Module - 1: Introduction For Power System Protection, Relay Construction and Operating Principles
Module - 1: Introduction For Power System Protection, Relay Construction and Operating Principles
Module -1
Introduction for Power System Protection, Relay Construction and Operating Principles
A protective system includes circuit breakers, transducers (CTs and VTs), and protective
relays to isolate the faulty section of the power system from the healthy sections. A circuit breaker can
disconnect the faulty element of the system when it is called upon to do so by the protective relay.
Transducers (CTs and VTs) are used to reduce currents and voltages to lower values and to isolate
protective relays from the high voltages of the power system. The function of a protective relay is to
detect and locate a fault and issue a command to the circuit breaker to disconnect the faulty element. It
is a device which senses abnormal conditions on a power system by constantly monitoring electrical
quantities of the systems, which differ under normal and abnormal conditions. The basic electrical
quantities which are likely to change during abnormal conditions are current, voltage, phase-angle
(direction) and frequency. Protective relays utilize one or more of these quantities to detect abnormal
conditions on a power system.
Protection is needed not only against short circuits but also against any other abnormal
conditions which may arise on a power system. A few examples of other abnormal conditions are over
speed of generators and motors, overvoltage, under frequency, loss of excitation, overheating of stator
and rotor of an alternator etc. Protective relays are also provided to detect such abnormal conditions
and issue alarm signals to alert operators or trip circuit breaker.
A protective relay does not anticipate or prevent the occurrence of a fault; rather it takes
action only after a fault has occurred. However, one exception to this is the Buchholz relay, a gas
actuated relay, which is used for the protection of power transformers. Sometimes, a slow breakdown
of insulation due to a minor arc may take place in a transformer, resulting in the generation of heat
and decomposition of the transformer‘s oil and solid insulation. Such a condition produces a gas
which is collected in a gas chamber of the Buchholz relay. When a specified amount of gas is
accumulated, the Buchholz relay operates an alarm. This gives an early warning of incipient faults.
The transformer is taken out of service for repair before the incipient fault grows into a serious one.
Introduction to Power System Protection Page 2
Power System Protection EEE, ATMECE, Mysuru
Thus, the occurrence of a major fault is prevented. If the gas evolves rapidly, the Buchholz relay trips
the circuit breaker instantly.
Protective relaying is teamwork of the following Components for the protection of
equipment these include: protective current transformers and voltage transformers, protective
relays, time-delay relays, auxiliary relays, secondary circuits; trip circuits, auxiliaries and ac-
cessories, etc. Each component is important.
Symmetrical Faults
A three-phase (3-Ǿ) fault is called a symmetrical type of fault. In a 3-Ǿ fault, all the three
phases are short circuited. There may be two situations—all the three phases may be short circuited to
the ground or they may be short-circuited without involving the ground. A 3-Ǿ short circuit is
generally treated as a standard fault to determine the system fault level.
Unsymmetrical Faults
Single-phase to ground, two-phase to ground, phase-to-phase short circuits; single phase open
circuit and two-phase open circuit are unsymmetrical types of faults.
Single-phase to Ground (L-G) Fault
A short circuit between any one of the phase conductors and earth is called a single phase to
ground fault. It may be due to the failure of the insulation between a phase conductor and the earth, or
due to phase conductor breaking and falling to the ground.
Open-circuited Phases
This type of fault is caused by a break in the conducting path. Such faults occur when one or
more phase conductors break or a cable joint or a joint on the overhead lines fails. Such situations
may also arise when circuit breakers or isolators open but fail to close one or more phases. Due to the
opening of one or two phases, unbalanced currents flow in the system, thereby heating rotating
machines. Protective schemes must be provided to deal with such abnormal situations.
Winding Faults
All types of faults discussed above also occur on the alternator, motor and transformer
windings. In addition to these types of faults, there is one more type of fault, namely the short
circuiting of turns which occurs on machine windings.
Simultaneous Faults
Two or more faults occurring simultaneously on a system are known as multiple or
simultaneous faults. In simultaneous faults, the same or different types of faults may occur at the same
or different points of the system. An example of two different types of faults occurring at the same
point is a single line to ground fault on one phase and breaking of the conductor of another phase,
both simultaneously present at the same point. The simultaneous presence of an L-G fault at one point
and a second L-G fault on another phase at some other point is an example of two faults of the same
type at two different points. If these two L- G faults are on the same section of the line, they are
treated as a double line to ground fault. If they occur in different line sections, it is known as a cross-
country earth fault. Cross-country faults are common on systems grounded through high impedance or
Peterson coil but they are rare on solidly grounded systems.
