus

8N1, 8N2, 8E1, 8E2, 8O1, 8O2 8N1 ON or OFF ION, Modbus RTU, Modbus Master, DNP V3.00, GPS:Truetime/Datum,GPS: Arbiter, GPS:Arbiter-Vorne, Factory OFF

PROTOCOL

The communications protocol

ION

COM3 SETUP

BAUD RATE TRAN DELAY UNIT ID ANSWER HR RINGS NON-ANSWER HR RINGS PROTOCOL

The data rate, in bits per second The transmit delay in seconds

3001, 1200, 2400, 4800, 9600, 19,200 19200, 38400, 57600, 115200 0 to 1 0.010 102 1 5 ION 9600 0.010 103

Every meter on an RS-485 network 1 to 9999 must have a unique Unit ID number The number of rings during defined 0 to 255 answer hours The number of rings during defined 0 to 255 non-answer hours The communications protocol The data rate, in bits per second The transmit delay in seconds ION, Modbus RTU, DNP V3.00, Factory 1200, 2400, 4800, 9600, 19200 0 to 1

COM4 SETUP

BAUD RATE TRAN DELAY UNIT ID SERIAL PORT

Every meter on an RS-485 network 1 to 9999 must have a unique Unit ID number Parity and stop bits for the port

8N1, 8N2, 8E1, 8E2, 8O1, 8O2 8N1

2008 Schneider Electric. All rights reserved.

21

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

Menu

Setting
IP ADDRESS SUBNET MASK GATEWAY DNS PRIMARY DNS SECONDARY 10/100BT CONFIG

Description
Sets the IP address for the meter Used if subnetting applies to your network Used in multiple network configurations Sets the address for the primary DNS Server that is configured to resolve domain names Sets the address for the secondary DNS Server that is configured to resolve domain names Sets the BASE-T Ethernet max. link speed and duplexing

Range (Values)
000.000.000.000 to 999.999.999.999 000.000.000.000 to 999.999.999.999 000.000.000.000 to 999.999.999.999 000.000.000.000 to 999.999.999.999 000.000.000.000 to 999.999.999.999 Auto, 10BT half, 10BT full, 100BTX half, 100BTX full Full Duplex or Half Duplex

Default
varies3
255.240.0.0

NETWORK SETUP

0.0.0.0 none

none Auto Full Duplex Disabled 106

100BFX CONFIG Sets the Fiber Ethernet duplexing SNMP SERVER SWELL LIMIT

Determines whether SNMP protocol Enabled or Disabled is enabled on the meter or not Specifies the magnitude above which an input must rise for a swell 100 to 1000 to be recorded Specifies the magnitude below which an input must fall for a sag to 0 to 100 be recorded Specifies the amount by which an input must change during a 0 to 100 disturbance to be considered a new sub-disturbance Specifies the nominal voltage of the 0 to 1,000,000 power system Assigns a priority level to sag/swell events Specifies symbols used to delimit thousands & decimal place holder Number of decimal places displayed for voltages Number of decimal places displayed for currents 0 to 255 1000.0 or 1,000.0 or 1000,0 1. to 123456789.XXX 1. to 123456789.XXX

SAG LIMIT

88

PQ SETUP

CHANGE CRITERIA NOMINAL VOLTAGE4 EVENT PRIORITY DIGIT GROUP VOLTS DECIMAL CURRNT DECIMAL POWER DECIMAL

10

0 200 1000.0 1.XX 1.XXX 1.XXX IEEE ABC IEEE LD/LG MM/DD/ YYYY 24 H Yes

Number of decimal places 1. to 123456789.XXX displayed for power measurements Specifies the convention used for displaying measurements Specifies how phases are labelled Specifies the power factor sign convention used Sets how power factor is labelled (LD = leading/LG = lagging) Specifies how dates are displayed IEEE or IEC ABC, RST, XYZ, RYB, RWB, 123 IEEE or IEC LD/LG, +/-, CAP/IND MM/DD/YYYY, DD/MM/YYYY, YYYY/MM/DD

FORMAT SETUP

MEAS SYMBOL PHASE LABEL PF SIGN PF SYMBOL DATE FORMAT TIME FORMAT DISPLAY DST

Specifies whether time is displayed 12 H or 24 H in 12 hour or 24 hour clock format Specifies whether or not DST is displayed Yes or No

