NATIONAL STANDARD OF THE
GB 50116-2013
Issued on: September 06, 2013 Implemented on: May 01, 2014
Issued by: Ministry of Housing and Urban-Rural Development of the
People's Republic of China
www.ChineseStandard.net Page 1 of 66
GB 50116-2013
Table of Contents
Foreword ............................................................................................................................ 6
1 General Provisions ......................................................................................................... 8
2 Terms............................................................................................................................ 9
3 Basic Requirement ....................................................................................................... 10
3.1 General Requirements .................................................................................................... 10
3.2 Choice and Design of System ........................................................................................ 10
3.3 Division of the Alarm Zone and Detection Zone ........................................................... 11
3.4 Fire Control Center ........................................................................................................ 12
4 Automatic Control Design............................................................................................. 14
4.1 General Requirements .................................................................................................... 14
4.2 Automatic Control Design of the Automatic Sprinkler System ..................................... 14
4.3 Automatic Control Design of Fire Hydrant System ....................................................... 16
4.4 Automatic Control Design of Gases (Bubble) Fire-extinguishing System .................... 16
4.5 Automatic Control Design of Smoke Exhaust System .................................................. 18
4.6 Automatic Control Design of Fire Door and Fire Roller Shutter System ...................... 19
4.7 Automatic Control Design of Elevator ........................................................................... 20
4.8 Automatic Control Design of the Fire Alarm and Signalling Device............................. 20
4.9 Automatic Control Design of the Fire Emergency Lighting System ............................. 21
4.10 Automatic Control Design of the Related Equipment .................................................. 21
5 Fire Detector Choice..................................................................................................... 23
5.1 General Requirements .................................................................................................... 23
5.2 Choice of Point Type Fire Detector ................................................................................ 23
5.3 Choice of Line type Fire Detector .................................................................................. 26
5.4 Choice of Aspirating Smoke Detector ............................................................................ 28
6 Setting of the Equipment ............................................................................................... 29
6.1 Setting of the Fire Alarm Control Unit and Automatic Control Equipment ................... 29
6.2 Setting of the Fire Detector ............................................................................................ 29
6.3 Setting of the Manual Call Point .................................................................................... 35
6.4 Setting of the Fire Display Panel ................................................................................... 35
6.5 Setting of the Fire Alarm Singalling Device .................................................................. 35
6.6 Setting of the Sounder Equipment for Fire Emergency Purposes .................................. 35
6.7 Setting of the Fire Telephone ......................................................................................... 36
6.8 Setting of the Module ..................................................................................................... 36
6.9 Setting of the Graph Indicator in Fire Control Center .................................................... 37
6.10 Setting of the Routing Equipment ................................................................................ 37
6.11 Setting of the Indicator and Control Unit for Fire Doors ............................................. 37
7 Fire Alarm and Safety System Installed in Dwelling Building ........................................... 38
7.1 General Requirement ..................................................................................................... 38
7.2 System Design ................................................................................................................ 38
7.3 Setting of the Fire Detector ............................................................................................ 39
7.4 Setting of the Fire Alarm Control Unit for Household ................................................... 39
www.ChineseStandard.net Page 4 of 66
GB 50116-2013
www.ChineseStandard.net Page 5 of 66
GB 50116-2013
1 General Provisions
1.0.1 This code is formulated with view to rational design of automatic fire alarm system,
prevention and reduction of fire hazards and protection of the personal and property safety.
1.0.2 This code is applicable to design of automatic fire alarm system located in the
constructed, renovated and extended building and structure but not applicable to that located
at the places for production and storage of gunpowder, explosive, ammunition and explosive
device.
1.0.3 Aimed at the features of the protected objects, the design of automatic fire alarm
system shall comply with the relevant national guideline and policy and realize the safety and
reliability, advanced technology and economic feasibility.
1.0.4 The design of automatic fire alarm system shall not only comply with this code but
those in the current relevant standards of the nation.
www.ChineseStandard.net Page 8 of 66
GB 50116-2013
2 Terms
www.ChineseStandard.net Page 9 of 66
GB 50116-2013
3 Basic Requirement
3.1.1 The automatic fire alarm system may be used at the places where the persons live or
stay frequently and those where the valuable supplies are stored or the serious pollution will
be alarmed timely after the burning.
3.1.2 The automatic fire alarm system shall be equipped with automatic and manual trigger
gears.
3.1.3 The automatic fire alarm system device shall select the products in conformity with
relevant national standards and related to the market-access system.
3.1.4 Compatibility of interfaces among system devices with the communication protocols
shall meet the relevant requirements of the current standard GB 22134 "Compatibility
Requirements of Automatic Fire Alarm System Components".
3.1.5 The total amount of fire detector, manual fire alarm call point and module connected
with any fire alarm control unit and the total addresses shall not exceed 3200 points and the
total amount of the connecting devices for each bus circuit should not exceed 200 points and
at least an allowance of 10% of rated capacity shall be reserved; the total amount of addresses
for any automatic controller for fire protection or total amount of various modules controlled
by the (linkage-type) fire alarm control unit shall not exceed 1600 points and the total amount
of the connecting device for each linkage bus circuit should not exceed 100 points and at least
an allowance of 10% of rated capacity shall be reserved.
3.1.6 The short circuit isolator shall be arranged at the system bus and the total amount of
the fire equipment protected by the isolator, like fire detector, manual fire alarm call point and
module shall not exceed 32 points; the short circuit isolator shall be arranged at the place
where the bus goes through the fire zone where necessary.
3.1.7 In the 100m or over long buildings, the fire detector, manual alarm button, module, etc.
which are controlled by each controller shall not cross over the refuge storey other than the
controller located in the Fire control center.
3.1.8 Variable frequency startup mode shall not be adopted for the electric fire control unit
like pump control cabinet and fan control cabinet.
3.1.9 The automatic fire alarm system located at the subway trains shall send the fire
position information to the trains via wireless network, etc.
3.2.1 Choice of automatic fire alarm system shall meet the following requirements:
1 The local alarm system should be adopted for the protected object with alarm needed
but without the necessity to link the automatic fire equipment.
2 The centralized alarm system shall be adopted for the protected objects which need
the alarm and automatic fire equipment and on which only one fire alarm control unit and
automatic controller for fire protection with centralized control and a Fire control center shall
be arranged.
www.ChineseStandard.net Page 10 of 66
GB 50116-2013
shall be determined according to demand of fume exhaust system or fire extinguishing system
and should not exceed 150m.
3 The alarm zones of Class A, B and C liquid tank area shall be composed by one tank
area and each 50000m3 or above outer floating roof tank shall be classified into one
independent alarm zone.
