Product Manual 26159 (Revision H) : EM and LQ Digital Driver
Product Manual 26159 (Revision H) : EM and LQ Digital Driver
Product Manual 26159 (Revision H) : EM and LQ Digital Driver
(Revision H)
Original Instructions
The engine, turbine, or other type of prime mover should be equipped with an
overspeed shutdown device to protect against runaway or damage to the prime
mover with possible personal injury, loss of life, or property damage.
The overspeed shutdown device must be totally independent of the prime mover
control system. An overtemperature or overpressure shutdown device may also
be needed for safety, as appropriate.
Read this entire manual and all other publications pertaining to the work to be performed before
installing, operating, or servicing this equipment. Practice all plant and safety instructions and
precautions. Failure to follow instructions can cause personal injury and/or property damage.
This publication may have been revised or updated since this copy was produced. To verify that
you have the latest revision, be sure to check the publications page on the Woodward website:
www.woodward.com/searchpublications.aspx
The current revision and distribution restriction of all publications are shown in manual 26311.
The latest version of most publications is available on the publications page. If your publication is
not there, please contact your customer service representative to get the latest copy.
Any unauthorized modifications to or use of this equipment outside its specified mechanical,
electrical, or other operating limits may cause personal injury and/or property damage, including
damage to the equipment. Any such unauthorized modifications: (i) constitute "misuse" and/or
"negligence" within the meaning of the product warranty thereby excluding warranty coverage
for any resulting damage, and (ii) invalidate product certifications or listings.
Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward is
believed to be correct and reliable. However, no responsibility is assumed by Woodward unless otherwise expressly
undertaken.
© Woodward 2001
All Rights Reserved
Manual 26159 EM and LQ Digital Driver
Contents
Woodward i
EM and LQ Digital Driver Manual 26159
Contents
ii Woodward
Manual 26159 EM and LQ Digital Driver
Woodward iii
EM and LQ Digital Driver Manual 26159
Regulatory Compliance
These listings are limited only to those units bearing the CE Marking.
iv Woodward
Manual 26159 EM and LQ Digital Driver
2. Avoid the build-up of static electricity on your body by not wearing clothing
made of synthetic materials. Wear cotton or cotton-blend materials as much
as possible because these do not store static electric charges as much as
synthetics.
4. Do not remove the printed circuit board (PCB) from the control cabinet
unless absolutely necessary. If you must remove the PCB from the control
cabinet, follow these precautions:
When replacing a PCB, keep the new PCB in the plastic antistatic
protective bag it comes in until you are ready to install it. Immediately
after removing the old PCB from the control cabinet, place it in the
antistatic protective bag.
Woodward v
EM and LQ Digital Driver Manual 26159
vi Woodward
Manual 26159 EM and LQ Digital Driver
Chapter 1.
General Information
Introduction
The EM and LQ drivers and the EM/LQ actuator/valve provide rugged and
reliable all-electric actuation systems for various prime mover control
applications. The systems provide high bandwidth and high accuracy for the
most demanding applications such as gas valves, water valves, flow control
valves, and variable geometry steam valves. The EM and LQ drivers control an
EM actuator or LQ valve position proportional to a position demand signal
received from a controlling device.
The EM and LQ drivers are digital controls using advanced, model-based control
algorithms for robust control over a wide range of actuator load inertias and
friction levels. The Driver Interface Program (DIP) is provided as a configuration
tool. It connects from a PC to the EM/LQ drivers for setup and system
monitoring. The drivers may also be configured using RS-485 and a MicroNet™
control system.
Variations of the EM and LQ drivers are used to control several Woodward all-
electric actuators. The EM and LQ drivers provide extensive fault monitoring.
Some faults trip an alarm, while more serious faults both trip an alarm and
execute a user defined shutdown action.
For convenience, the EM and LQ driver will be referred to as the EM/LQ driver
and similarly, the EM actuator and LQ valve will be referred to as the EM/LQ
actuator.
Woodward 1
EM and LQ Digital Driver Manual 26159
Driver Communications
The EM/LQ digital drivers offer a variety of interfaces to use for control and
configuration:
4–20 mA position demand and feedback interface (control only).
RS-485 interface for control, setup, and configuration. This interface works
with a NetCon® or MicroNet™ control with the Real Time Serial I/O
(input/output) module.
RS-232 interface to a PC, using the Servlink protocol. A PC-based program
provides setup and configuration features.
2 Woodward
Manual 26159 EM and LQ Digital Driver
Chapter 2.
EM/LQ Driver Installation
The surface of this product can become hot enough or cold enough
to be a hazard. Use protective gear for product handling in these
circumstances. Temperature ratings are included in the specification
section of this manual.
Unpacking
Check the shipping container for evidence of mishandling during shipping.
Carefully remove the EM/LQ driver from the shipping container. Check the
hardware for evidence of damage during shipping. Notify the shipper and
Woodward if shipping damage is found.
Mount the EM/LQ driver using the bolt pattern shown in Figure 2-1. The bolt
pattern is a standard 19-inch (483 mm) rack mounting and is for an off-engine
mounted location.
Woodward 3
EM and LQ Digital Driver Manual 26159
Wiring Requirements
General
The ground terminals on the EM/LQ driver enclosure and EM/LQ actuator must
be connected to Protective Earth (PE) ground. The input power supply should be
referenced to PE ground for safety and to enable ground fault detection.
The PE terminal is for Protective Earth. The terminal uses green and
PE yellow earth ground wire, which is routed to the EM/LQ driver with the
input power. This terminal must be connected directly to Protective
Earth.
The circled ground symbol identifies the earth wire running from the
EM/LQ actuator to the EM/LQ driver. In the event of a fault in the
actuator, this terminal may be used to carry fault currents through the
chassis of the EM/LQ driver and out the PE terminal to earth.
All terminal block screws should be tightened to 0.56—0.79 Nm (5.0—7.0 lb-in).
All wiring shields in the driver are connected to earth ground. For
best noise immunity, connect the other end of all shields to earth
ground through a capacitor (0.001 F, 1000 V).
4 Woodward
Manual 26159 EM and LQ Digital Driver
For best noise immunity, the actuator power cables should be run in separate
cable trays or conduits from the resolver cables. Similarly, the power input cables
should be run in separate cable trays or conduits from the I/O cables.
The EM/LQ driver chassis must be connected to PE ground using one of the
grounding lugs on the back inside surface of the EM/LQ driver enclosure. The
wire used for PE ground must be the same size used for the input wires.
The EM/LQ actuator motor ground wire must be connected to the EM/LQ driver
chassis using one of the grounding lugs on the back inside surface of the EM/LQ
driver enclosure. The wire for this connection must be the same size used for the
motor drive wires.
Woodward 5
EM and LQ Digital Driver Manual 26159
6 Woodward
Manual 26159 EM and LQ Digital Driver
Remove, modify, and replace one or both gland plates to provide watertight wire
feedthrough. Use agency-approved conduit hubs when installing in hazardous or
ordinary locations. Gland plate fasteners must be well tightened (1.8 Nm or 16
lb-in) for proper sealing.
Connect all wires as shown in the plant-wiring diagram for the appropriate
actuator type.
Refer to Chapter 7 for the EML100 actuator.
Refer to Chapter 8 for the EM35MR/EBV 63 and 100.
Refer to Chapter 9 for the EM35MR/3103 and 3171A gas valves.
Refer to Chapter 10 for the LQ25, LQ25T, and LQ Bypass liquid fuel valves.
Refer to Chapter 11 for the EM70 and EM140 actuators.
Refer to Chapter 12 for the EGV and ESV actuators.
The cable between the valve and driver must be no longer than 100 m (328 ft) in
order to ensure position accuracy and slew time.
The actuator must also be connected to Protective Earth (PE) via a green and
yellow wire, as shown on the wiring diagram. This wire must not be smaller than
the power wires, by code. This wire may be run directly to Protective Earth, or to
the terminal provided in the driver chassis and marked with the circled ground
symbol.
For best noise immunity, the valve power cables should be run in separate cable
trays or conduits from the resolver cables.
The EM/LQ driver will not operate if these resolver connectors are
connected to the wrong resolver.
Woodward 7
EM and LQ Digital Driver Manual 26159
Cables should conform to the following requirements:
Code and regulatory requirements applicable to the site location
EM/LQ driver cable size for the installed length to the power source
EM/LQ driver cable size for the installed length to the actuator
Maximum cable length to controlling device
Shielded wiring with shields grounded as shown in the wiring diagram for
the appropriate actuator type
Resolver feedback wires isolated from motor power wires
Wire rated for the maximum expected ambient temperature
Woodward can supply all mating connectors needed as component parts for
wiring the motor and resolvers.
The functions of the terminals on the EM/LQ driver are described in the following
paragraphs.
RS-232 Port
Connector J4 is a 9-pin serial port (DSUB) that connects to a PC computer COM
port through a null modem cable. The wiring must meet the requirements of EIA
RS-232. This standard states a maximum cable length of 16 m (50 ft) with a total
capacitance less than 2500 pF and a data rate not exceeding 56 kbps. The
driver’s RS-232 port configuration is fixed at 38.4 kbps, no parity, 8 bits, and
1 stop bit. Do not leave the RS-232 null modem cable attached to the driver if its
other end is removed from the PC. This reduces the possibility of EMC noise
being introduced to the EM/LQ driver.