The most dangerous type of fault is a short circuit as it may have the following effects on a power
system, if it remains uncleared.
Heavy short circuit current may cause damage to equipment or any other element of the
system due to overheating and high mechanical forces set up due to heavy current.
Arcs associated with short circuits may cause fire hazards. Such fires, resulting from arcing,
may destroy the faulty element of the system. There is also a possibility of the fire spreading
to other parts of the system if the fault is not isolated quickly.
There may be reduction in the supply voltage of the healthy feeders, resulting in the loss of
industrial loads.
Short circuits may cause the unbalancing of supply voltages and currents, thereby heating
rotating machines.
There may be a loss of system stability. Individual generators in a power station may lose
synchronism, resulting in a complete shutdown of the system. Loss of stability of
interconnected systems may also result. Subsystems may maintain supply for their individual
zones but load shedding would have to be resorted in the sub-system which was receiving
power from the other subsystem before the occurrence of the fault.
The above faults may cause an interruption of supply to consumers, thereby causing a loss of
revenue.
High grade, high speed, reliable protective devices are the essential requirements of a power system to
minimise the effects of faults and other abnormalities
The protected zone is that part of a power system guarded by a certain protection Scheme and
usually contains one or at the most two elements of the power system. The zones are arranged to
overlap so that no part of the system remains unprotected. Figure (1.1) shows a typical arrangement of
overlapping zones of protection.
A power system contains generators, transformers, bus bars, transmission and distribution
lines, etc. There is a separate protective scheme for each piece of equipment or element of the power
system, such as generator protection, transformer protection, transmission line protection, bus bar
Introduction to Power System Protection Page 5
Power System Protection EEE, ATMECE, Mysuru
protection, etc.
Neighboring zones overlap so that no ‘dead spot’ are left in the protected system
It can be seen that for a fault at X the circuit breakers of ‗Zone B‘ including breaker C
will be tripped; however, this does not interrupt the flow of fault current from ‗Zone A‘, the
relaying equipment of ‗Zone B‘ must also trip certain breaker in zone ‗Zone A‘
This is all right for fault at X, but for faults in zone B to the right of breaker C the
operation of breakers in zone A is not useful. How far this unnecessary operation can be
tolerated will depend on the particular application.
Primary protection (Main protection) is the essential protection provided for protecting an
equivalent/machine. As a precautionary measure, an addition protection is generally provided and is
called ‗Back-up Protection‘. The primary protection is the first to act and the Back-up Protection is
the next in the line of defense-meaning, if primary protection fails, the back-up protection comes into
action and removes the faulty part from the healthy system. Back-up protection is provided for the
following reasons:
If due to some reason, the Main protection fails, the Back-up protection serves the purpose of
protection. Main protection can fail due to failure of one of the components in the protective system
such as relay, auxiliary relay CT, PT, trip circuit, circuit-breaker, etc. If the primary protection fails,
there must be an additional protection; otherwise the fault may remain uncleared, resulting in a
disaster.
Back-up protection. It is the second line of defence in case of failure of the primary protection.
It is designed to operate with sufficient time delay so that primary relaying will be given enough time
to function if it is able to. Thus referring to above Fig., relay A provides back-up protection for each
of the four lines. If a line fault is not cleared by its relay and breaker, the relay A on the group breaker
will operate after a definite time delay and clear the entire group of lines. It is evident that when back-
up relaying functions, a larger part is disconnected than when primary relaying functions correctly.
Therefore, greater emphasis should be placed on the better maintenance of primary relaying.
The back-up relays are made independent of those factors which might cause primary relays
to fail. A back-up relay operates after a time delay to give the primary relay sufficient time to operate.
When a back-up relay operates, a larger part of the power system is disconnected from the power
source, but this is unavoidable.
tive systems are different. Separate trip coils may be provided for the same-breaker.
2. Breaker Back-up. Different breakers are provided for main and back-up protection, both the
breakers being in the same station
3. Remote back-up. The main and Back-up protections provided at different stations and are
completely independent.
The qualities should be carefully considered while selecting protection schemes for power
system protection. Cost is also equally important. A better protective system costs more
This is the property by which only the faulty element of the system is isolate and
remaining healthy section should are left intact.
Discrimination is ‘the act Discriminating’ or ‘distinguishing the difference between’ the
following:
Normal Condition & Abnormal condition
The protective system should operate only during abnormal conditions and
should not operate under normal condition. In other words, the protective relaying system
should discriminate between normal condition and abnormal condition. It should select and
disconnect only faulty part without disconnecting the remaining healthy part.