4 Alarm zone of train shall be divided in accordance with cars and each car shall be
classified into one alarm zone.
3.3.2 Division of detection zone shall meet the following requirements:
1 The detection zone shall be divided according to the independent room (suite). The
area for one detection zone should not exceed 500m2; the rooms of which the internal can be
seen clearly from the main entrance and the area shall not exceed 1000m2 may also be
classified into one detection zone.
2 The length of detection zone for infrared beam smoke fire detector and cable type
linear heat fire detector should not exceed 100m; detection zone length of air pipe
temperature difference fire detector should be at 20m~100m.
3.3.3 Independent detection zone shall be divided for the following places:
1 Open or enclosed staircase and smoke-proof staircase.
2 Smoke-proof staircase front room, fire elevator front room, front room served for fire
elevator and smoke-proof staircase, runway and ramp.
3 Electrical piping shafts, communication piping shafts and cable tunnel.
4 Building loft and interlayer.
3.4.1 Fire control center shall be arranged for the protected object of automatic fire alarm
system in possession of automatic functions for fire protection.
3.4.2 The fire equipment located in the fire control center shall cover fire alarm control unit,
automatic controller for fire protection, graphic display unit in fire control center, switchboard
for special telephone for fire, fire emergency broadcast control device, control device for fire
emergency lighting and evacuate indicating system, fire power supply monitor, combination
unit in possession of corresponding functions. The graphic display unit in fire control center
located in fire control center shall be able to display the dynamic information of all the fire
fighting system and relevant equipment within the buildings specified in Appendix B of this
code and the fire safety management information specified in Appendix B and the interfaces
for the remote monitoring system shall be reserved and the functions of sending relevant
information specified in Appendix A and Appendix B to the remote monitoring system shall
be provided.
3.4.3 The fire control center shall be equipped with the outside line used for fire alarm.
3.4.4 The fire control center shall be provided with the corresponding completion drawings,
each subsystem control logic relationship description, equipment operation instruction,
system operation regulations, emergency plan, duty system, maintenance system and
documentary data like log.
3.4.5 The fire valve shall be arranged at the place where the supply and return air duct in
fire control center passes through the wall.
www.ChineseStandard.net Page 12 of 66
GB 50116-2013
4.1.1 The automatic controller for fire protection shall send the control signal to start & stop
an automatic equipment to each relevant controlled equipment according to the preset control
logics and receive the feedback signal from automatic equipment of the relevant equipment.
4.1.2 As for the automatic controller for fire protection, the voltage control output shall
adopt dc 24V so that the power supply capacity can meet the requirements to simultaneously
starting and keeping the working of controlled fire equipment.
4.1.3 The characteristic parameter of each controlled equipment interfaces shall be matched
with the control signal to start & stop an automatic equipment generated from automatic
controller for fire protection.
4.1.4 The control equipment of fire pump and smoke control and smoke exhaust fan shall
not only adopt automatic control but also set manual direct control device at the fire control
center.
4.1.5 Fire equipment with larger starting current should be started up at different time.
4.1.6 As for the fire equipment requiring automatic control of automatic fire alarm system,
the signal for logical program shall adopt " and " logical combination of alarm signal of two
independent alarm trigger gears.
4.2.1 Automatic control design of wet pipe system and dry pipe system shall meet the
following requirements:
1 The automatic control method shall use the operation signal of wet alarm valve
pressure switch as the triggering signal to directly control and start the sprinkling fire pump
and the automatic control shall not be affected by the automatic or manual state of automatic
controller for fire protection.
2 In the manual control, the start up and stop button of sprinkling fire pump control
box (cabinet) shall be connected directly to the manual control disc of automatic controller for
fire protection in fire control center with the dedicated line to manually control the start up
and stop of sprinkling fire pump directly.
3 The operation signal of start up and stop of water flow indicator, signal valve,
pressure switch and sprinkling fire pump shall be returned to the automatic controller for fire
protection.
4.2.2 Automatic control design of precaution system shall meet the following requirements:
1 In the automatic control, the alarm signal of two or more independent smoke fire
detector or one smoke fire detector and one manual fire alarm call point as the signal for
logical program for opening of pre-action valve set. The automatic controller for fire
protection shall control the opening of the pre-action valve set so that the system turns into
the wet pipe system; when the system is provided with rapid exhauster, the opening of electric
www.ChineseStandard.net Page 14 of 66
GB 50116-2013
protection shall make an automatic control over the opening of relevant control valve set of
water curtain system.
2 In the manual control, the startup and stop button of water curtain system relevant
control valve set and fire pump control box (cabinet) shall be connected directly to the manual
control disc of automatic controller for fire protection in fire control center with the dedicated
line to manually control the start up and stop of water curtain system relevant control valve
set directly.
3 The operation signal of start up and stop of pressure switch, water curtain system
relevant control valve set and fire pump shall be returned to the automatic controller for fire
protection.
4.3.1 In the automatic control, the signal for low voltage pressure switch located on main
outlet pipe of fire hydrant system and the flow switch or alarm valve located on outlet pipe of
elevated water tanks shall be used as the trigger signal to directly control the opening of fire
hydrant pump; the automatic control shall not be affected by the automatic or manual state of
automatic controller for fire protection. When the fire hydrant button is provided, the
operation signal of fire hydrant button shall be used as the alarm signal and signal for logical
program to opening fire hydrant pump and the opening of fire hydrant pump shall be
subjected to the automatic control by the automatic controller for fire protection.
4.3.2 In the manual control, the startup and stop button of fire hydrant pump control box
(cabinet) shall be connected directly to the manual control disc of automatic controller for fire
protection in fire control center with the dedicated line to manually control the startup and
stop of fire hydrant pump directly.
4.3.3 Operation signal of fire hydrant pump shall be returned to the automatic controller for
fire protection.
4.4.1 The gases (bubble) fire extinguishing system shall be controlled by the specialized gas
fire extinguishing controller and bubble fire extinguishing controller respectively.
4.4.2 The automatic control mode of gases (bubble) fire extinguishing system shall meet the
following requirements when the gas fire extinguishing controller and bubble fire
extinguishing controller are directly connected with the fire detector:
1 The alarm signal of two independent fire detectors within the same protected zone, of
one fire detector and one manual fire alarm call point or the emergency starting signal beyond
the protected zone are used as the signal for logical program of the system; the detector
should adopt the combination of smoke fire detector and heat fire detector and the detectors
shall be subjected to the calculation of monitoring area according to 6.2 of this code.
