Delta VFD c2000 Simplified Manual
Delta VFD c2000 Simplified Manual
Simplified Manual
C US
CE Mark UL/cUL
UNPACKING ................................................................................................................................................................3
WIRING.........................................................................................................................................................................6
ACCESSORIES..........................................................................................................................................................20
SPECIFICATIONS ......................................................................................................................................................33
WARNING CODES.....................................................................................................................................................44
; Never connect the AC motor drive output terminals U/T1, V/T2 and W/T3 directly to the
AC mains circuit power supply.
CAU TION
; Only qualified persons are allowed to install, wire and maintain the AC motor drives.
; Even if the 3-phase AC motor is stop, a charge may still remain in the main circuit
terminals of the AC motor drive with hazardous voltages.
NOTE
The content of this manual may be revised without prior notice. Please consult our distributors or download the most updated
version at http://www.delta.com.tw/industrialautomation
Receiving
After receiving the AC motor drive, please check for the following:
1. Please inspect the unit to assure it was not damaged during shipment after unpacking.
2. Make sure that the part number printed on the package corresponds with the part number
indicated on the nameplate.
3. Make sure that the voltage for the wiring lie within the range as indicated on the nameplate.
5. Before applying the power, please make sure that all the devices, including power, motor,
control board and digital keypad, are connected correctly.
6. When wiring the AC motor drive, please make sure that the wiring of input terminals “R/L1,
S/L2, T/L3” and output terminals ”U/T1, V/T2, W/T3” are correct to prevent drive damage.
7. After applying the power, it can select languages and set the parameter groups by the digital
keypad (KPC-CC01).
8. After applying the power, please trial run with the low speed and then increase the speed
gradually to the desired speed.
Nameplate Information
1
Model Name
VF D 007 C 43 A
Ver sion type
Input voltage
23:230V 3-PHASE
43:460V 3-PHASE
C2000 series
Applicable motor capacity
007:1HP(0.75kW) ~ 1K1:150HP( 110kW)
Refer to the s pec ifications for details
Seri es name(Var iable F requency Dr ive)
Serial Number
007V43A0 T 9 30 0002
Pr oduction number
Pr oduction week
Pr oduction year
T: Tauy uan W: Wujian
S: S hanghai Pr oduction factor y
460 V 3-P HASE 1HP(0.7 5kW )
Model number
2
Unpacking
The AC motor drive should be kept in the shipping carton or crate before installation. In order to
retain the warranty coverage, the AC motor drive should be stored properly when it is not to be
used for an extended period of time.
For frame D and E models, it is packed in the crate. Please unpack by the following steps.
Frame D Frame E
Loosen all the cover screws to open the Loosen all the screws on the 4 iron plates at the
crate. (total is 12 screws) four bottom corners of the crate with 4 screws on
each iron plate.
Remove the EPEs and manual. Remove the crate cover, EPEs and manual.
3
Frame D Frame E
Lifting the drive by hooking the lifting hole as Loosen 8 screws fastened on the pallet as shown
shown in the following figure. in the following figure.
D E
4
Frame D Frame E
Make sure that the lifting hook is set as Ensure that the angle between the lifting hole and
shown in the following diagram. lifting device is within the specification as shown
in the following diagram.
Weights
VFDXXXXCXXA
D 37.6 kg(82.9 Ibs.) VFDXXXXCXXE
D 40 kg(88.2 Ibs.)
5
Wiring
Wiring d iagram for DC choke
Frame A, Frame B, Frame C (optional) Br ak e res istor
J umper
(optional)
6
Wiring diagram for frame D and above
7
Figure 1
Input power terminals for frame G and H
fuse or NFB(no fuse breaker)
L1
R1
L2
S1
L3
T1
L12
R2
L22
S2
L32
T2
Figure 2 Wiring diagram for AFE connected in parallel
AC r eactor Activ e F ront End AC motor driv e
IM/PM
R(L1) R(L1)DC+ +1/DC+
S( L2) S( L2) DC- -/DC- Motor
T (L3) T (L3)
AF E VF D
AC r eactor
R(L1)DC+
S( L2) DC-
T (L3)
AF E
Activ e F ront End
R(L1)DC+
S( L2) DC-
T (L3)
Regener ator
Figure 2 and 3 are for the option accessory-Active Front End (AFE)
8
Figure 4
Wiring for SINK (NPN)/SOURCE (PNP) mode
1 Sink Mode 2 Sourc e Mode
with internal power (+24VDC ) w ith internal power (+24VD C)
MI1 MI1
MI2 MI2
~
~
MI8 MI8
+2 4V DCM
COM COM
MI1 MI1
MI2 MI2
~
MI8 MI8
+2 4V +2 4V
COM COM
DCM DCM
external power +24V internal c irc ui t internal c irc ui t
external pow er +24V
9
Main Circuit Terminals
Figure 1
For frame A~C Br ak e res istor
(optional)
* Provide both 1-phase and 3- phase
J umper
input power
F us e/NF B(No F use B reaker) - +2 +1 B1 B2
R(L1) U(T 1)
R(L1) Motor
S(L2)
IM
S( L2) V( T2) 3~
T(L3) W(T 3)
T(L3)
DC choke
For frame A~C (optional) Br ak e r es istor
(optional)
* Provide both 1-phase and 3- phase J umper
input power
F us e/NF B(No F use B reaker) - +2 +1 B1 B2
R(L1) U(T 1)
R(L1) Motor
S(L2)
IM
S(L2) V(T2) 3~
T(L3) W(T 3)
T(L3)
Figure 2
10
Figure 3
For frame G and f rame H
* Provide both 1-phase and 3-phase
input power
Fuse/NFB(No Fuse Breaker)
L1 +1/DC+ -/DC-
R1 Motor
U(T 1)
L2
S1 V(T2) IM
L3 3~
T1 W(T 3)
R2 L12
L22
S2
L32
T2
Terminals Descriptions
R/L1, S/L2, T/L3 AC line input terminals (1-phase/3-phase)
U/T1, V/T2, W/T3 AC drive output terminals for connecting 3-phase induction motor
Connections for DC reactor to improve the power factor. It needs to
remove the jumper for installation.
+1, +2
(for 230V models: ≧30kW, built-in DC reactor)
(for 460V models: ≧37kW, built-in DC reactor)
B1, B2 Connections for brake resistor (optional)
Connections for brake unit (VFDB series)
+, - (for 230V models: ≦22kW, built-in brake unit)
(for 460V models: ≦30kW, built-in brake unit)
E Earth connection, please comply with local regulations.
11
; Please use the shield wire or tube for the power wiring and ground
the two ends of the shield wire or tube.
; Do NOT run/stop AC motor drives by turning the power ON/OFF.
Run/stop AC motor drives by RUN/STOP command via control
terminals or keypad. If you still need to run/stop AC motor drives by
turning power ON/OFF, it is recommended to do so only ONCE per
hour.
Output terminals for main circuit
+1 +2
; Connect a brake resistor or brake unit in applications with frequent
deceleration ramps, short deceleration time, too low brake torque
or requiring increased brake torque.
Brak e re sistor
(optional)
Brak e re sistor
(optional) BR
Brak e un it
VFDB (o ption al)
B1 B2 + -
12
; When the terminals +1, +2 and - are not used, please leave the
terminals open.
; DO NOT connect [+1, -], [+2, -], [+1/DC+, -/DC-] or brake resistor
directly to prevent drive damage.
13
Frame C Main circuit terminals:
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, , B1, B2, +1, +2, -
Frame D
Main circuit terminals:
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, , DC+, DC-
14
Frame E
Main circuit terminals:
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, , +1/DC+, -/DC-
Figure 1 Figure 2
17.0MAX. E
+0
16-4
31MAX.
28.0MAX.
70MAX.
8.2M I
N.
65.0MAX.
8 .2 M I N
.
26.5MAX.
Figure 3
15
Control Terminals
0- 10V
0- 10V 0- 10V 0- 20mA O pen
RC 2 RB2 R A2 RC 1 RB1 RA1
AFM 1 AFM 2 AVI ACI 485
- 10- 10V
0- 20mA 0- 20mA 0- 10V 120
Notes:
; Please place the wire into the wiring hole and tighten the wire with the slot type
screwdriver. It needs to leave 7mm at the wiring end for the optimal wiring. Please be
careful for using the wiring without terminal block and put the wires into the wiring hole in
order.
; The factory setting is SINK mode (NPN) and +24V-COM is short circuit. Refer to chapter
wiring (figure 4) for details.
16
Terminals Terminal Function Factory Setting (NPN mode)
MI7 Multi-function input 7
MI8 Multi-function input 8
Digital frequency meter Regard the pulse voltage as the output monitor
DFM signal
DFM
Duty-cycle: 50%
DCM Min. load impedance: 1kΩ/100pf
Digital frequency signal Max. current: 30mA
DCM Max. voltage: 30Vdc
common
MO1
Multi-function Output 2
MO2 MO2
(photocoupler)
MCM
Multi-function Output Max 48Vdc 50mA
MCM
Common
+10V Potentiometer power supply +10Vdc 20mA
-10V Potentiometer power supply -10Vdc 20mA
Impedance: 20kΩ
Range: 4 ~ 20mA/0~10V =0~Max. Output
AVI Analog voltage input
Frequency (Pr.01-00)
AVI switch, factory setting is 0~10V
17
Terminals Terminal Function Factory Setting (NPN mode)
+10V AVI circuit
AVI
ACM
internal circuit
18
Analog input terminals (AVI, ACI, AUI, ACM)
; Analog input signals are easily affected by external noise. Use shielded wiring and keep
it as short as possible (<20m) with proper grounding. If the noise is inductive, connecting
the shield to terminal ACM can bring improvement.
; If the analog input signals are affected by noise from the AC motor drive, please connect
a capacitor and ferrite core as indicated in the following diagram.
AVI/ACI/AUI
C
ACM
ferrite core
wind each wires 3 times or more around the core
Digital inputs (FWD, REV, MI1~MI8, COM)
; When using contacts or switches to control the digital inputs, please use high quality
components to avoid contact bounce.
19
Accessories
Following are the accessories that users are able to purchase or inquire your dealer for the suitable
specification and model to improve the efficiency of the drive.
All Brake Resistors & Brake Units Used in AC Motor Drives
230V series
Applicable
*1 125% Brake Torque 10%ED *2 Max. Brake Torque
Motor
Brake Unit Equivalent Brake Resistor
Brake Min. Max. Max.