The Driver Interface Program cannot configure the driver if the NetCon® unit is
being used to control the driver over the RS-485 interface. However, the Driver
Interface Program is able to monitor the condition and parameters on the driver
while simultaneously communicating over RS-485.
Due to the low priority and low speed of RS-232 communications on the PC, this
protocol is not robust enough to support demand input control. Time-out errors
may also interrupt the supported communications functions over RS-232.
8 Woodward
Manual 26159 EM and LQ Digital Driver
The EM/LQ driver’s terminal blocks on the top board are designed to be removed
by hand. After the EM/LQ driver’s input power is disconnected, the terminal
blocks can be removed one at a time by prying them off using the fingertips.
When removing the terminal block, never pull on the wires connected to the
terminal block.
RS-485 Port
Pins 1 through 4 are for the RS-485 interface. The wiring must be one continuous
cable between nodes and must meet the requirements of EIA RS-485 for 500
kbps excepting that one-half of the cable length limit is recommended due to
harsh environments typical of prime mover installations as follows.
This interface allows control of the EM/LQ driver using a proprietary Woodward
protocol with 5 ms updates when connected to one of the following Woodward
controls:
MicroNet with a real time SIO module
NetCon with a real time SIO module
Woodward 9
EM and LQ Digital Driver Manual 26159
The following functions are provided though this interface:
Alarm and fault indication
Driver shutdown and reset
Position command (demand)
Position feedback
The EM/LQ driver supports RS-485 at speeds of 38.4, 57.6, and 417 kbaud. The
real time SIO module communicates at 417 kbaud. To enable this option, the
user must select RS-485 from the Driver Interface Program Tune page for the
communications demand setting. The RS-485 demand input may be specified as
the primary demand input or a redundant input to be used after a failure of the
primary demand input.
To initiate communications, connect the EM/LQ driver to the Real Time SIO
module and select Reset from the MicroNet or NetCon control. The MicroNet or
NetCon control will provide all configuration/RUN information to the EM/LQ
driver, according to the Graphical Application Program (GAP™).
The RS-485 connection has two jumpers for the termination resistor. From the
factory, the termination resistor jumpers are in the “OUT” position. If this driver is
at the end of the RS-485 network, move the jumpers to the “IN” position.
The drivers have address switches (S1 and S2) on the control circuit board, as
shown in Figure 2-5. S1 sets the tens digit, and S2 sets the ones digit for the
driver address. Although these switches allow up to 20 drivers on the network,
the Real Time SIO can only support one driver per channel.
During initialization, the driver reads the position of the switches which then
becomes its address. It responds to data to this address, and sends data with
this driver address. The MicroNet or NetCon GAP application has an input field
for address, which should be configured by the customer or application engineer
to match the driver address switches.
Analog Input
Pins 11 and 12 allow input of a 4 to 20 mA position command (demand) signal.
Pin 13 is a shield terminal for this cable. A 4 mA input will position the EM/LQ
actuator to the 0% position. A 20 mA input will position the EM/LQ actuator to the
100% position.
10 Woodward
Manual 26159 EM and LQ Digital Driver
An overtravel setting may be enabled to allow an additional 2% travel at both
ends of the stroke to drive into optional external mechanical stops. This allows
3.68 mA to provide –2% position and 20.32 mA to provide 102% travel. The
EM/LQ driver will shut down due to a demand error if the 4 to 20 mA input drops
below 2 mA or exceeds 22 mA, or if the polarity is reversed. If this feature is
used, verify that your Position Error Alarm and Shutdown set points are set to
greater than 2% to avoid false trips. See Chapter 4 on how to change these set
points using the Driver Interface Program.
The 4–20 mA position command is less accurate than using the RS-485 digital
interface for position command.
If the 4–20 mA analog input is used for position command, we recommend that
the 4–20 mA analog output be used to monitor position as a means of verifying
correct driver operation.
If using the Servlink interface, the user must verify that Analog is selected for
Demand Input on the Driver Interface Program’s Tune page to ensure that the 4
to 20 mA input will control the actuator’s position. The analog demand input may
be specified as the primary demand input or a redundant input to be used after a
failure of the primary demand input. If the RS-485 interface is used, demand and
backup demand can be configured through the GAP block.
Analog Output
Pins 14 and 15 provide an isolated 4 to 20 mA output signal from the driver that
is proportional to the EM/LQ actuator shaft position feedback sensor output. Pin
16 is a shield terminal for this cable. A 4 mA output occurs when the EM/LQ
actuator is at the 0% position. A 20 mA output occurs when the EM/LQ actuator
is at the 100% position.
The 4–20 mA position feedback is less accurate than using the RS-485 digital
interface for position feedback.
Discrete Input
Pins 17 through 19 provide an isolated shutdown and reset discrete input to the
driver. Use pins 17 and 19 with an external contact or use pins 18 and 19 with an
external contact in series with an external power supply.
Open the external contact to shut down the driver. Close the external contact to
reset the driver and clear any latched driver fault alarms. Keep the external
contact closed while the driver is running. Keep this external contact open when
initially applying power to the EM/LQ driver.
Woodward 11
EM and LQ Digital Driver Manual 26159
Rotary Address
Switches
S2 = Ones Digit
S1 = Tens Digit
RS-485 Termination
Jumpers
Discrete Output
Pins 20 through 22 provide a relay output. Pin 20 to pin 21 is a normally open
output contact. The contact is closed (energized) when the EM/LQ driver is
operating properly. Pin 21 to pin 22 is a normally close output contact. In the
case of a power shutdown by fault or loss of power, pins 20 and 21 open and
pins 21 and 22 close.
12 Woodward
Manual 26159 EM and LQ Digital Driver
Pins 23 through 25 are to be used for a thermal switch input. The EM70 or
EM140 Actuators have internal thermal switches to prevent overheating of the
motor. Use pins 23 and 24 to connect to the switch. Pin 25 is the shield terminal
for this cable.
This switch will open if the motor temperature rises above 177 °C (350 °F) and
toggles an alarm within the EM120V driver. It will not cause a shutdown but will
warn that the ambient temperature is too high. It could also be that the thermal
conductivity of the mounting pad is too low or that a problem exists in the
actuator.
Motor Resolver
Pins 26 through 34 connect to the motor rotor shaft resolver (per actuator plant
wiring diagram). This resolver provides motor shaft position feedback that is
required to allow brushless commutation of the motor. Cables to the resolver
should be properly shielded from the motor power connections and other EMC
sources to avoid problems due to induced noise that may distort the feedback
signal. The LQ valves do not have a motor resolver.
Position Resolver #1
Pins 35 through 43 connect to the actuator output shaft resolver (see actuator
plant wiring diagram). This resolver provides actuator position feedback and
allows the EM/LQ actuator to position with high accuracy. Cables to the resolver
should be properly shielded from the motor power connections and other EMC
sources to avoid problems due to induced noise that may distort the feedback
signal. In order to meet positioning accuracy, the maximum capacitance of the
resolver wires should be 180 pF/m (55 pF/ft) or less.
Position Resolver #2
Pins 44 through 52 connect to the actuator output shaft resolver (see actuator
plant wiring diagram). This optional redundant resolver provides a second
actuator position feedback signal. Some units do not offer this redundant
resolver. Cables to the resolver should be properly shielded from the motor
power connections and other EMC sources to avoid problems due to induced
noise that may distort the feedback signal. In order to meet positioning accuracy,
the maximum capacitance of the resolver wires should be 180 pF/m (55 pF/ft) or
less.
Woodward 13
EM and LQ Digital Driver Manual 26159
Input Power
Pins 53(+) and 54(–) connect the EM/LQ driver to input power from an external
power source. Refer to Table 5-1 for input voltage recommendations. The input
power must meet overvoltage category III. The voltage between either pin 53 or
54 and the EM/LQ driver enclosure must not exceed the maximum specified for
each model (Table 5-1). The input power source should be referenced to PE
ground for safety and to enable ground fault detection. The power source may be
negative-grounded, positive-grounded, or middle-grounded.
The EM/LQ driver is not equipped with input power switches. For this reason,
some means of switching input power must be provided for installation and
servicing. Do not use a fuse as a switch. A circuit breaker meeting the above
requirements or a separate switch with appropriate ratings may be used for this
purpose. See Table 5-1 for appropriate fusing specifications. The fuse or circuit
breaker must have appropriate dc voltage ratings.
Branch circuit fuses, breakers, and wiring must have applicable safety approval
and be selected according to applicable codes and area classifications. The
system disconnect must be in easy reach of the operator and marked as a
disconnect device. Use only the wire sizes specified below or equivalent metric
sizes which meet local code requirements.
Also note that the wire gauge must comply with local code requirements and be
of sufficient size such that the power supply voltage minus the IR loss in the two
lead wires to the EM/LQ driver does not drop below minimum voltage
specification (Table 5-1) when the current draw is 20 A.
Example calculation: 10 AWG wires will drop 0.050 V/ft at 20 A. Using 100 feet
between the EM/LQ driver and the power supply would provide a voltage drop of
100 x 0.05 = 5.0 V. Thus the power supply must always provide between 23 and
32 Vdc or between 95 V and 150 V depending on the driver input power
specification.