2 After the gas fire extinguishing controller and bubble fire extinguishing controller
have received the first signal for logical program to meet the automatic logical relation, the
audible and visible fire alarm device in the protected zone shall be started up and the signal
for logical program shall be the first alarm signal of smoke fire detector and other types of fire
www.ChineseStandard.net Page 16 of 66
GB 50116-2013
2 The manual startup and stop button different from the protected zone shall be
arranged on the gas fire extinguishing controller and bubble fire extinguishing controller;
when the manual startup button is pushed down, the gas fire extinguishing controller and
bubble fire extinguishing controller shall carry out the operation in Item 3 and Item 5 in 4.4.2
of this code; when the manual stop button is pushed down, the gas fire extinguishing
controller and bubble fire extinguishing controller shall stop the working operation.
4.4.5 The feedback signal for the gas fire extinguishing device and bubble fire extinguishing
device and automatic control at different opening and spraying stages and for the system shall
be returned to the automatic controller for fire protection. The feedback signal from automatic
equipment of the system shall cover the following items:
1 Alarm signal of fire detector directly connected with gas fire extinguishing controller
and bubble fire extinguishing controller.
2 Operation signal of selector valve.
3 Operation signal of pressure switch.
4.4.6 As for system arranged with manual and automatic control conversion device at the
protected zone, the operation state of manual or automatic control mode shall be displayed on
the manual and automatic control status display in and out of the protected zone and the
information shall be returned to the automatic controller for fire protection.
4.5.1 Automatic control method of smoke control system shall meet the following
requirements:
1 The alarm signal of two independent fire detectors or one fire detector and one
manual fire alarm call point at the fire zone where the pressurization air supply outlet is
located is used as the signal for logical program for start of air supply outlet and forced
draught blower and the automatic controller for fire protection shall make an automatic
control over the startup of the pressurization air supply outlet and forced draught blower at the
place where the pressurization air supply is needed like front room of relevant floor.
2 The alarm signal of two independent smoke fire detectors at the same smoke zone
and nearby the electric ceiling screen shall be used as the signal for logical program for
electric ceiling screen falling and the automatic controller for fire protection shall have an
automatic control over the falling of electric ceiling screen.
4.5.2 Automatic control of smoke exhaust system shall meet the following requirements:
1 The alarm signal of two independent fire detectors at the same smoke zone shall be
used as the signal for logical program for opening of smoke vent, exhaust louver or smoke
exhaust damper and the automatic controller for fire protection shall have an automatic
control over opening of smoke vent, exhaust louver or smoke exhaust damper and stop of air
conditioning system of smoke zone.
2 The operation signal of opening of smoke vent, exhaust louver or smoke exhaust
damper shall be used as the signal for logical program of starting up of smoke discharge fan
and the automatic controller for fire protection shall have an automatic control over the
startup of smoke discharge fan.
www.ChineseStandard.net Page 18 of 66
GB 50116-2013
2 In the manual control, the manual control at both sides of fire roller shutter shall
control the lifting and falling of fire roller shutter and the falling of fire roller shutter shall be
manually controlled by automatic controller for fire protection at fire control center.
4.6.5 The operation signal of falling of fire roller shutter to 1.8m from the floor slab and to
the floor slab and the alarm signal of fire roller shutter controller directly connected to the
smoke and heat fire detectors shall be returned to the automatic controller for fire protection.
4.7.1 The automatic controller for fire protection shall be able to send out the control signal
to start & stop an automatic equipment to make all the elevators stop at the first floor or
elevator transfer floor.
4.7.2 The feedback signal of running state information and stopping at the first floor or
transfer floor shall be returned to the fire control center display and the special telephone shall
be provided in the elevator car to have a conversation with the fire control center directly.
4.8 Automatic Control Design of the Fire Alarm and Signalling Device
4.8.1 The automatic fire alarm system shall be equipped with audible and visible fire alarm
device and start up all the audible and visible fire alarm devices in a building after the
confirmation.
4.8.2 As for the automatic fire alarm system without automatic controller for fire protection,
the audible and visible fire alarm device shall be controlled by the fire alarm control unit; as
for the automatic fire alarm system with automatic controller for fire protection, the audible
and visible fire alarm device shall be controlled by the fire alarm control unit or automatic
controller for fire protection.
4.8.3 The fire sound alarm with the same fire modified tone shall be set at the public places;
the fire sound alarm with voice prompt should be selected for the protected object with
multiple alarm zones; the alarm bell shall not be used as the fire sound alarm at the place
using the electrical bell as daily use like the school and factory.
4.8.4 The voice synchronizer shall be set when the fire sound alarm is provided with the
voice prompt function.
4.8.5 The automatic fire alarm system shall start up and stop all the fire sound alarms
simultaneously when multiple fire sound alarms are provided at the same building.
4.8.6 The fire sound alarm shall send the fire alarm for 8s~20s each and when the fire sound
alarm is used, the fire alarm shall be played alternately with the fire sound alarm.
4.8.7 Fire emergency broadcast shall be arranged for centralized alarm system
4.8.8 Control signal to start & stop an automatic equipment of fire sound alarm system shall
be sent out by the automatic controller for fire protection. After the confirmation of fire
hazards, the whole building shall be announced simultaneously.
4.8.9 The fire sound alarm should last the voice for 10s~30s each time and shall work
alternately with the fire sound alarm at the different time and the circulating and alternate play
of one fire sound alarm play and one or two fire sound alarm play may be adopted.
www.ChineseStandard.net Page 20 of 66
GB 50116-2013
4.8.10 In the fire control center, the manual control or the automatic control according to
preset control logic shall be used to select broadcast zone and start up or stop and monitor the
fire sound alarm. The sound recording shall be done automatically when the emergency
broadcast is conducted by the microphone.
4.8.11 The working state of broadcast zone of fire emergency broadcast shall be shown in
the fire control center.
4.8.12 The function of cutting in fire emergency broadcast forcibly shall be provided when
fire emergency broadcast is used together with ordinary broadcast or background music
broadcast.
4.9.1 Automatic control design of the fire emergency lighting system shall meet the
following requirements:
1 The centralized control type fire emergency lighting system shall be realized through
the starting of the emergency lighting controller by the fire alarm control unit or automatic
fire-fighting controller.
2 The fire emergency lighting system of intensive power supply and non-centralized
control type shall be realized by the intensive emergency lighting power supply linked by the
non-centralized control type shall be realized by the intensive emergency lighting distribution
4.9.2 When the fire is confirmed, the fire emergency lighting system of the exit
passageways in the whole building is orderly started up from the alarm zone of the fire, the
starting time that the system takes to enter into the emergency state totally shall not be greater
than 5s.