Resistor Value
HP kW *3 Model Current Brake Brake Peak
VFDB Quantity for Each AC Quantity
Name (A) Resistor Resistor Power
Motor Drive
1 0.7 80W200Ω BR080W200 1 1.9 63.3 6 2.3
2 1.5 200W91Ω BR200W091 1 4.2 47.5 8 3.0
3 2.2 300W70Ω BR300W070 1 5.4 38.0 10 3.8
5 3.7 400W40Ω BR400W040 1 9.5 19.0 20 7.6
7.5 5.5 1000W20Ω BR1K0W020 1 19 14.6 26 9.9
10 7.5 1000W20Ω BR1K0W020 1 19 14.6 26 9.9
15 11 1500W13Ω BR1K5W013 1 29 13.6 28 10.6
20 15 2000W8.6Ω BR1K0W4P3 2 44 8.3 46 17.5
25 18 2000W8.6Ω BR1K0W4P3 2 44 8.3 46 17.5
30 22 3000W6.6Ω BR1K5W3P3 2 58 5.8 66 25.1
40 30 2015 2 4000W5.1Ω BR1K0W5P1 4 75 4.8 80 30.4
50 37 2022 2 4800W3.9Ω BR1K2W3P9 4 97 3.2 120 45.6
60 45 2022 2 6000W3.3Ω BR1K5W3P3 4 118 3.2 120 45.6
75 55 2022 3 7200W2.6Ω BR1K2W3P9 6 145 2.1 180 68.4
100 75 2022 4 9600W2Ω BR1K2W3P9 8 190 1.6 240 91.2
460V series
Applicable
*1 125% Brake Torque 10%ED *2 Max. Brake Torque
Motor
Brake Unit Equivalent Brake Resistor Min. Max. Max.
Resistor Value Brake
HP kW Brake Brake Peak
for Each AC Current (A)
VFDB Qty. Model Name Qty. Resistor Resistor Power
Motor Drive
1 0.7 80W750Ω BR080W750 1 1 190.0 4 3.0
2 1.5 200W360Ω BR200W360 1 2.1 126.7 6 4.6
3 2.2 300W250Ω BR300W250 1 3 108.6 7 5.3
5 3.7 400W150Ω BR400W150 1 5.1 84.4 9 6.8
5 4.0
1000W75Ω BR1K0W075 1 10.2 54.3 14 10.6
7.5 5.5
10 7.5 1000W75Ω BR1K0W075 1 10.2 47.5 16 12.2
15 11 1500W43Ω BR1K5W043 1 17.6 42.2 18 13.7
20 15 2000W32Ω BR1K0W016 2 24 26.2 29 22.0
25 18 2000W32Ω BR1K0W016 2 24 23.0 33 25.1
30 22 3000W26Ω BR1K5W013 2 29 23.0 33 25.1
40 30 4000W16Ω BR1K0W016 4 47.5 14.1 54 41.0
50 40 4045 1 4800W15Ω BR1K2W015 4 50 12.7 60 45.6
60 45 4045 1 6000W13Ω BR1K5W013 4 59 12.7 60 45.6
75 55 4030 2 7200W10Ω BR1K2W015 6 76 9.5 80 60.8
100 75 4045 2 9600W7.5Ω BR1K2W015 8 100 6.3 120 91.2
125 90 4045 2 12000W6.5Ω BR1K5W013 8 117 6.3 120 91.2
150 110 4045 3 15000W5.2Ω BR1K5W013 10 145 4.2 180 136.8
20
*1 Calculation of 125% brake torque: (kw)*125%*0.8 (0.8 is the motor efficiency)
Because of the limit of power consumption of resistor, the longest working time of 10%ED is 10sec(on:
10sec/ off: 90sec)
*2 See the curve diagram of brake performance for the relation of duty-cycle value ED and brake current.
*3 The resistors under 400W need to set on the rack with the surface temperature less than 250℃. For
the resistors more than 1000W, the surface temperature must be less than 350℃.
NOTE
1. Definition for Brake Usage ED%
Explanation: The definition of the brake usage ED(%) is for assurance of enough time for the brake
unit and brake resistor to dissipate away heat generated by braking. When the brake resistor heats up,
the resistance would increase with temperature, and brake torque would decrease accordingly.
Suggested cycle time is one minute
10 0%
3. If damage to the drive or other equipment are due to the fact that the brake resistors and the brake
modules in use are not provided by Delta, the warranty will be void.
4. Take into consideration the safety of the environment when installing the brake resistors.
5. If the minimum resistance value is to be utilized, consult local dealers for the calculation of the Watt
figures.
6. When using more than 2 brake units, equivalent resistor value of parallel brake unit can’t be less than
the value in the column “Equivalent Resistor Value for Each AC Drive”. When using the brake unit,
please read the wiring information in the user manual of brake unit thoroughly prior to taking into
operation.
7. This table shows the recommended value for the common applications. For those applications with
frequent brake, it is recommended to use Watt values with 2 to 3 times of recommended values.
21
No-fuse Circuit Breaker Chart
Per UL 508, paragraph 45.8.4, part a,
For 3-phase drives, the current rating of the breaker shall be within 2-4 times drive input rated
current.
22
Fuse Specification Chart
Smaller fuses than those shown in the table are permitted.
23
AC Reactor
230V, 50/60Hz, 3-Phase
Inductance mh)
Max. continuous
kW HP Fundamental Amps 3~5% impedance
Amps
3% impedance 5% impedance
0.75 1 4 6 3 6.5
1.5 2 8 12 1.5 3
2.2 3 12 18 1.25 2.5
3.7 5 18 27 0.8 1.5
5.5 7.5 25 37.5 0.5 1.2
7.5 10 35 52.5 0.4 0.8
11 15 45 67.5 0.3 0.7
15 20 55 82.5 0.25 0.5
18.5 25 80 120 0.2 0.4
22 30 100 150 0.15 0.3
30 40 130 195 0.1 0.2
37 50 160 240 0.075 0.15
45 60 200 300 0.055 0.110
55 75 250 375 0.090 0.150
75 100 320 480 0.040 0.075
24
Zero Phase Reactor
RF220X00A UNIT: mm(inch)
Cable Recommended
Wire Size (mm2) Diagram A
Wiring
Type Qty. Please wind each wire 4 times around the core.
Nominal Method
(Note) AWG mm
2 The reactor must be put at inverter output as
(mm2) close as possible.
Diagram Zero Phase Reactor
≤10 ≤5.3 ≤5.5 1
Single- A R/L1 U/T1
Power
core Diagram Supply
S/L2 V/T2 MOTOR
≤2 ≤33.6 ≤38 4 T/L3 W/T3
B
Diagram
≤12 ≤3.3 ≤3.5 1
Three- A
core Diagram
≤1 ≤42.4 ≤50 4
B
25
DC Reactor
EMI Filter
AC Motor Filter Model Input Cable Length C2 Cable Length C1
Drive Name Current 2kHz 8kHz 15/10/9kHz 2kHz 8kHz 15/10/9kHz
VFD037C23A KMF325A 20A 50m 50m 50m × × ×
VFD110C23A KMF370A 59A 50m 50m 50m 50m × ×
VFD220C23A KMF3100A 99A 50m 50m 50m × × ×
KMF3150A
VFD370C23A 150A 50m × × × × ×
MIF3150
VFD750C23A MIF3400A 225A 50m 50m 50m × × ×
VFD055C43A KMF318A 17A 50m 50m 50m × × ×
VFD150C43A KMF350A 44A 50m 50m 50m × × ×
VFD300C43A KMF370A 63A 50m 50m 50m × × ×
VFD750C43A MIF3150 150A 50m 50m 50m × × ×
VFD1100C43A KMF3400B 220A 50m 50m 50m × × ×
26
Option Cards
Following are optional cards used to enhance drive’s performance. Please choose by your
requirement or consult our distributors if there is any question.
1 RJ45(female) for digital keypad
KPV-CC01
1
KPV-CE01
3 Slot 3 2 Communication extension card (Slot 1)
CMC-MOD01
2 CMC-PD01
4 Slot 2 Slot 1
CMC-DN01
EMC-COP01
CMC-EIP01
3 I/O card & Relay card (Slot 3)
EMC-D42A
EMC-R6AA
EMC-D611A
4 PG cards (Slot 2)
EMC-PG01L
EMC-PG01O
EMC-D42A
I/O extension Terminals Descriptions
card Common for Multi-function input terminals
COM Common for digital control signals
SINK (NPN)/SOURCE (PNP)
Refer to parameters 02-26~02-29 to program the
multi-function inputs MI10~MI13.
MI10 Internal power is applied from terminal E24: +24Vdc±5%
MI11 200mA, 5W
MI12 External power +24VDC: max. voltage 30VDC, min. voltage
19VDC, 30W
MI13 ON: the activation current is 6.5mA
OFF: leakage current tolerance is 10μA
Multi-function output terminals (photocoupler)
Duty-cycle: 50%
MO10
Max. output frequency: 100Hz
MO11
Max. current: 50mA
Max. voltage: 48VDC
27
Common for multi-function output terminals MO10,
MO11(photocoupler)
MXM
Max 48VDC 50mA
EMC-D611A
Terminals Descriptions
Common for Multi-function input terminals
COM Common for digital control signals
SINK (NPN)/SOURCE (PNP)
Refer to parameters 02-26~02-31 to program the
MI10
multi-function inputs MI10~MI13.
MI11 Internal power is applied from terminal E24: +24Vdc±5%
MI12 200mA, 5W
MI13 External power +24VDC: max. voltage 30VDC, min. voltage
19VDC, 30W
I/O extension MI14 ON: the activation current is 6.5mA
card MI15 OFF: leakage current tolerance is 10μA
Multi-function output terminals (photocoupler)
Duty-cycle: 50%
MO10
Max. output frequency: 100Hz
MO11
Max. current: 50mA
Max. voltage: 48VDC
Common for multi-function output terminals MO10,
MO11(photocoupler)
MXM
Max 48VDC 50mA
EMC-R6AA
Terminals Descriptions
Resistive load:
5A(N.O.)/3A(N.C.) 250VAC
5A(N.O.)/3A(N.C.) 30VDC
Relay card R10A~R15A Inductive load (COS 0.4):
R10C~R15C 2.0A(N.O.)/1.2A(N.C.) 250VAC
2.0A(N.O.)/1.2A(N.C.) 30VDC
It is used to output each monitor signal, such as drive is in
operation, frequency attained or overload indication.
EMC-PG01L
PG card Terminals Descriptions
28
Output voltage for power: +5V/+12V±5% (use FSW3 to
VP switch +5V/+12V)
Max. output current: 200mA
PG1 DCM Common for power and signal
Input signal. Input type is selected by ABZ1. It can be
A1, /A1, B1,
1-phase or 2-phase input. Max. output frequency:
/B1, Z1, /Z1
300kP/sec
Input signal. Input type is selected by AB2. It can be
A2, /A2,
PG2 1-phase or 2-phase input. Max. output frequency:
B2, /B2
300kP/sec.