14 Woodward
Manual 26159 EM and LQ Digital Driver
Example calculation: 6 mm² wires will drop 0.144 volts per meter at 20 A. Using
50 meters between the EM/LQ driver and the power supply would provide a
voltage drop of 50 x .144 = 7.2 V. Thus the power supply must always provide
between 25.2 and 32 Vdc or 97.2 V and 150 V depending on the driver input
power specification.
Heavier wires than those listed above will not fit into EM/LQ driver terminals 53
and 54.
If wires larger than 12 AWG or 2.5 mm² are required, the larger wires
given below must be spliced as close as possible to the actuator
using a junction box. From the junction box, 12 AWG or 2.5 mm²
need to be used to the actuator.
In order to meet the specified slew time, the wiring practices for the input and
motor drive must be followed. Larger wire diameters can be used to further
minimize the voltage drop in the wire.
Example calculation: Suppose the cable length between actuator and driver is 50
m (164 ft). Single 10 mm or 8 AWG wires (total of 3 wires) or double 6 mm or 10
AWG wires (total of 6 wires) may be used.
For best noise immunity, the actuator power cables should be run in separate
cable trays or conduits from the resolver cables.
The EM/LQ driver will not operate properly if the motor phases are
wired incorrectly. Verify connections before operation.
Woodward 15
EM and LQ Digital Driver Manual 26159
Chapter 3.
Control Using the RS-485 Interface
Introduction
This chapter describes using a Real Time SIO module in a MicroNet™ or
NetCon® control to configure and control the driver over the RS-485 port. If you
are using the Driver Interface Program to monitor the driver via RS-232 with an
analog input controlling position, refer to Chapter 4.
A more detailed description of the Real Time SIO module can be found in the
MicroNet manual.
After the MicroNet or NetCon control is reset and the EM/LQ driver is reset, the
Comm faults can be cleared and the EM/LQ system(s) should be ready to control
actuator position(s).
The RS-485 interface provides all necessary information to the EM/LQ digital
driver.
Verify that fuel pressure is not present to actuators that may open
due to actuator motion.
Applying Power
1. Verify that the power source is set within the input voltage range, taking into
consideration the cable IR loss.
2. Verify that all EM/LQ driver connections listed in Chapter 2 are properly
made, including earth and motor ground cables and cable shield grounding
terminations.
3. Verify that the EM/LQ driver cover is installed and all cover fasteners are
tightened.
4. Verify that fuel pressure is not present to valves that may open due to
actuator motion.
5. If a brake is present, turn on the power supply to the brake.
6. Verify that the pin 17 to 19 external contact is open to prevent the driver from
running.
7. Apply power to the NetCon or MicroNet system and wait for all modules to
initialize.
8. Verify that the input command is between 0% and 100% for RS-485.
16 Woodward
Manual 26159 EM and LQ Digital Driver
9. Apply power to the EM/LQ driver and wait for the driver(s) to initialize
(approximately 5 seconds).
10. Reset COMM Faults on all EM/LQ systems (method of reset can differ
depending on GAP application).
11. Close contact from pin 17 to 19 and make sure that actuator(s) drive to
commanded position.
Woodward 17
EM and LQ Digital Driver Manual 26159
Chapter 4.
Configuration Using the Driver Interface
Program
Introduction
Purpose
The Driver Interface Program is a configuration tool for the EM/LQ driver. The
following functions are provided through this interface:
Driver setup, configuration, and tuning
Calibrate the actuator stroke
Set the Alarm and Shutdown set points
Set Shutdown action
Set source for demand signal
Fault indication
Monitor Alarms
Monitor Shutdowns
Reset driver Alarms and Shutdowns
Monitor actuator position
Monitor actuator current
System Requirements
The recommended PC is a 166 MHz or faster Pentium with at least 32 MB RAM
running Windows® 95 or 98, or Windows NT®. A 9-pin null-modem RS-232 cable
is required to connect to the driver. The Driver Interface Program requires the
Servlink Server, version 1.54 or later. Servlink is included in the installation
package and will automatically install and configure itself.
Limitations
The Driver Interface Program is a configuration tool and is not designed to
provide permanent remote monitoring capabilities.
The Driver Interface Program cannot reset or configure the driver if any other
serial communications port, such as RS-485, is being used to control the driver.
However, if this protocol is used, the Driver Interface Program is still able to
monitor the condition and parameters on the driver while simultaneously
communicating over RS-485.
The driver’s RS-232 port configuration is fixed at 38.4 kbps, no parity, 8 bits, and
1 stop bit. This chapter describes using the Driver Interface Program to configure
the driver over the RS-232 port. If a Real Time SIO module (usually in
combination with other NetCon® or MicroNet™ modules) is being used to control
and configure over RS-485, refer to Chapter 3.
18 Woodward
Manual 26159 EM and LQ Digital Driver
Verify that fuel pressure is not present to actuators that may open
due to actuator motion.
Applying Power
1. Verify that the power source is set between the input voltage range, taking
into consideration the cable IR loss.
2. Verify that all EM/LQ driver connections are properly made, including earth
and motor ground cables and cable shield grounding terminations.
3. Verify that the EM/LQ driver cover is installed and all cover fasteners are
tightened.
4. Verify that the pin 17 to 19 external contact is open to prevent the driver from
running.
5. If a brake is present, turn on the power supply to the brake.
6. Verify that the input command is between 4 and 20 mA for analog control or
between 0% and 100% for RS-485 control.
7. Apply power to the EM/LQ driver and wait for driver(s) to initialize
(approximately 5 seconds).
8. Close the contact from pin 17 to 19 and make sure that actuator(s) drive to
commanded position.
If the Servlink server has not been configured on the PC used to run the Driver
Interface Software, it should be configured at this time.
Woodward 19
EM and LQ Digital Driver Manual 26159
1. Connect the PC to the driver using a null modem RS-232 cable. (The EM/LQ
driver only requires pins 2, 3, and 5 on a standard 9-pin RS-232 connector.)
Use a male connector on one end and a female connector on the other for
normal PC configurations. It is recommended that in actual use this cable be
kept as short as is practical. From the Start menu, go to Programs =>
Servlink => Servlink server, and run the program.
2. From the Servlink File menu, select New. Servlink will display a
communications dialog box. Verify that the correct serial port is selected
(either COM1 or COM2), and that it is set for Point-to-Point communications
at 38.4 kbps, then select OK. Servlink will now communicate with the driver
and compile the information the PC needs to interface with the driver.
Compiling this information will take ten to fifteen seconds.
3. After this process is complete, select Save As from the Servlink File menu.
Save the file as WGC.NET. This file contains information about the program
that runs the driver, as well as PC setup information such as baud rate, port
number, etc.
4. Close the Servlink program. The above process of creating the WGC.NET
file only needs to be completed once for any PC and driver combination.
However, if a different PC is used with this driver, or a different driver with
this PC, a new WGC.NET file must be created at that time.
If the page being opened has a Ready Light on it, wait for the light to turn green
before pressing any buttons on that page. The Ready Light indicates that the
control is in the desired mode and is ready to accept new data or commands
from the Driver Interface Program.
The Shutdown button can be pressed at any time and will result in the driver
reverting to its shutdown state. The Reset button will not work if the driver is not
in RS-232 Configuration mode. This mode is set on the Tune page.
The Alarm/Shutdown Monitor LEDs at the bottom of the screen will latch ON
(red) when an error occurs. When an error is indicated, refer to the Alarm or
Shutdown pages to identify the problem. The Status Relay LED follows the status
of the fault relay output. When “Shutdown Input Trips Fault Relay Output” on the
Tune page is True, it causes the fault relay output to trip when any shutdown
occurs. When it is False, the fault relay will not indicate a trip state when the
shutdown comes from, and only from, the Shutdown/Reset discrete input. All
other shutdowns will cause the relay to trip.
20 Woodward
Manual 26159 EM and LQ Digital Driver
1. Start the Driver Interface Program on the PC to configure the EM/LQ driver.
2. Wait for the Driver Interface Program to stop displaying Initializing in the
Driver Detected box.
3. Go to the Tune page.
4. Under Configuration, select RS-232.
5. Under Demand, select the interface which will be used to provide position
demands to the driver. Analog represents the 4–20 mA interface, and is the
usual choice.
6. Under Backup, select None.
7. Verify that the desired shutdown action is set.
8. Verify that the communications values are properly configured.
Configuration Set to RS-232
Demand Analog or RS-485
Backup None, Analog, or RS-485
9. Go to the Configure page.
10. Under Driver Type, select the actuator/valve type that is being used.
Figure 4-1 shows the first screen that will be displayed when the Driver Interface
Program is first started.
Woodward 21
EM and LQ Digital Driver Manual 26159
Bottom of Window
Shutdown Box
Shutdown Button
This shuts down the EM/LQ driver and opens the Discrete Output (opens
pins 20 and 21 and closes pins 21 and 22).
Reset Button
This resets Alarms and Shutdowns and will attempt to restart the EM/LQ
driver.
Top of Window
Demand Input
This shows the demand input from the controlling device, where 0% is the
minimum actuator position demand and 100% is the maximum actuator
position demand. The controlling device is selected on the Tune page. If this
source has failed, it will follow the input from the Backup demand source if a
Backup has been selected.
Actuator Position
The Actuator Position box will be identical to the Resolver #1 display. 0%
represents the minimum actuator position and 100% represents the
maximum actuator position, using the same scaling as Demand Input,
above.
