Catalogo CB41
Catalogo CB41
Catalogo CB41
10-VPR-D
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
http://Global.MitsubishiElectric.com
Safety Warning
To ensure proper use of the products listed in this catalog,
please be sure to read the instruction manual prior to use.
The All-new
10-VPR-D Series
Incorporates
Mitsubishi Electric vacuum interrupter technology, realizing a more compact vacuum interrupter
(VI) 16% smaller than in the previous type* and high reliability (class E2).
Self-cooling vacuum circuit breakers (VCBs) that do not require a fan to be mounted on the side of the panel.
Available in a wide range, from rated current of 600 to 3,150A.
Compliant with IEC 62271-100- 2012 and has passed type tests for classes M2, E2 and C2, which represent
the highest levels of quality.
Type Selection
06
Ratings
07
09
External Dimensions
11
Connection Diagrams
17
Accessories
19
Optional Accessories
21
Relevant Devices
25
28
Technical Information
29
Applicable Standards
33
Ordering Information
39
Exposure
of live parts in the main circuit has been minimized even in VCBs with a 3,150A rating. This
enhances safety through prevention of potential hazards such as short circuits caused by intrusion of
small animals.
Earthing switch
The
mechanical parts are coated with a long-life grease that contributes to the prevention of oxidation
degradation and oilless bearings has been adopted for the bearing section of latch, thus extending the
lubrication cycle to mechanical parts from three to six years and reducing the time required for maintenance.
Includes a new withdrawable with door closed* (in addition to the conventional lever-based insert/draw-out
mechanism) with cam-slide mechanism that reduces operating effort, saves time and enhances VCB safety.
*Mechanism used to insert/draw-out the circuit breaker from the external panel based on IEC 62271-200 switchgear standards.
No
use of the six hazardous substances (mercury, cadmium, lead, hexavalent chromium, PBB and PBDE), a
measure that exceeds the requirements of RoHS standards. One example is use of a rust-proofing treatment
for small parts such as pins and screws that is free of hexavalent chromium, a substance known to
contaminate soil.
Marking of main resin materials to facilitate recycling.
01
02
Through
Greater
performance reliability and extension of the lubrication cycle from three to six years through measures for the
mechanism such as minimizing the number of parts, reducing the number of moving parts, adopting oilless
bearings and use of a long-life grease.
Heat flow
release
operating
More
reliable distribution of operating friction (which, due to the addition of a spring load, is difficult to verify/evaluate)
has been achieved thanks to utilization of a three-dimensional mechanical simulation used to switch operation from the
operating mechanism to a VI contact.
Compound
100
Insulation rod displacement [%]
and
Improved
Analytical value
0
0
engineering
Measured value
0.01
0.02
0.03
0.04
Time [s]
Fixed terminal
Flange
Fixed conductor
In
Fixed contact
Arc shield
Movable contact
Insulator
Movable conductor
VCBs
*1 As of 2012
Bellows shield
Bellows
Flange
Connected position
Movable terminal
Test/Disconnected position
Fig. 2 Three-dimensional model of a VI.
Current
Fixed contact
Fixed contact
Arc
Magnetic force
Spiral slit
Movable contact
Arc
Conductor
Fig. 3 Current flow at the time of breaking.
Current flows along the spiral electrode causing a radial magnetic field
which generates an electromagnetic force circumferentially towards
the contacts. This results in arcs that rotate circumferentially on the
contact surface.
03
Moving contact
A
B
Approx. 60
Fig. 6 Withdrawable with door closed (Type-M) operation mechanism.
04
Type Selection
The IEC standards broadly divide the mechanical operating test into classes M1 and M2. At the control voltages shown in
Table 1, class M1 requires the rated operation sequence to be performed 2,000 times in total while class M2 requires the
rated operation sequence to be performed 10,000 times in total. At five times the actuating cycle of class M1, class M2
represents a highly reliable operation class.
Table 1 M1 and M2 operating sequence.
Control
voltage
Actuating cycle
M1
M2
C-O
85%
500
2,500
C-O
100%
500
2,500
C-O
110%
500
2,500
O-CO-C
100%
250
1,250
Type
Rated short-circuit
breaking current
Series name
Classification*1
Mounting
configuration *2
10
VPR
25
10,000
Actuating cycle
Actuating cycle
Sequence
Rated voltage
8,000
6,000
M2
10,000
4,000
2,000
0
M1
2,000
M1
M2
3.6kV
25
25kA
Class E1
7.2kV
32
31.5kA
Class E2
10
12kV
40
40kA
15
15kV
Fig. 7
Type
Description
10%
30%
Operating
sequence
O-CO-CO
80
E2
1
O-CO-CO
15
60%
O-CO-CO
15
100%
(symmetry)
O-CO-CO
100%
(asymmetry)
O-O-O
70
Number of breaking test
Testing current
(percentage of
rated short-circuit
breaking current)
60
50
40
100% (asymmetry)
100% (symmetry)
60%
30%
10%
LSC1
LSC2B-PI
LSC2B-PM
Withdrawable
type
20
10
0
30
E1
High-voltage
switchgear standards
(IEC62271-200)
Fixed type
LSC2B-PM
LSC1
E2
Fig. 8
*1 Rated short-circuit breaking current of 40kA with E2 class cannot be manufactured. And basic impulse level (BIL) with rated voltage 12kV
has BIL75kV and BIL95kV.
*2 Fixed (type-L) with rated current of 2,500A or 3,000/3,500A cannot be manufactured.
*3 Please refer to the JNEC-SI-0150 catalog for 3/6-VPR-25D type with a rating of 1,250A or lower for information regarding class E1,
withdrawable (types C,D and G) and fixed type-L.
LSC1 : No partition
LSC2A-PI : No partition in the cable room
LSC2A-PM : No partition in the cable room
LSC2B-PI : Partitions in all compartments
LSC2B-PM : Partitions in all compartments
*Arc restrike is the phenomenon that occurs when current flows later than a 1/4 of a cycle after zero when there are insufficiencies in the VCB arc
extinction or in insulation stress between VCB poles for recovery voltage.