Protective relaying should be inoperative and stable during faults and abnormal conditions
beyond its protective zone. It should not operate for faults, abnormal conditions beyond its protective
zone. Referring to below Fig, if a fault occurs on transmission line, the protective relaying should
isolate only the faulty line without tripping the neighbouring line or the transformer. For fault F1, only
circuit-breaker CB1 should open. For fault F2, both CB2 and CB3 should open.
If protective relaying is not selective, and operates for faults beyond its protective zones, a
larger portion of the system gets disconnected unnecessarity, causing embarrassment to supplier and
consumers
Fast Operation
A protective system should be fast enough to isolate the faulty element of the system as
quickly as possible to minimise damage to the equipment and to maintain the system stability.
Fault clearing time is the time between the instant of fault and instant of final are interruption (in
circuit breaker).
Fault clearing time is the sum of relay-time and circuit breaker-time.
The relay-time is the time between the instant of occurrence of fault and the instant of closure
of relay contacts. Or, it is the time between the instant when the operating quantity reaches the pick-
up value and the instant of closure of relay contacts.
The circuit breaker time is the total of time taken by operating mechanism to open to circuit
breaker contacts and the arching time. It is also called total break time.
1. Rapid fault clearing minimizes the damage. During short circuit tests on bus bars, with fault
duration of 0.07 second, with 60 kA R.M.S. value of current, no damage was observed after
the tests. With fault duration of 7 seconds, however, the bus bars were completely destroyed.
2. Rapid fault clearing improves power system stability. For the reason, the slow relays and slow
circuit breakers should not be preferred for protection, where stability is important. This ap-
plies to protection of EHV transmission lines, protection of large machines like important
generator, large transformer, large-motors, etc., and protection in important generating
stations and receiving stations
Though fast fault clearing is desirable, time lag is purposely provided in majority of protection
systems for the following purposes:
To permit discrimination between main and back-up protection.
To prevent the operation of relay during transients, starting currents, permissibly load fluc-
tuations, etc.
The relay-time of fast relays is of the order of a few cycles and that of inverse time relays can be
adjusted between about 6 seconds to 60 seconds. The circuit-breaker time of slow circuit- breakers is
of the order of 5 cycles and that of fast circuit-breakers is of the order of 2 cycles to 3 cycles.
Sensitivity
A protective relay should operate when the magnitude of the current exceeds the preset
(Pick-up) value. This value is called the pick-up current. The relay should not operate when the
current is below its pick-up value. A relay should be sufficiently sensitive to operate when the
operating current just exceeds its pick-up value.
Reliability
A protective relay must operate reliably when a fault occurs. The reliability of a
protective relay should be very high, a typical value being 95%.
Reliability means trustworthiness. The protective relaying should not fail to operate in
the event of faults in the protected zone. Secondly, there should not be any fault in the components
of protective system. Protective system should not operate unnecessarily. Reliability of protective sys-
tems is assessed from statistical data.
The protective system is teamwork of several components. A failure or defect in any one of
them can result in failure of protection system. Hence the basic requirement of reliable protection is
reliability of each component including circuit-breaker, relays, CT‘s, PT‘s secondary cables, trip
circuit, battery system accessories, etc.
To achieve a high degree of reliability, greater attention should be given to the design,
installation, maintenance and testing of the various elements of the protective system.
Robustness and simplicity of the relaying equipment also contribute to reliability.
Stability
This is the ability of the protective system to remain inoperative under all load conditions, and
also in case of external faults. The relay should remain stable when a heavy current due to an external
fault is flowing through it
OR
A protective system should remain stable even when a large current is flowing through
its protective zone due to an external fault, which does not lie in its zone. The concerned
circuit breaker is supposed to clear the fault. But the protective system will not wait
indefinitely if the protective e scheme of the zone in which fault has occurred fails to
operate. After a preset delay the relay will operate to trip the circuit breaker.
Adequateness
There can be many abnormal conditions and providing protection against every
abnormal condition is economically impossible. However, the protection provided for any
machine, should be adequate.
The adequateness of protection is judged by considering the following aspects :
Rating of the protected machine.
Location of the protected machine.
Probability of abnormal condition due to internal and external causes.
Cost of the machine, important.
Continuity of supply as affected by failure of machine.
for low voltage machine/equipment, at the remote end of the system, an elaborate and costly protec-
tive system is not necessary. For example, distribution transformers below, say 500 kVA arc protected
simply by drop-out fuses. Motors below 100 kW are protected by thermal over-load relays and HRC
fuses. In these cases, the cost of CT‘s and protective relays, circuit-breakers, etc. is not generally
justified. Whereas for a large machine, say generator, a very complex protective scheme is necessary.