Drive Current
This represents the quadrature (torque) current sent to the actuator.
Calibrated LED
The Calibrated LED should always be on during normal operation, thus
indicating that the control has been through Calibration at least once. Note
that the calibrated LED is not reset if the Calibration mode has been aborted
or if it failed for any reason. The control simply returns to the previous set of
Calibration values. The LED will not be on when the control is initially
delivered from the factory.
22 Woodward
Manual 26159 EM and LQ Digital Driver
Calibration Using the Driver Interface Program
Refer to Chapter 7 for calibrating the EML100 and EML100/3151A using the
RS-232 Interface.
Refer to Chapter 8 for calibrating the EM35MR/EBV 63 and 100 using the
RS-232 Interface.
Refer to Chapter 9 for calibrating the EM35MR/3103 and 3171A Gas Valves
using the RS-232 Interface.
Refer to Chapter 10 for calibrating the LQ25, LQ25T, and LQ Bypass Liquid
Valves using the RS-232 Interface.
Refer to Chapter 11 for calibrating the EM70 and EM140 actuators using the
RS-232 Interface.
Refer to Chapter 12 for calibrating the EGV actuator using the RS-232
interface.
Verifying Calibration
1. Go to the Run page.
2. Move the input demand to 4 mA for analog control or 0% for RS-485 and
verify that the actuator moves to its minimum position and that Position
Feedback, Analog Input, and Actuator Position are all 0%.
3. Move the input demand to 20 mA for analog control or 100% for RS-485, and
verify that the actuator moves to its maximum position and that Position
Feedback, Analog Input, and Actuator Position are all 100%.
4. Move the input demand to 12 mA for analog control or 50% for RS-485, and
hit the Shutdown button at the bottom of the window to verify that the correct
shutdown action occurs.
5. The EM/LQ driver is now calibrated. The Driver Interface Program should be
left running during initial engine operation to monitor for fault indications.
6. The null modem RS-232 cable may now be removed from the EM/LQ driver,
or may be left in place to allow future use of the Driver Interface Program.
The Driver Interface Program should not be left running for long-term
monitoring of the driver. If the cable is left connected to the driver it should
also stay connected at the PC end to avoid possible stray EMC emissions.
Troubleshooting Calibration
Actuator Calibration Verification Procedure—Go to the Configure page and
select the Shutdown Configuration box. Select Drive to Minimum. Go to the Run
page. Press the Shutdown button at the bottom of the page to shut down the
control. The actuator should go to its minimum (4 mA) position. Go to the
Configure page and select the Shutdown Configuration box. Select Drive to
Maximum. Go to the Run page. Press the Shutdown button at the bottom of the
page to shut down the control. The actuator should go to its maximum (20 mA)
position. If this procedure works as described, then the actuator is calibrated
correctly. After performing this test, return the Shutdown Configuration to the
desired setting.
Run Page–Note—The Calibrated LED on the Run page should always be on,
indicating that the control has been through Calibration at least once. Note that
the Calibrated LED is not reset if the Calibration mode has been aborted or if it
has failed for any reason, because the control simply returns to the previous set
of calibration values. The LED will not be on when the control is initially delivered
from the factory. This LED is a safety precaution to ensure that the user
calibrates the actuator/control before the actuator is allowed to move.
Woodward 23
EM and LQ Digital Driver Manual 26159
On the Tune page, in the Communications box, Configuration should be set to
RS-232, Demand should be set to Analog, and Backup should be set to None.
This does not apply for RS-485 (NetCon or MicroNet) controlled drivers.
Applying Power to a Calibrated EM/LQ driver—If the EM/LQ driver has been
calibrated, the Driver Interface Program and Servlink software do not need to be
started, and the PC and null modem RS-232 cable do not need to be installed.
For faults resulting only in an alarm and not a shutdown, the user is warned that
a situation exists which, if it worsens, may result in a shutdown fault.
Alarms and shutdown fault indications may be reset through the Driver Interface
Program. Opening and closing the discrete input contact may also reset the
EM/LQ driver, but this will shut down the EM/LQ driver while the discrete input is
open, and is not recommended while the engine is running.
24 Woodward
Manual 26159 EM and LQ Digital Driver
The Driver Interface Program and RS-485 interface may each shut down the
driver at any time. As long as the source of the shutdown is active, no other
source can Reset the driver. For example, if the driver is being controlled by a
NetCon or MicroNet over RS-485 and the Shutdown button is pressed from the
Driver Interface Program, a Reset command from the NetCon or MicroNet will
not clear the shutdown condition. Either the Reset has to come from the Driver
Interface Program itself (set to RS-232 Configuration on the Tune page), or the
RS-232 cable should be disconnected from the PC for 15 seconds before a
Reset command from a NetCon or MicroNet will clear the Shutdown condition.
Alarms Page
The LEDs on the Alarms page indicate the current status of the alarms. If any
LEDs are gray, that alarm does not apply to the selected actuator type. A red
LED indicates a fault status, while for normal operation all LEDs are green. If the
Alarm LED at the bottom of the page is Red and no alarms are showing on the
page, the alarm condition does not exist anymore. Many of the set points that
drive these alarms are set from the Tune page, Figure 4-4.
Woodward 25
EM and LQ Digital Driver Manual 26159
Feedback Max Difference
If the difference between the two position resolvers exceeds the Redundant
Feedback Fail Alarm % setting on the Tune page for longer than the allowed
delay, an alarm is generated. The difference between the resolver readings is
averaged when the spread value is under this alarm setting. This indication
should only happen if one of the resolvers comes loose from its mounting and
moves from its calibrated position. If a wire fault occurs on either resolver, this
alarm is meaningless.
RS-485 Alarm
An RS-485 communication error was detected or the Configure page time-out
limit was exceeded.
This switch will open if the motor temperature rises above 180 °C (356 °F). It
could also be that the thermal conductivity of the mounting pad is too low or that
a problem exists in the actuator.
26 Woodward
Manual 26159 EM and LQ Digital Driver
Output Resolver #1 Sine Fault
Indicates a fault with the Resolver #1 Sine circuitry or wiring. If this circuit opens,
it will trip a position error depending on the position of the actuator.
Feedback 1 Failure
Turns red to show the actuator output position feedback resolver #1 circuit has
failed. This alarm may also indicate that one of the sine, cosine, or excitation
wires for resolver #1 is shorted. If a shorted wire is detected and Reset is
received, the driver must see a change in Demand and a corresponding change
in the resolver feedback before the alarm is actually cleared.
Feedback 2 Failure
Turns red to show the actuator output position feedback resolver #2 circuit has
failed. This alarm may also indicate that one of the sine, cosine, or excitation
wires for resolver #2 is shorted. If a shorted wire is detected and Reset is
received, the driver must see a change in Demand and a corresponding change
in the resolver feedback before the alarm is actually cleared.
Woodward 27
EM and LQ Digital Driver Manual 26159
Shutdowns Page
The LEDs on the Shutdown page indicate the condition that caused the
shutdown. If any LEDs are gray, that shutdown does not apply to the selected
actuator type. A red LED indicates a fault status, while for normal operation all
LEDs are green. Many of the set points that drive these shutdowns are set from
the Tune page, shown in Figure 4-4.
CAN Shutdown
This LED should not be annunciated because CAN is not supported in this
version of the driver.
RS-485 Shutdown
Turns red if a Shutdown was received across RS-485, or a protocol or wiring
error occurred while RS-485 was controlling the position of the actuator.
28 Woodward
Manual 26159 EM and LQ Digital Driver
Phase-to-Phase Current Fault
Turns red if a short exists between two of the motor phases.
Discrete Input
Turns red if a shutdown came from the discrete input (opened).
Position Error
Turns red if the difference between the actuator position and demand is greater
than the Tune tab page alarm amplitude and duration setting.
Demand Failure
Turns red if analog input is selected for demand and it is not between 2 and 22
mA. Also turns red if RS-485 is selected and the time-out limit is exceeded or the
input is not between 0% and 100% (–2% and +102% if Extend Travel by 2% is
selected). This input may be redundant such that failure of the primary demand
signal will only produce an alarm when the controlling demand input switches to
the backup demand signal.
DSP Failure
Turns red if the DSP processor inside the EM/LQ driver has a fault. Cycling
power to the EM/LQ driver may correct the Feedback Failure.
Feedback Failure
Turns red to show the actuator output shaft position resolver circuit has failed.
Woodward 29
EM and LQ Digital Driver Manual 26159
Tune Page
The Tune page contains items that can be modified while the driver is controlling
a valve or actuator.
30 Woodward
Manual 26159 EM and LQ Digital Driver
Redundant Feedback Fail Shutdown %, Redundant Feedback Fail
Shutdown Delay
This is the difference allowed between the two position resolvers without
generating a shutdown. If the set percentage is exceeded for longer than the set
delay time, a shutdown is generated. To clear the shutdown, a reset must be
asserted and the resolvers must be within the spread percentage. The difference
between the resolver readings is averaged when the spread value is under this
shutdown setting. If this shutdown occurs, the unit will default to the highest or
lowest resolver reading as determined by the setting of the Use Highest Resolver
Reading box on the Tune page. Setting the delay to 0 ms disables the shutdown.
Extend Travel by 2%
Allows a 3.68 mA input to provide a –2% position, and a 20.32 mA input to
provide 102% of travel. This feature can be used to drive the actuator past the
calibrated 0% to 100% positions.