Output signal. It has division frequency function. Max.
output voltage for Line driver: 5VDC
PG OUT A/O, B/O, C/O
Max. output current: 50mA
Max. output frequency: 300kP/sec
EMC-PG01O
Terminals Descriptions
Output voltage for power: +5V/+12V±5% (use FSW3 to
VP switch +5V/+12V)
Max. output current: 200mA
PG1
DCM Common for power and signal
A1, /A1, B1, Input signal. Input type is selected by ABZ1. It can be
/B1, Z1, /Z1 1-phase or 2-phase input. Max. output frequency: 300kP/sec
A2, /A2, Input signal. Input type is selected by AB2. It can be 1-phase
PG2
B2, /B2 or 2-phase input. Max. output frequency: 300kP/sec
PG card
V+ External power
Output voltage for power: +5V ~ +20V
V-
Max. output current: 50mA
Output signal. It has division frequency function.
PG OUT
Input signal of open collector. Please add a pull-high resistor
A/O, B/O, C/O on the external power V+~V- (e.g. power of PLC) to prevent
the interference of the receiving signal.
Max. output frequency: 300kP/sec
CMC-MOD01
Interface RJ-45 with Auto MDI/MDIX
Number of Port 1 Port
Transmission Method IEEE 802.3, IEEE 802.3u
Communication Cable Category 5e shielding 100M
Communication Speed 10/100 Mbps Auto-Detect
29
ICMP, IP, TCP, UDP, DHCP, SMTP, MODBUS OVER TCP/IP, Delta
Network Protocol
Configuration
CMC-PN01
Data Type Periodic data switch
Module Model CMC-PD01
GSD Document DELTA08DB.GSD
Product ID 08DB(HEX)
Serial Communication Support 9.6kbps, 19.2kbps, 93.75kbps, 187.5kbps, 500kbps,
Speed (auto detection) 1.5Mbps, 3Mbps, 6Mbps, 12Mbps (bits/sec)
CMC-DN01
Connector 5-pin pluggable connector (pin interval: 5.08mm)
Transmission Method CAN
Transmission Cable Shielded twisted pair with 2-wire bus power cable and drain
Transmission Rate 125kbps, 250kbps, 500kbps and extension serial transmission rate
Network Protocol DeviceNet protocol
CMC-EIP01
Interface RJ-45 with Auto MDI/MDIX
Number of Port 1 Port
Transmission Method IEEE 802.3, IEEE 802.3u
Communication Cable Category 5e shielding 100M
Communication Speed 10/100 Mbps Auto-Detect
Network Protocol ICMP, IP, TCP, UDP, DHCP, SMTP, EtherNet/IP, Delta Configuration
30
CMC-COP01
Interface RJ-45
Number of Port 1 Port
Transmission Method CAN
Communication Cable Standard CAN cable
Communication Speed 1M 500k, 250k, 100k, 50k
Network Protocol CANopen protocol
CANopen communication cable
L
Title Part No.
mm inch
1 TAP-CB03 500 ± 10 19 ± 0.4
2 TAP-CB04 1000± 10 39 ± 0.4
31
32
Specifications
230V Series
Frame Size A B C D E
Model Number
007 015 022 037 055 075 110 150 185 220 300 370 450 550 750
VFD-_ _ C_ _
Max. Applicable Motor Output
0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75
(kW)
Max. Applicable Motor Output
1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100
(hp)
Rated Output Capacity
1.9 2.8 4.0 6.4 9.6 12 19 25 28 34 45 55 68 81 96
(kVA)
HEAVY DUTY
300.00Hz
(Hz)
Carrier Frequency (kHz) 2~6kHz
Rated Output Capacity
2.0 3.2 4.4 6.8 10 13 20 26 30 36 48 58 72 86 102
NORMAL DUTY
(kVA)
Rated Output Current
5 8 11 17 25 33 49 65 75 90 120 146 180 215 255
(A)
Overload Endurance 120% of rated current for 1 minute, 160% of rated current for 3 seconds
Max. Output Frequency
600.00kHz (45kW: 400.00Hz)
(Hz)
Carrier Frequency (kHz) 2~15kHz 2~10kHz 2~9kHz
Input Current (A) Heavy
6.1 11 15 18.5 26 34 50 68 78 95 118 136 162 196 233
Duty
Input Rating
33
460V Series
Frame Size A B C
Model Number VFD-_ _ C 007 015 022 037 040 055 075 110 150 185 220 300
Max. Applicable Motor Output
0.75 1.5 2.2 3.7 4.0 5.5 7.5 11 15 18.5 22 30
(kW)
Max. Applicable Motor Output
1 2 3 5 5 7.5 10 15 20 25 30 40
(hp)
Rated Output
2.3 3.0 4.5 6.5 7.6 9.6 14 18 24 29 34 45
Capacity(kVA)
HEAVY DUTY
Carrier Frequency
2~6kHz
(kHz)
Rated Output Capacity
2.4 3.2 4.8 7.2 8.4 10 14 19 25 30 36 48
(kVA)
NORMAL DUTY
34
460V Series - continue
Frame Size D E *F *G *H
Model Number VFD-_ _ C 370 450 550 750 900 1100 1320 1600 1850 2200 2800 3150 3550
Max. Applicable Motor
37 45 55 75 90 110 132 160 185 220 280 315 355
Output (kW)
Max. Applicable Motor
50 60 75 100 125 150 175 215 250 300 375 425 475
Output (hp)
Rated Output
55 69 84 114 136 167 197 235 280 348 417 466 517
Capacity(kVA)
Rated Output
HEAVY DUTY
69 86 105 143 171 209 247 295 352 437 523 585 649
Current (A)
Overload
150% of rated current for 1 minute, 180% of rated current for 2 seconds
Endurance
Max. Output
300Hz
Frequency (Hz)
Output Rating
Carrier Frequency
2~6kHz
(kHz)
Rated Output
58 73 88 120 143 175 207 247 295 367 438 491 544
Capacity (kVA))
NORMAL DUTY
Rated Output
73 91 110 150 180 220 260 310 370 460 550 616 683
Current (A))
Overload
120% of rated current for 1 minute, 160% of rated current for 3 seconds
Endurance
Max. Output
600kHz (55kW: 400.00Hz)
Frequency (Hz)
Carrier Frequency
2~10kHz 2~9kHz
(kHz)
Input Current (A)
70 96 108 149 159 197 228 285 361 380 469 527 594
HEAVY Duty
Input Current (A)
Input Rating
74 101 114 157 167 207 240 300 380 400 494 555 625
NORMAL Duty
Rated Input Current
3-phase AC 380V -15%~480V +10%, 50/60Hz
(A) Heavy Duty
Operating Voltage
323~528VAC
Range
Frequency Tolerance 47~63Hz
Cooling Method Fan Cooling
Brake Chopper Option
DC Reactor Built-in
VFDXXXC43A: need to be used with conduit box kit for NEMA1
EMI Filter
VFDXXX43E: NEMA1
NOTE
*Frame F~H are under development.
35
General Specifications
Control Method 1: V/f, 2: VF+PG, 3: FOC, 4: open loop vector control
Torque Heavy duty (low carrier, constant torque applications): 2 kHz carrier
Characteristics frequency, 150% overload for 1 minute, higher carrier frequency possible
with current derating.
Normal duty (high carrier, variable torque applications): maximum carrier
frequency, depending on inverter capacity, 120% overload for 1 minute.
Starting Torque For Open Loop Vector Control and CT mode: up to 150% or above at 0.5Hz
For Flux Vector Control and CT mode: up to 150% at 0Hz for 1 minute
Speed Control 1:40 (V/f control)
Range 1:100 (Open Loop Vector control)
1:1000 (Close Loop Vector control)
Speed Control ±0.3% (V/f control)
Accuracy ±0.03% (V/f+PG control)
±0.2% (Open Loop Vector control)
±0.02% (Close Loop Vector control)
Speed Response
5Hz (vector control can be up to 40Hz)
Ability
Control Characteristics
36
Motor Protection Electronic thermal relay protection
Over-current The current forces 220% of the over-current protection and 300% of the rated
Protection current
Fuse blown
Stops for fuse blown.
Protection Characteristics
protection
Over-voltage 230: drive will stop when DC-BUS voltage exceeds 410V
Protection 460: drive will stop when DC-BUS voltage exceeds 820V
Low-voltage 230: drive will stop when DC-BUS voltage exceeds 190V
Protection 460: drive will stop when DC-BUS voltage exceeds 380V
Overload Ability Constant/variable torque: 150% for 60 seconds; 200% for 2 seconds
Over-temperature
Built-in temperature sensor
Protection
Stall prevention Stall prevention during acceleration, deceleration and running independently.
Grounding
Leakage Current Leakage current is higher than 50% of rated current of the AC motor drive
Protection
Certifications
37
0-1000m.
For 1000-3000m, please derate 2% rated current or
Altitude Operation decrease 0.5oC surrounding temperature per 100m.
The corner grounded system can only be used at 2000m
and below.
Package Storage
ISTA procedure 1A(according to weight) IEC60068-2-31
Drop Transportation
1.0mm peak to peak, 2-13.2Hz; 0.7G~1.0G from 13.2-55 Hz; 1.0G from 55-512 Hz (comply
Vibration
with IEC 60068-2-6)
Shock
15G for 11 ms (comply with IEC/EN 60068 2-27)
Resistance
10 10
Operation Max. allowed offset angle ±10o (for normal
Position installation position)
38
Digital Keypad
KPC-CC01 KPC-CE01 (optional)
Communication
RJ-45 (socket), RS-485 interface.
interface
Installation Embedded type and can be put flat on the surface of the control box. The front
Method cover is water proof.
39
Key Descriptions
Cancel Key
1. It is used to cancel the input value in the parameter setting display
before pressing “OK” key.
2. It can be used to return to the previous menu in those pages with
sub-menu.
It can return to the main menu after pressing MENU key.
ENTER Key
It is used to enter the selected sub-menu or confirm the command if it is
the last level.
40
Key Descriptions
Function Key
1. It has the factory setting function and the function can be set by the user.
The present factory setting: F1 is JOG function.
