Pressure Sensors QBE2003-P QBE2103 - P : Smart Infrastructure
Pressure Sensors QBE2003-P QBE2103 - P : Smart Infrastructure
Pressure Sensors QBE2003-P QBE2103 - P : Smart Infrastructure
QBE2003-P…
Pressure Sensors QBE2103-P…
for neutral and slightly aggressive liquids and gases
• High-precision measuring
• Measuring range 0 to 60 bar relative
• Supply voltage AC 24 V / DC 12...33 V or DC 7…33 V
• DC 0 ...10 V or DC 4…20 mA output signal
• Measurement unaffected by changes in temperature
• High temperature stability
• Connection: external thread G ½", inside thread M5
• Maintenance free thanks to outstanding long-term stability
• High overload resistance
• Robust and compact construction
A6V10432494_en--_d
2019-06-04 Smart Infrastructure
Use
The pressure sensors are suitable for the measurement of relative pressure in HVAC
plant, particularly in hydraulic and pneumatic systems using liquid or gaseous media
(steam applications).
Type summary
Type reference Order number Pressure range Output signal
QBE2003-P1 S55720-S290 0...1 bar 0...100 kPa 0…10 V
QBE2003-P1.6 S55720-S291 0...1.6 bar 0...160 kPa 0…10 V
QBE2003-P2.5 S55720-S292 0...2.5 bar 0...250 kPa 0…10 V
QBE2003-P4 S55720-S293 0...4 bar 0...400 kPa 0…10 V
QBE2003-P6 S55720-S294 0...6 bar 0...600 kPa 0…10 V
QBE2003-P10*) S55720-S295 0...10 bar 0...1.0 MPa 0…10 V
QBE2003-P16*) S55720-S296 0...16 bar 0...1.6 MPa 0…10 V
QBE2003-P25*) S55720-S297 0...25 bar 0...2.5 MPa 0…10 V
QBE2003-P40 S55720-S298 0...40 bar 0...4.0 MPa 0…10 V
QBE2003-P60 S55720-S299 0...60 bar 0...6.0 MPa 0…10 V
QBE2103-P1 S55720-S300 0...1 bar 0...100 kPa 4…20 mA
QBE2103-P1.6 S55720-S301 0...1.6 bar 0...160 kPa 4…20 mA
QBE2103-P2.5 S55720-S302 0...2.5 bar 0...250 kPa 4…20 mA
QBE2103-P4 S55720-S303 0...4 bar 0...400 kPa 4…20 mA
QBE2103-P6 S55720-S304 0...6 bar 0...600 kPa 4…20 mA
QBE2103-P10*) S55720-S305 0...10 bar 0...1.0 MPa 4…20 mA
QBE2103-P16*) S55720-S306 0...16 bar 0...1.6 MPa 4…20 mA
QBE2103-P25*) S55720-S307 0...25 bar 0...2.5 MPa 4…20 mA
QBE2103-P40 S55720-S308 0...40 bar 0...4.0 MPa 4…20 mA
QBE2103-P60 S55720-S309 0...60 bar 0...6.0 MPa 4…20 mA
*) These types do not have M5 inside threads.
Ordering and delivery
When ordering a pressure sensor, please provide quantity, type reference, order
number and product name.
Example Quantity Type ref. (ASN) Order number (SSN) Product Name
1 QBE2003-P1 S55720-S290 Pressure
sensor
Any accessories required must be ordered separately.
Accessories
Type Order No.(SSN) Name Data Sheet
AQB2004**) S55720-S318 Mounting bracket to attach the A6V10434028
pressure sensor for remote
mounting.
AQB2001**) S55720-S116 Connection set for remote A6V10434028
mounting with 1 m copper
capillary line. Pressure
connection external thread
G ⅛" or G ½".
**) Cannot be used with types QBE2003-P10, QBE2003-P16, QBE2003-P25, QBE2103-P10,
QBE2103-P16, and QBE2103-P25. These types do not have M5 inside threads.
2/6
Mechanical design
The pressure sensor consists of:
• Sensor hood with DIN EN 175301-803-A plug-in connection
• Piezo-resistive measuring element integrated in the stainless steel case
• Pressure connection external thread G ½" and inside thread M5*) for use with
accessory AQB2001**)
• Plug DIN EN 175301-803-A (plugged in)
No changes or adjustments are possible.
*) The following types do not have M5 inside threads:
QBE2003-P10, QBE2003-P16, QBE2003-P25, QBE2103-P10, QBE2103-P16, and QBE2103-P25
**) Cannot be used on types QBE2003-P10, QBE2003-P16, QBE2003-P25, QBE2103-P10,
QBE2103-P16, and QBE2103-P25. A solution on the construction side using the ½" threaded
connection is possible.
Mounting notes
Mounting Instructions are enclosed with the sensor. For further information about
mounting location and mounting position refer to the sensor mounting user's manual at
the BT download center: http://siemens.com/bt/download.
Appropriate measures must be taken to ensure a leak-proof fitting.
To provide for test measurements without leakage of the medium, it is strongly
recommended that an appropriate test adapter and shutoff device be fitted.
Pressure measurement The tapping point should be at the side, near the bottom of
with liquids the pipe. Do not measure the pressure from the top of the
pipe (where it may be affected by airlocks) or the bottom
1909Z03
(where it may be affected by dirt).
Pressure measurement The tapping point should be at the top so that no condensate
with condensing gases reaches the sensor.
1909Z04
Important note Ensure suitable constructions measures are undertaken to avoid pressure shocks in
the plant; pressure shocks may damage the pressure sensor's diaphragm.
In the event that pressure shocks are unavoidable, a panel screw (M5) may be able to
weaken the effect. Contact in this case your nearest Siemens branch office.
Disposal
The device is considered electrical and electronic equipment for disposal in terms of the
applicable European Directive and may not be disposed of as domestic garbage.
• Dispose of the device via the channels provided for this purpose.
• Comply with all local and currently applicable laws and regulations.
3/6
4/6
Internal diagram
QBE2003…
BT-Terminal Terminal nr. Meaning
marking
U( ) 2 Output signal DC 0...10 V
(signal ground GND)
M (0) 3 GND
5/6
QBE2003-P…
QBE2103-P…
Published by:
Siemens Switzerland Ltd.
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
Switzerland
Tel. +41 58-724 24 24 © Siemens Switzerland Ltd 2005
www.siemens.com/buildingtechnologies Delivery and technical specifications subject to change
6/6