A Ele Spe 800 30021 0
A Ele Spe 800 30021 0
A Ele Spe 800 30021 0
Document No : A-ELE-SPE-800-30021
Revision 0
Revision History
Revision Changes
Holds
Hold No. Location Description
Page 2 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
Content
REVISION HISTORY 2
CONTENT 3
1 ABBREVIATIONS 4
2 INTRODUCTION 5
2.1 Project Description 5
2.2 Purpose of the Document 5
2.3 Order of Precedence 5
2.4 Definitions 6
3 CODES AND STANDARDS 7
3.1 General 7
3.2 Algerian Government Requirements 7
3.3 Project Documents 7
3.4 International Codes and Standards 8
4 SITE CONDITIONS 12
5 SCOPE OF SUPPLY 13
5.1 Supplier Proposals and Exceptions 13
5.2 Conflicts 13
5.3 General requirements 13
5.4 Modular Substation 13
5.5 Substation Layout 15
5.6 Clearances 15
5.7 Cable Entry 15
5.8 Lighting and Small Power requirement 16
5.9 Wiring and Cabling 17
5.10 Earthing Protection 18
5.11 HVAC System 18
5.12 Fire Detection, Fighting and Safety Equipment 20
5.13 Operator provided items 21
5.14 Warning labels 21
5.15 Painting 22
6 TEST, DELIVERY AND INSTALLATION 23
6.1 Testing 23
6.2 Transportation 24
6.3 Lifting 25
6.4 Installation 25
6.5 Special Tools and Test Equipment 26
7 SPARES 27
8 QUALITY ASSURANCE 28
9 DOCUMENTATION 29
Page 3 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
1 ABBREVIATIONS
API American Petroleum Institute
ATEX Directive for the supply and use of equipment in potentially explosive
atmospheres (Atmosphere Explosive)
IP Ingress Protection
LV Low Voltage
HV High Voltage
Page 4 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
2 INTRODUCTION
Page 5 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
2.4 Definitions
The terms and definitions as used within this document are listed below:
“CONTRACTOR” means the party, which carries out all or part of the design,
engineering, installation and commissioning, procurement
and construction applicable to this specification
“shall” or “must” indicates that the specified action is mandatory (i.e. must be
done by the specified action party)
“Goods” means the physical items delivered under the terms of the
purchase order or contract
Page 6 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
3.1 General
The design, construction and supply of the Modular Substation shall be in accordance
with the latest revisions of the following specifications, data sheets, codes and
standards.
Where national Algerian regulations, codes and standards exist, their recommendations
shall always apply. Such national regulations shall therefore supplement or amend the
provisions of this document.
Equipment supplied shall in addition to complying with national standards, also be in
compliance with the following guides and recommended standards. Codes and
Standards referred here shall be of the latest revision issued at the effective date 21st
Dec-2018
Discipline: Electrical
A-ELE-BOD-800-30001 Electrical System Basis of Design
A-ELE-PHL-800-30001 Power System Design Philosophy
A-ELE-SPE-000-00012 Distribution board specification
A-ELE-SPE-000-00015 Electrical Power and Control Cables Specification
Discipline: Instrumentation
A-INS-SPE-000-30016 Specification of Instrument cables
A-INS-SPE-000-30015 Specification of Fire and Gas Devices
A-INS-BDM-000-30000 Integrated Control & Safety System Architecture Diagram
A-INS-BOD-000-30000 Control and Instrumentation Design Basis
A-INS-SPE-000-30000 Specification of General Instrumentation
Discipline: Civil & Structural
A-CIV-BOD-000-30001 Civil & Structural Design Basis
A-ARC-PHL-000-30000 Architectural Works Philosophy
A-CIV-SPE-000-30013 Specification for Building Materials
A-CIV-SPE-000-30007 Specification for Str Steel Fab & Erection
Discipline: HSE
A-TSE-PHL-000-30000 HSE Design Philosophy
Page 7 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
Page 8 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
Page 9 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
Page 10 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
Supplier shall provide an EC declaration of conformity, which shall state full compliance
to the EC directives and standards. The declaration shall further state the method of
compliance followed, e.g.:
• Self-certification to appropriate harmonized European standards;
• Technical file, which is approved by an accepted, notified body;
• Type examination.