4.10.1 The automatic fire-fighting controller shall be provided with the function of cutting
the non-fire power in the conflagration area and relevant areas, the normal illumination
should be cut down before the action of the automatic spraying system, fire hydrant system if
needed.
www.ChineseStandard.net Page 21 of 66
GB 50116-2013
5.1.1 The choice of fire detectors shall meet the following requirements:
1 The smoke fire detector shall be selected for the places where there is the smoldering
stage in the early stage of the fire and large amount of smoke and small amount of heat and
2 The one of or a combination of the heat fire detector, smoke fire detector, flame
detector may be selected for the places where the fire spreads rapidly and a great deal of heat,
3 The flame detector shall be selected for the places where the fire spreads rapidly and
4 The carbonic oxide fire detector should be added for the places where there is the
smoldering stage in the early stage of the fire and that need early detection.
5 The incombustible gas detector shall be selected for the places where the combustible
6 The fire detector shall be selected according to relative analyses of the incendiary
material and possible parts to cause fire as well as the type, sensitivity and response time of
the fire detector, for the places where the form characteristics of the fire are unpredictable, the
fire detector may be selected according to the result of the simulation test.
7 The fire detector and fire alarm control unit with the function of compound
judgement towards fire may be selected when multiple fire detectors are set in a detecting
area.
5.2.1 For rooms of different height, the point type fire detector may be selected according to
Table 5.2.1.
www.ChineseStandard.net Page 23 of 66
GB 50116-2013
5.2.5 The places under one of the following conditions should choose point type heat fire
detector and shall choose the heat fire detector of proper classification according to the typical
4 The places where the smoke or steam is detained under normal conditions.
5 The places where the smoke fire detector should not be installed, such as the kitchen,
6 The inner side of the emergency exit that needs automatic extinction marker light
"emergency exit".
7 Other places where no one stays and that are unsuitable to install the smoke fire
5.2.6 The point type heat fire detector should not be selected for the places where the
smoldering fire may happen or heavy losses will be caused if the alarm is not in time when
the fire happens; the constant temperature detector should not be selected for the places under
0℃; the detector with differential temperature characteristic should not be selected for the
5.2.7 The places under one of the following conditions should choose point type fire
5.2.8 The places under one of the following conditions should not choose point type fire
3 The sight of the detector is easy to be sheltered by the oil mist, smog, water fog and
www.ChineseStandard.net Page 25 of 66
GB 50116-2013
5.3.2 The places under one of the following conditions should not choose line type light
4 The places where the building structure that fixes the detector may cause large bias
5.3.3 The cable line type heat fire detector should be selected for the following places or
parts:
2 The interlayers, blind ceilings where the point type detector is difficult to install.
4 Other places that are in bad conditions and unsuitable for the installation of the point
type detector.
5.3.4 The line type optical fibre heat fire detector should be selected for the following
places or parts:
1 The storage tank for the petroleum except for the liquefied petroleum gas.
2 The inflammable and explosive places needed to be equipped with the line type heat
fire detector.
3 The line type optical fibre heat fire detector with the function of real time
temperature monitoring should be set in the places like the underground space needed
4 The highway tunnels, railway tunnels with power cables and urban subway tunnels
etc.
5.3.5 The line-style constant temperature fire detector shall be selected to ensure its
www.ChineseStandard.net Page 27 of 66
GB 50116-2013
6.1 Setting of the Fire Alarm Control Unit and Automatic Control Equipment
6.1.1 The fire alarm control unit and automatic control equipment shall be set in the fire
6.1.2 The arrangement of the fire alarm control unit and automatic control equipment in the
fire control center shall meet those specified in Article 3.4.8 in this code.
6.1.3 When the fire alarm control unit and automatic control equipment are installed on the
wall, the height of their main display screens should be 1.5 m ~ 1.8 m, the distance from their
side faces close to the door pivot to the wall shall not be less than 0.5 m, the front operated
6.1.4 The zone fire alarm control unit in the centralized alarm system and control center
warning system may be set in unattended places under the following conditions:
2 All the information of this fire alarm control unit may be displayed on the central fire
alarm control unit, this fire alarm control unit can receive the control signal to start & stop an
automatic equipment of the fire alarm control unit with centralized control function and
3 Only the watch keeper may have access to the set place.
6.2.1 The specific arrangement part of the detector shall be adopted in accordance with
6.2.2 The setting of point type fire detector shall meet the following requirements:
1 At least one fire detector shall be set in each room of the detecting area.
2 The monitoring area and monitoring radius for the smoke fire detector and the heat
fire detector of Type A1, A2, B shall be determined according to those specified in Table
6.2.2; the monitoring area and monitoring radius for the heat fire detector of Type C, D, E, F,
www.ChineseStandard.net Page 29 of 66
GB 50116-2013
6.2.3 When the point type smoke fire detector, the heat fire detector is set on the beamed
1 When the beam is of less than 200mm higher than the ceiling plate, the impact of the
beam towards the monitoring area of the detector may not be calculated.
2 When the beam is 200mm ~ 600 mm higher than the ceiling plate, the impact of the
beam towards the monitoring area of the detector and the quantity of areas between beams
this code.
3 When the beam is over 600 mm higher than the ceiling plate, at least one detector
4 When the area divided by the beam exceeds the monitoring area of one detector, the
set quantity of the detectors in the divided areas shall be calculated in accordance with Article
5 The impact of the beam towards the monitoring area of the detector may not be
calculated when the clear distance between the beams is less than 1m.
6.2.4 The point type detector should be arranged in the middle when being set on the inner
walkway ceiling with its width being less than 3m. The installation spacing for the heat fire
detector shall not be greater than 10m; the installation spacing for the smoke fire detector
shall not be greater than 15m; the distance from the detector to the end wall shall not be
6.2.5 The horizontal distance from the point type detector to the wall shall not be less than
0.5 m.
6.2.6 No shelter shall be within 0.5 m around the point type detector.
6.2.7 When the room is divided by the bookshelf, equipment or partition etc. and the
distance from its top to the ceiling plate or the beam is less than 5% of the stud, at least one
6.2.8 The horizontal distance from the point type detector to the air supply outlet of the air
conditioner shall not be less than 1.5 m and the point type detector should be installed near
www.ChineseStandard.net Page 31 of 66
GB 50116-2013
4 The single range fire detectors shall not be set in the places directly or indirectly
exposed by light sources such as the sunshine, filament lamp etc. at ordinary times.
