SDS-Operator Manual For Boiler Combustion Optimization and Automation - English
SDS-Operator Manual For Boiler Combustion Optimization and Automation - English
Catalog
1 GENERAL................................................................................................................................................................3
2 OPERATE DISPLAY EXAMPLE..................................................................................................................................3
3 INSPECTION AND SETTING WORK BEFORE PUTTING AUTO MODE INTO FUNCTION.................................................4
4 CONTROL SCHEME AND OPERATION DESCRIPTION.................................................................................................4
Operator
Manual
Combustion
for
Optimization
Boiler
and
Automation Scheme
1 General
PT. Sari Dumai Sejati DUMAI 2*16MW project equipped with 3 unit 130t/h CFB running in
main-steam pipe mode, the automation control ratio is low, the already function automation control of
feed water and desuperheater water is not so good, the whole combustion system isnt running in
automation mode. The function of combustion automation will be more economical and also been
able to protect from not-in-time manual operate and even mis-operation. The manual is to make sure
of the reliability and safety during the combustion automation commission work.
The boiler combustion automation loop including: feed water automation, desuperhater water
automation, induced air automation, primary air automation, secondary air automation, boiler bed
temperature automation, coal feeder automation, boiler pressure automation and coordination control.
When the color of manual operator is yellow force manual, only can manual operation
allowed, not allowed to put into auto mode.
When the color of manual operator is green manual, able to operate manual and allowed
to put into auto mode.
When the color of manual operator is purple : its in auto mode, manual change the output command
is not allowed, but switch to manual control is allowed.
Process value
Valve
feedback
Set point
Running mode
Valve output
Button
for
put
into
auto mode
Button
for
put
into
manual mode
4
Quickly increase/decrease
button
Graph 1
operate panel
Inspection and setting work before putting auto mode into function
Its suggested to switch to relative process control graph to make sure things like the controlled
parameter normal (no sudden change),device status be normal (no fault), still got space for manual
regulate before putting into auto mode. Operators may choose to put into auto mode after making sure all
the parameters are normal. Modify the set point according to requirements after putting into auto mode,
then system will automatically adjust the controller. If the adjusted parameters are over the setting limits,
the control loop will switch to manual control mode automatically and alarm, then operator should
accordingly adjust manually.
1
1)
Main feed water loop choose typical 3-element cascade PID controller, by adjusting feed water
control valve to control drum level. Control drum level by main controller, control feed-water flow by
vice controller, using the main steam flow as a feed-forward signal to directly fix feed-water flow.
Automation loop equips with switch on and cut condition, its not allowed to put into auto mode
when the required conditions are not meet. The automation mode will be cut when the control valve
fault, signal fault or the differential between set-point and drum level is high. When drum level is in
abnormal situation, fluctuation frequently and drum level high II or low II happens, its no need to
switch to manual mode, because the controller function direction is correct. Besides after you switch
to manual mode, you will adjust toward the same direction, so generally no need to switch to manual
mode at this particularly abnormal situation, unless its dangerous.
The purpose of main feed-water automation is to control drum level, including single-element
control and 3-element control. Only when the load (boiler main-steam flow) is >30% rated capacity
(40t/h), the main feed-water automation is allowed to put into function.
Before putting into auto mode, operators should manually adjust the drum level to be stable,
make sure main feed-water flow signal, main steam flow signal and drum level signal are normal (no
fault), then put bypass feed-water control valve into auto mode and change set-point.
2)
Control objective
Actuator:
and
feed-water
Steps
check if the control valve move smoothly or not, the deviation between valve output and feedback
<2.0%, the feedback better in range of 15%-75%, by adjust low capacity bypass to meet this
requirement , the deviation between drum level and set-point <30mm, otherwise manually
adjustment required. Operators may put it into auto mode after the drum level is normal, and
change the set-point.
4)
When in auto mode and any of blow conditions happens, the controller immediately switch to
manual mode and alarm.