Page 11 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
4 SITE CONDITIONS
Electrical equipment shall be suitable for Site conditions detailed into Specification A-
ENG-BOD-000-30001 -Basis of Design – Surface facilities. Operation will be in a desert
environment, with frequent sandstorms with both elevated and freezing temperatures
within a twenty-four (24) hour period.
Power distribution equipment shall be located in positive pressure ventilated
substations. Design criteria for equipment located inside Substation Electrical Room
(Switchboards, Distribution Boards, UPS Panels), Instrument room and Battery Room
(Cells, Automatic Isolation Breaker & System Monitoring) will be as follows:
Minimum Maximum
Area – Equipment
C C
Normal operation 15 27
Abnormal operation -5 45
Page 12 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
5 SCOPE OF SUPPLY
5.2 Conflicts
If any of the reference documents conflict and definition is not established in this
Specification, then the Suppliers shall bring this to the attention of Ain Tsila Project and
shall state the basis of design used.
Page 13 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
The substation unit shall be supported on concrete columns (by CONTRACTOR) and
shall be of 2.1m in height. Base of the substation unit shall have 2.3m clearance above
the FGL.
Floor penetrations for switchgear shall be made as large as practical especially those
beneath the Switchgear, LV MCC’s. The cable entry systems shall be in situ for
shipment to site. Where cable entries are provided for single core cables, the design
and materials used shall prevent circulation of eddy currents.
The Supplier shall provide a detailed description, including drawings and technical data
of the cables/busduct penetration system.
Walls shall be made sufficiently rigid to allow for the support of typical wall mounted
equipment. The roof shall be pitched along the width of the structure for adequate
drainage, away from doors and any equipment mounted through the substation walls.
The substation shall have a personnel access door at each end. The door nearest the
switchgear shall be designed to permit the passage of the largest equipment item
installed in the substation.
All doors shall have a minimum swing of 105o and shall open outward.
Each door shall be of uniform thickness free from warps, bows and shall have sufficient
rigidity to maintain a positive seal when closed.
Exterior door furniture shall consist of a stainless-steel handle and cylinder lock. All
external doors shall be locked and keyed to master key system, unless noted otherwise.
Four keys shall be provided.
Interior door furniture shall consist of a panic bar assembly designed to override all
locks for emergency exit from the substation. Doorknobs shall not be provided to
escape doors.
Each door shall be equipped with a pneumatic or hydraulic door closer, heavy duty type,
surface mounted, fixed and adjusted to ensure the smooth, slow full closing of the door
leaf and doorstop to lock the door in the open position.
A designated entrance door shall be complete with observation window (to ascertain
any fire hazard etc. in response to a fire alarm signal) and shall be blast proof where
applicable.
In addition to the personnel door, an equipment door of suitable size shall be provided
to move the installed and future equipment.
The modular building shall include all features and equipment necessary to house and
protect the equipment in the site environmental conditions and provide for adequate
access to support maintenance and system expansion.
Air locks: The package shall be complete with an additional set of doors to form an
airlock, out with each of the inner doors to preserve the positive pressure within the
building.
Ingress Protection (IP) Rating: The equipment provided inside the building will be
minimum IP42 as defined in IEC 60529.
Page 14 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
Equipment within the Substation shall be labelled in accordance with Specification for
Equipment numbering system.
The Substation shall be fitted with 2 x 100% HVAC units with suitable dust
filtration/extraction (constant temperature control) as per HVAC Design basis and
Specification Doc.no A-HVA-BOD-000-30000. It shall be possible to monitor the
temperature in each room remotely.
5.6 Clearances
The layout of substation electrical equipment shall be arranged to provide adequate
access for installation, inspection, maintenance, operation and possible repairs. The
clearances for main HV & LV equipment shall be as per Electrical System Basis of
Design (Doc.no. A-ELE-BOD-800-30001, clause no.6.6.2)
If the equipment manufacture recommends a larger clearance, this shall be followed.
Vertical clearance shall be measured from the highest part of the equipment to the
underside of the lowest roof beam or HVAC ducting.
Page 15 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
Page 16 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
5.9.1 Cables
All Electrical cables shall be provided by the Contractor comply with Electrical Power &
Control Cables Specification (Doc. no. A-ELE-SPE-800-30015).
All cabling and wiring shall be continuous; splices are not permitted. Cables shall be
installed in one length.
Single phase lighting and small power cables shall include an integral earth conductor.
All Instrumentation cables shall comply with Specification for Instrument Cables
(Doc.no. A-INS-SPE-000-30016).
