Omron PDF
Omron PDF
MY New model
Versatile and Function-filled Miniature Power
Relay for Sequence Control and Power
Switching Applications
• Models with lockable test buttons now available.
• Many variations possible through a selection of operation indi-
cators (mechanical and LED indicators), lockable test button,
built-in diode and CR (surge suppression), bifurcated contacts,
etc.
• Arc barrier standard on 4-pole Relays.
• Dielectric strength: 2,000 VAC (coil to contact)
• Environment-friendly cadmium-free contacts.
• Safety standard approvals obtained. LR
• Wide range of Sockets (PY, PYF Series) and optional parts are
available.
• Max. Switching Current: 2-pole: 10 A, 4-pole: 5 A
• Provided with nameplate.
Ordering Information
■ Relays
Standard Coil Polarity
Type Contact form Plug-in socket/Solder terminals Without LED indicator
Standard with LED indicator With LED indicator and
lockable test button
Standard DPDT MY2N MY2IN MY2
4PDT MY4N MY4IN MY4
4PDT (bifurcated) MY4ZN MY4ZIN MY4Z
With built-in diode DPDT MY2N-D2 MY2IN-D2 ---
(DC only)
4PDT MY4N-D2 MY4IN-D2 ---
4PDT (bifurcated) MY4ZN-D2 MY4ZIN-D2 ---
With built-in CR DPDT MY2N-CR MY2IN-CR ---
(220/240 VAC, 110/120 VAC
only) 4PDT MY4N-CR MY4IN-CR ---
4PDT (bifurcated) MY4ZN-CR MY4ZIN-CR ---
Note: When ordering, add the rated coil voltage and “(s)” to the model number. Rated coil voltages are given in the coil ratings table.
Note: PYP-18 and PYP-36 can be cut into any desired length in accordance with the number of Sockets.
Specifications
■ Coil Ratings
Rated voltage Rated current Coil Coil inductance Must Must Max. Power
resistance (reference value) operate release voltage consumption
voltage voltage (approx.)
50 Hz 60 Hz Arm. OFF Arm. ON % of rated voltage
AC 6 V* 214.1 mA 183 mA 12.2 Ω 0.04 H 0.08 H 80% max. 30% min. 110% 1.0 to 1.2 VA
(60 Hz)
12 V 106.5 mA 91 mA 46 Ω 0.17 H 0.33 H
24 V 53.8 mA 46 mA 180 Ω 0.69 H 1.30 H
48/50 V* 24.7/ 21.1/ 788 Ω 3.22 H 5.66 H
25.7 mA 22.0 mA
110/120 V 9.9/10.8 mA 8.4/9.2 mA 4,430 Ω 19.20 H 32.1 H 0.9 to 1.1 VA
(60 Hz)
220/240 V 4.8/5.3 mA 4.2/4.6 mA 18,790 Ω 83.50 H 136.4 H
DC 6 V* 151 mA 39.8 Ω 0.17 H 0.33 H 10% min. 0.9 W
12 V 75 mA 160 Ω 0.73 H 1.37 H
24 V 37.7 mA 636 Ω 3.20 H 5.72 H
48 V* 18.8 mA 2,560 Ω 10.60 H 21.0 H
100/110 V 9.0/9.9 mA 11,100 Ω 45.60 H 86.2 H
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/–20% for rated currents and
±15% for DC coil resistance.
2. Performance characteristic data are measured at a coil temperature of 23°C.
3. AC coil resistance and impedance are provided as reference values (at 60 Hz).
4. Power consumption drop was measured for the above data. When driving transistors, check leakage current and connect a bleeder
resistor if required.
5. Rated voltage denoted by “*” will be manufactured upon request. Ask your OMRON representative.
Note: Don’t exceed the carry current of a Socket in use. Please see page 10.
■ Characteristics
Item All Relays
Contact resistance 100 mΩ max.
Operate time 20 ms max.
Release time 20 ms max.
Max. operating frequency Mechanical: 18,000 operations/hr
Electrical: 1,800 operations/hr (under rated load)
Insulation resistance 1,000 MΩ min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1.0 min (1,000 VAC between contacts of same polarity)
Vibration resistance Destruction: 10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude)
Malfunction: 10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude)
Shock resistance Destruction: 1,000 m/s2
Malfunction: 200 m/s2
Endurance See the following table.
Ambient temperature Operating: –55°C to 70°C (with no icing)
Ambient humidity Operating: 5% to 85%
Weight Approx. 35 g
■ Endurance Characteristics
Pole Mechanical life (at 18,000 operations/hr) Electrical life
(at 1,800 operations/hr under rated load)
2-pole AC:50,000,000 operations min. 500,000 operations min.
4-pole DC:100,000,000 operations min. 200,000 operations min.
4-pole (bifurcated) 20,000,000 operations min. 100,000 operations min.
DC resistive load
DC resistive load
Endurance
MY2 (Resistive Loads) MY2 (Inductive Loads)
Endurance (x10 3 operations)
10000 10000
5000 5000
3000 250 VAC 3000
250 VAC
250 VAC
250 VAC
100 100
50 50
30 30
10 10
10000 10000
5000 5000
3000 250 VAC 3000
30 VDC
1000 1000
10 10
1000 1000
250 VAC
500 500 30 VDC
300 300
30 VDC 30 VDC
10 10
0.6
0.4
cos(p.f.)
Multiple Contact DC Switching Capacity Effect of temperature on coil voltages
Switching capacity of DC resistive load MY2/4 Operating range (DC and AC type) vs ambient temperature
100 2
10 1.5
Switching Current (A)
U/Un
MY4
1 1.0
4 contacts
3 contacts
2 contacts
in series MY2
1: Max coil voltage permitted.