Communications
Configuration—This must be set to RS-232 for the Driver Interface Program to
be able to configure, calibrate, or reset alarms and shutdowns.
Demand—This is the source for the position demand signal. This value will
usually be set to Analog.
Backup—This is for the backup source for the position demand signal. If the
Demand input fails, the control will default to the Backup demand input.
Woodward 31
EM and LQ Digital Driver Manual 26159
Configure Page
Entering the Configure page will shut down the driver. DO NOT enter
the Configure page of the Driver Interface Program unless you have
taken precautions to prevent a shutdown from damaging your
system.
The Configure page is used to modify values that cannot be changed while the
driver is controlling an actuator.
32 Woodward
Manual 26159 EM and LQ Digital Driver
Actuator Type
Changing the Actuator Type will reload the parameters that control the actuator,
requiring recalibration. It is recommended that after changing this setting, the
driver be power-cycled, then the calibration procedure be performed. The
Actuator Type would only be changed if the driver were moved from its initial
actuator to an entirely different type of actuator.
Shutdown Configuration
Sets action taken after a shutdown fault:
Turn off power
Drive to minimum (4 mA or 0%) position
Drive to maximum (20 mA or 100%) position
Woodward 33
EM and LQ Digital Driver Manual 26159
Chapter 5.
EM/LQ Driver Detailed Specifications
Storage Temperature
–40 to +85 °C (–40 to +185 °F)
Component life is adversely affected by high temperature, high humidity
environments. Room temperature storage is recommended for equipment
longevity.
Humidity
Lloyd’s environment 4 humidity test 1 (2 cycles 20–55 °C at 95% RH
non-condensing, over 48 hours)
EN 50178 (96 hours @ 93 +2 -3 % RH @ 40°C 104 F)
Vibration
Lloyd’s environment 4 vibration test 2 (5-25 Hz @ ± 1.6 mm; 25–100 Hz @ 4.0 g,
10 sweeps per axis at 1 octave/minute)
EN 50178 vibration test 1 (10-57 Hz @ 0.075 mm amplitude and 57–150 Hz @ 1
g, 10 sweeps per axis at 1 octave/minute)
Shock
US MIL-STD 810C Method 516.3, Procedure I
(30 G, 11 ms half-sine waveform)
Air Quality
Pollution degree 2
Ingress Protection
Certified under UL E156028 to the requirements of IP56 as defined in IEC 60529
Dielectric Withstand
707 Vdc from power input and motor drive outputs to PE, for 24 Vdc and 28 Vdc
nominal drivers
1838 Vdc from power input and motor drive outputs to PE, for 120 Vdc nominal
drivers
34 Woodward
Manual 26159 EM and LQ Digital Driver
Electrical Specifications
Power supply to be a Class III (SELV) for the 24 V version drivers (EM
24V and LQ 24V). Also power input is at the input terminals of the
driver.
Nominal Input
18–32 Vdc 90–152 Vdc 18–32 Vdc
Voltage Range
3.3 A 5.5 A
Power Consumption 1.1 A continuous 2.4 A continuous
continuous continuous
Ambient Operating
–20 to +68 °C (–4 to +154 °F)
Temperature
4-20 mA Input
Number Of Channels 1
Input Type 4–20 mA, 0–25 mA maximum
Isolation 0 Vrms, –60 dB CMRR, 200 Vdc common mode
voltage
Input Impedance 200
Anti-Aliasing filter 2 poles at 5 ms
Resolution 16 bits
Accuracy ±0.02 mA at 25 °C
Temp Drift ±6.7 µA/°C, maximum
4-20 mA Output
Number Of Channels 1
Output Type 4–20 mA, 0–25 mA maximum
Current Output 4–20 mA
Isolation 0 Vrms
Min Load Resistance 10
Max Load Resistance 600
Current Readback 10 bits
Resolution 12 bits
Accuracy ±0.064 mA @ 25 °C
Temperature Drift ±1.5 µA/°C, maximum
Woodward 35
EM and LQ Digital Driver Manual 26159
Discrete Input
Three terminals are provided for this input: +24V, Input, and Common. Either a
dry contact or an externally powered circuit may be used. Connect a dry contact
between +24V and Input. The internal power supply will conduct approximately 4
mA through the contact. When using an externally powered circuit, connect the
Common terminal to the external voltage common, and connect the Input
terminal to a voltage source.
Number Of Channels 1
Input Type Optically isolated discrete input
Input Thresholds < 8 Vdc = “OFF”
> 16 Vdc = “ON”
Input Current 3 mA @ 24 Vdc
External Input Voltage Range 18–32 Vdc
Isolated 24 Vdc supply may be used to power contacts, 20 mA maximum
This input is isolated from all other I/O at 500 Vdc. It is not isolated from the other
Discrete Input.
Relay Output
This is a dry contact output providing simplified driver and actuator status
information. A form-C relay contact (NC, Com, and NO terminals) is available. If
any fault is present in the driver or actuator, this relay will be de-energized (Com
and NC connected). If no faults are present, this contact will be energized (Com
and NO connected). The relay specifications are as follows:
Communications Ports
The communications ports are isolated from all other I/O and each other to 500
Vdc.
36 Woodward
Manual 26159 EM and LQ Digital Driver
Chapter 6.
EM/LQ Driver Troubleshooting
Introduction
A clear understanding of the function of the EM/LQ driver and the EM/LQ
actuator is important for troubleshooting. Please read this manual to become
familiar with the hardware prior to troubleshooting.
The following list contains suggestions for quick troubleshooting of the EM/LQ
Digital Driver. If a problem is found, correct the problem and then reset the driver
either by toggling the shutdown/reset switch or by cycling power off and on.
Is the correct input power applied? (Verify correct voltage present between
terminals 53 [+] and 54 [–].) Refer to Table 5-1.
Is the appropriate voltage (18–32 V) present at pin 19 referenced to pin 18
(either from pin 17 or from an external supply)?
If the driver is not communicating via RS-232, follow the procedure on
setting up the Servlink Server file again. Refer to Chapter 4.
If the driver is configured to accept analog (4–20 mA) demand signal, is a 4–
20 mA signal present between terminals 11 (+) and 12 (–)? (If analog
demand is selected, the driver will shut down if this signal is < 2 mA or > 22
mA, unless a backup is configured.)
If the driver is configured to accept RS-485 demand signal, is the driver
properly connected to an RS-485 device such as a MicroNet™ system Real
Time SIO module? Are the address switches and termination jumpers in the
correct position?
Are any of the power wires from the driver terminals 55–60 to the actuator
shorted to each other or to earth ground? Are they connected to the
actuator? Are they phased correctly?
Are all wires of the appropriate size, length, and shielded with properly
grounded shields?
Woodward 37
EM and LQ Digital Driver Manual 26159
The Driver Interface Program Fails to Run Properly—If the Driver Interface
Program fails to run, consider the following actions:
Verify that the EM/LQ driver is running
Verify that the RS-232 cable is properly connected to the EM/LQ driver and
the PC
Exit the Driver Interface Program
If Servlink is still running on the PC, exit Servlink
Shutdown and restart the PC
Start the Driver Interface Program
Verify that Servlink is running
Wait until the Driver Interface Program finishes initialization
Calibration Problems
Actuator/Valve Calibration Verification Procedure
Go to the Tune page and select the Shutdown Configuration box. Press the
Shutdown button at the bottom of the page to shutdown the control. Select Drive
to Minimum. The actuator should go to its minimum (4 mA) position. Select Drive
to Maximum. The actuator should go to its maximum (20 mA) position. If this
procedure works as described, then the actuator is calibrated correctly. After
performing this test, return the Shutdown Configuration to its previous setting.
Both the Set Maximum and Set Minimum buttons must have been
pressed at least once during the Calibration procedure, or else
pressing the Accept button merely reverts the control to its
previously saved Calibration values.
Exiting the Calibration page in any form exits the control from
Calibration mode and returns it to normal operation. If the RS-232
connection is broken during Calibration, the control will return to an
uncalibrated state in approximately 5 seconds.
Run Page—Note
The Calibrated LED on the Run page should always be lit, thus indicating that the
control has been through Calibration at least once. Note that the calibrated LED
is not reset if the Calibration mode has been aborted or if it failed for any reason,
because the control simply returns to the previous set of Calibration values. The
LED will not be lit when the control is initially delivered from the factory. This LED
is a safety precaution to ensure that the user Calibrates the actuator/control
before the actuator is allowed to move.
38 Woodward
Manual 26159 EM and LQ Digital Driver
Calibration Testing
For testing purposes, go to the Tune page and set Shutdown Configuration to
Turn Off Power. Go to the Calibration page. Press the Shutdown button. Press
the Set Minimum Position button. Move the actuator toward the maximum
position. Press the Set Maximum Position button, followed by the Accept button.
Perform the Actuator Calibration Verification Procedure above. Verify that the
actuator moves. If it does not, something may be wrong with the control and this
procedure should be performed on the backup unit. After this test, recalibrate the
actuator to its original settings and return Shutdown Configuration to its previous
state.
On the Run page, press the Shutdown button. Move the actuator. Is the
movement somewhat related to the identical movement of the Resolver #1 and
the Actuator Position box? If yes, then the actuator resolver is working. If no,
there may be a wiring problem or a problem with the actuator.