The adequateness of protection should be assessed while planning the protection scheme. Each
installation generally needs particular attention, as the protective relaying needs are influenced by
local conditions
Introduction to Power System Protection Page 10
Power System Protection EEE, ATMECE, Mysuru
(i) First part is the primary winding of a current transformer (C.T.) which is connected in series with
the line to be protected.
(ii) Second part consists of secondary winding of C.T. and the relay operating coil.
(iii) Third part is the tripping circuit which may be either a.c. or d.c. It consists of a source of supply,
the trip coil of the circuit breaker and the relay stationary contacts. When a short circuit occurs at
point F on the transmission line, the current flowing in the line increases to an enormous value. This
results in a heavy current flow through the relay coil, causing the relay to operate by closing its
contacts. This in turn closes the trip circuit of the breaker, making the circuit breaker open and
isolating the faulty section from the rest of the system. In this way, the relay ensures the safety of the
circuit equipment from damage and normal working of the healthy portion of the system.
1.8 Instrument transformers. The lines in sub-stations operate at high voltages and carry current of
thousands of amperes. The measuring instruments and protective devices are designed for low
voltages (generally 110 V) and currents (about 5 A). Therefore, they will not work satisfactorily if
mounted directly on the power lines. This difficulty is overcome by installing instrument transformers
on the power lines. The function of these instrument transformers is to transfer voltages or currents in
the power lines to values which are convenient for the operation of measuring instruments and relays.
There are two types of instrument transformers viz.
(i) Current transformer (C.T.)
(ii) Potential transformer (P.T.)
(i) Current transformer (C.T.). A current transformer in essentially a step-up transformer which
steps down the current to a known ratio. The primary of this transformer consists of one or more turns
of thick wire connected in series with the line. The secondary consists of a large number of turns of
fine wire and provides for the measuring instruments and relays a current which is a constant fraction
of the current in the line. Suppose a current transformer rated at 100/5 A is connected in the line to
measure current. If the current in the line is 100 A, then current in the secondary will be 5A.
Similarly, if current in the line is 50A, then secondary of C.T. will have a current of 2·5 A. Thus the
C.T. under consideration will step down the line current by a factor of 20.
(ii) Voltage transformer. It is essentially a step down transformer and steps down the voltage to a
known ratio. The primary of this transformer consists of a large number of turns of fine wire
connected across the line. The secondary winding consists of a few turns and provides for measuring
instruments and relays a voltage which is a known fraction of the line voltage. Suppose a potential
transformer rated at 66kV/110V is connected to a power line. If line voltage is 66kV, then voltage
across the secondary will be 110 V.
Fig. above shows the use of instrument transformers. The *potential transformer rated 66,000/110V
provides a voltage supply for the potential coils of voltmeter and wattmeter. The current transformer
rated 1000/5 A supplies current to the current coils of wattmeter and ammeter. The use of instrument
transformers permits the following advantages:
(a) They isolate the measuring instruments and relays from high-voltage power circuits.
(b) The leads in the secondary circuits carry relatively small voltages and currents. This permits to use
wires of smaller size with minimum insulation.
1.9 Auto-Reclosing
Faults on overhead lines fall into one of three categories:
A. transient
B. semi-permanent
C. permanent
80-90% of faults on any overhead line network are transient in nature. The remaining 10%-20% of
faults are either semi-permanent or permanent
Most of the faults on over head lines are transient in nature. About 80% to 90% of faults are
momentary and caused by tree branches, lightning, birds etc. These conditions results in arcing faults
which lasts for very small duration and clears after that moment. The arc generated can be
extinguished and the line can be re energized. For this momentary faults which recovers on its own
normal circuit breaker operation of opening the faulty part is not advisable. Some provision should be
permitted in circuit breakers to close the breaker contacts if the fault is cleared momentarily. This fact
is employed as a basis for auto- reclosures.
In this scheme after the relays of both ends have picked up, the circuit breakers are tripped as for as
possible at the same time and reclosed after time has be allowed for deionization. The fault disappears
if it is transient and line is restored to normal service after the reclosure. If the fault is not cleared after
the first reclosure a double or triple attempt of separation and reclosure is made. If the fault still
persists, the breaker may permanently open till it is manually reset.
Auto reclosures may be single or three phase type. Mostly single phase auto reclosing breakers are
preferred as most of the transmission faults are single phase to ground faults. Auto reclosures of single
pole type improves the stability of the system as power remains transmitted through the remaining
two healthy phases when fault on one phase occurs.