05
06
Ratings
Table 3 List of Ratings (JEC / IEC Standards).
Type
3-VPR-25D* 6
3-VPR-32D
3-VPR-40D
6-VPR-25D*6
6-VPR-32D
6-VPR-40D
Standards* 1
7.2
600 / 630
600 / 630
600 / 630
600 / 630
600 / 630
600 / 630
600 / 630
600 / 630
1,200 / 1,250
1,200 / 1,250
1,200 / 1,250
1,200 / 1,250
1,200 / 1,250
1,200 / 1,250
1,200 / 1,250
1,200 / 1,250
1,600
1,600
1,600
1,600
1,600
1,600
1,600
1,600
1,600
1,600
1,600
1,600
2,000
2,000
2,000
2,000
2,000
2,000
2,000
2,000
2,000
2,000
2,000
2,000
2,500
2,500
2,500
2,500
2,500
2,500
2,500
2,500
2,500
3,000 / 3,150
3,000 / 3,150
3,000 / 3,150
3,000 / 3,150
3,000 / 3,150
3,000 / 3,150
3,000 / 3,150
3,000 / 3,150
3,000 / 3,150
25
31.5
40
25
31.5
40
65
81.9
104
65
81.9
104
Rated short-time
withstand current
(kA)
JEC, 2s
25
31.5
40
25
31.5
40
IEC, 3s
25
31.5
40
25
31.5
40
0.03
Power frequency
(JEC/IEC)
Lightning
impulse
22 / 20
45
60
*1
*2
*3
*4
E1
IEC
: JEC: Japanese standard JEC 2300-2010, IEC: International standards, IEC 62271-100-2012.
: Type test class described in IEC62271-100 (see page 5)
: Closing operation/control current and opening control current show the value of 110V DC.
: Auxiliary switches are available up to 10a10b by adding 5a5b.
In addition, when selecting additional shunt tripping coil from optional accessories, the switches are 3a3b and will be 8a8b by adding 5a5b.
*5 : Mass of VCB units (including 12kg of the type-M) (excluding for options).
*6 : Refer to the catalog (JNEC-SL-0150) for class E1 of 25kA, standard draw-out operation (types C,D and G), and the fixed (type-L), for the rated current of 1,250A and lower of
products rated at 3.6/7.2kV.
*7 : Fixed (type-L) is not compatible with the rated voltage 15kV BIL95kV and code B. In addition, withdrawable (type M) is not compatible with the mounting configuration of class CW.
07
40
25
31.5
40
JEC
63
80
100
63
80
100
IEC
65
81.9
104
65
81.9
104
JEC, 2s
25
31.5
40
25
31.5
40
IEC, 3s
25
31.5
40
25
31.5
40
0.03
3
Power frequency
(JEC/IEC)
Lightning
impulse
C2
O-1min-CO-3min-CO (A), CO-15s-CO (B), O-0.3s-CO-1min-CO (R)
Mounting configuration*7
Mass (kg)* 5
E1, E2
E1
31.5
28 / 28
/ 36
75, 95
95
M2
Mechanical
JEC
Rated withstand
voltage (kV)
M2
E1, E2
25
16 / 10
Mechanical
50 / 60
Auxiliary switch
50 / 60
IEC
15
1,200 / 1,250
100
Tripping device
12
600 / 630
80
(Closing coil)
IEC 62271-100-2012
1,200 / 1,250
63
Motor
Closing operation/
control current (A)*3 Control current
600 / 630
100
15-VPR-40D
1,200 / 1,250
80
Rated operating
sequence
15-VPR-32D
600 / 630
63
Small capacitive
current switching
15-VPR-25D
1,200 / 1,250
JEC
10-VPR-40D
Rated making
current (kA)
Rated withstand
voltage (kV)
10-VPR-32D
600 / 630
10-VPR-25D
Standards* 1
Type
Rated operating
sequence
E1, E2
E1
IEC
Motor
Closing operation/
control current (A)*3 Control current
(Closing coil)
Tripping device
Opening control current (A)
(STC)*3
Auxiliary switch
Operating counter (mechanical)
Mounting configuration*7
E1
C2
JEC
Mass (kg)* 5
E1, E2
0.1
1.2 (motor charging time: 6s)
3.5
Shunt tripping coil (STC)
4
5a5b (10a10b)* 4
Standard equipment
Fixed (type-L) / Withdrawable (types M, C, D and G)
124 (6001,250A)
152 (1,600A, 2,000A)
200 (2,500A3,150A)
*1
*2
*3
*4
: JEC: Japanese standard JEC 2300-2010, IEC: International standards, IEC 62271-100-2012.
: Type test class described in IEC62271-100 (see page 5)
: Closing operation/control current and opening control current show the value of 110V DC.
: Auxiliary switches are available up to 10a10b by adding 5a5b.
In addition, when selecting additional shunt tripping coil from optional accessories, the switches are 3a3b and will be 8a8b by adding 5a5b.
*5 : Mass of VCB units (including 12kg of the type-M) (excluding for options).
*6 : Refer to the catalog (JNEC-SL-0150) for class E1 of 25kA, standard draw-out operation (types C,D and G), and the fixed (type-L), for the rated current of 1,250A and lower of
products rated at 3.6/7.2kV.
*7 : Fixed (type-L) is not compatible with the rated voltage 15kV BIL95kV and code B. In addition, withdrawable (type M) is not compatible with the mounting configuration of class CW.
