Inspection Checklist (Icl) : Civil-Compaction Testing Inspection
Inspection Checklist (Icl) : Civil-Compaction Testing Inspection
Inspection Checklist (Icl) : Civil-Compaction Testing Inspection
ITEM
ACCEPTANCE CRITERIA PASS FAIL N/A RE-INSP DATE
No.
One Modified Proctor Test per ASTM D1557 with corresponding Proctor curve shall be performed for each
2
type of fill material or where there is a change in the type or the source of material.
For cohesionless free draining soils, ASTM D4253 Maximum Index Density and Unit Weight of Soils Using
a Vibratory Table and ASTM D4254 Minimum Index Density and Unit Weight of Soil and Calculation of
3
Relative Density shall also be performed for each type of cohesionless, free draining material or where
there is a change in the type or the source of material..
Acceptance testing of in-place density and moisture content (field density testing) on compacted fill will be
performed at the following rates:
1. Under all foundations - one test every 1000 ft² (90 m²) of each lift.
5 2. Under area paving - one test every 2000 ft² (180 m²) of each lift.
3. Road base and sub-base - one test every 2000 ft² (180 m²) of base or sub-base.
4. Backfill of trenches - one test for every 50 linear ft (15 m) of each lift.
5. General fill - one test every 5000 ft² (460 m²) of each lift.
As a minimum, at least one in-place density test must be performed on every lift of fill and further
6
placement shall not be allowed until the required density has been achieved.
Nuclear density gauges, when used, shall have a valid calibration certificate per the requirement of ASTM
7
D2922, Sec. A1.2.
Fill or backfill placed beneath footings, grade beams, mats, buildings or process areas shall be compacted
8
to at least 95% of the maximum Modified Proctor density as determined by ASTM D1557.
For cohesionless free draining soils, 70% relative density as determined by ASTM D4253 and ASTM
9
D4254 shall be achieved under footings, grade beams, mats, buildings or process areas.
Under foundations with static loads over 320kPa and foundations for vibrating or heavy machinery and
10 pavements, 85% of relative density (ASTM D4253/ASTM D4254) for cohesionless soils or 95% of of the
maximum density as determined by ASTM D1557 for cohesive materials.
When the backfill material cannot clearly be classified as cohesive or cohesionless both relative density
11
and Proctor density tests must be performed. The backfill shall then be compacted to the greater density.
The compaction requirement for base coarse shall not be less than 100% of the maximum laboratory dry
12
density as determined by ASTM D1557 or AASHTO T180..
The compaction requirement for subbase shall not be less than 95% of the maximum laboratory dry
13
density as determined by ASTM D1557 or AASHTO T180..
All other fill shall be compacted to the density equal to that shown on the drawings or equal to that
14
adjacent in-situ material as appropriate.
15 The depth of the test holes shall be no greater than 300mm (12 inches) deep. (ASTM D 2922, Sec. 1.1)
REMARKS:
REFERENCE DOCUMENTS:
CONTRACTOR SEC-SA
Page 1 of 1