2. These function keys can be re-defined in software TPEditor.
41
CAN~”ERR”
42
Flow Chart of Digital Keypad
(1) POW ER ON
Start-up display
Auto sk ip to m ai n menu
after 3 seconds
Pr es s key
Pr es s key
NO F ault code or
w arning c ode key
key
Select an item
YES
Select a parameter group
Display faul t or
warning c ode Pr es s
key
(2) Pr es s key
Change the setti ng
Main menu of frequency command
Pr es s key (F )
Pr es s
key
When s electing
Select
(U) User- defined function
(F ) Fr equency command
(H) Output frequency Change the setti ng of
(U) User- defined function Pr es s user- defined function
key
(A ) O utput current
CAM S laver
43
Warning Codes
Warning m es sage indication
Warning D isplay warning c ode in abbrev iation
T hi s c ode is the same as shown in the keypad
CE01 (K PC- CE01)
Comm. Error 1 Descr ipti ons of warning code
Warning
CE01 Modbus function code error
Comm. Error 1
Warning
CE02 Address of Modbus data is error
Comm. Error 2
Warning
CE03 Modbus data error
Comm. Error 3
Warning
CE04 Modbus communication error
Comm. Error 4
Warning
CE10 Modbus transmission time-out
Comm. Error 10
Warning
CP10 Keypad transmission time-out
Keypad time out
Warning
SE1 Keypad COPY error
Save Error 1
44
Display on LCM Keypad Descriptions
Warning
SE2 Keypad COPY error 2
Save Error 2
Warning
oH1 IGBT over-heating warning
Over heat 1 warn
Warning
oH2 Capacity over-heating warning
Over heat 2 warn
Warning
PID PID feedback error
PID FBK Error
Warning
ANL ACI signal error
Analog loss
Warning
uC Low current
Under Current
Warning
AUE Auto tuning error
Auto-tune error
Warning
PGFbK PG feedback error
PG FBK Warn
Warning
PGL PG feedback loss
PG Loss Warn
45
Display on LCM Keypad Descriptions
Warning
oSPD Over-speed warning
Over Speed Warn
Warning
DAvE Over speed deviation warning
Deviation Warn
Warning
PHL Phase loss
Phase Loss
Warning
ot1 Over torque 1
Over Torque 1
Warning
ot2 Over torque 2
Over Torque 2
Warning
oH3 Motor over-heating
Motor Over Heat
Warning
CC Current clamp
C.C Warn
Warning
oSL Over slip
Over Slip Warn
Warning
tUn Auto tuning warning
Auto tuning
46
Display on LCM Keypad Descriptions
Warning
CGdn Guarding time-out
Guarding T-out
Warning
CHbn Heartbeat time-out
Heartbeat T-out
Warning
CSYn CAN synchrony time-out
SYNC T-out
Warning
CbFn CAN bus off
Can Bus Off
Warning
CSdn CAN SDO transmission time-out
SDO T-out
Warning
CSbn CAN SDO received register overflow
Buf Overflow
Warning
Cbtn CAN boot up error
Boot up fault
Warning
CPtn CAN format error
Error Protocol
Warning
PLod PLC download error
Opposite Defect
47
Display on LCM Keypad Descriptions
Warning
PLSv Save error of PLC download
Save mem defect
Warning
PLdA Data error during PLC operation
Data defect
Warning
PLFn Function code of PLC download error
Function defect
Warning
PLor PLC register overflow
Buf overflow
Warning
PLFF Function code of PLC operation error
Function defect
Warning
PLSn PLC checksum error
Check sum error
Warning
PLEd PLC end command is missed
No end command
Warning
PLCr PLC MCR command error
PLC MCR error
Warning
PLdF PLC download fail
Download fail
48
Display on LCM Keypad Descriptions
Warning
PLSF PLC scan time time-out
Scane time fail
Warning
ECLv Low voltage of communication card
ExCom pwr loss
Warning
ECtt Communication card enters test mode
ExCom Test Mode
Warning
ECbF DeviceNet bus-off
ExCom Bus off
Warning
ECnP No power supply on the DeviceNet network
ExCom No power
Warning
ECFF Manufactory error
ExCom Facty def
Warning
ECiF Serious internal error
ExCom Inner err
Warning
ECio IO communication is interrupted
ExCom IONet brk
49
Display on LCM Keypad Descriptions
Warning
ECPP Error occurs when the master sets the parameters
ExCom Pr data
Warning
ECPi Profibus layout data error
ExCom Conf data
Warning
ECEF Ethernet communication error
ExCom Link fail
Warning
ECrF Re-set the communication card to the factory settings
ExCom Rtn def
Warning
ECo0 Modbus TCP exceeds max. communication number
ExCom MTC P over
Warning
ECo1 EtherNet/IP exceeds max. communication number
ExCom EIP over
Warning
ECiP IP error
ExCom IP fail
50
Display on LCM Keypad Descriptions
Warning
EC3F Mail warning
ExCom Mail fail
51
Fault Codes Information
F ault code indic ation
Fault Display faul t code in abbreviation
ocA T hi s c ode is the same as shown in the keypad
(K PC- CE01)
Oc at accel Descr ipti ons of fault code
Ground fault. When (one of) the output terminal(s) is grounded, short
circuit current is more than 50% of AC motor drive rated current, the
AC motor drive power module may be damaged.
Fault
NOTE: The short circuit protection is provided for AC motor drive
GFF
Ground fault protection, not for protection of the user.
Corrective Actions:
1. Check the wiring connections between the AC motor drive and
motor for possible short circuits, also to ground.
52
Display on LCM Keypad Descriptions
2. Check whether the IGBT power module is damaged.
3. Check for possible poor insulation at the output line.
Short-circuit is detected between upper bridge and lower bridge of the
Fault IGBT module.
occ
Corrective Actions:
Short Circuit
Return to the factory.
DC BUS over-voltage during acceleration (230V: DC 450V; 460V: DC
900V)
Corrective Actions:
Fault
1. Check if the input voltage falls within the rated AC motor drive
ovSA input voltage range.
Ov at accel 2. Check for possible voltage transients.
3. If DC BUS over-voltage due to regenerative voltage, please
increase the Deceleration Time or add an optional brake
resistor.
DC BUS over-voltage during deceleration (230V: DC 450V; 460V: DC
900V)
Corrective Actions:
Fault
1. Check if the input voltage falls within the rated AC motor drive
ovSd input voltage range.
Ov at decel 2. Check for possible voltage transients.
3. If DC BUS over-voltage due to regenerative voltage, please
increase the Deceleration Time or add an optional brake
resistor.
DC BUS over-voltage in constant speed (230V: DC 450V; 460V: DC
900V)
Corrective Actions:
Fault
1. Check if the input voltage falls within the rated AC motor drive
OvSn input voltage range.
Ov at normal SPD 2. Check for possible voltage transients.
3. If DC BUS over-voltage due to regenerative voltage, please
increase the Deceleration Time or add an optional brake
resistor.
Hardware failure in voltage detection.
Fault Corrective Actions:
ovSS
Check if input voltage is within specification range and monitor if there
Ov at stop
is surge voltage.
53
Display on LCM Keypad Descriptions
DC BUS voltage is less than Pr.06-00 in constant speed.
Fault Corrective Actions:
Lvn 1. Check if the input voltage is normal
Lv at normal SPD 2. Check for possible sudden load
Phase Loss.
Corrective Actions:
Fault Check Power Source Input if all 3 input phases are connected without
OrP
loose contacts.
Phase lacked
For models 40hp and above, please check if the fuse for the AC input
circuit is blown.
IGBT overheating
IGBT temperature exceeds protection level
1 to15HP: 90 oC
o
20 to 100HP: 100 C
Fault Corrective Actions:
oH1 1. Ensure that the ambient temperature falls within the specified
IGBT over heat temperature range.
2. Make sure that the ventilation holes are not obstructed.
3. Remove any foreign objects from the heatsinks and check for
possible dirty heat sink fins.
4. Check the fan and clean it.
5. Provide enough spacing for adequate ventilation.
Heatsink overheating
Heat sink temperature exceeds 90oC
Corrective Actions:
Fault 1. Ensure that the ambient temperature falls within the specified
oH2 temperature range.
Heat Sink oH 2. Make sure that the ventilation holes are not obstructed.
3. Remove any foreign objects from the heatsinks and check for
possible dirty heat sink fins.
4. Check the fan and clean it.
5. Provide enough spacing for adequate ventilation.
Motor overheating
The AC motor drive detects that the internal temperature exceeds
Fault
Pr.06-30 (PTC level)
oH3 Corrective Actions:
Motor over heat 1. Make sure that the motor is not obstructed.
2. Ensure that the ambient temperature falls within the specified
temperature range.
3. Take the next higher power AC motor drive model.
54
Display on LCM Keypad Descriptions
These two fault codes will be displayed when output current exceeds
Fault the over-torque detection level (Pr.06-07 or Pr.06-10) and exceeds
ot1
over-torque detection(Pr.06-08 or Pr.06-11) and it is set 2 or 4 in
Over torque 1
Pr.06-06 or Pr.06-09.
Corrective Actions:
Fault 1. Check whether the motor is overloaded.
ot2 2. Check whether motor rated current setting (Pr.05-01) is
Over torque 2 suitable
3. Take the next higher power AC motor drive model.
Fault
UC1 Low torque 1
Under torque 1
Fault
UC2 Low torque 2
Under torque 2
55
Display on LCM Keypad Descriptions
U-phase error
Fault Corrective Actions:
cd1
Re-power on to try it. If fault code is still displayed on the
Ias sensor err
keypad please return to the factory.
V-phase error
Fault Corrective Actions:
cd2
Re-power on to try it. If fault code is still displayed on the keypad
Ibs sensor err
please return to the factory.
W-phase error
Fault Corrective Actions:
cd3
Re-power on to try it. If fault code is still displayed on the
Ics sensor err
keypad please return to the factory.
CC (current clamp).
Fault Corrective Actions:
Hd0
Re-power on to try it. If fault code is still displayed on the keypad
cc HW error
please return to the factory
OC hardware error.
Fault Corrective Actions:
Hd1
Re-power on to try it. If fault code is still displayed on the
Oc HW error
keypad please return to the factory.
OV hardware error.
Fault Corrective Actions:
Hd2
Re-power on to try it. If fault code is still displayed on the
Ov HW error
keypad please return to the factory.
GFF hardware error.
Fault Corrective Actions:
Hd3
Re-power on to try it. If fault code is still displayed on the
GFF HW error
keypad please return to the factory.
56
Display on LCM Keypad Descriptions
PG feedback error
Fault
PGF1 Corrective Actions:
PG Fbk error Check if Pr.10-01 is set to 0 when it is PG feedback control.
PG feedback loss
Fault
PGF2 Corrective Actions:
PG Fbk loss Check the wiring of the PG feedback.