08
Primary junction
Fig. 9
Fig. 10
Fig. 17
Fig. 18
Fig. 11
Fig. 12
Fig. 19
Fig. 20
Fig. 13
Fig. 14
Fig. 21
Fig. 16
Fig. 23
Fig. 24
(Vertical)
Fig. 22
(Horizontal)
(+)
52a
52a
STC
(-)
09
Fig. 15
10
Fixed (type-L)
Class CW (type-C)
450
25
613
320
195
208.5
34
34
Vacuum
interrupter
Primary
junction
693
Operation
counter
34
Fig. 26
391
188
Shutter guide
18
238
152
638
263
38
15
45
20
20
45
15
263
38
38
253
484
15
45
Length=1820
20
18
35
M12 bolt
Torque35Nm
210
210
30
30
20
20
80
29
56
15
45
320
133
60
Maximum
displacement
magnitude
300
Rear view
Partition
(not supplied)
Interlock lever
21
Draw-out
handle aperture
Shutter
device
25
Main-circuit terminal
693
783
505
195
208.5
19
Handle
Interlock plate
Wheels
613
Connected
position
Code A
without interlock
Nameplate
Partition
(not supplied)
15
Manual trip
button
25
80
Secondary
junction
450
80
On-O
indicator
312
788.5
Closing spring
charge indicator
49
320
Manual close
button
(with the cover)
22-11 holes
for shipping clamp
(pitch=40)
189.5
Primary
junction
16.5
80
579
50
34
100
340
Manual charging
handle aperture
Vacuum
interrupter
10
Front plate
180
190
2-entrance holes
for control wire
1018.5
540
22-10 holes
188
Shutter guide
180
Interlock pin
410
320
391
325.5
67
605
300
260
Wheels
Partition
(not supplied)
300
74.5
133
320
Additional auxiliary
switch (option)
Draw-out
handle aperture
30
20
56
60
505
566
30
258
783
Maximum
displacement
magnitude
Classes PW and MW
(types M, D and G)
Partition
(not supplied)
Nameplate
21
30
80 126 80 126 80
Fig. 27
Interlock plate
Code A
without interlock
210
50
680
Length=1820
Handle
Manual trip
button
210
80
30
M12 bolt
Torque35Nm
320
Secondary
junction
18
152
Closing spring
charge indicator
On-O
indicator
35
23
638
Operation
counter
Manual close
button
(with the cover)
18
275.5
Manual charging
handle aperture
579
20
80
Front plate
180
788.5
166
238
540
180
Partition
(not supplied)
M8 tap screw
for earth terminal
(center of VCB)
85
Fig. 25
300
Rear view
Main-circuit terminal
1018.5
210
391
Wheels
19
25
15
133
65
60
505
534
564
253
484
Connected
position
4-14 holes
38
320
Nameplate
11
Partition
(not supplied)
Interlock plate
312
189.5
49
16.5
783
693
12
22-11 holes
for shipping clamp
(pitch=40)
100
80
Lower
terminal
Handle
340
320
Secondary
junction
50
On-O
indicator
Manual trip
button
2-entrance holes
for control wire
12
Closing spring
charge indicator
10
Manual close
button
(with the cover)
22-10 holes
Operation
counter
190
410
325.5
Upper
terminal
Vacuum
interrupter
Manual charging
handle aperture
75
4-14 holes
82
80
475
260
34
258
Front plate
300
180
Partition
(not supplied)
275.5
540
Partition
(not supplied)
20
17
605
300
210
35 40 25
30
80 126 80 126 80
23
30
680
50
Fig. 28
12
34
579
Primary
junction
Vacuum
interrupter
30
Nameplate
Partition
(not supplied)
22-11 holes
for shipping clamp
(pitch=40)
49
312
450
30
34
Shutter
device
29
56
391
188
Shutter guide
80
688
263
38
253
484
189.5
15
263
38
253
484
38
320
30
680
23
50
45
20
Length=1820
210
210
20
260
18
152
238
Interlock lever
Fig. 30
18
35
45
15
320
133
60
Interlock pin
20
80
788.5
1018.5
693
783
Interlock plate
Wheels
Main-circuit terminal
Partition
(not supplied)
Code A
without interlock
Maximum
displacement
magnitude
300
Rear view
15
Handle
21
25
80
Manual trip
button
195
208.5
320
Secondary
junction
19
Connected
position
Closing spring
charge indicator
Draw-out
handle aperture
20
Partition
(not supplied)
625
Operation
counter
190
Interlock plate
(types D,G)
189.5
Primary
junction
15
579
16.5
340
80
34
Vacuum
interrupter
505
30
2-entrance holes
for control wire
50
Front plate
10
180
Nameplate
30
126 80 126 80
325.5
188
Shutter guide
100
391
540
On-O
indicator
30
655
300
410
300
133
60
74.5
67
Wheels
Manual close
button
(with the cover)
80
22-10 holes
6
566
Manual charging
handle aperture
210
320
Additional auxiliary
switch (option)
Maximum
displacement
magnitude
Classes PW and MW
(types M, D and G)
Partition
(not supplied)
56
505
180
210
50
275.5
Code A
without interlock
Length=1820
320
693
783
Interlock plate
258
Manual trip
button
Handle
20
Draw-out
handle aperture
M12 bolt
Torque35Nm
Fig. 31
Secondary
junction
21
190
38
680
Closing spring
charge indicator
On-O
indicator
18
23
688
Operation
counter
Manual close
button
(with the cover)
18
35
80
Front plate
20
152
238
180
Main-circuit terminal
80
788.5
1018.5
166
300
Rear view
45
320
M8 tap screw
for earth terminal
(center of VCB)
85
540
180
Manual charging
handle aperture
13
15
Partition
(not supplied)
Fig. 29
195
208.5
133
65
60
210
391
Wheels
34
19
25
Connected
position
20
30
450
625
Nameplate
4-14 holes
Partition
(not supplied)
45
312
15
49
260
20
783
693
10
22-11 holes
for shipping clamp
(pitch=40)
Interlock plate
16.5
80
50
Lower
terminal
Handle
100
340
320
Manual trip
button
2-entrance holes
for control wire
320
20
Secondary
junction
505
534
564
22-10 holes
Closing spring
charge indicator
On-O
indicator
410
325.5
Upper
terminal
Operation
counter
Manual close
button
(with the cover)
80
82
475
Vacuum
interrupter
Manual charging
handle aperture
Partition
(not supplied)
275.5
34
4-14 holes
258
Front plate
35
300
180
655
300
Partition
(not supplied)
20
540
180
Class CW (type-C)
40 25
40
75
17
210
Fixed (type-L)
30
30
30
80 126 80 126 80
Details of main-circuit terminal
Fig. 32
14
Class CW (type-C)
755
300
Partition
(not supplied)
20
Partition
(not supplied)
38
38
253
484
16.5
Main-circuit terminal
10
14
50
26
35
98 126 98 126 98
160
47.5
80
40
30
680
47.5
40
*set
the busbars so
that this distance keep
125mm or more, or
cover busbars with
insulation cover.