Page 17 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
Page 18 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
The Substation building shall be provided with 2x100% package HVAC System utilising
R134 a to maintain the building positive pressure in order to prevent ingress of
potentially flammable gases and to maintain the internal design condition as per
referred HVAC Design Basis and Specification.
Package air conditioning shall have pre-filter and final filter. The ventilation system for
the battery room shall have 2x100% exhaust fans suitable for Zone-1, IIC, T3. The
ventilation system shall be designed to provide adequate air changes and cooling to
limit internal air temperature as specified in the HVAC Design basis and Specification
referred above.
Humidifiers and heaters shall be provided as required to maintain the inside design
condition.
The fresh air intake (drawn from safe area) shall be provided with sand trap louver with
filter, gas detection and fire and gas damper. The Supplier shall ensure all ventilation
incorporates enough filtering to prevent the ingress of sand and dust into the substation.
The ventilation of the battery room shall extract air from the higher part of the room and
shall always provide enough air changes to keep the hydrogen concentration below
25% of the Lower Flammable Limit (LFL). Continuous ventilation at an appropriate rate
of changes per hour should be provided for the battery room/cabinet associated with
the 110V DC tripping and closing system. The ventilation should be enough to ensure
no hazardous build-up of battery gases within the room/cabinet or substation package.
Air into the battery room shall be once through and will not pass into other rooms.
Battery chargers shall be interlocked with supply fan, battery room shut-off dampers
and battery room extract fan such that boost charging of batteries shall not take place
without a functioning extract system. The extract system shall continue to operate upon
hydrogen detection in either battery room, whilst boost charging shall be inhibited.
The HVAC system filters shall be located so that they can be readily inspected, cleaned
or replaced with the minimum use of special tools or equipment.
The substation building complete HVAC System power supply shall fed from normal
and essential power distribution board to ensure that during a power outage, the
substation building complete HVAC system will be kept running by the essential
services diesel generator. Heating and ventilation design calculations and all design
documents shall be prepared as per the HVAC Design basis and specification referred
above and submitted for Operator engineers review and approval before fabrication
begins.
Based on the QRA report, in case of any blast rated building design, all external wall
duct penetrations, shall be provided with blast resistant dampers meeting the blast
overpressure requirements specified.
Earthing of HVAC ducts to be followed as per Electrical Earthing installation drawing.
The complete HVAC system shall be monitored and controlled from a dedicated DDC
HVAC Control panel. All fire dampers, fire and smoke dampers shall be controlled by
HVAC control panel.
Page 19 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
Three gas detectors at the inlet to the HVAC shall be provided to detect any hazardous
gas drawn into the substation from outside. The gas detectors shall be wired to a
Junction box supplied by building supplier. These gas detectors from the Junction box
to Plant F&G system cabinet shall be wired by CONTRACTOR. Upon confirmed
detection of flammable gas and confirmed fire detection, the Plant F&G system/FACP
shall provide command to HVAC Control Panel to close the certified gas tight inlet
damper and set the HVAC to shutdown mode.
Following signals of each HVAC unit shall be communicated from the HVAC control
panel to ICSS through hardwired signal.
• HVAC System Running
• HVAC Common Fault
• HVAC Shutdown
• HVAC Common alarm
Page 20 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
Supplier shall comply with firefighting and safety equipment specification for Fire
extinguisher, eye wash stations/bottles, fire blankets, first aid kits, safety signage,
Electrical safety kit, stretcher.
Supplier shall comply the requirement of Specification for Fire Suppression System
(Doc no: A-TSE-SPE-000-30001) for FM200 and CO2 system.
Page 21 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
contrast
All safety signs shall be illuminated by one of the following means:
• Directly or indirectly by the essential lighting;
• Photoluminescence.
Safety signs shall be located in accordance with statutory requirements and good
engineering practice.
5.15 Painting
Surface finish and painting shall be compliant with the Specification for Painting
(Doc.no. A-MTL-SPE-000-30003) and suitable for the expected environment at site.
The Supplier / Vendor can suggest using his standard painting finish (if suitable for the
environment specified) with the agreement of the COMPANY.
Page 22 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
6.1 Testing
Supplier shall be responsible for the testing and commissioning of the equipment in his
scope of supply. Testing shall be in accordance with equipment Specifications.
