Installation Data
Installation Data
Installation Data
Page 1
DAT’Air Installation Data
2.4 Air Distribution
2.5 Room Characteristics
Air treated by HIROTEC DAT’AIR
conditioners is used to condition the The ceiling, walls and floor of the
environment, in which the unit is room should have a vapor barrier to
operating after having passed prevent the ingress or egress of
through the floor plenum (Under moisture between the room and
unit) or a distribution duct (Over unit) outside.
which forms the supply plenum.
Installations and
Ducting must be designed in the
Connections
proper way to allow adequate airflow
to the unit and provide optimal
working operation. For this reason,
3.1 Installation Clearance
duct pressure drop should not
exceed the available static pressure
given by the fans (in the case of Clearances indicated in the unit’s
particular applications please dimensional drawings must be
consult our Technical Department). complied with.
Page 2
DAT’Air Installation Data
Pipe diametres can be seen in Table
3.2 Connection to Remote 3.1 depending on the unit size and
Aircooled Condensers length of run. Further information on
pipe sizes can be obtained by
The route between the HIROTEC contacting our Technical
DAT’AIR unit and the air cooled Department.
condenser should not exceed 25-30
metres (equivalent length), if Note: air cooled units are
necessary call our Technical shipped with a 3 bar precharge
Department or use water cooled of nitrogen
models where long pipe runs are
required. Table 3.1 Refrigeration Lines
(*EDA version) (‘)
All refrigeration piping should be
installed by a qualified Refrigeration Model Hot Gas Liquid
Technician in accordance with good 50 16 12
refrigeration practice and Local
Regulations. 80 16 12
100 16 12
The route should be the shortest 110 16 12
possible to reduce the quantity of
freon in circulation and system 140 18 12
pressure drops. If copper pipes have 150 18 12
to cross over electrical cables it is
170 18 12
advisable to insulate between the
two. 180 18 12
230 18 12
Pipe insulation, unless otherwise
required by the Customer, can be 235 18 12
limited to the following locations; 260 22 16
350 22 16
a) Hot gas and liquid lines that run
in the raised floor cavity of the 440 28 16
facility. 520 28 16
550 28 16
b) Hot gas lines that are exposed to
low ambient temperatures 280 18 12
(available on request). 360 18 12
460 18 12
The maximum difference in height of
10 metres from the HIROTEC 13V 18 12
DAT’AIR to the air cooled 15V 22 16
condenser(s) is recommended.
20V 22 16
On rising vertical hot gas pipes, 26V 28 16
traps or syphons should be fitted 30V 28 16
every 6 metres to allow oil
(‘) valid for lenths up to 30 m (equivalent
circulation in the system. On
length).
horizontal hot gas discharge
pipelines a minimum 1% slope (in
flow direction) should be installed to
achieve oil return to the compressor.
Page 3
DAT’Air Installation Data
MODULAR
Model
100 140 180 230 235 260 350 440 520 550
O/UEDA
Hot Gas Line
18 18 18 18 18 22 22 22 22
O.D. Copper (mm) 22
Liquid Line
12 12 12 12 12 16 16 16 16
O.D. Copper (mm) 16
BIGDAT UNITS
Model
280 360 460 13V 15V 20V 26V 30V
O/UEDA
Discharge Line
2×18 2×18 2×18 2x22 2×22 2×22 2×22 2×22
O.D. Copper (mm)
Liquid Line
2×12 2×12 2×12 2x16 2×16 2×16 2×16 2×16
O.D. Copper (mm)
Page 4
DAT’Air Installation Data
Page 5
DAT’Air Installation Data
Page 6
DAT’Air Installation Data
i Metal mesh filter (in the inlet Supply voltage should not be
pipe) with a maximum mesh of 1 subject to variations greater than
mm, to protect the heat +5% and the unbalance between
exchanger from waste or phases should always be lower than
impurities present in the pipes. 2%.
i Air valves, located at the highest If this is not the case, contact our
point of the water circuit, to allow Technical Department to decide
bleeding of air from the system. upon the most appropriate
protection.
i Automatic filling valves to
maintain system pressure and to Electrical connections should be
compensate for thermal carried out following the instructions
expansion. given on the wiring diagram supplied
with the unit.
i Drain cock, and where
necessary, a drainage tank to Earthing is compulsory by law. The
empty the unit for maintenance. installer shall connect the earth
cable to the earth bar on the
3.4 Electrical Power and electrical panel.
Earthing Power for the control circuit is from
the main line through a transformer
located in the electric panel.
3.4.1 General
The control circuit is protected by a
i Check visually that the electrical circuit breaker.
circuits have not been damaged
during transportation. Wiring diagrams are attached to the
equipment inside the electric panel.
i Check that the screws on all The power cable has to be
various terminals are well connected to the input terminals.
secured.
Page 7
DAT’Air Installation Data
3.4.2 Alarm and External HIROTEC DAT’AIR units are
Connections designed to work properly over a
wide operating range, it is highly
In the terminal block. there is a recommended not to exceed these
voltage free contact for a general operating limits, room temperature,
alarm. outdoor air and water temperatures.
For a remote ON-OFF of the unit, If this situation should occur the unit
connect the external switch to may stop due to safety devices In
contacts indicated in the wiring the worst case, it may fail. These
diagram. limits are reported in Table 1. If
there is need to exceed these limits,
N.B: The external switch disables please contact our Technical
the ON-OFF control on the small Department.
front panel of the unit.
Refrigerant Relief Valve
When carrying out the connections
described, follow exactly the Each (Direct Expansion) unit is fitted
instructions given in the wiring with a relief valve on the liquid line in
diagram. order to reduce the risk of damage
to the system in the event of high
system pressure.
Operating Limits
Air Cooled
Min Max Min Max
Room inlet 18 30 Condenser Inlet air temperature °C 15 40
air temperature °C
Water Cooled
Min Max Min Max
Room inlet 18 30 Condenser inlet water 19 47
air temperature °C temperature °C
Outlet water temperature °C 27 50
Water thermal difference °C (‘) 3 8
(‘) Water thermal difference must always guarantee water inlet-outlet operation limit
Weight percentage % 10 20 30 40 50
Freezing point °C -4.8 -9.9 -17.2 -26.6 -38.3
Page 8