40
23
788
Length=1820
26
10
90
20
M12 bolt
Torque35Nm
50
1018.5
Shutter guide
Wheels
263
204
15
Partition
(not supplied)
188
271.5
391
Note
Connected
position
320
195
208.5
300
Rear view
238
Draw-out
handle aperture
67
19
25
730
133
74.5
60
566
Interlock plate
30
450
720
34
Code A
56
without interlock
Additional auxiliary
21
switch (option)
Maximum
displacement
magnitude
505
312
14
783
Interlock plate
Nameplate
49
780
Manual trip
button
320
Handle
Secondary
junction
Code Bwith interlock
22-11 holes
for shipping clamp
(pitch=40)
189.5
80
10
50
Closing spring
charge indicator
On-O
indicator
100
Manual close
button
(with the cover)
2-entrance holes
for control wire
340
Operation
counter
788.5
Manual charging
handle aperture
22-10 holes
248
Vacuum
interrupter
410
325.5
Primary
junction
90
579
258
34
Front plate
300
200
320
540
200
50
Fig. 34
Classes PW and MW
(types M, D and G)
Partition
(not supplied)
312
450
30
34
263
38
38
4-M12 tap screws
(depth=22)
Main-circuit terminal
M12 bolt
Torque35Nm
90
10
160
23
30
680
50
Length=1820
26
35
Partition
(not supplied)
98 126 98 126 98
26
10
50
90
788.5
188
Shutter guide
Additional auxiliary switch (option)
20
14
391
50
14
56
788
Fig. 33
Rear view
15
80
29
Maximum
displacement
magnitude
204
238
Interlock pin
Draw-out
handle aperture
Wheels
1018.5
320
21
133
60
Interlock lever
505
Note
300
Code A
without interlock
Nameplate
19
25
720
730
Interlock plate
Partition
(not supplied)
248
49
271.5
Manual trip
button
22-11 holes
for shipping clamp
(pitch=40)
Interlock plate
(types D,G)
780
Secondary
junction
320
On-O
indicator
10
Handle
253
484
80
50
Closing spring
charge indicator
783
100
Manual close
button
(with the cover)
2-entrance holes
for control wire
340
Operation
counter
189.5
Vacuum
interrupter
410
16.5
Primary
junction
320
579
325.5
34
258
Front plate
300
200
Manual charging
handle aperture
15
20
540
200
Partition
(not supplied)
755
300
47.5
40
47.5
40
40
*set
the busbars so
that this distance keep
125mm or more, or
cover busbars with
insulation cover.
Fig. 35
16
Connection Diagrams
Withdrawable: Standard Connection Diagram (Code A)
On
27
J3
52X
D1 D2
D3 D4
R1
52Y
R2 R3
D7 D8
ZNR4
J2
52Y
J5
D5 D6
J2
ZNR2
J4
ZNR3
D9
ZNR5
CC
52b
LS0
STC
Capacitor
tripping device
AC1 AC2 DC+ DC-
J1
(-)
J3
ZNR1
D1 D2
D3 D4
M
: Motor (for charging the closing spring)
CC : Closing coilSTC : Shunt tripping coil
52Y : Auxiliary relays (for motor)
52X : Auxiliary relays (for prevention of pumping)
52a/b : Auxiliary contacts for circuit breaker
14
15
16
17
1
2
3
4
5
6
7
8
9
25 18
26 19
27 20
21
28 22
29 23
30 24
17P
13P
LS0
: Limit switch (for detecting VCB's position)
LS1
: Limit switch (for detecting the charging of the closing spring)
LS2
: Limit switch (for starting up and stopping motor)
LS3
: Limit switch (for closing spring charged indication)
R1/2/3/4 : Resistor (R3 and R4 200/220V only)
Fig. 36
ZNR2
52Y
J4
ZNR3
D5 D6
J2
R2 R3
D7 D8
ZNR4
J2
52Y
(+)
9 11 13 15 17 19 21 23 25
D9
ZNR5
39
8 10 12 14 16 18 20 22 24 26
52a
LS1
CC
52b
52b
52X R4
38
LS0
STC
Capacitor
tripping device
AC1 AC2 DC+ DC-
J1
J5
10
11
12
13
Note:
The following are VCB options:
the micro current specication auxiliary switch,
the tripping coil disconnection monitoring
(terminal No. 30),
the capacitor tripping device and LS3.
R1
52Y
52X
J1
52a
52X
(-)
Secondary junction
37
52a
AC input
DC output
40
LS3
J4
LS2
J5
J5
2
17
(+)
J5
8 10 12 14 16 18 20 22 24 26
29
52a
LS1
52b
52X R4
28
J3
52a
52X
J1
52a
J5
AC or DC
J4
52Y
LS3
LS2
ZNR1
On
9 11 13 15 17 19 21 23 25
(+)
J5
J3
AC or DC
(+)
30
Note:
For DC voltage,
set the COM to the positive terminal.
in the control
substrate
J5
Note:
For DC voltage,
set the COM to the positive terminal.
in the control
substrate
AC input
DC output
Secondary junction
Note:
The following are VCB options:
the micro current specication auxiliary switch,
the tripping coil disconnection monitoring
(terminal No. 40),
the capacitor tripping device and LS3.