2: Min pick-up voltage with coil
at ambient temperature
0,1 0.5
20 40 60 80 100 120 140 160 180 200 220 0 10 20 30 40 50 60 70 80
Switching Voltage (Vdc) Ambient temperature (˚C)
This graph can be used to estimate the number of contacts that can be This graph shows the typical relationship between the maximum / mini-
used to switch DC resistive loads mum coil and pick-up voltage and ambient temperature
2-Pole Models
MY2N
2.6
0.5
28 max.
36 max. 6.4
21.5 max.
4-Pole Models
MY4N
2.6
0.5
28 max.
36 max. 6.4
21.5 max.
28 max.
5
80.5
14.2 36 max.
21.5 max.
MY4IN 2.6
0.5
28 max.
5
80.5
14.2 36 max.
<1.417> 6.4 21.5 max.
1 4 1 4 1 4 1 4
5 8 5 8 5 8 5 8
9 12 9 12 9 12 9 12
− + − +
13 14 13 14 13 14 13 14
1 4 1 4 1 4
5 8 5 8 5 8
9 12 9 12 9 12
+ − + −
13 14 13 14 13 14
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
5 6 7 8 5 6 7 8 5 6 7 8 5 6 7 8
9 10 11 12 9 10 11 12
− + − +
13 14 13 14 13 14 13 14
1 2 3 4 1 2 3 4 1 2 3 4
5 6 7 8 5 6 7 8 5 6 7 8
9 10 11 12
+ − + −
13 14 13 14 13 14
Back-connecting Sockets
■ Specifications
Item Pole Model Carry current Dielectric withstand Insulation resistance
voltage (see note 2)
Screwless Clamp 2 PYF08S 10 A 2,000 VAC, 1 min Less than 1,000 MΩ
Terminal Socket 4 PYF14S 5A
Track-mounted 2 PYF08A-E 7A 2,000 VAC, 1 min 1,000 MΩ min.
Socket PYF08A-N (see note 3) 7 A (see note 4)
4 PYF14A-E 5A
PYF14A-N (see note 3) 5 A (see note 4)
4 PYF14-ESN/-ESS 12 A > 3 kV > 5 MΩ
Back-connecting 2 PY08(-Y1) 7A 1,500 VAC, 1 min 100 MΩ min.
Socket PY08QN(-Y1)
PY08-02
4 PY14(-Y1) 3A
PY14QN(-Y1)
PY14-02
23.2 max.
---
85 max.
(5.3)
72 max.
(TOP VIEW)
23 max.
Note: Track mounting is also
possible. Refer to page
31 max. 12 for supporting tracks.
PYF08A-N 22 max.
42 12
4 1
4 1
42 12
44 14
8 5
8 5
44 14 3.0 dia.
18.7 3.5 dia. or M3
67 max.
41
PYF-08A-N
11
73
12 9
Note: Track mounting is also
12 9
41 11
possible. Refer to page
A2 A2 A1
14 14 13 14 14 13
A2 A2 A1
12 for supporting tracks.
30 max.
31 max.
---
85 max.
72 max.
(TOP VIEW)
Note: Track mounting is also
29.5 max. possible. Refer to page
12 for supporting tracks.
31 max.
PYF14A-N 42 32 22 12
4 3 2 1
4 3 2 1 Two, 4.5 dia. or M4
42 32 22 12
8 7 6 5
44 34 24 14
44 34 24 14 8 7 6 5
67 max.
PYF-14A-N 26
41 31 21 11
12 11 10 9 73
A2 A2 A1
14 14 13
12 11 10 9 Note: Track mounting is also
41 31 21 11 possible. Refer to page
14 14 13 12 for supporting tracks.
29.5 max. 30 max.
A2 A2 A1
4.1
Relay 6.3
6.4
82 75
3.2
COIL
COM.
24
22.5 Module
53
80
PYF14-ESS
27
61 COM.
9 NO
NC
4.45 4.45 4.45
4.1
6.3
6.4
83 3.2 75
COIL
29
22.5
55
82
25.5 max.
29.5 max.
20 max. 24 max.
42 max.
PY08QN/
PY08QN-Y1
(See note)
29.5 max.
41.5 max.
22 max.
42 max. 24 max.
PY08-02
25.5 max.
29.5 max.
25.5 max.
29.5 max.
20 max. 24 max.
42 max.
29.5 max.
41.5 max.
42 max. 22 max.
24 max.
25.5 max.
29.5 max.
22 max.
16.5 max. Fourteen, 1.3-dia.
holes
Note: Use a panel with plate thickness of 1 to 2 mm for mounting the Sockets.
PYC-P PYC-P2
5
10
29 max.
28
3.3
38.5
72 elliptical holes
t=1.6
PYP-18
72 elliptical holes
35±0.3 27±0.15
1
15 25 25 25 25 15 (5)
10 10
1000 (500) *
15 25 25 25 10 25 15 1 1.5
10 1000
End Plate
PFP-M
10
M4 x 8 pan head screw 6.2
1.8
1
50 35.5 35.3
1.8
11.5
10 1.3
M4 spring washer 4.8
Spacer
PFP-S
16
5 12
34.8
44.3
16.5
Precautions
Refer to General Precautions on page 11 of the General-purpose Relays and Power Relays Group Catalog (X034).
■ Connections ■ Mounting
Do not reverse polarity when connecting DC-operated Relays with • Whenever possible, mount Relays so that it is not subject to vibra-
built-in diodes or indicators or high-sensitivity DC-operated Relays. tion or shock in the same direction as that of contact movement.
Cat. No. J03E-EN-01A In the interest of product improvement, specifications are subject to change without notice.
16