PG feedback stall
Fault Corrective Actions:
PGF3 1. Check the wiring of the PG feedback
PG Fbk over SPD 2. Check if the setting of PI gain and deceleration is suitable
3. Return to the factory
PG slip error
Fault Corrective Actions:
PGF4 1. Check the wiring of the PG feedback
PG Fbk deviate 2. Check if the setting of PI gain and deceleration is suitable
3. Return to the factory
Pulse input error
Fault
Corrective Actions:
PGr1
1. Check the pulse wiring
PG Ref error
2. Return to the factory
ACI loss
Fault
Corrective Actions:
ACE
1. Check the ACI wiring
ACI loss 2. Check if the ACI signal is less than 4mA
57
Display on LCM Keypad Descriptions
External Fault
Fault Corrective Actions:
EF 1. Input EF (N.O.) on external terminal is closed to GND. Output U,
External fault V, W will be turned off.
2. Give RESET command after fault has been cleared.
Emergency stop
Corrective Actions:
Fault
1. When the multi-function input terminals MI1 to MI6 are set to
EF1
emergency stop, the AC motor drive stops output U, V, W and
Emergency stop the motor coasts to stop.
2. Press RESET after fault has been cleared.
External Base Block
Corrective Actions:
Fault
1. When the external input terminal (B.B) is active, the AC motor
BB
drive output will be turned off.
Base block 2. Deactivate the external input terminal (B.B) to operate the AC
motor drive again.
Password is locked.
Fault Corrective Actions:
PcodE
Keypad will be locked. Turn the power ON after power OFF to
Password error
re-enter the correct password. See Pr.00-07 and 00-08.
Illegal function code
Fault Corrective Actions:
cE1
Check if the function code is correct (function code must be 03, 06,
PC err command
10, 63)
Fault
cE10 Modbus transmission time-out.
PC time out
58
Display on LCM Keypad Descriptions
Fault
cP10 Keypad transmission time-out.
PU time out
Fault
S1 External emergency stop
S1-emergy stop
Fault
Aocc A-phase short-circuit
A phase short
Fault
bocc B-phase short-circuit
B phase short
Fault
cocc C-phase short-circuit
C phase short
59
Display on LCM Keypad Descriptions
Fault
CGdE Guarding time-out 1
Guarding T-out
Fault
CHbE Heartbeat time-out
Heartbeat T-out
Fault
CSyE CAN synchrony error
SYNC T-out
Fault
CbFE CAN bus off
Can bus off
60
Summary of Parameter Settings
This chapter provides summary of parameter settings for user to get the parameter information of
setting ranges and factory settings and set parameters. The parameters can be set, changed
and reset by the digital keypad.
NOTE
00 Drive Parameters
Factory
Parameter Explanation Settings
Setting
4: 230V, 1HP (0.75kW)
5: 460 V, 1HP (0.75kW)
6: 230V, 2HP (1.5kW)
7: 460 V, 2HP (1.5kW)
8: 230V, 3HP (2.2kW)
9: 460 V, 3HP (2.2kW)
10: 230V, 5HP (3.7kW)
11: 460 V, 5HP (3.7kW)
12: 230V, 7.5HP (5.5kW)
13: 460 V, 7.5HP (5.5kW)
14: 230V, 10HP (7.5kW)
15: 460V, 10HP (7.5kW)
16: 230V, 15HP (11kW)
17: 460V, 15HP (11kW)
18: 230V, 20HP (15kW)
Identity Code of the AC 19: 460V, 20HP (15kW)
00-00 20: 230V, 25HP (18.5kW) Read-only
Motor Drive
21: 460V, 25HP (18.5kW)
22: 230V, 30HP (22kW)
23: 460V, 30HP (22kW)
24: 230V, 40HP (30kW)
25: 460V, 40HP (30kW)
26: 230V, 50HP (37kW)
27: 460V, 50HP (37kW)
28: 230V, 60HP (45kW)
29: 460V, 60HP (45kW)
30: 230V, 75HP (50kW)
31: 460V, 75HP (50kW)
32: 230V, 100HP (75kW)
33: 460V, 100HP (75kW)
35: 460V, 125HP (90kW)
37: 460V, 150HP (110kW)
93: 460V, 5HP (4.0kW)
Rated Current Display of
00-01 Display by models Read-only
the AC Motor Drive
0: No function
1: Read only
2: Reserved
6: Reset PLC (including CANopen Master Index)
00-02 Parameter Reset 7: Reset CANopen Index (Slave) 0
8: keypad lock
9: All parameters are reset to factory settings(base
frequency is 50Hz)
10: All parameters are reset to factory settings (base
61
Factory
Parameter Explanation Settings
Setting
frequency is 60Hz)
0: F (frequency command)
a 00-03 Start-up Display Selection 1: H (output frequency) 0
2: U (multi-function display, see Pr.00-04)
3: A (output current)
0: Display output current (A)
1: Display counter value (c)
2: Display actual output frequency (H)
3: Display DC-BUS voltage (u)
4: Display output voltage (E)
5: Display output power angle (n)
6: Display output power in kW (P)
7: Display actual motor speed rpm (r)
8: Display estimate output torque in % (t)
9: Display PG feedback (G) (refer to Pr.10-00, 10-01)
10: Display PID feedback in % (b)
11: Display AVI in % (1.)
12: Display ACI in % (2.)
13: Display AUI in % (3.)
o
14: Display the temperature of heat sink in C (i.)
Content of Multi-function 15: Display the IGBT temperature of drive power
a 00-04 0
Display module oC (c.)
16: The status of digital input (ON/OFF) (i)
17: The status of digital output (ON/OFF) (o)
18: Display the multi-step speed that is executing (S)
19: The corresponding CPU pin status of digital
input(d.)
20: The corresponding CPU pin status of digital
output(0.)
Bit 0: Group 0
Bit 1: Group 1
Bit 2: Group 2
Bit 3: Group 3
Bit 4: Group 4
Display Advanced Bit 5: Group 5
a 00-09 0
Parameters Bit 6: Group 6
Bit 7: Group 7
Bit 8: Group 8
Bit 9: Group 9
Bit 10: Group 10
Bit 11: Group 11
62
Factory
Parameter Explanation Settings
Setting
0: Speed mode
00-10 Control Mode 1: Reserved 0
2: Torque mode
0: VF (V/f control)
1: VFPG (V/f control+ Encoder)
00-11 Control of Speed Mode 0
2: SVC (Sensorless vector control)
3: FOCPG (Sensorless vector control+encoder)
00-12 Reserved
0: TQCPG (Torque control + encoder)
00-13 Control of Torque Mode 0
1: Reserved
00-14 Reserved
00-15 Reserved
0: Normal duty
a 00-16 Duty Selection 1: Heavy duty 0
Normal duty:
1-15HP: 2~15kHz 8
20-50HP: 2-10kHz 6
60-100HP: 2-09kHz 2
00-17 Carrier Frequency
Heavy duty:
1-15HP: 2-15kHz 2
20-50HP: 2-10kHz 2
60-100HP: 2-09kHz 2
00-18 Reserved
00-19 Reserved
0: Digital keypad
1: RS-485 serial communication
2: External analog input (Pr.03-00)
3: External UP/DOWN terminal
Source of the Master 4: Pulse input without direction command (Pr.10-16
a 00-20 0
Frequency Command without direction)
5: Pulse input with direction command (Pr.10-16)
6: CANopen card
7: Reserved
8: Communication card (not includes CANopen card)
0: Digital keypad
1: External terminals. Keypad STOP disabled.
Source of the Operation 2: RS-485 serial communication. Keypad STOP
a 00-21 disabled. 0
Command (AUTO)
3: CANopen card
4: Reserved
5: Communication card (not includes CANopen card)
63
Factory
Parameter Explanation Settings
Setting
4: Pulse input without direction command (Pr.10-16
without direction)
5: Pulse input with direction command (Pr.10-16)
6: CANopen card
7: Reserved
8: Communication card (not includes CANopen card)
0: Digital keypad
1: External terminal, “Stop” key on the keypad is
invalid
Source of the Operation
a 00-31 2: RS-485, “Stop” key on the keypad is invalid 0
Command (HAND)
3: CANopen card
4: Reserved
5: Communication card (not includes CANopen card)
01 Basic Parameters
Factory
Parameter Explanation Settings
Setting
60.00/
01-00 Max. Operation Frequency 50.00~600.00Hz 50.00
60.00/
01-01 Base Frequency of Motor 1 0.00~600.00Hz 50.00
Max. Output Voltage of 230V: 0.0V~255.0V 220.0
01-02
Motor 1 460V: 0.0V~510.0V 440.0
Mid-point Frequency 1 of
01-03 0.00~600.00Hz 0.50
Motor 1
Mid-point Voltage 1 of Motor 230V: 0.0V~240.0V 5.0
a 01-04
1 460V: 0.0V~480.0V 10.0
Mid-point Frequency 2 of
01-05 0.00~600.00Hz 0.50
Motor 1
Mid-point Voltage 2 of Motor 230V: 0.0V~240.0V 5.0
a 01-06
1 460V: 0.0V~480.0V 10.0
Min. Output Frequency of
01-07 0.00~600.00Hz 0.00
Motor 1
Min. Output Voltage of Motor 230V: 0.0V~240.0V 0.0
a 01-08
1 460V: 0.0V~480.0V 0.0
64
Factory
Parameter Explanation Settings
Setting
Pr.01-45=0: 0.00~600.00 sec 10.00
a 01-17 Decel Time 3
Pr.01-45=1: 0.00~6000.0 sec 10.0
Pr.01-45=0: 0.00~600.00 sec 10.00
a 01-18 Accel Time 4
Pr.01-45=1: 0.00~6000.0 sec 10.0
Pr.01-45=0: 0.00~600.00 sec 10.00
a 01-19 Decel Time 4
Pr.01-45=1: 0.00~6000.0 sec 10.0
Pr.01-45=0: 0.00~600.00 sec 10.00
a 01-20 JOG Acceleration Time
Pr.01-45=1: 0.00~6000.0 sec 10.0
Pr.01-45=0: 0.00~600.00 sec 10.00
a 01-21 JOG Deceleration Time
Pr.01-45=1: 0.00~6000.0 sec 10.0
a 01-22 JOG Frequency 0.00~600.00Hz 6.00
1st/4th Accel/decel
a 01-23 0.00~600.00Hz 0.00
Frequency
S-curve for Acceleration Pr.01-45=0: 0.00~25.00 sec 0.20
a 01-24
Departure Time 1 Pr.01-45=1: 0.0~250.0 sec 0.2
S-curve for Acceleration Pr.01-45=0: 0.00~25.00 sec 0.20
a 01-25
Arrival Time 2 Pr.01-45=1: 0.0~250.0 sec 0.2
S-curve for Deceleration Pr.01-45=0: 0.00~25.00 sec 0.20
a 01-26
Departure Time 1 Pr.01-45=1: 0.0~250.0 sec 0.2
S-curve for Deceleration Pr.01-45=0: 0.00~25.00 sec 0.20
a 01-27
Arrival Time 2 Pr.01-45=1: 0.0~250.0 sec 0.2
Skip Frequency 1 (upper
01-28 0.00~600.00Hz 0.00
limit)
Skip Frequency 1 (lower
01-29 0.00~600.00Hz 0.00
limit)
Skip Frequency 2 (upper
01-30 0.00~600.00Hz 0.00
limit)
Skip Frequency 2 (lower
01-31 0.00~600.00Hz 0.00
limit)
Skip Frequency 3 (upper
01-32 0.00~600.00Hz 0.00
limit)
Skip Frequency 3 (lower
01-33 0.00~600.00Hz 0.00
limit)
0: Output waiting
01-34 Zero-speed Mode Selection 1: Zero-speed operation 0
2: Fmin (4th output frequency setting)
60.00/
01-35 Base Frequency of Motor 2 0.00~600.00Hz 50.00
Max. Output Voltage of 230V: 0.0V~255.0V 220.0
01-36
Motor 2 460V: 0.0V~510.0V 440.0
Mid-point Frequency 1 of
01-37 0.00~600.00Hz 0.50
Motor 2
Mid-point Voltage 1 of Motor 230V: 0.0V~240.0V 5.0
a 01-38
2 460V: 0.0V~480.0V 10.0
Mid-point Frequency 2 of
01-39 0.00~600.00Hz 0.50
Motor 2
Mid-point Voltage 2 of Motor 230V: 0.0V~240.0V 5.0
a 01-40
2 460V: 0.0V~480.0V 10.0
Min. Output Frequency of
01-41 0.00~600.00Hz 0.00
Motor 2
Min. Output Voltage of Motor 0.0
a 01-42 230V: 0.0V~240.0V
2 0.0
65
Factory
Parameter Explanation Settings
Setting
460V: 0.0V~480.0V
0: V/f curve determined by Pr.01-00~01-08
01-43 V/f Curve Selection 1: 1.5 power curve 0
2: Square curve
0: Linear accel./decel.