8 15 22
9 16 23
37
3 10 17 24
38
4 11 18 25
39
5 12 19 26
40
6 13 20
7 14 21
Front view of the VCB
M
: Motor (for charging the closing spring)
CC : Closing coilSTC : Shunt tripping coil
52Y : Auxiliary relays (for motor)
52X : Auxiliary relays (for prevention of pumping)
52a/b : Auxiliary contacts for circuit breaker
LS0
: Limit switch (for detecting VCB's position)
LS1
: Limit switch (for detecting the charging of the closing spring)
LS2
: Limit switch (for starting up and stopping motor)
LS3
: Limit switch (for closing spring charged indication)
R1/2/3/4 : Resistor (R3 and R4 200/220V only)
Fig. 37
18
Accessories
Secondary Connector
Lifting Adapter
Lifting
Code A
Number of accessories:
1 per unit
Number of accessories:
1 per 1-5 VCBs (min. 1)
Code B
Shipping Clamp
Number of accessories:
1 per 1-5 VCBs (min. 1)
For type-M
3,150A rating
(shipped with a panel)
600-1,250A
1,600-3,150A
For types C, D and G
Number of accessories:
1 per unit
For types C, D and G
For type-M
19
20
Optional Accessories
Closing Spring Charged Indication Switch
125AC/DC
5.5
5.5
250AC/DC
1.5
Secondary
junction
Secondary
junction
37
38
39
17P
27
LS3
NC
N0
X-10GW22-B
(OMRON)
28
29
28
LS3
NC
13P
N0
29
COM
27
+
COM
X-10GW22-B
(OMRON)
38
39
37
(+)
(+)
52a
52a
52a
52a
STC
STC
(-)
(-)
Fig. 40
The interlock system is configured to lock the VCB in the off position. To
shut down the VCB either automatically or manually requires the VCB to
be locked using the key. The key can only be removed after the VCB has
been opened and locked. The VCB cannot be closed in this state.
Note that users are responsible for preparing the interlock key; a key will
not be supplied by the manufacturer. In addition, note that this feature
cannot be used together with the draw-out mechanism padlock device.
Castell
Model
FS1
User option
Key rotation
Spigot dimensions
52a
52a
STC
(-)
21
Fig. 39
22
Optional Accessories
Position Switch (Connected Position / Test and Disconnected Position)
200250DC
196.5
2 units
40
65
1 unit
2-12 holes
1.25mm2 , yellow, 2m
No.1 SW
142
1R1 1W1
D4
NC
N0
D6
NC
D5
N0
D2
1R2
COM+
D3
1R3
D1
Position detecting
switch timing
1W2
2R2
1W3
2R3
No.1 SW
2W2
2W3
No.2 SW
12
COM+
1.25mm2 , yellow, 2m
513
Connected position
contact
NOON
Fig. 43
NCON
1755
NOON
NCON
Connected position
Fig. 41
4-15 holes
17.5
40
Rated voltage
Current f low
100110V DC
63mA
Option
Electric interlock circuit
(-)(+)
Earth position
40
75
This earthing switch is used to ground the main circuit part (lower
side of the mounting frame). It enables simple safety checks at
the time of maintenance and inspections.
20
For 630-2,000A
4-15 holes
Terminal block
TE-K2-9S
(M3.5 screw)
COM(+)
NC
E4
LS1
(O position)
X-10GW22-B (OMRON)
COM(+)
E3
NO
E2 NC
E1
121
32-14 holes
411
30
24.5
Earth position
A: terminal thickness
600-2,000A:20
2,500-3,150A:24
Protrusion of shutter
50
88
End of mounting frame
710
O position
11 hole for earth
212
411
20
301
306
305.5
130
8
133.5
24.5
361
(68)
82
Indicator
82
20
101
51
25
89
Open: 250(max.)
Close: 130
Handle insertion
part
25
Fig. 44
Connection diagram
15
Shutter open
position
306
50
For 2,500-3,150A
COM(+)
108
301
14
24
210
101 89
60
210
(33
)
(610)
30
890
IC
LS2
(Earth position)
X-10GW22-B (OMRON)
E6
NO
E5 NC
S1 C2
50
98
S1 C2 E1 E2 E3 E4 E5 E6
Operating handle
O position
20
2R1 2W1
19.5
The ground-fault current to the VCB frame flows into the earth bus on
the panel side at the VCB's connected position.
Current flow of 40kA-3 seconds.
160
210
210
636
Fig. 42
23
24
Relevant Devices
Vacuum Checker
Sold Separately
Sold Separately
This is a device to check the VI vacuum level of a VCB using a vacuum checker.
Panel
External
CR-12
CR-15
11
15
16
20
Capacitance (F)
0.053 phases
0.053 phases
0.13 phases
0.13 phases
Resistance ()
1003 phases
1003 phases
1003 phases
1003 phases
8.5
10
31
33
Mass (kg)
Precautions
Caution for circuits containing harmonics
As is the case with general high-pressure capacitors, please exercise caution when applying CR suppressors to circuits
with higher harmonic waves. Particular care is required regarding multiple-order harmonic waves which may have
flowed into circuits used for current control via the thyristor. When using a CR suppressor, set the effective value of
resultant current with harmonic waves to the values shown in the table below (values are 1.3 times the rated value).
Table 11 Effective value of resultant current with harmonic waves.
Type
CR-3
CR-6
CR-12
CR-15
0.05A
eective value / phase
0.1A
eective value / phase
0.37A
eective value / phase
0.37A
eective value / phase
How to install
Install the CR suppressor vertically; do not install it horizontally or upside down.
Pilot lamp
Input voltage
selection
switch
Removable cover
Power supply
outlet
136
192
Ammeter
V-1C
100/110/120
V-2C
200/220/240
Between T-C
10 minutes
CR-3
CR-6
CR-12
CR-15
6.6V
13.2V
24V
30V
7.6V
14.2V
28V
36V
Lifter
L, C, D, G
F-3C
F-3C adapter
4.95V
9.9V
18V
22.5V
180
Cap
180
Terminal details
M12 screw
Cap
3
220
430 MAX
2-1520
oval
holes
25
140
Earth terminal
M8 screw
260
535 MAX
C
B MAX
2-1520
oval
holes
A
1.6
350
370
M12 screw
Winch box
39
180
Center load
2450N
Wire rope
Earth terminal
M8 screw
Main mast
Steering handle
Floor lock
(one-touch pedal type)
Free wheel with rubber
(2-125)
Fixed wheel
made of plastic
25
M6 screw
180
Terminal details
640
605
640
605
Inner R7.5
(installation foot)
Inner R7.5
(installation foot)
Terminal details
75
324
540
140
110
Wire cover
105
150
105
150
80
122
Earth terminal
M6 screw
110
540
249
37
Sheave
Guide roller
620
598
49
(Adapter size)
2-20
holes
F-3C
Safety catcher
322
Test
switch
Sold Separately
2-20
holes
T: Terminal C: Case
100
0.05 F
66
22
1 minute
Power
switch
Lifting stroke
Between T-T
Between T-C
AC
Remote control
Fig. 46
Remote control
outlet
Fuse
Base foot
(made of rubber)
This is the lifter necessary to carry the circuit breaker unit in and out of the panel.