Woodward 39
EM and LQ Digital Driver Manual 26159
Check for blinking LEDs. The LEDs on the PCB of an operational driver will
be off. Blinking LEDs usually indicate a hardware problem on the driver.
Reset the driver (turn power off, then back on). If the blinking LEDs still exist,
the driver has a problem and most likely will need to be returned to
Woodward for repair or replacement.
If Shutdown Configuration is set to Turn Off Power and you are having
trouble clearing the Position Error Alarm and Shutdown conditions, keep in
mind that external forces may move the actuator beyond the Position Error
Alarm and Shutdown settings (Tune page). For example, if a return-to-
minimum spring is used, the actuator's physical minimum position, or hard
stop, is 0 degrees, the Minimum Position (or Offset) is set to 30 degrees, and
the Position Error Shutdown setting is 10 degrees, a Reset will not be able to
clear the Position Error Shutdown because a 30-degree difference exists
between the desired position (assuming a 0% demand) and the current
position. If Turn Off Power is used, it is mandatory that your Position Error
Shutdown setting be greater than the difference between your Minimum Hard
Stop and your Minimum Position settings.
Driver moves the actuator backwards or always drives into a hard stop
Check Wiring. If the excitation resolver wiring is reversed, the actuator moves
in the opposite direction from what is expected. The driver is unable to detect
reversed resolver wiring.
Existing Installation
Driver does not control the actuator
Check all conditions under New Installation, but you can assume the wiring is
OK if it has not been modified since it last ran successfully.
Driver moves the actuator backwards or always drives into a hard stop
Check Calibration. Verify that the hard stop numbers are outside of the
Min/Max numbers. For example, if Hard Stop Min is 100, Min Position is 110,
Max Position is 190, and Hard Stop Max is 200 degrees, the Hard Stop Min
number is outside the Min/Max span for a clockwise direction, but is inside
the Min/Max span (and therefore incorrect) for a counterclockwise direction.
The driver cannot make an intelligent decision about what the user wants to
do. For most installations, the Hard Stop Min and Hard Stop Max numbers
should be taken directly from numbers marked on the actuator housing.
40 Woodward
Manual 26159 EM and LQ Digital Driver
Check your address switches. The driver always receives the Demand input,
but if its address is different from what is configured in the GAP block, it won't
respond to the NetCon or MicroNet controls. The highest recognized address
is 63.
For a new driver shipped from Woodward, it takes four reset commands from
the NetCon or MicroNet control to fully initialize and calibrate the driver. The
first reset puts it in RS-485 Configuration mode. The second sends a regular
reset. The third calibrates the driver. Finally, the fourth gets the driver
running, assuming all faults have been cleared.
General Guidelines
Don't run the Driver Interface Program while the driver is controlling an
actuator from a NetCon or MicroNet control, especially if using a 5 ms rate
group. While COMM_FAULTs are rare, the additional processing required by
the incoming RS-232 data does modify the RS-485 interrupt timing. This
causes an occasional RS-485 fault when the driver takes more than a few
hundred microseconds to respond to the request from the NetCon or
MicroNet control.
If using RS-485 (NetCon or MicroNet), don't configure the Analog Input as
the primary demand source. The digital data is more accurate and should
always be configured as the primary demand source when it is available. The
Analog Input can be used as the backup demand source.
If the NetCon or MicroNet control modifies the driver configuration (any Reset
command) and the Driver Interface Program is also being used to monitor
the driver, some fields on the Driver Interface Program will not reflect the
changes from the NetCon or MicroNet until a page change or the Driver
Interface Program is restarted.
When the NetCon or MicroNet is rebooted or receives a full system reset, the
driver will report a Feedback Fail alarm (#1 or #2) until the Demand is
stepped any small amount and the driver can tell for certain that a resolver
wire short does not exist.
Since calibration information is sent on every Reset command from the
NetCon or MicroNet control to the driver, the driver only performs the
calibration task when the calibration information has changed. Consequently,
there can be cases where the NetCon or MicroNet control tries to calibrate
the driver and it does not calibrate because the stored data is identical to the
sent data. The work-around is to slightly bump any Feedback Offset or
Minimum/Maximum stop number, send a Reset, then return the variable to its
original value.
Actuator/Valve Problems
Refer to the applicable actuator/valve manual.
Woodward 41
EM and LQ Digital Driver Manual 26159
Driver Failure
If all of the previous troubleshooting techniques have been tried and the driver
still does not work, try power-cycling the driver. If the driver still does not work, try
the following:
42 Woodward
Manual 26159 EM and LQ Digital Driver
Chapter 7.
EML100 Actuator and EML100/3151A
Water Valve
Introduction
The EM24 Digital Driver and the EML100 actuator provide a rugged and reliable
all-electric actuation system for various prime mover control applications. The
system provides high bandwidth and high accuracy for the most demanding
applications for water valves, flow control valves, and variable geometry steam
valves. The EM24 Digital Driver controls the EML100 actuator position
proportional to a position demand signal received from a controlling device.
System Accuracy
EML100 Actuator Position Hysteresis ±0.010 inch/0.25 mm (±0.67% of 1.5
inch/38 mm stroke)
EML100 Actuator Position Threshold ±0.002 inch/0.05 mm (±0.13% of 1.5
inch/38 mm stroke)
Using RS-485 for control:
Initial Accuracy: ±0.0125 inch/0.318 mm
Accuracy over temperature: ±0.0127 inch/0.323 mm
Using 4–20 mA for control:
Initial Accuracy: ±0.0125 inch/0.318 mm
Accuracy over temperature: ±0.042 inch/1.07 mm
4–20 mA Position Readback
Initial Accuracy: ±0.4% of stroke + 0.0075 inch/0.19 mm
Accuracy Over Temperature: ±0.81% of stroke + 0.0075 in./0.19 mm
System Performance
Slew Time (10-90% stroke) 0.150 seconds max for 1.5 inch/38 mm
travel at 445 N (100 lbs force) within
rated temperature range at 28 Vdc input
voltage to the driver.
System bandwidth is nominally greater than 18.85 rad/s (3 Hz). The frequency
response mimics a 2-pole linear system, with the bandwidth corresponding to –6
dB gain. The damping factor is set to 1.
Equivalent dead time does not exceed 20 ms, which includes all effects such as
the communications, processing time, mechanical times, etc.
Woodward 43
EM and LQ Digital Driver Manual 26159
The cable between the valve and driver must be no longer than 100 m (328 ft) in
order to ensure position accuracy and slew time.
The actuator must also be connected to Protective Earth (PE) via a green and
yellow wire, as shown on the wiring diagram. This wire must not be smaller than
the power wires, by code. This wire may be run directly to Protective Earth, or to
the terminal provided in the driver chassis and marked with the circled ground
symbol.
For best noise immunity, the valve power cables should be run in separate cable
trays or conduits from the resolver cables.
The EM24 Digital Driver will not operate if these resolver connectors are attached
to the wrong resolver.
44 Woodward
Manual 26159 EM and LQ Digital Driver
Woodward 45
EM and LQ Digital Driver Manual 26159
46 Woodward
Manual 26159 EM and LQ Digital Driver
Set Maximum (20 mA) Position
Press this button when the actuator is positioned at the desired maximum stroke
(20 mA or 100% demand).
Actuator Current
This is the same as Actuator Current on the Run page.
Accept
This saves the changes made in the Calibrate page and returns the user to the
Run page. The changes are not saved if both the Set Minimum and the Set
Maximum buttons were not pressed while on this page. The Set Minimum and
the Set Maximum buttons can be pressed in any order and any number of times
before the Accept button is pressed.
Cancel
Returns the user to the Run page without saving any changes made in the
Calibrate page.
While in Calibration Mode, the driver ignores any Demand change requests from
Analog Input, or RS-485. It is not capable of controlling an engine while in this
mode. Exiting the Calibrate page will return to allowing Demand changes from
the normal sources. This change may result in a sudden change of the actuator’s
position.
Woodward 47
EM and LQ Digital Driver Manual 26159
The best endpoint settings for electric actuators differ from the best
settings for hydraulic actuators. Read this section carefully before
setting endpoints.
48 Woodward
Manual 26159 EM and LQ Digital Driver
In addition to the normal functions, the shorted resolver wire detection algorithm
uses the Redundant Feedback Fail Alarm values. Modifying these values
determines how quickly the algorithm can detect the shorted wire and how far the
resolver reading drifts before the error is detected and the resolver removed from
the position calculations. Using smaller values than the defaults can result in
premature or invalid error detection.
Under no circumstances should your configuration use numbers less than those
indicated above. These numbers can be increased to make an alarm or
shutdown condition less likely to occur, but only at the expense of actuator
movement when a resolver wire is shorted. In general, most turbine applications
will use the above numbers. Most reciprocating engine applications can afford to
increase these numbers. These are installation-dependent values.
Woodward 49
EM and LQ Digital Driver Manual 26159
Chapter 8.
EM35MR/EBV63 and EM35MR/EBV100
Introduction
The EM/LQ driver with the EM35MR actuator and the Electric Bleed Valves
(EBV) provide a rugged and reliable all electric actuation system for various
prime mover control applications. The system provides high bandwidth and high
accuracy for the most demanding applications for gas turbine airflow metering.
The EM/LQ driver controls the EM35MR actuator position proportional to a
position demand signal received from a controlling device.