Optimal 1: Auto accel., linear decel.
a 01-44 Acceleration/Deceleration 2: Linear accel., auto decel. 0
Setting 3: Auto accel./decel.
4: Linear, stall prevention by auto accel./decel. (limit by
Pr.01-21 to 01-22)
Time Unit for
01-45 Acceleration/Deceleration 0: Unit: 0.01 sec 0
and S Curve 1: Unit: 0.1sec
Time for CANopen Quick
01-46 0.00~600.00 sec 1.00
Stop
01-47
~ Reserved
01-50
66
Factory
Parameter Explanation Settings
Setting
15: operation speed command from AVI
16: operation speed command from ACI
44~47: Reserved
67
Factory
Parameter Explanation Settings
Setting
53: Enable CANopen quick stop
68
Factory
Parameter Explanation Settings
Setting
26: Reverse command
27: Output when current >= Pr.02-33
28: Output when current <=Pr.02-33
29: Output when frequency >= Pr.02-34
30: Output when frequency <= Pr.02-34
31: Y-connection for the motor coil
32: Δ-connection for the motor coil
33: Zero speed (actual output frequency)
34: Zero speed with stop(actual output frequency)
35: Error output selection 1(Pr.06-23)
36: Error output selection 2(Pr.06-24)
37: Error output selection 3(Pr.06-25)
38: Error output selection 4(Pr.06-26)
39: Position attained (Pr.10-19)
40: Speed attained (including zero speed)
41: Multi-position attained
42: Crane function
43: Motor zero-speed output (Pr.02-47)
44~46: Reserved
47: Brake is close to output
48~49: Reserved
50: Output for CANopen control
51: Output for communication card
52: Output for RS-485
a 02-18 Multi-output Direction 0~65535 (0: N.O., 1: N.C.) 0
a 02-19 Terminal Count Value 0~65500 0
a 02-20 Preliminary Counter Value 0~65500 0
a 02-21 Digital Output Gain (DFM) 1 ~ 40 1
Desired Frequency 60.00/
a 02-22 0.00 ~ 600.00Hz
Attained 1 50.00
Width of the Desired
a 02-23 0.00 ~ 600.00Hz 2.00
Frequency Attained 1
Desired Frequency 60.00/
a 02-24 0.00 ~ 600.00Hz
Attained 2 50.00
Width of the Desired
a 02-25 0.00 ~ 600.00Hz 2.00
Frequency Attained 2
02-32 Brake Delay Time 0.000~65.000sec 0.000
Output Current Level
a 02-33 Setting for Multi-function 0~100% 0
Output Terminals
69
Factory
Parameter Explanation Settings
Setting
Output Boundary for
a 02-34 Multi-function Output 0.00~+-60.00Hz (it is motor speed when using PG) 0
Terminals
External Operation Control 0: Disable
a 02-35 0
Selection after Reset 1: Drive runs if run command exists after reset
a 02-47 Zero-speed Level of Motor 0~65535 rpm 0
Max. Frequency for
a 02-48 0.01~600.00Hz 60.00
Switching Resolution
Delay Time for Max. Output
a 02-49 0.000~65.000sec 0.000
Frequency Switch
Display the Status of
a 02-50 Multi-function Input Monitor the status of multi-function input terminals Read-only
Terminal
Display the Status of
02-51 Multi-function Output Monitor the status of multi-function output terminals Read-only
Terminal
Display the Status of
External Multi-function
02-52 Monitor the status of PLC input terminals Read-only
Input Terminal Used by
PLC
Display the Status of
02-53 Analog Input Terminal Monitor the status of PLC output terminals Read-only
Used by PLC
70
Factory
Parameter Explanation Settings
Setting
Positive/negative Bias the center
a 03-09 4: Serve bias as the center
Mode (AUI)
03-10 Reserved
Analog Input Gain 1
a 03-11 -500.0~500.0% 100.0
(AVI)
Analog Input Gain 2
a 03-12 -500.0~500.0% 100.0
(ACI)
Analog Positive Input
a 03-13 -500.0~500.0% 100.0
Gain 3 (AUI)
Analog Negative Input
a 03-14 -500.0~500.0% 100.0
Gain 4 (AUI)
Analog Input Filter Time
a 03-15 0.00~2.00sec 0
(AVI)
Analog Input Filter Time
a 03-16 0.00~2.00sec 0
(ACI)
Analog Input Filter Time
a 03-17 0.00~2.00sec 0
(AUI)
Addition Function of the 0: Disable (AVI, ACI, AUI)
a 03-18 0
Analog Input 1: Enable
0: Disable
a 03-19 Loss of the ACI Signal 1: Continue operation at the last frequency 0
2: Decelerate to 0Hz
3: Stop immediately and display EF
Multi-function Output 1
a 03-20 0: Output frequency (Hz) 11
(AFM1)
Multi-function Output 2
a 03-23 1: Frequency command (Hz) 1
(AFM2)
2: Motor speed (Hz)
3: Output current (rms)
4: Output voltage
5: DC Bus voltage
6: Power factor
7: Power
8: Output torque
9: AVI
10: ACI
11: AUI
12: Iq current
13: Iq feedback value
14: Id current
15: Id feedback value
16: Vq-axis voltage
17: Vd-axis voltage
18: Torque command
19: PG2 frequency command
20: Output for CANopen control
71
Factory
Parameter Explanation Settings
Setting
21: Analog output for communication card
Gain for Analog Output 1
a 03-21 0~200.0% 0
(AFM1)
72
Factory
Parameter Explanation Settings
Setting
a 04-16 Multi-position 2 0~65535 0
a 04-17 Multi-position 3 0~65535 0
a 04-18 Multi-position 4 0~65535 0
a 04-19 Multi-position 5 0~65535 0
a 04-20 Multi-position 6 0~65535 0
a 04-21 Multi-position 7 0~65535 0
a 04-22 Multi-position 8 0~65535 0
a 04-23 Multi-position 9 0~65535 0
a 04-24 Multi-position 10 0~65535 0
a 04-25 Multi-position 11 0~65535 0
a 04-26 Multi-position 12 0~65535 0
a 04-27 Multi-position 13 0~65535 0
a 04-28 Multi-position 14 0~65535 0
a 04-29 Multi-position 15 0~65535 0
05 Motor Parameters
Factory
Parameter Explanation Settings
Setting
0: No function
05-00 Motor Auto Tuning 1: Rolling test of induction motor 0
2: Static test of induction motor
Full-load Current of 40~120% of drive’s rated current
05-01 #.##
Induction Motor 1(A)
Rated Power of Induction 0~655.35kW
a 05-02 #.##
Motor 1(kW)
Rated Speed of Induction 0~65535
a 05-03 1710
Motor 1 (rpm) 1710(60Hz, 4 poles), 1410(50Hz, 4 poles)
Pole Number of Induction 2~20
05-04 4
Motor 1
No-load Current of 0~factory setting of Pr.05-01
05-05 #.##
Induction Motor 1 (A)
Stator Resistance (Rs) of
05-06 0~65535mΩ 0
Induction Motor 1
Rotor Resistance (Rr) of
05-07 0~65535mΩ 0
Motor 1
Magnetizing Inductance 0~65535mH
05-08 0
(Lm) of Induction Motor 1
Stator Inductance (Lx) of 0~65535mH
05-09 0
Induction Motor 1
05-10
~ Reserved
05-12
Full-load Current of 40~120%
05-13 #.##
Induction Motor 2 (A)
Rated Power of Induction 0~655.35kW
a 05-14 #.##
Motor 2 (kW)
Rated Speed of Induction 0~65535
a 05-15 1710
Motor 2 (rpm) 1710(60Hz, 4 poles), 1410(50Hz, 4 poles)
73
Factory
Parameter Explanation Settings
Setting
Pole Number of Induction 2~20
05-16 4
Motor 2
No-load Current of 0~ factory setting of Pr.05-01
05-17 #.##
Induction Motor 2 (A)
Stator Resistance (Rs) of
05-18 0~65535mΩ 0
Induction Motor 2
Rotor Resistance (Rr) of
05-19 0~65535mΩ 0
Induction Motor 2
Magnetizing Inductance 0~65535mH
05-20 0
(Lm) of Induction Motor 2
Stator Inductance (Lx) of 0~65535mH
05-21 0
Induction Motor 2
Induction Motor 1/ 2 1: Motor 1
a 05-22 1
Selection 2: Motor 2
Frequency for 0.00~600.00Hz
a 05-23 Y-connection/△-connection 60.00
Switch of Induction Motor
Y-connection/△-connection 0: Disable
a 05-24 0
Switch of Induction Motor 1: Enable
Delay Time for 0.000~60.000sec
a 05-25 Y-connection/△-connection 0.200
Switch of Induction Motor
05-26
~ Reserved
05-30
Accumulative Motor 00~1439
05-31 0
Operation Time (Min)
Accumulative Motor 00~65535
05-32 0
Operation Time (day)
06 Protection Parameters
Factory
Parameter Explanation Settings
Setting
230V: 160.0~220.0Vdc 180.0
a 06-00 Low Voltage Level
460V: 320.0~440.0Vdc 360.0
74
Factory
Parameter Explanation Settings
Setting
stop operation after detection
3: Over-torque detection during operation, continue to
operation after detection
4: Over-torque detection during operation, stop operation
after detection
Over-torque Detection
a 06-07 10~250% (100%: drive’s rated current) 150
Level (OT1)
Over-torque Detection
a 06-08 0.0~60.0sec 0.1
Time (OT1)