Please use F-3C and adapter for type-M.
Type
Warning
label
Warning
label
Output voltage
selection
switch
Panel portion
120
337
22
237
Earth
terminal
High voltage
lead terminal
235
Remote control
box storage
portion
150
200
136
20
6.6
150
Carrying knob
320
3.3
CR-6
140
CR-3
(10)
Type
192
Table 10 Ratings.
286
320
555
644
(Adapter size)
(2-150)
25
26
Relevant Devices
Capacitor Tripping Device (CTD)
Through optional processing of the panel door, the VCB unit can be installed together
Sold Separately
This device makes it possible to trip the circuit breaker electrically within a fixed time via remote
control even when the control power is out.
45
45
Table 15 Ratings.
Type
45
2-M6
Mounting screws
27
f100
4-M4
Terminal screws
Protective cover
16
75
110.6
0.5W240
KF-200CD
820F
10W300
10W100
0.5W240
Items
Rated working voltage (V)
100/110AC
200/220AC
140/155DC
Function
0.1
1
VCB can only be moved when the panel door is in the closed state.
2.3
An insertion/draw-out handle (for type-M) can be used to move the VCB after closing the panel door with
the unlocking pin attached to the door.
100125DC
79 oval hole
2.3
Fig. 48
D1
KF-200CD
50/60
Device-mounting xture
AC1
KF-100E
90 (Pitch)
90
f104
Power consumption
(steady state) (W)
7
15
4-7
120
90
10W100
50
35
70
10W300
87
110
Dimension of CTD
130
820F
R1
DC+
AC1
R1
DC+
AC
power
supply
SW
ZNR
C
R3
52a
R2 LED
AC
power
supply
ZNR
SW
C
R3
DC-
52a
52a
R2 LED
STC
D2
AC2
52a
STC
AC2
Install a 5mm unlocking pin (figure below shows M5 screw) in the position shown in the figure below (dimensions:
117mm, 32.5mm).
Use an unlocking pin with a length that enables it to be inserted in a position 11mm from the edge of the mounting
frame.
Please process the handle aperture for a
panel cover of 16025 mm or larger.
DC-
*53
+2
117 1
Draw-in/draw-out handle
(Testing position)
Panel door
Unlocking pin
Panel opening160
Unlocking pin
32.52
(42)
26
1. Please note that the KF-200CD output voltage is 140/155VDC. It cannot be used to open circuit breakers with a tripping
voltage of 200/220VDC and may cause an accident in this case.
2. Be sure to completely charge a capacitor before performing opening operation or giving the opening command.
3. The sole purpose of this device is tripping a VCB. Do not use for any other purpose.
4. One device is required per VCB unit.
5. Recommended replacement period: 6 years
60
25
Caution:
(97.5)
113
Remarks
32.52
R6
4-
KF-100E
14.3
13
Function
VCB can only be moved when the panel door is in the
closed state.
45
10
l
ho
Panel opening160
113
*53
Mounting frame end
Fig. 52
27
28
Technical Information
Operation Mechanism and Operating Principles
Closing Operation
Fig. 53 shows the state where the circuit breaker is opened and the closing spring is discharged.
Standard
If consecutive closing commands are given to the closing operation switch CS1 while charging the closed spring (charge time
of motor: 6 seconds): limit switch LS1 closes, the closing coil CC is excited, and the circuit breaker closes after completing the
charging of the closing spring.
When the circuit breaker is opened (tripped), circuit breaker auxiliary contact 52a opens and shuts off excitation of STC to
prepare for the next closing operation.
Trip-free Operation
If the closing command and trip command are given simultaneously when the circuit breaker is in an opened state and the
closing spring is in a charged state (closing preparation):
When performing the closing operation, it is necessary to release the closing command by closing command switch CS1 and
then restore auxiliary relay 52X.
(0n)
CS1
DC
75125
AC
85110
DC
J4
LS2
52a
24
ZNR1
D1
52X
J4
ZNR3
3/6/10/15-VPR-25D/32D/40D
Closing
48
D2
D5
52Y
ZNR2
D6
D3 D4
M
52Y
D9
J2
Motor circuit
52a
52X
R4
LS0
STC
CC
: Closing coil
STC
LS0
: Limit switch
LS1
LS2
200/220
0.05
0.05
3.5
0.05
4.5
0.05
1.5
0.05
0.05
1.8
0.05
24
I
Type
48
Is
3/6/10/15-VPR-25D/32D/40D
VAC*1
VDC
I
8
100/110
Is
0.03 0.03
I
4
125
Is
0.03 0.03
100/110
200/220
Is
0.03 0.03
I
2
Is
200/220
Is
Is
0.03
Table 19 Motor operation control current and current-flow time for DC and AC (see Fig. 55).
Control voltage (V)
Current (A), Time (s)
VDC
24
48
VAC
100/110
125
200/220
100/110
200/220
I1 I2 T1 T2 I1 I2 T1 T2 I1 I2 T1 T2 I1 I2 T1 T2 I1 I2 T1 T2 I1 I2 T1 T2 I1 I2 T1 T2
Type
3/6/10/15-VPR-25D/32D/40D
6 1.2 0.1 6 7.5 1.5 0.1 6 3.5 0.6 0.1 6 8.5 3 0.1 6 4.5 1.5 0.1 6
: Limit switch
: Limit switch (for starting/stopping motor)
52Y
52X
T1
T2run time
T
time
Burden (VA)
680
0.05
R1/2/3/4 : Resistor
(R3 and R4 are equipped only for 200/220V)
Isteady-state
2
current
current
I
J5
100/110
J1
200/220
: No-voltage condition
52b
29
J1
52b
52Y
ZNR5
J5
R2 R3
D7 D8
ZNR4
125
I1
inrush current
52X
CC
R1 J2
VAC
100/110
(0ff)
CS2
LS1
85110
12
Type
52a
J3
70110
VDC
J5
J3
85110
60125
AC
In the control
substrate
J5
85110
AC
Table 18 Closing and tripping control current and current-flow time for DC and AC (see Fig. 54).
