Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
Download as pdf or txt
Download as pdf or txt
You are on page 1of 32

VPI PRESSURE INDEPENDENT

CONTROL VALVES AND ACTUATORS


PRODUCT DATA

• Automatic balancing eliminates overflows, regardless of


fluctuating pressure conditions in the system.
• Close-off pressure range up to 800 kPa.
• Shut-off leakage as per ANSI / FCI 70-2 206 / IEC 60534-4
- Class IV/ 0.01% leakage of full open valve capacity.
• Differential pressure operating range up to 800 kPaD.
• Available with and without Pressure test ports.
• Two-way, modulating to accept digital or analog input
signals. The valves accept 0(2)-10V, 3-point floating or
ON/OFF input signals.
• Simple Maintenance – Internal parts can be accessed
without removing the valve housing from the piping lines.

APPLICATION
SPECIAL FEATURES Honeywell threaded pressure independent control valves are
• Compact one-unit PICV, including modulating control valve, used in heating and cooling systems such as Air Handling
dynamic flow limiter and differential pressure control valve Units, Fan Coil Units, and other central plant applications.
in one body. Honeywell VPI series provides modulating control with full
authority regardless of pressure fluctuations in the system.
• Available in DN female threaded (ISO) sizes varying from Honeywell VPI series combines an externally adjustable
DN15-50. automatic balancing valve, a differential pressure control valve
• Easy setting and Field adjustable – flow setting is stepless and a full authority modulating control valve in single unit.
and can easily be set to any design flow in the flow range.
Setting can be done before or after installation and flow may Honeywell VPI series makes it simple to achieve 100% control
be changed on demand without removing the valve from the of the water flow in the building, while creating high comfort
installation. and energy savings at the same time. An additional benefit is
that no balancing is required if further stages are added to the
• “Sealed” setting - actuator will cover the setting and protect system, or if the dimensioned capacity is changed. Energy
against tampering. saving due to optimal control, lower flow and pump pressure.
• Standard or failsafe actuator; always incl. feedback signal - Maximized ΔT due to faster response and increased system
an easy solution for designers, installers and end-users. stability.

• Honeywell VPI series PICVs combine 3 functions into one Contents


valve body:
1. Control valve Special Features.....................................................................................1
2. Differential pressure controller that protects against Application ...............................................................................................1
pressure fluctuations. Technical Specifications - Valve .......................................................2
3. Presetting scale to set the desired maximum flow Construction............................................................................................2
• Controls chilled or hot water in closed loop systems with up Measurements and Dimensions.......................................................3
to 50% glycol. Honeywell MLP Actuators (Fail-in-Place) ...................................5
• Flow balancing in valve body through diaphragm. Honeywell MLE Actuators (Electronic Fail-safe) .................... 15
Honeywell ML Actuators - Thermoelectrical............................. 21
• Higher presetting precision due to step less analogue scale
Flow Rate Settings.............................................................................. 25
with 41 Maximum flow setting trough dial on valve body.
Model Selection (Nomenclature) .................................................. 28
• Electrical actuators with selectable control modes, Linear or Valve and Actuator Compatibility ................................................. 29
Equal percentage.
Ordering Information ........................................................................ 32
VPI PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

TECHNICAL SPECIFICATIONS - VALVES


Table 1. Technical Specifications of DN15-DN50 PICVs
Parameter Specifications
Valve Type: Pressure Independent Control Valve

Body Style: Globe / Linear

Size Range: DN15 - DN50 (1/2” - 2”)

PN Pressure Rating: PN25

Static Pressure: 2500 kPa / 360 psi

Ambient Temperature: +1ºC to +50ºC / +34ºF to +122ºF

Medium Temperature: -20ºC to +120ºC / -4ºF to +248ºF

Maximum Close-Off Pressure: 800 kPa / 116 psi


DN15 – DN32: 800 kPaD / 116 psid
Maximum Operational ΔP:
DN40 - DN50: 600 kPaD / 87 psid
Flow Characteristic: Linear, can be converted to equal percentage in the actuator

Shut-Off Leakage: ANSI / FCI 70-2 206 / IEC 60534-4 - Class IV/ 0.01% leakage of full open valve capacity

Control Range: 1:1000 / IEC 60534

Rangeability: 100:1

Turn Down Ratio: 100:1


DN15 - DN25: 3.4 mm (0.13”)
Stroke: DN32: 5.2 mm (0.2”)
DN40 - DN50: 6.2 mm (0.24”)
DN15LF - DN20LF: 64 to 1110 l/hr
DN15HF - DN25HF: 620 to 2650 l/hr
Maximum Flow Rate Setting:
DN32: 865 to 4630 l/hr
DN40 - DN50: 1900 to 13647 l/hr

CONSTRUCTION
Table 2. Construction details of DN15-DN50 PICVs.
Materials
Components
DN15-DN32 DN40-DN50