0: Disable
1: Over-torque detection during constant speed operation,
continue to operate after detection
Over-torque Detection 2: Over-torque detection during constant speed operation,
a 06-09 stop operation after detection 0
Selection (OT2)
3: Over-torque detection during operation, continue to
operation after detection
4: Over-torque detection during operation, stop operation
after detection
Over-torque Detection
a 06-10 10~250% (100%: drive’s rated current) 150
Level (OT2)
Over-torque Detection
a 06-11 0.0~60.0sec 0.1
Time (OT2)
a 06-12 Reserved
Electronic Thermal 0: Inverter motor
a 06-13 Relay Selection (Motor 1: Standard motor 2
1) 2: Disable
Electronic Thermal
a 06-14 Characteristic for Motor 30.0~600.0sec 60.0
1
Heat Sink Over-heat
a 06-15
(OH) Warning 0.0~110.0 OC 85.0
Stall Prevention Limit
a 06-16 0 ~ 100% (refer to Pr.06-03, 06-04) 50
Level
06-17 Present Fault Record 0: No fault 0
Second Most Recent
06-18 1: Over-current during acceleration (ocA) 0
Fault Record
Third Most Recent Fault
06-19 2: Over-current during deceleration (ocd) 0
Record
Fourth Most Recent
06-20 3: Over-current during constant speed(ocn) 0
Fault Record
Fifth Most Recent Fault
06-21 4: Ground fault (GFF) 0
Record
Sixth Most Recent Fault
06-22 5: IGBT short-circuit (occ) 0
Record
6: Over-current at stop (ocS)
7: Over-voltage during acceleration (ovA)
8: Over-voltage during deceleration (ovd)
9: Over-voltage during constant speed (ovn)
10: Over-voltage at stop (ovS)
11: Low-voltage during acceleration (LvA)
12: Low-voltage during deceleration (Lvd)
13: Low-voltage during constant speed (Lvn)
75
Factory
Parameter Explanation Settings
Setting
14: Low-voltage at stop (LvS)
15: Phase loss (PHL)
16: IGBT over-heat (oH1)
17: Heat sink over-heat (oH2) (for 40hp above)
18: TH1: IGBT hardware failure (tH1o)
19: TH2: Heat sink hardware failure (tH2o)
20: Reserved
21: over-load (oL)(when it exceeds 150% rated current,
1min later it will be overload)
22: Electronics thermal relay 1 (EoL1)
23: Electronics thermal relay 2 (EoL2)
24: Motor PTC overheat (oH3) (PTC)
25: Reserved
26: Over-torque 1 (ot1)
27: Over-torque 2 (ot2)
28: Reserved
29: Reserved
30: Memory write-in error (cF1)
31: Memory read-out error (cF2)
32: Reserved
33: U-phase current detection error (cd1)
34: V-phase current detection error (cd2)
35: W-phase current detection error (cd3)
36: Clamp current detection error (Hd0)
37: Over-current detection error (Hd1)
38: Over-voltage detection error (Hd2)
39: Ground current detection error (Hd3)
40: Auto tuning error (AuE)
41: PID feedback loss (AFE)
42: PG feedback error (PGF1)
43: PG feedback loss (PGF2)
44: PG feedback stall (PGF3)
45: PG slip error (PGF4)
46: PG ref loss (PGr1)
47: PG ref loss (PGr2)
48: Analog current input loss (ACE)
49: External fault input (EF)
50: Emergency stop (EF1)
76
Factory
Parameter Explanation Settings
Setting
51: External Base Block (bb)
52: Password error (PcodE)
53: Software password is locked (ccodE)
54: Communication error (cE1)
55: Communication error (cE2)
56: Communication error (cE3)
57: Communication error (cE4)
58: Communication Time-out (cE10)
59: PU Time-out (cP10)
60: Brake transistor error (bF)
61: Y-connection/△-connection switch error (ydc)
62: Decel. Energy Backup Error (dEb)
63: Slip error (oSL)
64~65: Reserved
73: S1 Power removal safety function error
101: CGdE CANopen software loss 1
102: CHbE CANopen software loss 2
103: CSyE CANopen synchrony error
104: CbFE CANopen hardware loss
105: CIdE CANopen
106: CAdE CANopen
107: CFrE CANopen
Factory
Parameter Explanation Settings
Setting
a 06-23 Fault Output Option 1 0~65535(refer to bit table for fault code) 0
a 06-24 Fault Output Option 2 0~65535(refer to bit table for fault code) 0
a 06-25 Fault Output Option 3 0~65535(refer to bit table for fault code) 0
a 06-26 Fault Output Option 4 0~65535(refer to bit table for fault code) 0
Electronic Thermal 0: Inverter motor
a 06-27 Relay Selection 2 (Motor 1: Standard motor 2
2) 2: Disable
Electronic Thermal
a 06-28 Characteristic for Motor 30.0~600.0sec 60.0
2
0: Warn and keep operation
a 06-29 PTC Detection Selection 1: Warn and ramp to stop 0
2: Warn and coast to stop
a 06-30 PTC Level 0.0 ~ 100.0% 50.0
a 06-31 Frequency Command 0.00~655.35 Hz Read
77
Factory
Parameter Explanation Settings
Setting
for Malfunction only
Output Frequency at Read
06-32 0.00~655.35 Hz
Malfunction only
Output Voltage at Read
06-33 0.0~6553.5 V
Malfunction only
DC Voltage at Read
06-34 0.0~6553.5 V
Malfunction only
Output Current at Read
06-35 0.00~655.35 Amp
Malfunction only
IGBT Temperature at Read
06-36
Malfunction 0.0~6553.5 OC only
Heat Sink Temperature Read
06-37
at Malfunction 0.0~6553.5 OC only
Motor Speed in rpm at Read
06-38 0~65535
Malfunction only
Torque Command at Read
06-39 0~65535
Malfunction only
Status of Multi-function
Read
06-40 Input Terminal at 0~65535
only
Malfunction
Status of Multi-function
Read
06-41 Output Terminal at 0~65535
only
Malfunction
Drive Status at Read
06-42 0~65535
Malfunction only
06-43 Reserved
06-44 Reserved
Treatment of Output
06-45 0~4 0
Phase Loss (OPL)
Deceleration Time of
06-46 0~65535 0
Output Phase Loss
06-47 Current Bandwidth 0~65535 0
DC Brake Time of
06-48 0~65535 0
Output Phase Loss
Level of Output Phase
06-49 0~65535 0
Loss
Time of Output Phase
06-50 0.00~600.00sec 0.00
Loss
06-51 Reserved
Ripple of Output Phase
06-52 0.0~320.0 0.0
Loss
0: Warn and keep operation
Treatment of Output
06-53 1: Warn and ramp to stop 0
Phase Loss (orP)
2: Warn and coast to stop
06-54 Reserved
0: constant rated current and limit carrier wave by load
current and temperature
Protection for Carrier 1: constant carrier frequency and limit load current by
06-55 0
Wave setting carrier wave
2: constant rated current(same as setting 0), but close
current limit
Operation Time when Read
06-63 0 to 64799 min
Malfunction 1 Occurs only
Operation Time when Read
06-64 0 to 64799 min
Malfunction 2 Occurs only
Operation Time when Read
06-65 0 to 64799 min
Malfunction 3 Occurs only
78
Factory
Parameter Explanation Settings
Setting
Operation Time when Read
06-66 0 to 64799 min
Malfunction 4 Occurs only
Operation Time when Read
06-67 0 to 64799 min
Malfunction 5 Occurs only
Operation Time when Read
06-68 0 to 64799 min
Malfunction 6 Occurs only
07 Special Parameters
Factory
Parameter Explanation Settings
Setting
230V: 350.0~450.0Vdc 380.0
a 07-00 Software Brake Level
460V: 700.0~900.0Vdc 760.0
a 07-01 DC Brake Current Level 0~100% 0
DC Brake Time at
a 07-02 0.0~60.0sec 0.0
Start-up
a 07-03 DC Brake Time at Stop 0.0~60.0sec 0.0
a 07-04 Start-point for DC Brake 0.00~600.00Hz 0.00
Proportional Gain for DC
a 07-05 1~500 50
Brake
0: Operation stop after momentary power loss
Momentary Power Loss 1: Operation continues after momentary power loss, speed
a 07-06 search starts with the Master Frequency reference value 0
Operation Selection
2: Operation continues after momentary power loss, speed
search starts with the minimum frequency
Maximum Allowable
a 07-07 0.1~5.0sec 2.0
Power Loss Time
B.B. Time for Speed
a 07-08 0.1~5.0sec 0.5
Search
Current Limit for Speed
a 07-09 20~200% 150
Search
79
Factory
Parameter Explanation Settings
Setting
0: Fan always ON
1: 1 minute after AC motor drive stops, fan will be OFF
2: AC motor drive runs and fan ON, AC motor drive stops
a 07-19 Fan Control and fan OFF 0
3: Fan ON to run when preliminary heat sink temperature
(around 60oC) attained.