1the deviation between control valve output and feedback >10%
2the deviation between drum level and set-point >60mm
3the deviation between feed-water flow and set-point >45t/h
4main-steam flow over limitnormally 30t/h< flow <150t/h, and change rate <30t/h
5feed-water flow over limitnormally 20t/h< flow <150t/h, and change rate <30t/h
6drum level over limitnormally -150mm< drum level <150mm, and change rate <30mm
2
1)
Desuperheater water loop use cascade PID controller, by adjusting desuperheater water valve to
control overheat outlet temperature. Using vice controller to control desuperheater water outlet
temperature (after water-spray temperature), using main controller to control overheat outlet
temperature.
Need to use main-steam flow , air flow signal to feed-forward control.
2)
Control objective
Actuator:
Control objective
steam temperature
and
main
temperature
and
3)
Steps
check if the control valve move smoothly or not, make sure the deviation between valve output
and feedback <2.0%, the valve is adjustable, the deviation between main steam temperature and setpoint <5, otherwise manually adjustment required. Operators may put it into auto mode when mainsteam temperature and main-steam flow is stable, and change the set-point.
4)
When in auto mode and any of blow conditions happen, the controller immediately switch to manual
mode and alarm.
1the deviation between control valve output and feedback>10%;
2the deviation between main steam temperature and set-point >60;
(3) the deviation between desuperheater outlet temperature(after water-spray) and set-point
>120;
4main steam temperature over limitnormally 150< temp <500, and change rate <2
5 desuperheater outlet temperature(after water-spray) over limit normally 150< temp
<500, and change rate <2
3
1)
Adjust induced air fan VFD by single-loop PID controller to maintain furnace negative pressure at
set-point. Meanwhile using primary air command and secondary air command as feed-forward
signal to fix IDF VFD output to avoid fluctuation.
2)
Control objective
Actuator:
and
Steps
check if the control valve move smoothly or not, make sure the dead-band area < 2.0%, the valve
is adjustable the deviation between negative pressure and set-point <30Pa, otherwise manually
adjustment required. Before put into auto mode, change the IDF VFD output safety range (automation
control output will not exceed these limits). Operators may change the set-point after put into auto
mode, and operators may also change the auto mode output limits to keep it at safety range.
4)
When in auto mode and any of blow conditions happen, the controller immediately switch to
manual mode and alarm.
1the deviation between IDF VFD output and feedback >10%
2the deviation between furnace negative pressure and set-point >300Pa
3 negative pressure signal over limit normally 700Pa< pressure signal <300Pa, and
change rate <300Pa
4
1)
Adjust SAF VFD by cascade PID controller using oxygen, total secondary air flow and total coal
flow signal. System will automatically calculate the required secondary air flow according to the
main-steam flow set-point, and using oxygen to fix secondary air flow. If coal increasing then will
increase secondary air flow, if coal decreasing then will decrease secondary air flow.
When negative pressure > 80Pa, temporary stop increasing the secondary air flow. When
negative pressure <-300Pa, temporary stop decreasing the secondary air flow. Cancel the temporary
stop adjusting limits until induced air automation have been adjust to normal range.
2)
Control objective
Actuator:
and
Steps
Before put into automation, SAF VFD output safety range should be set, and make sure the
feedback is in this safety range. After furnace negative pressure put into auto mode control, then put
secondary air and primary air into auto mode control. SAF VFD feedback range better at 15%----80%,
otherwise manually adjustment required. After put into automation, operators may change oxygen
set-point.
4)
5
1)
Adjust PAF VFD by cascade PID controller using boiler bed temperature, total primary air flow
and total coal flow signal. System will automatically calculate the required primary air flow according
to the load set-point, and using bed temperature to fix primary air flow. If coal increasing then will
increase primary air flow, if coal decreasing then will decrease primary air flow.
When negative pressure > 80Pa temporary stop increasing the primary air flow. When
negative pressure <-300Pa temporary stop decreasing the primary air flow. Cancel the temporary
stop adjusting limits until induced air automation have been adjust to normal range.