The breakers may be rapid auto reclosing type (about 20 cycles or 0.4 sec) or delayed auto reclosing
(5 to 30s) type. For rapid reclosing type it is not required to check synchronism while reclosing
however for delay reclosing synchronism should be checked before reclosing. For this purpose
synchronous relays are employed
Use of an auto-reclose scheme to re-energise the line after a fault trip permits successful re-
energisation of the line. Sufficient time must be allowed after tripping for the fault arc to de-energise
prior to reclosing otherwise the arc will re-strike. Such schemes have been the cause of a substantial
improvement in continuity of supply. A further benefit, particularly to EHV systems, is the
maintenance of system stability and synchronism
These parameters are influenced by: a. type of protection b. type of switchgear c. possible stability
problems d. effects on the various types of consumer loads
Dead Time
Several factors affect the selection of system dead time as follows:
a. system stability and synchronism
b. type of load
c. CB characteristics
d. fault path de-ionisation time
Introduction to Power System Protection Page 13
Power System Protection EEE, ATMECE, Mysuru
Reclaim time
Factors affecting the setting of the reclaim time are
Type of protection
Spring winding time
Number of Shots Factors affecting the setting of the reclaim time are
Circuit breaker limitations
System conditions
A typical single-shot auto-reclose scheme is shown in below Figure. The fig. shows a successful
reclosure in the event of a transient fault,
As 80% of overhead line faults are transient, elimination of loss of supply from this cause by the
introduction of auto-reclosing gives obvious benefits through:
a. improved supply continuity
b. reduction of substation visits
Electromechanical Relays
Electromechanical relays are further classified into two categories, i.e.
(i) Electromagnetic relays, and
(ii) Thermal relays.
Electromagnetic relays:
Thermal relays
o Utilize the electro thermal effect of the actuating current for their operation.
Static Relays
These are solid state relays and employ semiconductor diodes, transistors, thyristors,
logic gates, ICs, etc. The measuring circuit is a static circuit and there are no moving parts. In
some static relays, a slave relay which is a D.C. polarised relay is used as the tripping device
Static relays contain electronic circuitry which may include transistors, ICs, diodes and other
electronic components. There is a comparator circuit in the relay, which compares two or more
currents or voltages and gives an output which is applied to either a slave relay or a thyristor circuit.
The slave relay is an electromagnetic relay which finally closes the contact. A static relay containing a
slave relay is a semi-static relay. A relay using a thyristor circuit is a wholly static relay. Static relays
possess the advantages of having low burden on the CT and VT, fast operation, absence of
mechanical inertia and contact trouble, long life and less maintenance. Static relays have proved to be
superior to electromechanical relays and they are being used for the protection of important lines,
power stations and sub-stations. Yet they have not completely replaced electromechanical relays.
Static relays are treated as an addition to the family of relays. Electromechanical relays continue to be
in use because of their simplicity and low cost. Their maintenance can be done by less qualified
personnel, whereas the maintenance and repair of static relays requires personnel trained in solid state
Numerical Relays
A numerical relay is that in which the measured ac quantities are sequentially sampled and
converted into numerical (digital) data form. A microprocessor or a microcontroller processes the data
numerically (i.e., performs mathematical and/or logical operations on the data) using an algorithm to
calculate the fault discriminants and make trip decisions.
Microprocessor-based relay:
A microprocessor is used to perform all functions of a relay. It measures electrical quantities,
makes comparisons, performs computations, and sends tripping signals. It can realize all sorts of
relaying characteristics, even irregular curves which cannot be realised by electromechanical or static
relays easily.
Microcontroller-based relay:
A microcontroller is used for performing all the function of the relay. It measures the
electrical quantities by acquiring them in digital form through a data acquisition system, makes
comparisons, processes the digital data to calculate the fault discriminants and make trip decisions. It
can realised all sorts of relaying characteristics
These are some important relays many other relays specifying their duty they perform can be
put under this type of classification. The duty which a relay performs is evident from its name. For
example, an over current relay operates when the current exceeds a certain limit, an impedance relay
measures the line impedance between the relay location and the point of fault and operates if the point
of fault lies within the protected section. Directional relays check whether the point of fault lies in the
forward or reverse direction
High-speed Relays
These relays operate in less than a specified time. The specified time in present practice is 60
milliseconds (3 cycles on a 50 Hz system).
A protective scheme is used to protect an equipment or a section of the line. It includes one or
more relays of the same or different types. The following are the most common protective schemes
which are usually used for the protection of a modem power system.
