Tal A44 81 - 204 kVA: Common Data
Tal A44 81 - 204 kVA: Common Data
Tal A44 81 - 204 kVA: Common Data
Common Data
Drip Proof IP 23 Total Harmonic THD (**) in no-load ....: < 3.5 % according to C.E.I.
Altitude ≤ 1000 m Total Harmonic THD (**) in linear load: < 5 % according to C.E.I.
Duty/T°C Continuous / 40°C St. By/ 27°C Continuous / 40°C St. By/ 27°C
Y 380V 400V 415V 380V 400V 415V 380V 416V 440V 480V 380V 416V 440V 480V
∆ 220V 230V 240V 220V 230V 240V x’d x’’d 220V 240V 254V 277V 220V 240V 254V 277V
TAL-A44-D 100 100 95 110 110 105 15.1 9.4 95 104 109 120 104 114 120 132
TAL-A44-E 119 125 119 130 137.5 130 14.8 9.3 119 130 137 150 130 143 150 165
TAL-A44-H 137.5 137.5 128 151.5 151.5 141 14.1 8.8 130 143 150 165 143 157 165 182
TAL-A44-J 143 150 143 157 165 157 13.1 8.2 142 156 164 180 156 171 180 198
TAL-A44-K 161.5 170 161.5 178 187.5 178 12.4 7.8 161 177 186 204 177 194 204 224
www.leroy-somer.com/epg
TAL A44
81– 204 kVA
Efficiencies (%)
Class H / 40 ° C
DATA SHEET
1/4 2/4 3/4 4/4 St.By 1/4 2/4 3/4 4/4 St.By 1/4 2/4 3/4 4/4 St.By 1/4 2/4 3/4 4/4 St.By
TAL-A44-C 84.1 89.8 90.3 87.6 85.9 85.6 91.8 93.5 92.7 91.9 TAL-A44-C 83.9 89.3 90.6 88.7 87.1 85.6 90.4 93.2 92.9 92.1
TAL-A44-D 84.6 90.5 91.3 89.0 87.8 86.1 92.3 94.1 93.5 92.4 TAL-A44-D 84.7 90.0 91.5 90.0 88.8 86.3 91.0 93.9 93.7 93.0
TAL-A44-E 86.2 91.5 92.0 89.4 87.8 87.6 93.1 94.7 93.9 93.2 TAL-A44-E 86.6 91.1 92.3 90.4 89.1 88.2 92.0 94.5 94.1 93.4
TAL-A44-H 86.2 91.8 92.7 90.8 89.6 87.6 93.3 95.1 94.6 94.0 TAL-A44-H 86.7 91.4 92.9 91.6 90.7 88.2 92.2 94.9 94.7 94.4
TAL-A44-J 86.3 91.9 92.9 91.0 89.8 87.6 93.4 95.2 94.7 94.1 TAL-A44-J 86.9 91.6 93.1 91.8 90.9 88.4 92.3 95.0 94.9 94.5
TAL-A44-K 87.8 92.7 93.4 91.4 90.0 89.0 94.0 95.6 94.9 94.3 TAL-A44-K 88.5 92.4 93.6 92.2 91.2 89.9 93.5 95.4 95.1 94.7
400V - 50 Hz 480V - 60 Hz
C D E H J K C D E H J K
30% 30%
25% 25%
20% 20%
Voltage dip
Voltage dip
15% 15%
10% 10%
5% 5%
0% 0%
0 50 100 150 200 250 300 350 400 0 50 100 150 200 250 300 350 400 450 500