4: Fan always OFF
0: Coast stop
1: By deceleration Time 1
Emergency Stop (EF) & 2: By deceleration Time 2
a 07-20 3: By deceleration Time 3 0
Forced Stop Selection
4: By deceleration Time 4
5: System Deceleration
6: Automatic Deceleration
Auto Energy-saving 0: Disable
a 07-21 0
Operation 1: Enable
a 07-22 Energy-saving Gain 10 ~ 1000% 100
Auto Voltage 0: Enable AVR
a 07-23 Regulation(AVR) 1: Disable AVR 0
Function 2: Disable AVR when deceleration stop
Filter Time of Torque
a 07-24 0.001~10.000sec 0.020
Command
Filter Time of SVC Slip
a 07-25 0.001~10.000sec 0.100
Compensation
SVC Torque
a 07-26 0~10 0
Compensation Gain
SVC Slip Compensation
a 07-27 0.00~10.00 0.00
Gain
07-28 Reserved
a 07-29 Slip Deviation Level 0.0~100.0% 0
Detection Time of Slip
a 07-30 0.0~10.0sec 1.0
Deviation
0: Warn and keep operation
a 07-31 Over Slip Treatment 1: Warn and ramp to stop 0
2: Warn and coast to stop
a 07-32 Hunting Gain 0~10000 2000
Time for Restart after
07-33 00~60000sec 600
Fault
80
Factory
Parameter Explanation Settings
Setting
a 08-01 Proportional Gain (P) 0.0~500.0% 80.0
a 08-02 Integral Time (I) 0.00~100.00sec 1.00
a 08-03 Derivative Control (D) 0.00~1.00sec 0.00
Upper Limit for Integral
a 08-04 0.0~100.0% 100.0
Control
PID Output Frequency
a 08-05 0.0~110.0% 100.0
Limit
08-06 Reserved
a 08-07 PID Delay Time 0.0~2.5sec 0.0
Feedback Signal
a 08-08 0.0~3600.0sec 0.0
Detection Time
0: Warn and keep operation
Feedback Fault 1: Warn and ramp to stop
a 08-09 0
Treatment 2: Warn and coast to stop
3: Warn and keep at last frequency
a 08-10 Sleep Frequency 0.00 ~ 600.00Hz 0.00
a 08-11 Wake-up Frequency 0.00 ~ 600.00Hz 0.00
a 08-12 Sleep Time 0.0 ~ 6000.0sec 0.0
a 08-13 PID Deviation Level 1.0 ~ 50.0% 10.0
a 08-14 PID Deviation Time 0.1~300.0sec 5.0
Filter Time for PID
a 08-15 0.1~300.0sec 5.0
Feedback
PID Compensation 0: Parameter setting
a 08-16 0
Selection 1: Analog input
a 08-17 PID Compensation -100.0~+100.0% 0
08-18 Reserved
08-19 Reserved
0: Old PID mode
08-20 Selection of PID Mode 0
1: New PID mode
Change Operation 0: Disable
08-21 0
Direction by PID 1: Enable
09 Communication Parameters
Factory
Parameter Explanation Settings
Setting
a 09-00 Communication Address 1~254 1
COM1 Transmission
a 09-01 4.8 ~ 115.2kbps 9.6
Speed
0: Warn and keep operation
COM1 Transmission 1: Warn and ramp to stop
a 09-02 3
Fault Treatment 2: Warn and coast to stop
3: No warning and keep operation
COM1 Time-out
a 09-03 0.0 ~ 100.0sec 0.0
Detection
0: 7N1 (ASCII)
COM1 Communication 1: 7N2 (ASCII)
a 09-04 1
Protocol 2: 7E1 (ASCII)
3: 7O1 (ASCII)
81
Factory
Parameter Explanation Settings
Setting
4: 7E2 (ASCII)
5: 7O2 (ASCII)
6: 8N1 (ASCII)
7: 8N2 (ASCII)
8: 8E1 (ASCII)
9: 8O1 (ASCII)
10: 8E2 (ASCII)
11: 8O2 (ASCII)
12: 8N1 (RTU)
13: 8N2 (RTU)
14: 8E1 (RTU)
15: 8O1 (RTU)
16: 8E2 (RTU)
17: 8O2 (RTU)
09-05
~ Reserved
09-08
a 09-09 Response Delay Time 0.0~200.0ms 2.0
Transmission Master
a 09-10 0.00~600.00Hz 60.00
Frequency
a 09-11 Block Transfer 1 0~65535 0
a 09-12 Block Transfer 2 0~65535 0
a 09-13 Block Transfer 3 0~65535 0
a 09-14 Block Transfer 4 0~65535 0
a 09-15 Block Transfer 5 0~65535 0
a 09-16 Block Transfer 6 0~65535 0
a 09-17 Block Transfer 7 0~65535 0
a 09-18 Block Transfer 8 0~65535 0
a 09-19 Block Transfer 9 0~65535 0
a 09-20 Block Transfer 10 0~65535 0
a 09-21 Block Transfer 11 0~65535 0
a 09-22 Block Transfer 12 0~65535 0
a 09-23 Block Transfer 13 0~65535 0
a 09-24 Block Transfer 14 0~65535 0
a 09-25 Block Transfer 15 0~65535 0
a 09-26 Block Transfer 16 0~65535 0
09-27
~ Reserved
09-29
Communication Decode 0: 20XX
09-30 0
Method 1: 60XX
09-31
~ Reserved
09-34
09-35 PLC Address 1~254 0
09-36 CANopen Slave Address 1~127 0
0: 1M
09-37 CANbus Speed 0
1: 500k
82
Factory
Parameter Explanation Settings
Setting
2: 250k
3: 125k
4: 100k
5: 50k
CANbus Frequency
09-38 1.00 ~ 2.00 1.00
Gain
bit 0: CANopen Guarding Time out
bit 1: CANopen Heartbeat Time out
bit 2: CANopen SYNC Time out
CANbus Warning
09-39 bit 3: CANopen SDO Time out 0
Record
bit 4: CANopen SDO buffer overflow
bit 5: Can Bus Off
bit 6: Error protocol of CANopen
CANopen Decode 0: Communication definition of C2000 series
09-40 1
Method 1: CANopen DS402 protocol
0: Node reset status
1: COM reset status
2: Boot up status
09-41 CAN Master/Slave 0
3: Pre-operation status
4: Operation status
5: Stop status
0: Not ready for use status
1: Inhibit start status
2: Ready to switch on status
3: Switched on status
09-42 CANopen Control Status 0
4: Enable operation status
7: Active status of quick stop
13: Active status of error reaction
14: Error status
09-43 Reserved
09-44 Reserved
0: 20XX
09-45 CANopen Selection 1
1: 60XX
09-42 CAN Master Address 1~127 100
09-47
~ Reserved
09-59
0: No communication card
1: DeviceNet Slave
2: Profibus-DP Slave
Identifications for 3: CANopen Slave
09-60 0
Communication Card 4: Modbus-TCP Slave
5: EtherNet/IP Slave
6~8: Reserved
Firmware Version of
09-61 Read-only ##
Communication Card
09-62 Production Code Read-only ##
09-63 Error Code Read-only ##
09-64
~ Reserved
09-69
Address of DeviceNet: 0-63
09-70 1
Communication Card Profibus-DP: 1-125
Setting of DeviceNet Standard DeviceNet:
09-71 Speed (according to 0: 125Kbps 2
Pr.09-72) 1: 250Kbps
83
Factory
Parameter Explanation Settings
Setting
2: 500Kbps
84
Factory
Parameter Explanation Settings
Setting
Communication Card Bit0=1: it has password for the communication card.
Bit0=0: no password for the communication card
85
Factory
Parameter Explanation Settings
Setting
4: Phase A is a pulse input and phase B is a direction input.
(low input=forward direction, high input=reverse direction)
Electrical Gear A (PG1
a 10-17 1~5000 100
of PG card)
Electrical Gear B (PG2
a 10-18 1~5000 100
of PG card)
Positioning for Encoder
a 10-19 0~65535 pulses 0
Position
Range for Encoder
a 10-20 0~65535 pulses 10
Position Attained
a 10-21 PG2 Filter Time 0~65.535 sec 0.100
11 Advanced Parameters
Factory
Parameter Explanation Settings
Setting
bit 0: Auto tuning for ASR and APR
a 11-00 System Control bit 1: Inertia estimate (only for FOCPG mode) 0
bit 2: Zero servo
bit 3: Reserved
Per Unit of System
a 11-01 1~65535 (256=1PU) 400
Inertia
ASR1/ASR2 Switch
a 11-02 0.00~600.00Hz (0: disable) 7.00
Frequency
ASR1 Low-speed
a 11-03 0~40Hz 10
Bandwidth
ASR2 High-speed
a 11-04 0~40Hz 10
Bandwidth
a 11-05 Zero-speed Bandwidth 0~40Hz 10
ASR (Auto Speed
a 11-06 Regulation) Control ( P) 0~40Hz 10
1
ASR (Auto Speed
a 11-07 0.000~10.000sec 0.100
Regulation) Control (I) 1
ASR (Auto Speed
a 11-08 Regulation) Control ( P) 0~40Hz 10
2
ASR (Auto Speed
a 11-09 0.000~10.000sec 0.100
Regulation) Control (I) 2
a 11-10 P Gain of Zero Speed 0~40Hz 10
a 11-11 I Gain of Zero Speed 0.000~10.000sec 0.100
Gain for ASR Speed
a 11-12 0~100% 0
Feed Forward
a 11-13 PDFF Gain 0~200 30
Low-pass Filter Time of
a 11-14 0.000~0.350sec 0.008
ASR Output
a 11-15 Notch Filter Depth 0~20db 0
a 11-16 Notch Filter Frequency 0.00~200.00Hz 0.0
Forward Motor Torque
a 11-17 0~500% 200
Limit
Forward Regenerative
a 11-18 0~500% 200
Torque Limit
86
Factory
Parameter Explanation Settings
Setting
Reverse Motor Torque
a 11-19 0~500% 200
Limit
Reverse Regenerative
a 11-20 0~500% 200
Torque Limit
Gain Value of Flux
a 11-21 Weakening Curve for 0~200% 90
Motor 1
Gain Value of Flux
a 11-22 Weakening Curve for 0~200% 90
Motor 2
Speed Response of Flux
a 11-23 0~150% 65
Weakening Area
a 11-24 APR Gain 0.00~40.00Hz 10.00
Gain Value of APR Feed
a 11-25 0~100 30
Forward
a 11-26 APR Curve Time 0.00~655.35 sec 3.00
a 11-27 Max. Torque Command 0~500% 100
0: Digital keypad
a 11-28 Source of Torque Offset 1: RS-485 communication (Pr.11-29) 0
2: Analog input (Pr.03-00)
a 11-29 Torque Offset Setting 0~100% 0.0
a 11-30 High Torque Offset 0~100% 30.0
a 11-31 Middle Torque Offset 0~100% 20.0
a 11-32 Low Torque Offset 0~100% 10.0
0: Digital keypad
1: RS-485 communication (Pr.11-34)
Source of Torque 2: Analog input (Pr.03-00)
a 11-33 0
Command 3: CANopen
4: Reserved
5: Communication card
a 11-34 Torque Command -100.0~+100.0% (Pr.11-27=100%) 0
Low-pass Filter Time of
a 11-35 0.000~1.000sec 0.000
Torque Command
87