6.2.15 The setting of line type optical light beam smoke detector shall meet the following
requirements:
1 The vertical distance from the axial line of detector light beam to the ceiling plate
should be 0.3 m ~ 1.0 m, the height from the ground for the axial line of the detector light
2 The horizontal distance between two adjacent sets of detectors shall not be greater
than 14 m, the horizontal distance from the detector to sidewall shall not be greater than 7 m
and shall not be less than 0.5 m, the distance between the launcher and receiver of the detector
4 The setting of the detector shall ensure its receiving end away from the direct
5 The detector shall be ensured to response correctly when being selected and when the
simulation test is conducted in any part between the baffle board and the detector.
6.2.16 The setting of line type heat fire detector shall meet the following requirements:
1 The contact-type arrangement shall be adopted for the detector to protect the
protected objects like cable, stacking etc.; the detector should be arranged nearby the heat
spot of the device when being set on all kinds of belt transmission device.
2 The distance from the line type heat fire detector under the ceiling plate to the ceiling
plate should be 0.1 m. The monitoring radius for the detector shall meet the requirements of
the monitoring radius for the point type heat fire detector, and the distance from the detector
3 The monitoring area and monitoring radius for each grating of the optical grating
fibre heat fire detector shall meet the requirements of monitoring area and monitoring radius
4 When there are linkage requirements for places equipped with line type heat fire
detector, a combination of alarm signal of two different fire detectors should be adopted.
www.ChineseStandard.net Page 33 of 66
GB 50116-2013
5 If the ratio of the hollow-out area to total area is 30%~70% at places such as subway
platform affected by the piston wind, the detector should be arranged at the upper & lower
part of the suspended ceiling.
6.2.19 The setting of other fire detectors not concerned in this code shall be arranged in
accordance with design manuals or operating instructions provided by enterprise and the
setting conditions of the detectors may be verified through simulating the fire scene of
monitoring objects where necessary.
6.3.1 A manual call point (at least) shall be arranged in each fire zone. The walking distance
between any position and the nearest manual call point in each fire zone shall not be greater
than 30m. The manual call point should be arranged at the evacuation route or entrance/exit.
The manual call point set on the trains shall be at the entrance/exit of and in middle of each
carriage.
6.3.2 The manual call point shall be arranged in visible positions and positions for the
convenience of operation. If the manual call point is installed by hanging, the height from its
bottom edge to the ground should be 1.3m~1.5m. The manual call point shall be provided
with visible marks.
6.4.1 A fire display panel shall be arranged in each alarm zone; a fire display panel shall be
arranged in each alarm zone of such place as hotel and restaurant etc.. If there are many floors
in an alarm zone, a fire display panel shall be arranged in each floor, which can only display
the alarm information of this floor.
6.4.2 The fire display panel shall be arranged in visible positions and positions for the
convenience of operation such as entrance/exit. If the fire display panel is installed by
hanging, the height from its bottom edge to the ground should be 1.3m~1.5m.
6.5.1 The fire alarm singalling device shall be arranged in the visible positions such as stair
port of the each floor, front room of the fire elevator and internal corners of buildings etc.,
and it should not be arranged on the same wall together with the mandatory sign light fixture
of the emergency exit.
6.5.2 The fire alarm singalling device shall be uniformly arranged in each alarm zone
and its sound pressure level shall not be less than 60dB; its sound pressure level shall be
15dB greater than that of the background noise in the places where the ambient noise is
greater than 60dB.
6.5.3 If the fire alarm singalling device is installed by hanging, the height between the
bottom edge and the ground shall be greater than 2.2m.
www.ChineseStandard.net Page 35 of 66
GB 50116-2013
6.8.1 The module in each alarm zone should be arranged in the metal module case in this
alarm zone in a relative concentrated manner.
6.8.2 It is strictly forbidden to arrange the module in the power distribution (control)
cabinet (box).
6.8.3 The module in this alarm zone shall not control the equipment in other alarm
zone.
6.8.4 The modules which are not set intensively shall be provided with marks with the
dimension not less than 100mm×100mm.
6.9.1 The graph indicator in fire control center shall be arranged in the fire protection
control room and shall meet the requirements for installation and setting of the fire alarm
control unit.
6.9.2 Dedicated lines shall be adopted for connection between fire protection equipment
such as the graph indicator in fire control center, fire alarm control unit, automatic controller
for fire protection, alarm and control unit for electric fire protection and combustible gas
control unit etc..
6.10.1 The transmission equipment of fire alarm or the transmission device of the user
information shall be arranged in the fire protection control room and they shall be arranged
nearby the visible position of the fire alarm control unit once the fire protection control room
is not arranged.
6.10.2 The dedicated lines shall be adopted for connection between fire protection
equipment such as the graph indicator in fire control center, fire alarm control unit, automatic
controller for fire protection and combustible gas control unit etc..
6.10.3 The setting of the routing equipment shall ensure the sufficient operation and
overhauling distance.
6.10.4 The manual alarm device of the routing equipment shall be arranged in the visible
position for the convenience of operation.
6.11 Setting of the Indicator and Control Unit for Fire Doors
6.11.1 If the indicator and control unit for fire doors shall be arranged in the fire protection
control room, which is not arranged, the indicator and control unit for fire doors shall be
arranged at the place attended by someone.
6.11.2 The manual control point of the electric door opener shall be arranged on the
sidewall of the fire door, the distance between the point and the door should not exceed 0.5m,
the height between the bottom edge and the ground should be 0.9m~1.3m.
6.11.3 The indicator and control unit for fire doors shall be set according to the
requirements for installation and setting of the fire alarm control unit.
www.ChineseStandard.net Page 37 of 66
GB 50116-2013
1 The fire detector for household set in households shall be connected with the fire
alarm control unit for household directly.
2 The fire alarm control unit for household shall be able to start up the fire alarm
signalling device set in public positions.
3 In the Category B system, the fire alarm control unit for household set in each
dwelling shall be connected with the monitoring equipment of OCC (Operating Control
Center) and the monitoring equipment of OCC (Operating Control Center) shall be able to
display the households at which the fire happens.
7.2.3 The design of the Category D system shall meet the following requirements:
1 If there are many living rooms in one household, the independent fire detector &
alarm devices connected with each other should be adopted.
2 The independent fire detector & alarm device of which the battery life is not less than
3 years should be selected.
7.2.4 The independent fire detector & alarm devices are adopted to form the system in
wireless manner and the system design shall meet one of the requirements for design of
Category A, Category B and Category C systems.
7.3.1 A smoke fire detector (at least) shall be arranged in each bedroom or living room.
7.3.2 The combustible gas detector arranged in the kitchen shall meet the following
requirements:
1 The methane detector shall be selected for the user who uses the natural gas, the
propane detector shall be selected for the user who uses the liquefied gas and the carbon
monoxide detector shall be selected for the user who uses the coal gas.
