Data Sheet

s Fire Safety Products

Sinorix® Engineered Fire Suppression Systems


Cylinder / Valve Assemblies – 1-1/2” (6.4 cm.) Discharge Port
(Includes: Cylinder-Mounting Straps / Brackets; Top-Plug Adapter; Liquid-Level Indicator & Low-Pressure Switch)
Models CPY-150, CPY-250
ARCHITECT AND ENGINEER SPECIFICATIONS
• For use with Sinorix 227 and Sinorix 1230
• High-flow-rate valve
• 1-1/2 inch, discharge-port valve assembly
• Manual, electric or pressure operated
• Low-pressure monitoring switch
• Wall-mounting brackets included
• Liquid-level indicator
• UL Listed & ULC Listed
FM Approved
CPY-150 CPY-250

Product Overview Specifications


Models CPY-150, CPY-250 are filled as follows: The size 150 and 250 lbs. cylinders use a valve
Cylinder Max. Fill at Min. Fill at with a 1-1/2–inch (6.4 cm.), unified victaulic outlet.
Model
Size 70 LB/FT3 30 LB/FT3 These pressure-seated valves are designed for
CPY-150 150 Lbs. 150 Lbs. 65 Lbs. high-flow rates. Additionally, each valve meets
CPY-250 250 Lbs. 250 Lbs. 110 Lbs.
the rapid discharge time specified in NFPA 2001.
Models CPY-150 and CPY-250 can be filled with
All valve assemblies have:
HFC-227ea suppression agent or with 3M™
 Brass body
Novec™ 1230 Fire Protection Fluid. Models
 Brass piston with resilient seat
CPY-150 and CPY-250 are pressurized with
 Safety-disc assembly
nitrogen to 360 psig at 70°F (21.1°C), and
are manufactured, tested and marked in  Pressure gauge
accordance with D.O.T. specifications:  Pressure-releasing, pilot-check assembly for
manual and pressure actuation, which relieves
4BA500 or 4BW500 for the various sizes.
the pressure above the piston, and permits
All cylinder and valve assemblies are furnished the piston to travel upward
with an internal siphon tube. Cylinders must be  Optional electronic solenoid on the valve,
mounted in the vertical position. which relieves the pressure above the piston,
and permits the piston to travel upward

[Cylinder / Valve Assemblies – 1-1/2” Discharge Port] Sinorix® 6621


s I ndustry, Inc.
Building Technologies Division
Specifications ─ (continued) Electric Actuator & Manual Control Combination
Valve Controls Cylinder Valve Max. Qty. of Piston Copper
Size Size Actuators Tube
All valve sizes accept the same set of valve 150 Lbs. 1-1/2 " 7 50 Ft.
controls. 250 Lbs. 1-1/2 " 7 50 Ft.

Electronic Solenoid Valve The Manual Control Head may be installed


The Electronic Solenoid Valve is normally closed when using the electronic, top-plug-adapter
(NC), and opens upon electric energy being combination.
applied − therefore relieving pressure above the
valve piston, and causing the cylinder valve to
open. For electrical connections, the Electronic
Solenoid Valve is furnished with 24" (61 cm.)
pigtails. Details for Ordering
Part Part Cylinder
Model Description Model Weight
Number Number Size
CPYEC-2-24 500-697990BG Electronic Supervised Solenoid CPY-150 500-697902BG 150 Lbs. 104 Lbs.
CPY-250 500-697903BG 250 Lbs. 103 Lbs.
Local Manual Control Head Weight of empty cylinders

The Local Manual Control Head can be installed on


the top-plug adapter. When the safety pull pin is Cylinder and Valve Assembly
taken out, and the actuating lever is moved down,
it causes a pin to depress and open the pilot check
on the valve.
Agent pressure is then released
above the valve piston.
Pressure Actuator
The Pressure Actuator can be installed on the top-
plug adapter. The Pressure Actuator contains a
piston to provide the necessary force to open the
pilot check, once pressure from the agent
discharge of a primary cylinder is applied through
1/4" (0.64 cm.) tubing. The pressure actuator is
used on pressure-operated (secondary) cylinders,
which are released simultaneously with the
primary Sinorix cylinder.
One (1) primary cylinder can be used to pressure
operate up to a maximum of seven (7) secondary
cylinders. If more than seven (7) cylinders are
required, the engineer may use two (2) electric
primary Sinorix cylinders.
All cylinder valves have a pressure-actuation outlet
port. The pressure-actuation outlet port opens into
the same space as the valve outlet and is only
under pressure while the valve is discharging. The
port has a 1/8" (0.32 cm.) pipe victaulic, which is
fitted with a pipe plug. The pipe plug is removed
when the port is used. The tubing or pipe is
connected to the outlet `M,’ and is run to the
pressure actuators on the secondary cylinders.

s I ndustry, Inc.
Building Technologies Division
–2–
Cylinder Mounting Straps & Brackets Liquid-Level Indicator
The steel straps and brackets are used to The Liquid-Level Indicator works magnetically,
mount the cylinders in the vertical position: so it is not necessary to move or disconnect
cylinders. Uninterrupted hazard protection is
a key feature:

The brackets, which are used for wall-


mounting purposes, are secured to adjacent
wall studs. The brackets and straps are UL
Listed & ULC Listed; as well as FM Approved. The Liquid-Level Indicator must be factory
installed, and is UL Listed & ULC Listed;
as well as FM Approved.

Sinorix Liquid-Level Indicator 1 – (Cylinder Maintenance)

Low-Pressure Switch
The Sinorix Low-Pressure Indicating Switch Upon loss of pressure from the cylinder valve
(Model CPY-PSS1) is a single-pole, single- – due to discharge or leakage – Model CPY-
throw switch that is mounted to the cylinder PSS1 will move to a closed position at
valve during production. 291psig. Model CPY-PSS1 is monitored by a
Supervisory point on the fire-alarm control
Model CPY-PSS1 will remain in the (NC)
panel (FACP). The FACP will provide a
position when no pressure is set against the
Supervisory alarm upon loss of pressure
switch. In Normal operating position, the
below the PSIG set point.
Low-Pressure switch must be set at 360 psig.
When the cylinder valve is pressurized, Model
CPY-PSS1 will move into the open position.

s I ndustry, Inc.
Building Technologies Division
–3–