Over current protection
Distance protection
Differential protection
Over current Protection
This scheme of protection is used for the protection of distribution lines, large motors,
equipment, etc. It includes one or more over current relays. An over current relay operates when the
current exceeds its pick-up value.
Distance Protection
Distance protection is used for the protection of transmission or sub-transmission lines;
usually 33 kV, 66 kV and 132 kV lines. It includes a number of distance relays of the same or
different types. A distance relay measures the distance between the relay location and the point of
fault in terms of impedance, reactance, etc. The relay operates if the point of fault lies within the
protected section of the line. There are various kinds of distance relays. The important types are
impedance, reactance and mho type. An impedance relay measure the line impedance between the
fault point and relay location; a reactance relay measures reactance, and a mho relay measures a
component of admittance.
Differential Protection
This scheme of protection is used for the protection of generators, transformers, motors of
very large size, bus zones, etc. CTs are placed on both sides of each winding of a machine. The
outputs of CT secondary are applied to the relay coils. The relay compares the current entering a
machine winding and leaving the same. Under normal conditions or during any external fault, the
current entering the winding is equal to the current leaving the winding. But in the case of an internal
fault on the winding, these are not equal. This difference in the current actuates the relay. Thus, the
relay operates for internal faults and remains inoperative under normal conditions or during external
faults. In case of bus zone protection, CTs are placed on the both sides of the Bus bar.
(i) Attracted armature type relay. Fig. shows the schematic arrangement of an attracted armature type relay. It
consists of a laminated electromagnet M carrying a coil C and a pivoted laminated armature. The armature is
balanced by a counterweight and carries a pair of spring contact fingers at its free end. Under normal operating
conditions, the current through the relay coil C is such that counterweight holds the armature in the position
shown. However, when a short-circuit occurs, the current through the relay coil increases sufficiently and the
relay armature is attracted upwards. The contacts on the relay armature bridge a pair of stationary contacts
attached to the relay frame. This completes the trip circuit which results in the opening of the circuit breaker
and, therefore, in the disconnection of the faulty circuit. The minimum current at which the relay armature is
attracted to close the trip circuit is called pickupcurrent. It is a usual practice to provide a number of tappings on
the relay coil so that the number of turns in use and hence the setting value at which the relay operates can be
varied.
(ii) Solenoid type relay. Below Fig. shows the schematic arrangement of a solenoid type relay. It consists of a
solenoid and movable iron plunger arranged as shown. Under normal operating conditions, the current through
the relay coil C is such that it holds the plunger by gravity or spring in the position shown. However, on the
occurrence of a fault, the current through the relay coil becomes more than the pickup value, causing the plunger
to be attracted to the solenoid. The upward movement of the plunger closes the trip circuit, thus opening the
circuit breaker and disconnecting the faulty circuit
(iii) Balanced beam type relay. Below Fig. shows the schematic arrangement of a balanced beam type relay. It
consists of an iron armature fastened to a balance beam. Under normal operating conditions, the current through
the relay coil is such that the beam is held in the horizontal position by the spring. However, when a fault
occurs, the current through the relay coil becomes greater than the pickup value and the beam is attracted to
close the trip circuit. This causes the opening of the circuit breaker to isolate the faulty circuit
To understand the production of torque in an induction relay, refer to the elementary arrangement
shown in Fig.(i). The two a.c. fluxes 2 and 1 differing in phase by an angle α induce e.m.f.s‘ in the
disc and cause the circulation of eddy currents i2 and i1 respectively. These currents lag behind their
respective fluxes by 90º. Referring to Fig.(ii) Where the two a.c. fluxes and induced currents are
shown separately for clarity,
let φ1 = φ1max sin ω t
φ2 = φ2max sin (ω t + α)
where φ1 and φ2 are the instantaneous values of fluxes and φ2 leads φ1 by an angle α.
Assuming that the paths in which the rotor currents flow have negligible self-inductance, the
Introduction to Power System Protection Page 19
Power System Protection EEE, ATMECE, Mysuru
Now, F1 ∝ φ1 i2 and F2 ∝ φ2 i1
Fig. (ii) shows that the two forces are in opposition.
∴ Net force F at the instant considered is
F ∝ F2 − F1
∝ φ2 i1 − φ1 i2
∝ φ2max sin (ω t + α) φ1max cos ω t − φ1max sin ωt φ2max cos (ω t + α)
∝ φ1max φ2max [sin (ω t + α) cos ω t − sin ω t cos (ω t + α)]
∝ φ1max φ2max sin α
∝ φ1 φ2 sin α ... (i)
The following three types of structures are commonly used for obtaining the phase difference in
the fluxes and hence the operating torque in induction relays :
(i) shaded-pole structure
(ii) watthour-meter or double winding structure
(iii) induction cup structure
(i) Shaded-pole structure. The general arrangement of shaded-pole structure is shown in below Fig.
