Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Complience Sheet 15kva

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 4

NO Specification for one-unit 10KVA UPS Weight Bidders specification

1 Application to be used for production COMPLIANT


machinery RIELLO- S3M 15 XTD T2
Can be used for domestic use and home offices
through to factories like in production machineries,
utilities and data centers
2 Capacity: - 15KVA 10 COMPLIANT
RIELLO- S3M 15 XTD T2
Have 15KVA output power capacity
3 Technology: 7 COMPLIANT
 Microprocessor based digital RIELLO- S3M 15 XTD T2
control,  Has microprocessor based digital
 IGBT based, controlling appliance integrated with in it.
 True on-line double conversion,  Has designed and manufactured with IGBT
 AC to DC conversion and then DC based inverter technology
to AC  It is designed for double online conversion
system
 It has a capability of converting from AC to
DC using rectifier and the from DC to AC
using the IGBT based inverter mounted on
it.
4 Input voltage – 220-240V 5 COMPLIANT
Output voltage – 220/230/240V AC- RIELLO- S3M 15 XTD T2
selectable Is designed and manufactured with 220/230/240
input voltage
And also 220/230240V AC selectable output
voltage.
5 Input frequency -45-55 HZ (generator 5 COMPLIANT
compatible) RIELLO- S3M 15 XTD T2
Output frequency – 50HZ Is designed and manufactured to operate on high
range of frequency tolerance(40-72HZ) to fit the
incoming variable frequency from generator or
from Ethiopian electric utility
And has designed to operate with output frequency
of 50HZ and 60HZ auto selectable.
6 Input power factor -> 0.9 5 COMPLIANT
Output power factor – 0.9 RIELLO- S3M 15 XTD T2
Is designed and manufactured with output and input
power factor of 0.99.
7 Inverter efficiency -> 92% 3 COMPLIANT
Crest factor -3:1 RIELLO- S3M 15 XTD T2
Is designed and manufactured with inverter
efficiency of 96.6% and crest factor of 3:1
8 Over load on batteries- 105% -1255% for at 5 COMPLIANT
least 120 sec, if overload exceeds UPS shall RIELLO- S3M 15 XTD T2
to into bypass mode and auto recover on Is designed and manufactured to operate on 110%
removal of load. infinite, 125% for 60 min., 150% for 10 min and
will be get in to automatic bypass mode while it
exceeds the UPS
9 By pass switches – built in static/automatic 5 COMPLIANT
bi-directional type (manually by pass not RIELLO- S3M 15 XTD T2
acceptable) Is designed and manufactured with built in
static/automatic bidirectional type switch.
10 Protection: input over/under voltage, output 10 COMPLIANT
overload, short circuit, battery low/high, RIELLO- S3M 15 XTD T2
battery reversed polarity, protection for Is designed and manufactured with protection
IGBT and thermal overload. circuit for input over and under voltage, output
Operating conditions- 0-40deg. C, 0-90% overload, short circuit, battery low/high, battery
RH maximum, non-condensing reversed polarity, protection for IGBT and thermal
overload.
- And it will operate on 0-45 °C temperature
scale
- And will operate on 0-90% RH maximum,
non-condensing range
11 Display – LED 5 COMPLIANT
Audible noise – 50 DB at front 1 meter. RIELLO- S3M 15 XTD T2
Is designed and manufactured with LED display for
operating or managing the whole system.
And it is integrated with audible noise of 50DB at
front 1 meter.
12 5 COMPLIANT
Batteries – VRLA TYPE RIELLO- S3M 15 XTD T2
Is designed and manufactured with VRLA type
batteries
13 Back up time- 60 minutes on full load. 5 COMPLIANT
RIELLO- S3M 15 XTD T2
xxx
14 Features 10 COMPLIANT
 Alarms with details to be stated by RIELLO- S3M 15 XTD T2
suppliers  Has different alarm conditions
 Single phase input and single-phase  Is equipped with single phase input and
output output operation.
 Cooling internal built air forced type  Has built in air force type cooling system.
 Software support  And has PowerShield3 monitoring and
 Novel and user friendly shutdown software included for Windows
 UPS shall be free from operating systems 10, 8, 7, Hyper-V, 2019,
workmanship defects such as sharp 2016, 2012, and previous versions, Mac OS
edges, nicks, scratches, burrs, etc. X, Linux, VMWare ESXi, Citrix XenServer
 ALL FASTENERS SHALL BE and other Unix operating systems.
FIXED PROPERLY  Is noval and user friendly
 The brand and county of origin  Is new branded UPS so it is free from
should be stated by suppliers workmanship defects such as sharp edges,
nicks, scratches, burrs, etc.
 Its fasteners shall be fixed properly
 The brand is RIELLO- S3M 15 XTD T2
which is originated in Italy.
15 To be included: 10 COMPLIANT
 Batteries with battery rack and RIELLO- S3M 15 XTD T2
connecting loops. Have different features to be included
 Operational and troubleshooting  Is equipped with battery rack and has its
manuals, own connecting loops for connecting the
 Manufacturer’s authorization letter, batteries and the ups
additionally inclusion of  Will be supplied with operational, user and
manufacturer’s certifications shall troubleshooting manuals.
be favorable  Has manufacturer’s authorization letter,
 Reference letters for the supply UPS additionally inclusion of manufacturer’s
preferably in Ethiopia certifications will be favorable.
 The UPS must come complete with  Will be supplied with reference letters for
all parts required of independent the supply of UPS and also which is
operation compatible with Ethiopia
 The UPS will be supplied with all parts
required for independent operations.
16 Warranty: 2 years from installation, testing 10 COMPLIANT
and commissioning RIELLO- S3M 15 XTD T2
Will have 2 years warranty starting from
installation, testing and commissioning.

You might also like