Closing control current
Operation takes place in the order of , , and of the electrical (closing) operation. Then, because the trip command is
being continued, operation of the electrical (trip) operation occurs.
Electrical (closing) operation is returned but since the auxiliary relay 52X is continuously being excited, a closed circuit is
not formed by contact 52Xb and the circuit remains in the opened state.
85110*
DC
When Closing Commands are Consecutively Given While Charging Closed Spring
By closing the trip command switch CS2, the voltage trip coil STC is excited, the engagement of the tripping latch at the
operating mechanism is released and the circuit breaker opens.
IEC-62271-100
Tripping Operation
JEC-2300
Items
100110V AC
Burden (VA)
180
30
Technical Information
Sequence Timing
Operating sequence
250 AC/DC
220 AC/DC
100125V AC
200220V AC
2455V DC
100110V DC
200220V DC
100V AC / V DC
30
24V AC / V DC
50
Main contact
AC
Standard
contact
Rated
operational current
(A)
T2
T3
"b" contact
DC
Minimum
operational current
(A)
"a" contact
T1
TC
AC/DC
125 AC/DC
T4
TT
Fig. 56
For micro
current
Rated
operational current
(A)
AC ratings
100125V AC
1500
DC ratings
24125V DC
1500
31
0.5
Code descriptions
Time (ms)
TC
Closing time
3060
T1
08
T2
210
TT
Opening time
1030
T3
08
T4
08
32
Applicable Standards
Operating Environment and Application
Operating Environment
Ambient
temperature
-5 - 40
(The average temperature for 24 hours must
not exceed 35.)
Inuence of
solar radiation
Altitude
1,000m or lower
Powder dust
Humidity
Relative humidity: 45 - 85
(There must be no dew condensation.)
Vibration
CR suppressor used
23
Capacitor
IEC60871-1
28
60
75
49
60
75
Poisonous gas
Although a capacitor circuit can be used, please exercise caution in regard to the following:
3/6/10/15-VPR-D
Rated lighting
impulse withstand
voltage
kV (peak value)
28
Rotator IEC-34-15-1995
Table 25
Type
Oil IEC60076-3-2000
Dry IEC726-3-1982
Degree of
pollution
Motor
Transformer
Table 22 outlines surge protection standards for the load circuit. Please use this table as a reference when selecting VCB
Generator
Power frequency
rated withstand
voltage
kV (rms value)
Type
A reactor circuit can be applied because the current chopping surge is not at a problematic level.
Load device
Table 26 Withstand voltage test voltage value of load device (11kV system).
Dry transformer
Oil transformer
General purpose
arrester used
Not required
Not required
*1: To directly switch the semiconductor rectifier unit (for example, a electric power thyristor rectifier unit) to the secondary side of a transformer, use
a transformer with a contact-protective plate. Use a general-purpose arrester on the primary side and the surge protective device (such as a filter
capacitor) on the secondary side.
*2: Avoid interrupting the no-load excitation inrush current of a molded transformer oil transformer. When such current must be interrupted, use a
general-purpose arrester. Before using any oil transformer or molded transformer made by other manufacturers, consult the manufacturer.
*3: For motors in applications where inching operation is frequently performed and inching is the predominant switching duty (cranes, conveyors,
etc.), use a CR suppressor.
Circuit conditions
Fig. 57 Application example of a surge protection device (for general-purpose vacuum circuit breakers).
For a motor direct switch (with line and reduced voltage starting)
CR
SR
33
VCB
VCB
CR
VCB
T
CR
CR
CR
VCB
VCB
VCB
VCB
Full-voltage starting
Reactor starting
Korndorfer starting
VCB
VCB
Star-delta starting
34
Applicable Standards
For semiconductor
rectifier
Electric furnace
transformer
Multiple
switching capacity
kVar
3-VPR-D
2,500
1,500
6-VPR-D
5,000
3,000
10/15-VPR-D
7,000
4,000
Type
VCB
VCB
LA
VCB
VCB
CR
LA
CR
Furnace
transformer
with short-proong
plate)
10,000
Maximum
switching capacity
kVar
Number of switching
*1: Electrical service life for the max. switching capacity is approx 2,000
times; multiple switching capacity is 10,000 times.
*2: Applicable capacities with 6-13% series-connected reactor.
1,000
1,000
Generator
7.2kV
12kV
15kV
3.6kV
7.2kV
12kV
15kV
3.6kV
7.2kV
12kV
15kV
3/6/10/15-VPR-D
1,250A
1,250
4,900
9,800
16,100
20,300
7,000
14,000
23,000
29,000
3/6/10/15-VPR-D
2,000A
2,000
7,700
15,400
26,600
32,900
11,000
22,000
38,000
47,000
3/6/10/15-VPR-D
3,150A
3,150
12,600
25,200
42,000
52,500
18,000
36,000
60,000
75,000
The contact resistance and calorific value of each rated current are shown. Use this as a reference when selecting models.
Table 30 Contact resistance and calorific value of each rated current.
Type
Rated current (A)
3/6/10/15-VPR-D
*1: Values shown in the table above are based on the continuous switching test and apply to the short term; they are not guaranteed in the long term.
To ensure optimum performance, please follow the maintenance and inspection procedures described in the instruction manual.
100,000
3.6kV
Type
Calorific Value
This can be determined by the operation counter provided in the VCB (provided in all types as standard specification).
Type
The service life of VCBs is specified in terms of the vacuum service life of VI, as well as the electrical and the mechanical service lives.