It consists of a pivoted aluminium disc free to rotate in the air-gap of an electromagnet. One half
of each pole of the magnet is surrounded by a copper band known as shading ring. The alternating
flux φs in the shaded protion of the poles will, owing to the reaction of the current induced in the
ring, lag behind the flux φu in the unshaded portion by an angle α. These two a.c. fluxes differing in
phase will produce the necessary torque to rotate the disc. As proved earlier, the driving torque T is
T ∝ φs φu sin α
Assuming the fluxes φs and φu to be proportional to the current I in the relay coil,
T ∝ I2 sin α
This shows that driving torque is proportional to the square of current in the relay coil
(ii) Watthour-meter structure. This structure gets its name from the fact that it is used in watthour
meters. The general arrangement of this type of relay is shown in Fig. It consists of a pivoted
aluminium disc arranged to rotate freely between the poles of two electromagnets. The upper
electromagnet carries two windings ; the pirmary and the secondary. The primary winding carries the
relay current I1 while the secondary winding is connected to the winding of the lower magnet. The
primary current induces e.m.f. in the secondary and so circulates a current I2 in it. The flux φ2
induced in the lower magnet by the current in the secondary winding of the upper magnet will lag
behind φ1 by an angle α. The two fluxes φ1and φ2 differing in phase by α will produce a driving
torque on the disc proportional to φ1φ2 sin α.
An important feature of this type of relay is that its operation can be controlled by opening or
closing the secondary winding circuit. If this circuit is opened, no flux can be set by the lower magnet
however great the vaule of current in the pirmary winding may be and consequently no torque will be
produced. Therefore, the relay can be made inoperative by opening its secondary winding circuit
Induction cup structure. Fig. shows the general arrangement of an induction cup structure. It most
closely resembles an induction motor, except that the rotor iron is stationary, only the rotor conductor
portion being free to rotate. The moving element is a hollow cylindrical rotor which turns on its axis.
The rotating field is produced by two pairs of coils wound on four poles as shown.
The rotating field induces currents in the cup to provide the necessary driving torque. If φ1 and φ2
represent the fluxes produced by the respective pairs of poles, then torque produced is proportional to
φ1φ2 sin α where α is the phase difference between the two fluxes. A control spring and the back stop
for closing of the contacts carried on an arm are attached to the spindle of the cup to prevent the
continuous rotation. Induction cup structures are more efficient torque producers than either the
shaded-pole or the watthour meter structures. Therefore, this type of relay has very high speed and
may have an operating time less then 0·1 second
Restraining (Control) force or torque: A force or torque which opposes the operating force/ torque.
Actuating quantity: An electrical quantity (current, voltage, etc) to which relay responds
PICK-UP:
When the relay operates, we say, the relay has picked-up. It simply means that the relay with normally
open contacts, has closed its contacts.
The pick-up value or pick-up level is the minimum value of operating quantity at which the relay is one
the verge of operation, e.g., consider an over current relay. The current injected in the relay coil is very
gradually increased. At a current value of 2.51 amperes, the relay has not operated, at a value at a value of
2.52 amperes, the relay begins to operate. Then, 2.52 amperes is the pick-up value.
In induction disc relays, the pick-up value corresponds to plug-setting (described later). If plug setting
is 2.5 A, the relay starts operating at 2.5 A. If plug setting is 3.5 A, relay starts operating at 3.5 A and so on.
However, in such relays the pick-up value is not exact, within about 5% of plug setting. The relay may not
pick-up exactly at the plug setting value due to errors introduced by dust, friction, adjustment errors; and
because operating torque is minimum at pick-up value.
In these relays, there is a facility for selecting the plug setting and time setting such that the same
relay can be used for a wide range of current, time and characteristics.
Time Setting in Induction Disc Relays
Time multiplier setting is generally in the form of an adjustable back-stop which decides the arc-length
through which the disc travels, by reducing the length of travel, the time is reduced. The time multiplier setting
is marked from about 0.1 to 1, with major divisions marked in between. If relay takes a certain time, say S
seconds with time multiplier setting 1, the same relay will take time equal to T x S seconds for time multiplier
setting T, other conditions remaining the same.