PA flow dynamic
set point
2) Control objective
Actuator:
PA flow set-point,
no need to change
and changed value
will not function.
and
Steps
Before put into automation, PAF VFD output safety range should be set, and make sure the
feedback is in this safety range. After furnace negative pressure put into auto mode control, then put
secondary air and primary air into auto mode control. PAF VFD feedback range better at 30%----80%,
otherwise manually adjustment required. After put into automation, no need to change the set-point.
4)
10
6
1)
Adjust total coal feeder manual operator by cascade PID controller using boiler load, boiler bed
temperature, drum pressure and coal feeder speed signals. Then use the total coal feeder manual
operator to automatically adjust the coal feeder that have been put into auto mode (at least 2 of 4),
meanwhile using oxygen deviation as a feed-forward signal to fix coal feeder output.
#1 coal feeder flow
Average
temperature
Bed
2)
Control objectivedirectly control the speed of coal feeder, indirectly control main-steam flow or bed
temperature
Actuator4 coal feeder
3)
Steps
Operators should make sure all the coal feeder running normally and manually adjust them to
11
stable condition, then put them into auto mode in sequence (at least 2 of 4 put into auto mode, better
4 of 4). The set-point of total coal quantity may change by operators in total coal manual operator,
then system will automatically increase or decrease the auto-mode coal feeder to make the actual
total coal quantity be equal with coal quantity set-point. The deviation between 4 coal feeder is
allowed, operators may switch the coal feeder to manual mode for adjusting and making the balance
and put it into auto mode again after adjusting properly (meet bed temperature average allocate). The
transfer between auto mode and manual mode is bump less at any time. Operators may switch any
single coal feeder to manual mode when the deviation is not normal and put into auto mode again
when the speed is manually change to normal range. There is no need to change the set-point of any
single coal feeder.
The total coal manual operator is allowed to put into auto mode only when more than 2 coal
feeders have been put into auto mode. The boiler will be running in automation after the total coal
manual operator been put into auto mode, fixed main-steam flow or fixed main-steam pressure mode
will be select-able. Operators may change the main-steam flow set-point or main-steam pressure setpoint after choose running mode. After choose control mode, modification and set-point are not
allowed at any single coal feeder manual operator and total coal manual operator. Operators should
change these values at coordination part.
4)
When in auto mode, any of the below 8 conditions happens, the controller immediately switch to
manual mode and alarm.
12
Coordination control
Total
coal
Group
1 data
Group
2 data
Group
3 data
Group
4 data
Group
5 data
Group
6 data
MODE
Total coal
quantityPID
Press PID
Bed Temp PID
CTRL
Group
7 data
PID
flowminute.
PID
Upside data of group 1: bed temperature change Steam
rate per
Decrease 0.5T coal to
avoid bed temperature increase sharply when the change rate is >0.01. Increase 0.5T coal to
avoid bed temperature decrease sharply when the change rate is <-0.01.
Downside data of group 2: steam product of 1T coal (weighted average value of past 8
hours)
2
Upper data of group 2predicted coal quantityautomatically calculate according to the coal
13
Upside data of group 5actual average bed temperaturedelete the maximum and
minimum data, choose the average value of the remain 4 values.
Downside data of group 5average bed temperature set-point. This value will not put into
function when the bed temperature is changing following the fixed main-steam flow or fixed
pressure mode, when its in following mode, the fluctuation range is 20.
Control mode: fixed main-steam pressure control mode and fixed main-steam flow control
mode switch button, choose proper control mode according to requirement during normally
14
function.
Main-steam temperaturedesuperheaterautomation
Coal automation
1)
2)
3)
4)
Only after induced air putting into automation, primary air and secondary air automation been
allowed.
Only after primary air or secondary air put into automation, total coal feeder automation (mainsteam flow or main-steam pressure control mode) been allowed.
Main feed-water automation, desuperheater water automation are independent, no influence with
other automation system.
Slag quantity is very low and not frequently desalg, so its no meaning to put bed pressure into automation
control.
Reference graph
15