2 If the hose and connector are in the cabinet to connect the gas cooking appliances,
the detector should be arranged in the cabinet.
3 The methane detector shall be arranged at the top of the kitchen, the propane detector
shall be arranged at the lower part of the kitchen and the carbon monoxide detector may be
arranged at the lower part of kitchen or may also be arranged in other parts.
4 The combustible gas detector should not be arranged over the cooking appliance.
5 The combustible gas detector which can automatically shut down the shut off value
of the gas should be adopted.
6 The shut off value of gas for the automatic detector should be those which can be
reset by the users themselves and shall be able to protect the rubber pipes from shedding off.
7.4.1 The fire alarm control unit for household shall be independently arranged in each
household and shall be arranged in the visible position and positions where the operation is
convenient. If the unit is installed by hanging, the height from its bottom edge to the ground
should be 1.3m~1.5m.
7.4.2 The fire alarm control unit for household provided with graphic talkback function
should be arranged nearby the household door.
www.ChineseStandard.net Page 39 of 66
GB 50116-2013
8.1.1 The combustible gas detection and alarm system shall be composed of combustible
gas control unit, combustible gas detector and audible and visible fire alarm device etc.
8.1.2 The combustible gas detection and alarm system shall consist independently, the
combustible gas detector shall not be connected with the detector loop of the fire alarm
control unit; if the alarm signal of the combustible gas needs connecting with the automatic
fire alarm system, the connection may start from the combustible gas control unit.
8.1.3 The combustible gas detector which is in related to the process control in the
petrochemical industry, shall be set in accordance with the requirements of the current
national standard "Specification for Design of Combustible Gas and Toxic Gas Detection and
Alarm for Petrochemical Industry" (GB 50493), but, its alarm signal shall be connected with
the fire control center.
8.1.4 The alarm information and fault information of the combustible gas control unit shall
display on the graph indicator in fire control center or fire alarm control unit with the function
of centralized control; however, this kind of information shall be different from the fire alarm
information.
8.1.5 If the combustible gas control unit sends out the alarm signal, it shall be able to start
up the audible and visible fire alarm device in the monitoring zone.
8.1.6 If the automatic and alarm requirements are needed in the monitoring zone of the
combustible gas detection and alarm system, the combustible gas control unit or automatic
controller for fire protection shall be linked for that.
8.1.7 If the combustible gas detection and alarm system is arranged in the places where the
explosion-proof requirements are needed, it shall also meet the relevant explosion-proof
requirements.
8.2.1 As for the combustible gas detector, it shall be arranged at the top of the monitoring
space once the detecting gas density is less than the air density, shall be arranged at the lower
part of the monitoring space once detecting gas density is greater than the air density and may
be arranged in the middle of or at the top of the monitoring space once the detecting gas
density is equal to the air density.
8.2.2 The combustible gas detector should be arranged nearby the place where the
combustible gas may be generated.
8.2.3 The monitoring radius of point-type combustible gas detectors shall meet the relevant
requirements of the current national standard "Specification for Design of Combustible Gas
and Toxic Gas Detection and Alarm for Petrochemical Industry" (GB 50493).
8.2.4 The length of the monitoring zone for the line type combustible gas detector should
not be greater than 60m.
www.ChineseStandard.net Page 41 of 66
GB 50116-2013
9.1.1 The alarm and monitoring for electric fire protection may be used to places where the
potential electric fire may occur.
9.1.2 The alarm and monitoring for electric fire protection shall be composed of the partial
or whole equipment below:
1 Alarm and control unit for electric fire protection.
2 Leakage current detector for electric fire prevention,
3 Heat detector for electric fire prevention.
9.1.3 The alarm and monitoring for electric fire protection shall be arranged in accordance
with the building characteristic and electric fire hazard and the form and installation position
of the detector for electric fire prevention shall be determined in accordance with the specific
conditions of electric circuit laying and power equipment. If the fire control center is not
arranged and setting number of detectors for electric fire prevention is less than or equal to 8,
the independent detector for electric fire prevention may be adopted.
9.1.4 The non-independent detector for electric fire prevention shall not be connected with
the detector loop in the fire alarm control unit.
9.1.5 Where the fire control center is arranged, the alarm information and fault information
of the alarm and control unit for electric fire protection shall display on the graph indicator
in fire control center or fire alarm control unit with the function of centralized control;
however, this kind of information shall be different from the fire alarm information.
9.1.6 The setting of alarm and monitoring for electric fire protection shall not have an effect
on the normal operation of the power supply system and the power supply should not be shut
down automatically.
9.1.7 If the line type heat fire detectors are applicable to electric fire monitoring, the alarm
and control unit for electric fire protection may be connected directly.
9.2 Setting of the Leakage Current Detector for Electric Fire Prevention
9.2.1 The basic principle is that the leakage current detector for electric fire prevention shall
be arranged at the head end of the low-voltage distribution system; the detector should be
arranged at the outlet end of the first grade distribution cabinet (box). The detector should be
arranged in the next grade distribution cabinet (box), if the leakage current of the power
supply circuit is greater than 500mA.
9.2.2 The leakage current detector for electric fire prevention should not arranged in the
distribution lines and fire protection distribution lines in the IT system.
9.2.3 If the leakage current detector for electric fire prevention is selected, the effect caused
by the natural leakage current of power supply system shall be counted and the detectors with
the suitable parameters shall be selected; the alarm value of detectors should be
300mA~500mA.
www.ChineseStandard.net Page 43 of 66
GB 50116-2013
9.2.4 As for detectors for electric fire prevention which can detect the line fault electric arc,
the length of their protective circuit should not be greater than 100m.
9.3.1 The heat detector for electric fire prevention shall be arranged at positions such as
cable joint, terminal and important heating components etc..
9.3.2 The monitoring objects are distribution lines of 1000V or below and the contact-type
layout shall be adopted for the heat detector for electric fire prevention.
9.3.3 The monitoring objects are power supply circuits of 1000V, and the grating optical
fiber or infrared heat detectors for electric fire prevention should be selected for as heat
detectors for electric fire prevention; the grating optical fiber heat detector for electric fire
prevention shall be directly arranged on the surface of monitoring objects.
9.4.1 Setting of the independent detector for electric fire prevention shall meet those
specified in 9.2 and 9.3 of this code.
9.4.2 If the automatic fire alarm system is arranged, the alarm information and fault
information of the independent detector for electric fire prevention shall display on the graph
indicator in fire control center or central fire alarm control unit; however, this kind of
information shall be different from the fire alarm information.
