CSC-1321 Gateway User Guide: Downloaded From Manuals Search Engine
CSC-1321 Gateway User Guide: Downloaded From Manuals Search Engine
Compiled: Lv Hongchang Checked: Wu Fangying
Standardized: Li Lianchang Inspected: Yu Bin
Version : V1. 0
Doc.Code: F0SF.452.028(E)
Issued Date: 2013‐08‐19
Copyright: Beijing Sifang Automation Co., Ltd
Note: The Company reserves the right of modifying the specifications. If there are differences
between products and the specifications, please contact us timely. And we will provide
you with relevant serves.
Note: The company keeps the right to perfect the instruction. If equipments do not agree with
the instruction at anywhere, please contact our company in time. We will provide you with
corresponding service.
®
is registered trademark of Beijing Sifang Automation Co., Ltd.
We reserve all rights to this document, even in the event that a patent is issued and a different
commercial proprietary right is registered. Improper use, in particular reproduction and
dissemination to third parties, is not permitted.
This document has been carefully checked. If the user nevertheless detects any errors, he is
asked to notify us as soon as possible.
The data contained in this manual is intended solely for the Gateway description and is not to
be deemed to be a statement of guaranteed properties. In the interests of our customers, we
constantly seek to ensure that our products are developed to the latest technological standards
as a result it is possible that there may be some differences between the hardware/software
product and this information product.
Manufacturer:
Beijing Sifang Automation Co., Ltd.
Using the isolated test pins when measuring signals in open circuitry.
Potentially lethal voltages and currents are present
1 Installation
1 The fixing device shall be fastened to the panel (cabinet) firmly and the
coupling screws of the device shall be tightened.
2 The device grounding shall be of reliable connection to the panel (cabinet)
grounding with grounding wire and grounding busbar and system.
3 The device wiring shall comply with the requirements of wiring diagram.
2 Ethernet Module
The external terminal of -N type Ethernet module is same with that of -N type
main CPU module.
Serial No. 1 2 3 4 5 6 7 8 9 10
Serial No. 11 12 13 14 15 16 17 18 19 20
Meanwhile, there is a small table on the baffle on the top of the module
terminal, indicating the corresponding relation of AX and BX above under
RS232 and RS485 working mode as shown in table 3.
A B
RS485 A B
Serial No. 1 2 3 4 5 6 7 8 9 10
Mark DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 DI9 DI10
Serial No. 11 12 13 14 15 16 17 18 19 20
5 Time synchronization
Setting description of dial switch: (ON: corresponding position i s 1,
otherwise, the corresponding position is 0)
The dial switch J4 shall set the address of time synchronization module with a
range of 0x00-0x0f (see table 5). To distinguish it with the address of other
module, the 0x0c address is allocated for time synchronization module.
See table 6 for the specific setting of dial switch J12 (b1-b4: serial port
protocol type; b5-b8: B code).
Serial No. 1 2 3 4 5 6
synchronization
Ap synchronization
synchronization RS485
serial port
Under GPS pulse time synchronization method, IN1 and IN2 terminals are
pulse input terminals, TXD, RXD and GND terminals are serial port
connection terminal, in which TXD is sending line, connected to the receiving
line of opposite terminal and RXD is the receiving line, connected to the
sending line of opposite terminal and GND is grounding under RS232; TXD
connects to 485+ and RXD connects to 485- under RS485.
Under IRIG-B time synchronization method, IN1 and IN2 terminals are input
terminals, whether pulse time synchronization or level synchronization, IN1 is
positive input terminal and IN2 is the negative input terminal and GND
terminal is shielding grounding.
The selection of time synchronization method relies on the hardware jumper
and completed by coordinating with J5-J11 and J13 on the module. See table
8 for the specific use method.
pp synchronization
ati synchronization
synchronization
synchronization
The “B_C” and “GPS” marked in above table are the mark of jumper
position and there is clear mark near the corresponding jumper on the
hardware board of module. The “/” in the table means that the jumper
position has no impact on the application, which shall be vacant.
Serial No. 1 2 3 4 5 6 7 8
In case of AC input of 220V power module, 220V+ and 220V- terminals can
be connected to any two AC lines.
Terminal 7 and 8 is the loss-of-power alarm blank node output, which is a
normally closed node and closed upon loss of power.
module 2 Active
module 3 Active
……
……
The top line of the interface is time which indicates the local time to seconds.
Figure on the right side is the notion for pages. For example: “1/3” means that
there are totally 3 pages in display and the current page is the first one. The
right side of the top line always displays the similar notion for pages in the
whole menu. The upper right of the screen will display “*” while receiving GPS
time synchronization.
When the communication status of module is changed, the recycling display
will shift to notice display. The recycling display will be recovered when QUIT
button is pressed. After resetting the configuration, the machine prompts to be
restarted to take the new configuration into effect.
Pressing up/ down button under cycling display status can turn pages; long
pressing up/down button can perform rapid page turning.
Pressing QUIT button under cycling display status can lock the screen and
show an “L” in the top line, which indicates the locking status. Pressing QUIT
button again to unlock the screen, and then the “L” will disappear.