System Accuracy
Using RS-485 for control:
Initial Accuracy: ±0.3° (18 arc-minutes)
Accuracy Over Temperature: ±0.323° (19.4 arc-minutes)
Using 4–20 mA for control:
Initial Accuracy: ±0.3° + 0.125% of stroke
Accuracy Over Temperature: ±0.323° + 2.00% of stroke
4–20 mA Position Readback
Initial Accuracy: ±0.4% of stroke
Accuracy Over Temperature: ±0.81% of stroke
System Performance
Slew Time is 250 ms at a stroke of 90° at a nominal line voltage of 28 Vdc to the
driver. This slew rate must be measured using the speed achieved between the
10% and 90% points.
System bandwidth is nominally greater than 34 rad/s (5.5 Hz). The frequency
response mimics a 2-pole linear system, with the bandwidth corresponding to –6
dB gain. The damping factor is set to 1.
Equivalent dead time does not exceed 20 ms, which includes all effects such as
the communications, processing time, mechanical times, etc.
50 Woodward
Manual 26159 EM and LQ Digital Driver
Figure 8-1. EM 24V Digital Driver with EM35MR and EBV63/100 Plant Wiring
Diagram
Woodward 51
EM and LQ Digital Driver Manual 26159
52 Woodward
Manual 26159 EM and LQ Digital Driver
Set Maximum (20 mA) Position
Press this button when the actuator is positioned at the desired maximum stroke
(20 mA or 100% demand).
Actuator Current
This is the same as Actuator Current on the Run page.
Accept
This saves the changes made in the Calibrate page and returns the user to the
Run page. The changes are not saved if both the Set Minimum and the Set
Maximum buttons were not pressed while on this page. The Set Minimum and
the Set Maximum buttons can be pressed in any order and any number of times
before the Accept button is pressed.
Cancel
Returns the user to the Run page without saving any changes made in the
Calibrate page.
While in Calibration Mode, the driver ignores any Demand change requests from
Analog Input or RS-485. It is not capable of controlling an engine while in this
mode. Exiting the Calibrate page will return to allowing Demand changes from
the normal sources. This change may result in a sudden change of the actuator’s
position.
Woodward 53
EM and LQ Digital Driver Manual 26159
The best endpoint settings for electric actuators differ from the best
settings for hydraulic actuators. Read this section carefully before
setting endpoints.
The EM35MR/EBV actuator is available with one or two position resolvers. The
minimum and maximum positions are stamped into the nameplate attached to
each actuator. The driver and the actuator are not calibrated together at the
factory. The resolver minimum and maximum positions must be entered before
the driver will accurately control the actuator’s position.
54 Woodward
Manual 26159 EM and LQ Digital Driver
In addition to the normal functions, the shorted resolver wire detection algorithm
uses the Redundant Feedback Fail Alarm values. Modifying these values
determines how quickly the algorithm can detect the shorted wire and how far the
resolver reading drifts before the error is detected and the resolver removed from
the position calculations. Using smaller values than the defaults can result in
premature or invalid error detection.
Woodward 55
EM and LQ Digital Driver Manual 26159
Chapter 9.
EM35MR/3103 and EM35MR/3171A Gas
Valves
Introduction
The EM24 Digital Driver with the EM35MR actuator and the 3103 or 3171 Gas
Valves provides a rugged and reliable all electric actuation system for various
prime mover control applications. The system provides high bandwidth and high
accuracy for the most demanding applications like DLE. The EM24 Digital Driver
controls the EM35MR actuator position proportional to a position demand signal
received from a controlling device.
System Accuracy
Using RS-485 for control:
Accuracy: ±6 arc min RSS (Root Sum Squared)
Using 4–20 mA for control:
Initial Accuracy: ±0.22°
Accuracy Over Temperature: ±1.372°
4–20 mA Position Readback
Initial Accuracy: ±0.24°
Accuracy Over Temperature: ±0.49°
System Performance
Slew Time is 125 ms to open the valve and 120 ms to close the valve (internal
spring adding) at a nominal line voltage of 28 Vdc. This slew rate must be
measured using the speed achieved between the 10% and 90% points. The
rated stroke of the 3103 Gas Valve is 60°, while for the 3171 Gas Valve it’s 45°.
System bandwidth is nominally greater than 31.4 rad/s (5.0 Hz). The frequency
response mimics a 2-pole linear system, with the bandwidth corresponding to –6
dB gain. The damping factor is set to 1.
Equivalent dead time does not exceed 40 ms, which includes all effects such as
the communications, processing time, mechanical times, etc.
56 Woodward
Manual 26159 EM and LQ Digital Driver
Figure 9-1. EM24 Digital Driver with EM35MR/3103 Gas Valve Plant Wiring
Diagram
[This is the same for the EM35MR/3171A Gas Valve.]
Woodward 57
EM and LQ Digital Driver Manual 26159
The following calibration procedure applies for both the EM35MR/3103 and the
EM35MR/3171A Gas Valve.
58 Woodward
Manual 26159 EM and LQ Digital Driver
4. Press Accept to save the new resolver settings and return to Run mode.
5. Apply input commands from 4 mA to 20 mA to the analog input, and
observe the resolver readings on the Run page. If you have dual resolvers,
their readings should be very closely aligned. If the endpoint settings are not
correct, repeat the above procedure to correct the settings.
In addition to the normal functions, the shorted resolver wire detection algorithm
uses the Redundant Feedback Fail Alarm values. Modifying these values
determines how quickly the algorithm can detect the shorted wire and how far the
resolver reading drifts before the error is detected and the resolver removed from
the position calculations. Using smaller values than the defaults can result in
premature or invalid error detection.
Woodward 59
EM and LQ Digital Driver Manual 26159
Chapter 10.
LQ25, LQ25T, and LQ Bypass Liquid
Valves
Introduction
The LQ25, LQ25T, or LQ bypass valve assemblies with the LQ24V Digital Driver
are integrated liquid fuel metering systems which feature valve position control,
all electric actuation, fuel bypass, fuel flow regulation, and fault indication. These
systems may allow multiple independent metered flow paths with a single pump.
The LQ valve assemblies are brushless dc limited angle torquers which position
a metering port for liquid fuel control. The LQ actuators are directly coupled to
both the metering port and position feedback resolvers (single or dual). There are
no intervening gears, linkages, or flex couplings. The high torque actuator and
shearing action of the shoe on the rotor valve provide a high degree of
contamination resistance.
System Accuracy
Using RS-485 for control:
Initial Accuracy: ±0.1° (including temp. drift)
Using 4–20 mA for control:
Initial Accuracy: ±0.1° + (0.0179 x span)
The rotary valve travel for the LQ25 is 69 degrees, giving 1.335 degrees
positional accuracy. The rotary valve travel for the LQ25T and LQ25BP is 66
degrees, giving a positional accuracy of 1.281 degrees.
System Performance
System bandwidth is 40 rad/s (6.4 Hz). The frequency response mimics a 2-pole
linear system, with the bandwidth corresponding to –6 dB gain. The damping
factor is set to 1. Equivalent dead time does not exceed 20 ms, which includes all
effects, such as communications, processing time, mechanical times, etc.
60 Woodward
Manual 26159 EM and LQ Digital Driver
Figure 10-1. LQ24V Digital Driver with LQ25 Valve Plant Wiring Diagram
Woodward 61
EM and LQ Digital Driver Manual 26159
Figure 10-2. LQ24V Digital Driver with LQ25T or LQ Bypass Valve Plant Wiring
Diagram
62 Woodward
Manual 26159 EM and LQ Digital Driver
Woodward 63
EM and LQ Digital Driver Manual 26159
In addition to the normal functions, the shorted resolver wire detection algorithm
uses the Redundant Feedback Fail Alarm values. Modifying these values
determines how quickly the algorithm can detect the shorted wire and how far the
resolver reading drifts before the error is detected and the resolver removed from
the position calculations. Using smaller values than the defaults can result in
premature or invalid error detection.
64 Woodward
Manual 26159 EM and LQ Digital Driver
Chapter 11.
EM70 and EM140 Actuators
Introduction
The EM120V Digital Driver and the EM70 or EM140 actuator provide a rugged
and reliable all electric actuation system for various prime mover control
applications. The system provides high bandwidth and high accuracy for the
most demanding applications for positioning engine fuel injection linkage control,
flow control valves, and gas turbine variable geometry systems. The EM120V
Digital Driver controls the EM70 and EM140 actuator position proportional to a
position demand signal received from a controlling device.
System Accuracy
Total positioning accuracy depends on the calibrated stroke as follows:
Using RS-485 for control
Initial Accuracy: ±0.283° (17 arc-minutes)
Accuracy Over Temperature: ±0.31° (18.6 arc-minutes)
Using 4–20 mA for control
Initial Accuracy: ±0.283° + 0.125% of stroke
Accuracy Over Temperature: ±0.31° + 2.00 % of stroke
4–20 mA Position Readback
Initial Accuracy: ±0.4% of stroke
Accuracy Over Temperature: ±0.81% of stroke
System Performance
Slew Time for the EM70 is 0.112 seconds for 42° of travel at 84 Nm, and for the
EM140 0.225 seconds for 42° of travel at 168 Nm. This slew rate must be
measured using the speed achieved between the 10% and 90% points. The
rated stroke of these actuators is 10° to 320° adjustable (no internal mechanical
stops).