10,000
Applicable capacity
kVar
3/6/10-VPR-25D/32D
15-VPR-32D/
3/6/10/15-VPR-40D
3/6/10/15-VPR-32D/40D
3/6/10-VPR-32D/40D
600/630
1,200/1,250
600/630
1,200/1,250
2,000
3,150
72
63
42
24
338*2
366*2
504
715
*1: Measured value using the direct current voltage potential drop method.
*2: Value at the time of applying a 1,250A electrical current.
10,000
1,000
100
10
1
10
100
35
Fig. 60
36
Applicable Standards
Lifting the VCB
Altitude
Mounting hole
(30)
Mounting hole
(30)
Mounting hole
(30)
Lifting
Mounting hole
(30)
1.5
1.4
1.3
1.2
1.1
Mount both
sides with
accompanying
bolts
1
1,000
1,500
2,000
2,500
3,000
3,500
4,000
Altitude (m)
Fig. 65
Replace parts according to the following schedule (applies to all types) to ensure reliable operation for the full term of
the service life (20 years).
Fig. 61
Fig. 62
Do not lift VCBs while they are inserted in the mounting frame. When lifting the VCB or mounting frame,
please refer to the instruction manual and follow the specific conditions provided.
Shipping Clamps
When a switchgear is supplied with the mounting frame and VCB (in test position), it is necessary to mount the frame and
VCB on the switchgear. Follow the directions in the instruction manual and the accessories section of this catalog (page
20) to mount the devices using screws (M10) in the positions shown in the figure.
Replacement standard
Part
Usage period
Dumper
5,000
6 years
Auxiliary switch
5,000
Motor
5,000
Preventive maintenance
Limit switch
5,000
10-15
years
VI
(450)
Insulation performance
Degradation
Maintenance and
inspection classication
Normal environment
Substandard environment
(especially dew condensation, salt and powder dust)
Patrol inspection
6 months
1 month
37
2-10 holes or
M10 tap screws
(65)
320
119
Periodic inspection
Detailed inspection
6 years
Special inspection
2-12 holes for mounting
(pitch=450)
(40)
22-11 holes
for transport tting
(pitch=40)
1-2 years
2-4 years
*1: Please replace a VCB when the number of switching operations reaches 10,000 times.
*2: Please consider replacing the product after 20 years of use under normal environmental conditions.
10
50
49
312
450
37
30 times
2.Types of inspections
For 600-2,000A
Actuating cycle
38
VPR
3.6V
7.2V
12V
15V
0 3
0 6
1 0
1 5
4 0
3 2
2 5
40kA
31.5kA
25kA
Rated short-circuit
breaking current
Series
name
10
0 6
2 0
2,000A
2 5
2,500A
G
Withdrawable
with door
closed (type-G)
and class MW
L
Fixed
4
Class E2
BIL95kV
(12kV)
3,000A/3,150A
3 0
1,600A
1 6
1,200/1,250A
1 2
600/630A
Withdrawable
with door
closed (type-D)
and class PW
(type-L)
13
Rated current
12
closed (type-C)
and class CW
Withdrawable
with door
closed (type-M)
and class MW
Mounting
conguration
11
Class E1
BIL95kV
(12kV)
Class E2
J
JEC
2300-2010
1
Class E1
Classication Standards
2
7
8
48V DC
24V DC
200/220
VDC
100-125
VDC
Tripping
control
voltage
15
2, 7 and 8
will be manufactured
upon receipt of order
1 is standard.
48V DC
24V DC
200/220
VAC/V DC
100-125
VAC/V DC
Closing
operation/control
voltage
14
Connected
position 4C
Test position 2C
2 units
Connected
position 2C
Test position 2C
With
interlock
B
Code B
Without
interlock
Code A
Secondary
connector
17
1 unit
Position
switch
16
Additional
auxiliary switch
(additional 5a5b)
A
Additional shunt
tripping coil
D
Draw-out
mechanism
padlock device
P
padlock device
for close and
trip button
B
For
200/220AC
For
100/110AC
Capacitor tripping
device
(1), (2)
Without
electrical
interlock
With
electrical
interlock
Earthing switch
(Class E2)
(E), (F)
1 0 V P R 4 0 D 1 I D 1 2 11 0 B 0 0 0 0
Caution:Mechanical locking device (K) and draw-out mechanism padlock device (P) should not be used together.
Earthing switches are not compatible with type-C in the mounting configuration.
When the tripping power is AC and the capacitor tripping device (CTD) is selected, select 100 - 125V for the tripping control voltage.
When selecting an additional auxiliary switch and additional shunt tripping coil, it will be compatible only for control circuit plug: code B.
The tripping coil disconnection monitoring and the capacitor tripping device should not be used together.
The fixed (type-L) is not compatible with earthing switches, short-circuit capacity earthing, optional terminals or shutter padlock device.
Tripping coil
disconnection
monitoring
T
Mechanical
locking device
K
Optional Accessories
Optional
terminal
(V: Vertical,
H: Horizontal)
Standard 3a3b
contact For
microcurrent
2a2b contact
For microcurrent
Standard
5a5b
Auxiliary
switch
18
20
With
Optional
accessories
A
Without
mounting
frame
Optional
accessories
21
With
mounting
frame
Shutter padlock
device
S
With 1C
Closing spring
Mounting
charge indication
frame
switch
19
Lifter
Short-circuit
capacity
earthing
J
Caution:Refer to the catalog (JNEC-SL-0150) for the class E1 at 25kA, the standard draw-out operation (types C, D and G), and fixed (type-L) for items rated at 3.6kV/7.2kV (1,250A) and lower.
Rated short-circuit breaking current of 40kA with E2 class cannot be manufactured.
Withdrawable with door closed (type-M) is not compatible with mounting configuration class CW.
Fixed (type-L) is not compatible with the rated voltage 15kV, Bil95kV, and code B.
When selecting additional auxiliary switch and additional shunt tripping coil the control circuit plug configuration of code B should be applied.
Type
Rated voltage
VPR
Standard
Specifications
39
40
41
42