22

2008 Schneider Electric. All rights reserved.

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

Menu DISPLAY SETUP

Setting
UPDATE RATE CONTRAST DELTA VECTORS LANGUAGE TZ OFFSET DST OFFSET

Description
Sets when the display updates Higher numbers are sharper Specifies how vector diagrams are displayed when in Delta mode Specifies the language used on the meters front panel Sets the time zone of the meters location, relative to UTC 0 to 9

Range (Values)
1 to 6 (seconds) 1 7

Default

System or Instrument English, Spanish, French, Russian - 12:00 to +13:00

System English +00:00 +00:00 COM1 UTC Line Freq

TIME SETUP

Sets the daylight savings time offset -3:00 to +3:00 of the meters location Sets the port to receive time synchronization signals Specifies whether time sync signals are received in local time or UTC Sets the local date Sets the local time Sets the meter password Enables or disables meter security Enables or disables web browser configuration of the meter Enables or disables internal web server on the meter
1 2 3 4

SYNC SOURCE SYNC TYPE

Ethernet, COM1, COM2, COM3, COM4 Local Time or UTC Internal, Line Freq or COMM Same as Date Format setting 00000000 to 99999999 Yes or No Enabled or Disabled Yes or No

CLOCK SOURCE Specifies time sync source LOCAL DATE LOCAL TIME PASSWORD

00000000 No Enabled Yes

SECURITY SETUP

ENABLED WEB CONFIG WEB ACTIVE

A baud rate of 300 bps is only intended for paging applications. Serial number = PA-0302B222-01, Unit ID = 2222 Default IP ADDRESS = 172.16.xxx.xxx, where the last two bytes (decimal) match the last two bytes of the meters MAC address (hex). NOMINAL VOLTAGE must be set to your systems nominal voltage to activate the meters power quality features.

Step 9: Verify Meter Operation


The LEDs on the back of the meter flash during communications. LED
Ethernet 100 (Speed) Ethernet TX Ethernet RX/LINK Modem DCD Modem RI COM3 (Modem) TX COM3 (Modem) RX COM2 TX COM2 RX COM1 TX COM1 RX

Color
Green Green Green Green Green Yellow Yellow Yellow Yellow Yellow Yellow

Function
Off = link at 10 Mb, On = link at 100 Mb Blinking indicates Ethernet transmission On = link up, Off = link down Blinking indicates Ethernet reception Indicates a carrier signal is detected (active connection to the modem) Indicates a ring is detected by the modem Indicates serial transmission on COM3 Indicates serial reception on COM3 Indicates serial transmission on COM2 Indicates serial reception on COM2 Indicates serial transmission on COM1 Indicates serial reception on COM1

2008 Schneider Electric. All rights reserved.

23

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

The LEDs on the front panel indicate the following:


Top (green) LED indicates the meter is operational. The light should always remain on when the meter is in service. Watt-hour pulsing Middle (red) LED is a watt-hour pulser. During normal operations this LED should blink intermittently as the meter measures power. Bottom (red) LED is user programmable. It can be used for Alarm notification. See the ION7550 / ION7650 User Guide for more information.

Front Panel

Phasor Diagrams
You can also view the meters phasor diagram in real time. Use the Phasor Viewer available in PowerLogic ION Setup v2.1 and later (free download from the PowerLogic website) to verify your meters wiring. See the ION Setup online help for details.

NOTE
The following DELTA phasor diagrams are represented in System mode view.

DELTA phasors for UNITY Power Factor (resistive load)


Applicable Volts Mode = DELTA
VCA IC ABC Rotation IB ACB Rotation IA VAB VBC

VAB IB IA

IC VBC VCA

24

2008 Schneider Electric. All rights reserved.

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

WYE - ABC Rotation


Applicable Volts Mode = 4W-WYE and 3W-WYE

Q2: Leading PF (+)


VC IB

Q1: Lagging PF (-)


VC IC

+kVAR

Reactive Power

Active Power -kW Q3: Lagging PF (-)


VC IB VA

WYE - ACB Rotation


Applicable Volts Mode = 4W-WYE and 3W-WYE

Active Power -kW Q3: Lagging PF (-)


VB

2008 Schneider Electric. All rights reserved.

Rotation IA VB IC IA Rotation VB IC

Rotation

VA

VA IB VB IA

Active Power +kW Q4: Leading PF (+)


VC IA VA

IC

Reactive Power

Rotation

-kVAR

VB

IB

Q2: Leading PF (+)