I.e. Actual Operating Time of Relay = Time multiplier setting x Trip Time (Time required to close the
contacts)
Plug Setting in Induction Disc Relays
It should be possible to use the same relay for a certain range of current/voltage. Hence a plug setting
bridge is provided with electromagnetic relays. The plug setting refers to the reference value of operating
quantity at which the relay starts operating. If by inserting the plug, setting of 2.5 is selected, the relay will start
operating when the current in relay coil (secondary current of (CT) is about 2.5 A or more. Plug setting
determines the number of turns tapped from the relay coil. The current-time characteristic for various plug
setting is generally same, provided time setting remains unchanged. Such performance is achieved by matching
the plug-setting and corresponding number of turns tapped from the coil such that the Ampere-turns remains
same for various plug-settings
The arrangement is such that for various plug settings, the ampere-turns (amperes of plug setting x
turns of coil corresponding to the plug setting) are constant for various plug settings. Thereby, the relay
characteristics remains the same for various plug settings, for a given time setting. Actually, the relay should
start operating at current equal to plug setting. However, due to friction, dust etc, the operations may not take
Effect of Time-setting
By reducing the time multiplier, the characteristic is shifted to lower side, indicating that operating time is
reduced (Fig. 1)
Operating time: It is the time which elapses from the instant at which the actuating quantity exceeds the
relays pick-up value to the instant at which the relay closes its contacts.
Burden (Power consumption): The power consumed by the relay circuitry at the rated current or
voltage is known as its burden expressed in volt ampere in a.c and in watts in d.c circuit
Directional or reverse power relay: A directional relay is able to detect whether the point of fault lies in
the forward or reverse direction with respect to the relay location. It is able to sense the direction of power
flow, i.e. whether the power is flowing in the normal direction or the reverse direction
The operating time of all over current relays tends to become asymptotic (Straight Line) to a definite
minimum value with increase in the value of current. This is inherent in electromagnetic relays due to
saturation of the magnetic circuit. So by varying the point of saturation different characteristics are obtained;
these are:
Definite time.
Inverse characteristics
Inverse definite minimum time (IDMT).
Very inverse.
Extremely inverse
These characteristics are obtained by induction disc and induction cup relays.
The torque of these relays as shown earlier is proportional to Ø 1*Ø2*Sinα where Ø1 and Ø2 are the two
fluxes cutting the disc or cup and α is the angle between them. Where both fluxes are produced by the same
quantity, as in current or voltage operated relays, then below saturation the torque is proportional to I², the coil
current, or T=KI². If the core is made to saturate at very early stage with the result that by increasing I, K
decreases so that the time of operation remains same over the working range, the characteristics is shown by
curve (a) in fig1 and is known as definite minimum time characteristics i.e. (DMT) irrespective of the magnitude
of the current above the pickup value, the operating time is the same (i.e. the time of operation is almost
definite), however, DMT relay has also a slightly inverse characteristics.
In the case of inverse time characteristics, the relay operating time decreases as the current above the
pickup value increases (i.e. time is inversely propositional to current)
Now if the core is made to saturate at a later stage the characteristics assume the shape of curve (b) Fig 1, known
as IDMT (inverse definite minimum time (IDMT) characteristic)
The characteristics of DMT & of inverse time characteristics type is called inverse definite minimum time
(IDMT) characteristics as show in fig
In case of inverse definite minimum time (IDMT) Relay, the operating characteristics will be inverse time
characteristics at lower value of the fault current and DMT characteristics at higher values of fault current.
Now if the core saturation occurs at a still later stage the characteristics assume the shape show by the curve (C)
in fig 1 known as very inverse. The time-current characteristic is inverse over a greater range and after
saturation tend to definite time.
The curve (d) in fig 1 shows extremely inverse characteristics i.e. the saturation occurs at a very late stage and
the equation of the curve is roughly of the form I²t=k where I is the operating current and t is the time of
operation.
Example Determine the time of operation of a 5-ampere, 3-second overcurrent relay having a current
setting of 125% and a time setting multiplier of 0·6 connected to supply circuit through a 400/5
current transformer when the circuit carries a fault current of 4000 A. Use the curve (TMS = 1) shown
in Fig. 21.16.
Solution.
Rated secondary current of C.T. = 5 A
Corresponding to the plug-setting multiplier of 8 (See Fig. 21.16), the time of operation is 3.5seconds.
∴ Actual relay operating time = 3·5 × Time-setting multiplier = 3·5 × 0·6 = 2·1 seconds
Course outcomes Discuss performance of protective relays, components of protection scheme and relay
terminology
Further Readings
1. http://nptel.ac.in/downloads/108101039/
2. https://www.electrical4u.com/protection-system-in-power-system/
3. http://electrical-engineering-portal.com