Pressing the button SET to enter the main menu under cycling status.
menu menu
Display the
Default Sort
communication
CommState
Active Sort status of module
such function
Gateway has no
Sla Call Set
such function
Sla Config Change Gateway has no
Notify
such function
module (including
circuits in total)
module 15
DI&DO …
actuator operation in
module 15
menu menu
…… panel
All module
Display software
of the device
synchronization
information of
Alarm Event
protection events,
Dig Event alarm events,
telesignalisation
communication
display function
menu menu
of accident, alarm,
Alarm Enable
Comm Enable
Maintain Enable
GPS Enable
protection events,
protection alarm,
telesignalisation,
to display on the
panel or not.
Alarm Enable
Dig Enable
Comm Enable
RecList Enable
Run.con ValueSettg
TimeSettg EventInfo
LocalSettg LCD.Settg
语言(Language)
CommState
Functiong Set
DI&DO
Restart module
VersionInfo
S232 serial port is located on front panel, the software tool in PC can be
connected with the IED via this port to make setting, testing and cofiguration,
etc.
[1-1] 1/1
After selecting a view mode, press SET button to display communication status of
each module in line with sorting mode, and to display communication status of
each configured devices. The interface is as follows:
[1-1-1] 1/1
module2 Active
module7 Active
……
[1-2] 1/1
[1-3-1] 1/1
Figure 8 CSC-1321 display interface for input and output module selecting
Select module 14, press SET button to view each of the input and output
status of it:
[1-3-1-1] 1/1
DI:1 2 3 4 5 6 7 8 9 10
O O O O O O O O O O
DO:1 2
C C
Move the cursor to “input and output” menu item on operating conditionmenu
and enter it; press SET button to enter “output actuator” and display current
configured input and output module respectively. For example, module 14
and module 15 are input and output module, and it can be seen on the
interface as follows:
[1-3-2] 1/1
module 6
DO1 Open
DO1 Close
……
Select module 14, press SET button to enter output drive operation command
display interface:
[1-3-2-1] 1/1
DO1open
DO1close
DO2 open
DO2 close
[1-5]
[2] 1/1
module 1
module 2
module 3
…
Press SET at a certain module, protocol lists of this module are shown.
[2-2] 1/1
ProtConf
S.104Protl1 ProtConf
This left column is a name+serial number list of all the protocol configured for
[2-2-1] 1/1
Tcp Server1
Press SET at the serial interface channel 2 to enter the configuration of this
serial interface channel. More details are seen in 9.3.2.2.2. Channel
Configuration.
[2-1-2] 1/1
This interface is for reference only, and no modification of the protocol can be
made.
[2-3-2-1] 1/1
Move the cursor to the serial port number, and press the up or down keys to
modify its number. In a serial port module, its serial number can be chosen
from 1 to 6.
Move the cursor to the baud rate, and press the up or down key to change its
value.
Then, press SET to confirm your modification.
◆ Ethernet TCP server configuration
Interface of the Ethernet TCP server configuration is shown as follows:
[2-2-1-1] 1/1
Rem IP 192.188.110.001
Mon port 2040
Move the cursor to the remote IP address, and press the up or down key to
change its IP address.
Move the cursor to the monitoring port, and press the up or down key to
change port number.
Then, press SET to confirm your modification.
[2-2-3-1] 1/1
Move the cursor to the connection port, and press the up or down key to alter
the port number.
Move the cursor to the remote IP address, and press the up or down key to
change the IP address
Then, press SET to confirm your modification.
[2-3-1-1] 1/1
Receiving IP 192.188.110.101
Receiving port 2406
Sending IP 236.008.008.008
Sending port 1888
[2-3-1-1] 1/1
IP1 192.168.110.101
IP2 192.168.110.102
IP3 192.168.110.103
Receiving port 1 1888
Receiving port 2 1888
Sending port 1889
Move the cursor to the address of IP1, IP2, and IP3 respectively, and press
[3] 1/1
[3-1] 1/1
Current time
2013-03-20 16;14;15
Setting time
2013-03-20 16;14;15
In initial interface, setting time equals to the current time. When entering this
interface, its current time keeps going as its second beats, while its setting
time suspends for modification. Move the cursor to the figure needed, and
press the up or down key to adjust its figure. Long pressing can accelerate its
changing speed. Then, press SET to confirm your adjustment, QUIT to
cancel.
[3-2] 1/1
[4] 1/1
Real-time Info
If functions of the four events are all accessible, interface of menu appears
after entering real-time information as follows:
[4-1] 1/1
[4-1] 1/1
Fault event
Comm event
Event information arranged by the order of time can be seen in this interface,
including time, device, and event type. Press the up or down key to turn the
page while reading and long pressing can accelerate the page turning speed.
Press QUIT to log out.
[6] 1/1
Contrast
Backlight time
[6-1]
LCD test
In the interface, press the up or down key to adjust its contrast, and the
adjusted effect can be seen simultaneously.
[6-2]
05 Min
When in this interface, press the up or down key to adjust the backlight time
within 00~99, which indicates the time limit of backlight. For example, if
setting its value into 15, then the backlight would be out 15 minutes of
no-operation; if setting it into 0, the backlight would be long bright and won’t
be quenched.
After setting, press SET to confirm the adjustment, or QUIT to cancel.
3.7 Language
Language menu is to set the language (simplified Chinese,English) of LCD
display. Press the left or right key of the four buttons to enter the following
language setting interface:
简体中文
Englsih
No
No work, MMI and Not reliable connection of Check the power supply wiring
1 indicator lights are not power supply to assure it is reliably
on while powering on connected.
Loose terminal between Push the module closely to the