Equivalent dead time does not exceed 20 ms, which includes all effects such as
communications, processing time, mechanical times, etc.
Woodward 65
EM and LQ Digital Driver Manual 26159
Figure 11-1. EM 120V Digital Driver w/ EM70 or EM140 Actuator Plant Wiring
Diagram
66 Woodward
Manual 26159 EM and LQ Digital Driver
Woodward 67
EM and LQ Digital Driver Manual 26159
Set Maximum (20 mA) Position
Press this button when the actuator is positioned at the desired maximum stroke
(20 mA or 100% demand).
Actuator Current
Same as Actuator Current on the Run page.
Accept
This saves the changes made in the Calibrate page and returns the user to the
Run page. The changes are not saved if both the Set Minimum and the Set
Maximum buttons were not pressed while on this page. The Set Minimum and
the Set Maximum buttons can be pressed in any order and any number of times
before the Accept button is pressed.
Cancel
Returns the user to the Run page without saving any changes made in the
Calibrate page.
While in Calibration Mode, the driver ignores any Demand change requests from
Analog Input or RS-485. It is not capable of controlling an engine while in this
mode. Exiting the Calibrate page will return to allowing Demand changes from
the normal sources. This change may result in a sudden change of the actuator’s
position.
68 Woodward
Manual 26159 EM and LQ Digital Driver
In addition to the normal functions, the shorted resolver wire detection algorithm
uses the Redundant Feedback Fail Alarm values. Modifying these values
determines how quickly the algorithm can detect the shorted wire and how far the
resolver reading drifts before the error is detected and the resolver removed from
the position calculations. Using smaller values than the defaults can result in
premature or invalid error detection.
Woodward 69
EM and LQ Digital Driver Manual 26159
Chapter 12.
EGV and ESV Actuators
Introduction
The EM120V Digital Driver with the EGV (Electric Globe Valve) or the ESV
(Electric SonicFlo™ Valve) actuators provide a rugged and reliable all electric
actuation system for various prime mover control applications. The system
provides high bandwidth and high accuracy for the most demanding applications
for positioning turbine engine gas fuel flow control valves. The EM120V Digital
Driver controls the EGV or ESV actuator position proportional to a position
demand signal received from a controlling device.
System Accuracy
Accuracy Definition—Accuracy is a function of a 3-sigma tolerance analysis.
The equation is as follows:
%F.S. = Percent of full scale travel (unit)
%open = Percent of full scale open
ΔT = Temperature change in °C from 25 °C
%P = Position in percent of full scale
ΔP = Change in position due to temperature and position
70 Woodward
Manual 26159 EM and LQ Digital Driver
Total positioning accuracy depends on the calibrated stroke as follows:
Using RS-485 for control
Initial Accuracy: ±0.001 inch/0.03 mm (±0.1% of stroke)
Using 4–20 mA for control
Initial Accuracy: ±0.00125 inch/0.0318 mm (±0.125% of
stroke) @ 25 °C
Accuracy Over Temperature: 0.00042 inch/0.0107 mm (±0.042% of
stroke) per °C change from 25 °C
4–20 mA Position Feedback
Initial Accuracy: ±0.001 inch/0.03 mm (±0.1% of stroke)
@ 25 °C
Accuracy Over Temperature: ±0.000094 inch/0.00239 mm (±0.0094%
of stroke) per °C change from 25 °C
System Performance
Slew Time for the EGV or ESV is 12 to 10 inches per second, or 25% to 75% in
0.130 seconds regardless of load. This slew rate must be measured using the
speed achieved between the 40% and 60% points. The rated stroke of these
actuators is 1.00” (internal mechanical stops at –0.380”/–9.65 mm and at
1.180”/29.97 mm from closed position).
Equivalent dead time does not exceed 10 ms, which includes all effects such as
communications, processing time, mechanical times, etc.
Calibration
No calibration is required for either the EGV or ESV with the EM120 Digital
Driver.
Woodward 71
EM and LQ Digital Driver Manual 26159
72 Woodward
Manual 26159 EM and LQ Digital Driver
In addition to the normal functions, the shorted resolver wire detection algorithm
uses the Redundant Feedback Fail Alarm values. Modifying these values
determines how quickly the algorithm can detect the shorted wire and how far the
resolver reading drifts before the error is detected and the resolver removed from
the position calculations. Using smaller values than the defaults can result in
premature or invalid error detection.
Woodward 73
EM and LQ Digital Driver Manual 26159
Chapter 13.
Service Options
OEM and Packager Support: Many Woodward controls and control devices are
installed into the equipment system and programmed by an Original Equipment
Manufacturer (OEM) or Equipment Packager at their factory. In some cases, the
programming is password-protected by the OEM or packager, and they are the best
source for product service and support. Warranty service for Woodward products
shipped with an equipment system should also be handled through the OEM or
Packager. Please review your equipment system documentation for details.
You can locate your nearest Woodward distributor, AISF, RER, or RTR on our
website at:
www.woodward.com/directory.aspx
74 Woodward
Manual 26159 EM and LQ Digital Driver
This option allows you to call your Full-Service Distributor in the event of an
unexpected outage, or in advance of a scheduled outage, to request a
replacement control unit. If the unit is available at the time of the call, it can
usually be shipped out within 24 hours. You replace your field control unit with
the like-new replacement and return the field unit to the Full-Service Distributor.
Charges for the Replacement/Exchange service are based on a flat rate plus
shipping expenses. You are invoiced the flat rate replacement/exchange charge
plus a core charge at the time the replacement unit is shipped. If the core (field
unit) is returned within 60 days, a credit for the core charge will be issued.
Flat Rate Repair: Flat Rate Repair is available for the majority of standard
products in the field. This program offers you repair service for your products with
the advantage of knowing in advance what the cost will be. All repair work carries
the standard Woodward service warranty (Woodward Product and Service
Warranty 5-01-1205) on replaced parts and labor.
Flat Rate Remanufacture: Flat Rate Remanufacture is very similar to the Flat
Rate Repair option with the exception that the unit will be returned to you in “like-
new” condition and carry with it the full standard Woodward product warranty
(Woodward Product and Service Warranty 5-01-1205). This option is applicable
to mechanical products only.
When shipping the item(s), attach a tag with the following information:
return authorization number;
name and location where the control is installed;
name and phone number of contact person;
complete Woodward part number(s) and serial number(s);
description of the problem;
instructions describing the desired type of repair.
Woodward 75
EM and LQ Digital Driver Manual 26159
Packing a Control
Use the following materials when returning a complete control:
protective caps on any connectors;
antistatic protective bags on all electronic modules;
packing materials that will not damage the surface of the unit;
at least 100 mm (4 inches) of tightly packed, industry-approved packing
material;
a packing carton with double walls;
a strong tape around the outside of the carton for increased strength.
Replacement Parts
When ordering replacement parts for controls, include the following information:
the part number(s) (XXXX-XXXX) that is on the enclosure nameplate;
the unit serial number, which is also on the nameplate.
Engineering Services
Woodward offers various Engineering Services for our products. For these services,
you can contact us by telephone, by email, or through the Woodward website.
Technical Support
Product Training
Field Service
Technical Support is available from your equipment system supplier, your local Full-
Service Distributor, or from many of Woodward’s worldwide locations, depending
upon the product and application. This service can assist you with technical
questions or problem solving during the normal business hours of the Woodward
location you contact. Emergency assistance is also available during non-business
hours by phoning Woodward and stating the urgency of your problem.
For information on these services, please contact us via telephone, email us, or
use our website: www.woodward.com.
76 Woodward
Manual 26159 EM and LQ Digital Driver
You can also locate your nearest Woodward distributor or service facility on our
website at:
www.woodward.com/directory.aspx
Technical Assistance
If you need to telephone for technical assistance, you will need to provide the following information.
Please write it down here before phoning:
Your Name
Site Location
Phone Number
Fax Number
Engine/Turbine Model Number
Manufacturer
Number of Cylinders (if applicable)
Type of Fuel (gas, gaseous, steam, etc)
Rating
Application
Control/Governor #1
Woodward Part Number & Rev. Letter
Control Description or Governor Type
Serial Number
Control/Governor #2
Woodward Part Number & Rev. Letter
Control Description or Governor Type
Serial Number
Control/Governor #3
Woodward Part Number & Rev. Letter
Control Description or Governor Type
Serial Number
If you have an electronic or programmable control, please have the adjustment setting positions or
the menu settings written down and with you at the time of the call.
Woodward 77
EM and LQ Digital Driver Manual 26159
Appendix.
Product Support Statement
Introduction
This product support statement provides information about the support of the
Woodward EBV actuator and associated EM drivers.
All EBV applications should use the 8200-319 EM digital driver. this is currently
the only driver that is compatible with the EBV application.
Although some EBV applications originally used the 8200-177 driver, all were
upgraded to the 8200-319 EM digital driver in the field to provide better
functionality. Current revisions of the 8200-177 EM digital driver are not
compatible with the EBV and should not be used.
78 Woodward
Manual 26159 EM and LQ Digital Driver
Woodward 79
Revision History
Changes in Revision H—
Updated Regulatory Compliance information
Added updated Declarations
Declarations
We appreciate your comments about the content of our publications.
Send comments to: icinfo@woodward.com
2012/5/Colorado