9.4.3 If the automatic fire alarm system is not arranged, the independent detector for electric
fire prevention shall transmit the alarm signal at the place attended by someone.
9.5 Setting of the Alarm and Control Unit for Electric Fire Protection
9.5.1 If the fire control center is set, the alarm and control unit for electric fire protection
shall be arranged in the fire control center or nearby the monitoring zone; if the unit is
arranged nearby the monitoring zone, the alarm information and fault information shall be
introduced into the fire control center.
9.5.2 If the fire control center is not arranged, the alarm and control unit for electric fire
protection shall be arranged at the place attended by someone.
www.ChineseStandard.net Page 44 of 66
GB 50116-2013
10 Power Supply
10.1.1 The alternating current power supply and standby power supply for storage
batteries shall be arranged for the automatic fire alarm system.
10.1.2 The fire power supply shall be adopted for the alternating current power supply of
the automatic fire alarm system; and the battery power or the emergency power supply for fire
fighting equipment accompanied in the fire alarm control unit and automatic controller for
fire protection may be adopted for the standby power supply. If the emergency power supply
for fire fighting equipment is adopted as the standby power supply, the separate power supply
loop shall be adopted for the fire alarm control unit and automatic controller for fire
protection and shall have no influence on the normal operation of them, if the system is in
maximum load status.
10.1.3 UPS power supply device or emergency power supply for fire fighting equipment
shall serve as the power supply for graph indicator in fire control center and fire protection
communication equipment etc..
10.1.4 Residual current operated protection and overload protection devices shall not be
arranged for the main power supply of the automatic fire alarm system.
10.1.5 The output power of the emergency power supply for fire fighting equipment shall be
greater than 120% of the full load power for the automatic fire alarm & automatic control
system, the capacity of storage battery shall ensure that the automatic fire alarm & automatic
control system can continuous work for 3 hours more in fire hazard and under the working
load condition.
10.1.6 The specialized power supply loop shall be adopted for the fire protection power
equipment and its power distribution equipment shall be equipped with visible marks. Its
distribution lines and control loops should be classified in accordance with fire zone.
10.2.1 The ground resistance value of grounding devices in the automatic fire alarm system
shall meet the following requirements:
1 If adopting the common grounding devices, the grounding resistance value shall not
be greater than 1Ω.
2 If adopting the specialized grounding device, the grounding resistance value shall not
be greater than 4 Ω.
10.2.2 The equipotential bonding shall be adopted for metal outer casing cabinet, rack,
metal pipes and grooves of electrical and electronic equipment in the fire control room.
10.2.3 The copper-cored insulated wire with the core section area not less than 4mm2 shall
be selected for the specialized grounding wire led from the grounding plate in the fire control
center to the fire-protection electronic equipment.
www.ChineseStandard.net Page 45 of 66
GB 50116-2013
flame-retardant or flame-retardant & fire resisting electric wires and cables shall be
used for the alarm bus line and transmission lines for signalling device system and fire
telephone etc.
11.2.3 If the line is laid in a concealed way, protection shall be made with metal tubes,
flexible (metal) electric conduits or rigid plastic pipes (Class B1 or above) inside the
structural layer of non–combustible components, and the thickness of protection layer should
not be less than 30mm. If the line is laid in an open way, protection shall be provided with
metal tubes, flexible (metal) electric conduits or metal enclosed cable trays. The
11.2.4 The cable shafts for automatic fire alarm system should be set separately from those
for the electrical or illuminating low-voltage distribution lines. If they must serve for both the
said system and lines, the cables for the system and those for the lines shall be arranged
11.2.5 Cables with different voltage classes shall not be threaded into a same
protecting pipe; if they have to, partitions shall be provided inside the cable tray.
11.2.6 If the horizontal laying is carried out in the manner of pipe penetration, except for the
alarm bus line, lines for different fire compartments shall not be treaded into a same pipe.
11.2.7 All the lines from the junction box or cable tray to the detector base, control gear box
11.2.8 The transmission line of fire detector should consist of insulated wires or cables of
different color. The wire or cable fir positive pole "+" shall be red, and those for negative pole
"-" shall be blue or black. The conductors for a same purpose and same project shall be in the
same color, and the wiring terminals shall be marked with numbers.
www.ChineseStandard.net Page 48 of 66
GB 50116-2013
12.1.1 Urban traffic tunnels, super-long highway tunnels and subaqueous tunnels in road
shall be provided with both line-type optical fibre heat fire detector and point-type infrared
flame detector (or video image fire detector); other highway tunnel shall be provided with
either of them.
12.1.2 Line-type optical fibre heat fire detector shall be set over the lane and 100mm ~
200mm below the ceiling. The grating spacing of line-type optical grating fiber heat fire
detector shall not be greater than 10m; each distributed line-type optical fibre heat fire
detector or line-type optical grating fiber heat fire detector shall not monitor more than 2 lanes.
The point-type infrared flame detector or video image fire detector shall be set on the side
wall of lanes at the height over the lane surface for 2.7m~3.5m, and it shall be made sure
there is no detection gap; while being set by both sides of the lane, the detectors shall be
12.1.3 If the automatic fire alarm system has to be linked with the fire protection facilities,
12.1.4 Alarm reporting telephones shall be set for every other 200m in the tunnel and at
tunnel portals. Manual fire-alarm buttons and audible and visible fire alarm devices with red
flash light shall be set every other 50m in the tunnel. Audible and visible alarm devices shall
be arranged within 50m~250m ahead of the tunnel portal to indicate fires inside the tunnel.
12.1.5 Line-type heat detectors should be provided for cable channels in tunnel, and
detectors for electric fire prevention shall be provided for distribution lines in rooms for major
equipment.
12.1.6 The automatic fire alarm system in tunnel should be linked to the video monitoring
12.1.7 The Automatic fire alarm system shall send fire alarm signals to the central control &
www.ChineseStandard.net Page 49 of 66
GB 50116-2013
detection length shall be guaranteed at heating parts such as the cable joints and terminals.
Line-type heat detectors set in the tunnel may be connected to the electrical fire monitor.
12.3.2 Line-type heat detectors shall be arranged on the upper surface of cable layer in cable
tunnel without external ignition source, and on both the upper surface of cable layer and the
12.3.3 If the line-type heat detectors are arranged in "S" shape, or, if it is in the cable tunnel
with possible external ignition source, the detectors shall be capable of responding to flames
12.3.4 Line-type heat detectors shall monitor all the power table inside the tunnel in the
contact laying manner; cable type line heat fire detectors shall be arranged in the "S" shape on
the upper surface of each electric cable layer. One optical cable of a line-type optical fibre
heat fire detector shall monitor one power cable, and the temperature-sensitive cables shall be
12.3.5 If distributed line-type optical fibre heat fire detectors are laid at the heating parts
such as cable joints and terminals, the extension length of its temperature-sensitive optical
cable shall not be shorter than 1.5 times the detection unit length; if line-type optical grating
fiber heat fire detectors are laid, temperature-sensitive gratings shall be laid at such heating
parts.
