ATS (Automatic Trasfer Switch) : 2 Positions (A B)
ATS (Automatic Trasfer Switch) : 2 Positions (A B)
ATS (Automatic Trasfer Switch) : 2 Positions (A B)
Method Back - -
Type 61WN 62WN 64WN 66WN 68WN 610WN 612WN 616WN 620WN 625WN 630WN
AC33B 100 200 400 600 800 1000 1200 1600 2000 2500 3000
Rated Current (In) A
AC31B 150 300 600 800 1000 1200 1400 1800 2500 3000 3500
Rated voltage (Ue) V AC600, DC125 AC600, DC125 AC600, DC125 AC600, DC125 AC600, DC125 AC600, DC125 AC600, DC125 AC600, DC125 AC600, DC125 AC600, DC125 AC600, DC125
Poles P 2, 3, 4 2, 3, 4 2, 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4
Throw T Double Throw Double Throw Double Throw Double Throw Double Throw Double Throw Double Throw Double Throw Double Throw Double Throw Double Throw
Connection Front - - -
Method Back
- Saving power :
It is in an instantaneous excitation mode with little operating current
(1.6A in case of AC 220V operation)
- Safe Design :
The breaking part is molded for a dust-proof so the operational cycle
of the contact part is semi-permanent.
- 2-Coil Mode :
It adopted a simple operation mode using 2 coils
- Miniature :
It can be built inside the portable generator or UPS
- Low Cost :
It is a miniature type and it is optimal for a single phase with less than 200A (non-inductive)
- Applied Standard :
IEC 60947-6-1 / UL1008
Poles P 2
Performance
Transfer Sequence AB
H 165 176
W 127 151
D 100 121
Method Back
Performance
Short Time Current(1sec) kA 5 10 12 15 22 25 35 50
Short Circuit Peak Current kA 12.5 25 30 37.5 50 55 60 80
Switch Capacity Class AC33B AC33B AC33B AC33B AC33B AC33B AC33B AC33B
Electrical Times 50,000 50,000 50,000 10,000 10,000 10,000 5,000 5,000
Operational Cycle
Mechanical Times 250,000 250,000 250,000 50,000 50,000 50,000 10,000 10,000
Transfer Sequence A B, A Neutral (off) B, A Overlapping (overlapping) B
Conditions of uninterruptible transfer Phase difference : Within electrical angle 10, Frequency difference : Within 0.2Hz , Voltage : Voltage difference with the commercial one is within 5% , Instantaneous Interconnection Time : Within 0.05 second
closing msec 55 55 60 100 115 115 180 140
Apower
Opera- trip msec 20 20 25 30 30 30 30 35
tion Time closing msec 80 80 90 135 145 150 220 190
Bpower
trip msec 20 20 25 30 30 30 30 35
Operating Voltage & Current 2P 3P 4P 2P 3P 4P 2P 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P
DC110V A 4 4 5 5 5 7 6.4 6.4 9 7 8 8 10 10 13 13 16 16 18
Closing AC100/110V A 4 4 5 5 5 7 6.4 6.4 9 7 8 8 10 10 13 13 16 16 18
AC200/220V A 2 2 2.5 2.5 2.5 3.6 3.2 3.2 4.5 3.5 4 4 5 5 6.5 6.5 8 8 9
AC/DC110V A 1.4 1.4 2 2 2 2 4 4
Trip
AC220V A 0.7 0.7 1 1 1 1 2 2
External Size & Weight
H 268 268 268 283 283 283 307 307 307 545 545 609 609 645 645 - - - -
Front Size(mm) W 211 241 271 241 286 331 293 353 413 465 530 510 590 570 670 - - - -
D 112 112 112 112 112 132 132 132 220 220 220 220 220 220 - - - -
Front kg 6.5 8 10 8 10 12 14 17 21 53 61 66 76 72 84
Weight
Back kg 6.5 8 10 8 10 12 14 17 21 43 52 5043 61 57 69 130 150 165 205
Other Detailed Info
Circuit diagram A6-23 A6-23 A6-23 A6-23
Drawing A6-36 A6-36 A6-37 A6-37 A6-38
Precautions A6-20 A6-20 A6-20 A6-20