TOTAL

MARK WIRE SIZE CONDUIT BREAKER


COMPUTED LOAD
WATTS VOLTS AMP SIZE

MAIN 38-LO; 15-CO; 2-WH; 1-RO; 1-WP; 2-ACU 17800 220 80.909 2 - 22 mm2 25 mm 110 A
2 - #14 TW /
1/LP 10 - Light outlets at 100 Watts each 1000 220 4.545 13 mm 15 A
2.0 mm2
4.091 2 - #14 TW /
2/LP 9 - Light outlets at 100 Watts each 900 220 13 mm 15 A
2.0 mm2
2 - #14 TW / 15 A
3/LP 9 - Light outlets at 100 Watts each 900 220 4.091 13 mm
2.0 mm2
2 - #12 TW /
4/LP 5 - Conv outlets at 180 Watts each 1800 220 8.182 13 mm 20 A
3.5 mm2
2 - #12 TW /
5/LP 5 - Conv outlets at 180 Watts each 1800 220 8.182 13 mm 20 A
3.5 mm2
1800 220 2 - #12 TW / 13 mm 20 A
6/LP 5 - Conv outlets at 180 Watts each 8.182
3.5 mm2
2 - Water heater outlet 2 - #10 TW /
7/LP 2500 220 22.727 13 mm 30 A
5.5 mm2
2 - #12 TW /
8/LP 1 - Refrigerator outlet 1600 220 7.273 13 mm 30 A
3.5 mm2
2 - #10 TW /
9/LP 1 - Water Pump outlet 1000 220 4.545 13 mm 30 A
5.5 mm2
4.545 2 - #10 TW / 13 mm 30 A
10/LP 1 - Air Conditioning Unit 1000 220
5.5 mm2
2 - #10 TW / 30 A
11/LP 1 - Air Conditioning Unit 1000 220 4.545 13 mm
5.5 mm2