Page 23 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
6.2 Transportation
The enclosure should be fabricated and fitted out as a complete enclosure and if
necessary, the Supplier shall give consideration to the need to ship the enclosure in
sections in order to facilitate transportation.
Where shipping splits are required, the number of sections should be kept to the
minimum possible and the Supplier shall take into consideration the need to minimise
electrical cross connections between sections.
Enclosures shall preferably be split into transportable sections across the width of the
enclosure. Care should be taken to ensure that in-housed equipment is not disturbed
or damaged in any way. Supplier shall include for temporary walls and other
arrangements as appropriate to provide complete weather protection and to protect the
materials, equipment and component parts against corrosion, dampness, breakage or
vibration damage during transportation and handling and for prolonged storage in a
humid, high temperature environment.
If the enclosure is shipped in two or more sections, junction boxes shall be provided at
the interface between the sections for enclosure lighting only. The dc power, CT and
instrumentation/relaying control cable shall be connected by coiled cable connected at
site, not through an interface junction box.
Page 24 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
Supplier shall be responsible for shipping the package from their factory to the site
installation location and for building into their design whatever shipping limitations,
enclosure breakdown and protection that may be necessary. Electrical equipment to be
installed in substations by others shall be transported separately.
Any applicable weight limitations will be advised later. Shipped loose items shall be
clearly marked and identified in documentation, installation procedures and shipping
manifests.
The Supplier shall provide shipping details for approval prior to shipping to site.
The sections of all modules shall have enough support to withstand lifting and lashing
during transit. Suitable lifting unions and lashing points shall be provided on modules.
Modules shall be restrained to max 21 x 6.0 x 4.5 meters / 25 x 4.5 x 4.5 meters (Lx W
x H) and supported with transportation drawings. All internal fittings shall be suitably
fixed to avoid any damage during road transportation over 2000 KMS of unpaved road
in Algeria.
6.3 Lifting
Supplier shall advise on the locations, details and loadings of the base plates to the
support structure, platforms and stairs in order to design and construct concrete
foundations by others. Supplier shall provide all drawings about support structure,
stairs, handrails, walls, platforms etc. for approval. The schedule of this interface
information shall be agreed in advance. Supplier shall provide drawings of each housing
showing centre of gravity co-ordinates and lifting point reactions and the calculated
weight of finished unit(s).
All purpose-made spreader beams or lifting frames, shipping steel and tools shall be
the responsibility of the Supplier. Site cranage and standard slings, shackles, etc., will
be available at the job site. Care shall be taken in both design and handling to ensure
that electrical panels are not distorted or damaged during transport.
Location of lifting points and the weight shall be clearly marked on all shipping
containers.
6.4 Installation
Each pre-assembly shall be completely fitted out with all equipment and internal
services prior to despatch. The Supplier shall provide all documentation and procedures
necessary for the installation of the substation by others.
Where items are required to be dismantled for shipping, instructions shall be provided
for reassembly of sections in the field. Delivery shall include all bolts, splices, etc., for
joining the units together. These joining parts shall be securely packaged and clearly
labelled to enable immediate installation.
Page 25 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
Page 26 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
7 SPARES
The provision of commissioning spares is included in the scope of the CONTRACTOR.
Operational spares are required in addition to commissioning spares, which shall be
replaced as necessary. Spares shall be included in accordance with Specification for
Spare Parts, document.
Page 27 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
8 QUALITY ASSURANCE
To ensure that design objectives are met, the CONTRACTOR and its major SUB -
CONTRACTORS shall operate an accredited quality management system in line with
ISO 9001:2015 “Quality Management Systems – Requirements” or equivalent if agreed
with the COMPANY and demonstrate that effective quality control procedures are in
place to ensure that the requirements of this Specification, recognised codes, national
and industry standards are met. The Purchaser reserves the right to conduct a quality
audit at the Supplier’s/sub-supplier’s facilities at any stage during the design,
manufacture, assembly, inspection and/or factory acceptance testing processes.
Page 28 of 29
Spécification for Modular Substation
Document No : A-ELE-SPE-800-30021
Revision 0
9 DOCUMENTATION
All installation, commissioning and operating instructions for the offered electrical
equipment shall be included and indexed in the Installation, Commissioning, and
Operating Manuals for the modular Substation as per the Contract, as described in the
Requisition.
Shipping, handling and storage documentation shall be in the English and French
languages.
Manuals, training documents and documents produced by equipment suppliers shall
be in the English and French languages.
Page 29 of 29