12.3.6 If power cables are laid in other tunnels, the detectors shall be set according to the
requirements of this code, except that the line-type heat detectors at the tunnel top are not
necessary.
12.4.1 The large space places where higher than 12m should be equipped with fire detectors
12.4.2 As for places where large amount of fume would be generated at the initial stage of
fire line-type optical light beam smoke detectors, air sampling-type smoke detectors, or video
www.ChineseStandard.net Page 51 of 66
GB 50116-2013
12.4.3 Line-type optical light beam smoke detectors shall be arranged according to the
following requirements:
2 The detectors should be set with the detection method hierarchical networking.
3 If the building is not higher than 16m, an additional layer of detectors should be set
4 If the building is taller than 16m but shorter than 26m, two layers of detectors should
5 If the building has a tropospheric layer formed by open windows or ventilation air
conditioners at 7m~13m, the additional detector layer may be set 1m below such tropospheric
layer.
6 The monitoring area of detectors set in layers may be calculated as the usual area,
12.4.4 The air sampling-type smoke detectors for pipelines shall be set according to the
following requirements.
least two sampling holes shall be guaranteed below 16m, and 2 should be set 1m below the
2 Additional alarm sampling holes may be arranged at the return air inlet.
12.4.5 As for the places with small amount of smoke and obvious flames generated in the
initial stage of fire, the point-type infrared flame detectors with Grade 1 sensitivity or video
image type flame detectors shall be adopted, and they shall be set at a lower height.
12.4.6 Detectors for electric fire prevention shall be provided for electrical lines, and
detector for electric fire prevention with the failure electric arc detection function shall b
www.ChineseStandard.net Page 52 of 66
GB 50116-2013
Appendix B
SN Name Contents
The name, number, category, address, telephone, number and post code, fire control center
telephone number of the organization, the number of employees, the foundation time, the
name of its managing (or) administrative organization, the floor area, total building area,
1 Basic information
and general layout (including fire lanes and adjacent buildings) drawings; the names, ID
numbers and telephone of its legal representative, fire safety principal, fire safety manager
and full-time and part-time fire-fighting managers.
The structure/building's name, number, service purpose, fire resistance rating, structure
type, building height, over ground floors and building area, underground floors and
building area, tunnel height and length, built date, names and quantity of primary
Buildings and
storages, maximum capacity of the building, and elevation sand fire-fighting device layout
structures
plan of buildings; the location of fire control center, and the number, locations and forms
(such as emergency staircase) of escape exits; the service purpose, structure type, building
Information
height and space to this building of the adjacent buildings.
for major
2 The stockyard's name, names of main bulk-load, total storage, maximum stock height,
buildings and Stock yard
stockyard plan (including fire lanes and fire breaks)
structures etc.
The tank area's name, tank types (overground, underground, vertical, horizontal, floating
Storage tank roof or fixed roof etc.), total volume, maximum single tank volume and height, name,
nature and form of stored material, and tank area plan (including fire lanes and fire breaks)
The process plant area's name, coverage, maximum height, designed daily output, major
Process plant raw materials, main products, and process plant area plan (including fire lanes and fire
breaks)
Information of key fire safety The key position's name, location, service purpose, building area, fire resistance rating,
3 positions inside the organization fire-fighting device provision, and the name, ID number and telephone number of its
(place) principal
The established position, system form, name of maintenance and protection organization,
and telephone; the types, models, quantities and manufacturers of controllers (for fire
Automatic fire
Informatio alarm, fire automatic control, flammable gas alarm and electrical fire monitoring etc.),
alarm system
n of detectors (for fire, flammable gas or electrical fire etc.), manual fire alarm call points, and
interior electric fire control units etc.
4 and The form (annular or branch) and pipe diameter of municipal water supply network, the
exterior number and pipe diameters of water inlet pipes of building and structure water supply by
fire-fightin municipal pipe network, the locations and service discharge of fire cistern, the locations
Fire water source
g devices and capacities of attic tanks, the forms and service discharges of other sources, the
locations of fire pump rooms and number of pumps, and the layout plan of fire water
supply system
www.ChineseStandard.net Page 55 of 66
GB 50116-2013
Appendix C
Detector Application temperature Maximum application Lower limit of operating Upper limit of operating
category of the type ( ) temperature ( ) temperature(℃) temperature ( )
A1 25 50 54 65
A2 25 50 54 70
B 40 65 69 85
C 55 80 84 100
D 70 95 99 115
www.ChineseStandard.net Page 58 of 66
GB 50116-2013
Appendix D
1 Offices, business halls and bill vaults of commercial and financial buildings.
transmission technical rooms and prop & setting rooms of broadcast television buildings.
10 Wards, offices, medical facility rooms, medical records %filing rooms and
11 Offices, reference rooms, expensive equipment rooms, and laboratories with many
13 Bedrooms, study rooms, living rooms (ante hall) and kitchens of apartments
www.ChineseStandard.net Page 59 of 66
GB 50116-2013
16 Production shops and storage rooms for Class C and D articles which are built
underground.
subways.
19 The stages, dressing rooms, property rooms, projection rooms, auditorium, waiting
rooms and al auxiliary recreation areas of gymnasiums, cinemas and theaters, assembly halls,
and auditory
21 Fore-chambers and shared front rooms of fire elevators and smoke prevention
23 Technical interlayer with clear height over 2.6m and many combustible materials.
24 Cable shafts, cable interlayer, cable tunnels and cabling trays for cables laid with
28 Rooms people stays a lot or with many combustible materials in the places for
mechanical stereo garages, duplex garages, and garages with escalators as vehicle evacuation
30 Fore-chambers of dirty clothes chutes and waste& rubbish chutes, blind ceilings
with clear height over 0.8m and combustible materials, and commercial or common kitchens.
www.ChineseStandard.net Page 60 of 66
GB 50116-2013
32 Other places where people stay a lot, with many combustible materials or
www.ChineseStandard.net Page 61 of 66
GB 50116-2013
1 The explanation of wording for different degrees of strictness of provisions in this code
2) Words representing strict requirements which shall be complied with under normal
conditions:
conditions permit:
4) The word indicating alternations and the requirements which can be complied with
2 Expressions indicating the compliance to other relevant standards are "shall meet the