VB IC

Q1: Lagging PF (-)


VB IB

+kVAR

Reactive Power

Rotation IA VC IB IA IC Rotation VC IB

Rotation

VA

VA IC VC IA

Active Power +kW Q4: Leading PF (+)


VB IB

IA VA

Rotation

Reactive Power

VA

-kVAR

IC VC

25

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

2 Element (3Wire) DELTA - ABC Rotation


Applicable Volts Mode = DELTA

Q2: Leading PF (+)


VCA IB Rotation

Q1: Lagging PF (-)


VCA IC Rotation IB VAB

VAB IA IC VBC

+kVAR

Reactive Power

IA VBC

Active Power -kW

Active Power +kW

Q3: Lagging PF (-)


VCA IA Rotation Rotation IC VBC
VBC IC

Q4: Leading PF (+)


VCA IC

IA VAB

Reactive Power

VAB IB

2 Element (3Wire) DELTA - ACB Rotation


Applicable Volts Mode = DELTA

-kVAR

IB VBC

Q2: Leading PF (+)

Q1: Lagging PF (-)


VBC IB Rotation

+kVAR

Reactive Power

Active Power -kW Q3: Lagging PF (-)


VBC IC

Rotation Rotation IA VCA

IB VAB

VAB IA IC

IA VCA VCA

Active Power +kW Q4: Leading PF (+)


VBC IA Rotation

Reactive Power

VAB

IB IC VCA

VAB

-kVAR

IB

26

2008 Schneider Electric. All rights reserved.

PowerLogic PowerLogic ION7550 / ION7650 Installation Guide

Step 10: View Meter Data


Use the softkeys to select which data to display. Use the left and right arrow buttons to scroll through the available display screens.

Display Screens
Softkey V,I,PF Volts Amps Power Energy1 Demand1 Pk Dmd1 V Bar, I Bar, P Bar Summary1, Summary2 D Inputs DI - I/O D-Output Anlg - I/O Phasors Name Plt Events Setpoint Energy2 Demand2 Pk Dmd2 THD V1 Harm, V2 Harm,... I1 Harm, I2 Harm,... TOU TOU Egy TOU Dmd1 & TOU Dmd2 *PQ Freq *PQ Vmag1 *PQ Vmag2 *PQ Flk1 *PQ Flk2 *PQ Vdist *PQ Vunb *PQ Vhrm1 *PQ Vhrm2 V-Trend, I-Trend, P-Trend * Contents Volts, Amps, Power Factor Volts Amps Total Power Energy delivered Demand delivered Peak Demand delivered Voltage, Current and Power Bar Graphs Volts/Amps Summary, Power Summary Digital Inputs Digital I/O on expansion I/O card Digital Outputs Analog In and Out Phasors Nameplate information Events Setpoint status Energy received Demand received Peak Demand received Volts and Amps Total Harmonic Distortion V1, V2, V3, V4 harmonics I1, I2, I3, I4, I5 harmonics Time Of Use Active Rate / Season TOU Energy delivered TOU Peak Demand 1 and 2 Power Quality Power Frequency PQ Supply Voltage 1 PQ Supply Voltage 2 PQ Flicker 1 PQ Flicker 2 PQ Voltage Disturbance PQ Voltage Unbalance PQ Voltage Harmonics 1 PQ Voltage Harmonics 2 Voltage, Current, Power Trends

Additional display screens for ION7650 meters with EN50160 option.

2008 Schneider Electric. All rights reserved.

27

PowerLogic ION7550 / ION7650


with WebMeterTM and MeterM@ilTM

Installation Guide

For further assistance please contact us at:

Schneider Electric
Power Monitoring and Control 2195 Keating Cross Road Saanichton, BC Canada V8M 2A5 Tel: 1-250-652-7100 295 Tech Park Drive, Suite 100 Lavergne, TN 37086 USA Tel: 1-615-287-3400 Electropole (38 EQI) 31, rue Pierre Mends France F - 38050 Grenoble Cdex 9 Tel : + 33 (0) 4 76 57 60 60 Getting technical support: Contact your local Schneider Electric sales representative for assistance or go to the www.powerlogic.com website. PowerLogic, ION, ION Enterprise, MeterM@il, WebMeter and Modbus are either trademarks or registered trademarks of Schneider Electric in France, the USA and other countries. All other trademarks are property of their respective owners. Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. 70002-0247-11 2008 Schneider Electric. All rights reserved. 11/2008