Valve Housing: DZR Brass ASTM CuZn36Pb2As Ductile iron ASTM A395 Grade 60-40-18

Flow Regulator: Glass-reinforced PSU/POM/PPS Glass-reinforced PSU/POM/PPS

Cone: PPS Stainless Steel


EPDM/Hydrogenated acrylonitrile-butadiene-
Diaphragm: Hydrogenated acrylonitrile-butadiene-rubber
rubber
O-rings and Seat: EPDM EPDM

Head Nut: Forged brass ASTM CuZn40Pb2 --

Thread Connection: Fixed female ISO Fixed female ISO

Housing Taps: 1/4” ISO 1/4” ISO

31-00381-01 2
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

MEASUREMENTS AND DIMENSIONS


DN15-DN32 size valves

Figure 1. Dimension drawings of DN15-DN32 PICVs

Table 3. Dimensions for DN15-DN32

H2 H3 H4 H5

Valve mm (in) mm (in) mm (in) mm (in)


L H1 Weight1
Model no size Actuator Part number
mm (in) mm (in) kg (lb)
mm (in) MLP71MAA
MLP71TNA MLP41TNA MLP71MNA MLP41MNA
MLE71MAA
VPI015TWH2 15 (1/2) 81 (3.19) 31 (1.22) 118 (4.65) 116 (4.57) 124 (4.88) 130 (5.12) 0.50 (1.11)
VPI015TPH2 15 (1/2) 81 (3.19) 31 (1.22) 118 (4.65) 116 (4.57) 124 (4.88) 130 (5.12) 0.50 (1.11)
VPI020TWH2 20 (3/4) 85 (3.35) 31 (1.22) 118 (4.65) 116 (4.57) 124 (4.88) 130 (5.12) 0.52 (1.14)
VPI020TPH2 20 (3/4) 85 (3.35) 31 (1.22) 118 (4.65) 116 (4.57) 124 (4.88) 130 (5.12) 0.52 (1.14)
VPI025TWH2 25 (1) 102 (4.02) 31 (1.22) 118 (4.65) 116 (4.57) 124 (4.88) 130 (5.12) 0.72 (1.59)
VPI025TPH2 25 (1) 102 (4.02) 31 (1.22) 118 (4.65) 116 (4.57) 124 (4.88) 130 (5.12) 0.72 (1.59)
VPI032TWH2 32 (1 1/4) 128 (5.04) 47 (1.85) 138 (5.43) 137 (5.39) 144 (5.67) 153 (6.02) 1.70 (3.75)
VPI032TPH2 32 (1 1/4) 128 (5.04) 47 (1.85) 138 (5.43) 137 (5.39) 144 (5.67) 153 (6.02) 1.70 (3.75)
Note 1: Weight does not include actuator.
3 31-00381-01
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

DN40-DN50 size valves

Figure 2. Dimension drawing of DN40-DN50 PICVs

Table 4. Dimensions for DN40-DN50


Weight2
Valve size L H1 H2
Model no Ductile Iron
mm (in) mm (in) mm (in) mm (in)
kg (lb)

VPI040TPH2 40 (1 1/2) 4.3 (9.5)


191.0 (7.5) 100.2 (3.9) 194.7 (7.7)
VPI050TPL2 50 (2) 3.8 (8.4)

Note 2: Weight does not include actuator.

31-00381-01 4
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

HONEYWELL MLP ACTUATORS (FAIL-IN-PLACE)


It is critical to select and use the best possible actuators to achieve optimum indoor climate control with PICVs. Faster and more
accurate actuators respond better to the control signal, for better results and higher comfort.

Honeywell offers the impressive MLP, MLE, and thermoelectrical actuators, which have been designed for use with the threaded
VPI PICV series. They enable a new dimension of benefits to HVAC control, offering designers, system integrators, and building
owners.

MLP71MAA Actuators

Technical Specifications

Table 5. Technical specifications of MLP71MAA actuator


Parameter Specifications
Operation: Modulating
Supply Voltage: 24V AC/DC ±10%, 50/60 Hz
Failsafe Function: No
Control Signal: Analog 0(2)-10V DC, <0.5mA
Feedback: Yes, control signal
Actuating Force: High (250N -30N/+70N)
Stroke: 5.8 mm / 0.23 in (compensated)
Operation Time: 22 sec/mm
Power Consumption: 24V AC: 2.5VA operating (4.7VA maximum)
24V DC: 1.2W operating (2.2W maximum)
Ambient Temperature: 0°C to +50°C / +32°F to +122°F
Media temperature: 0°C to +120°C / +32°F to +248°F
Humidity rating: 0-85% RH, no condensation
Position Indicator: Yes
Wire Connection: Fixed, 5 wires x 0.50 mm2, 1.5 meter cable
CE Conformity: EN 60730
Protection Rating: IP54 incl. upside-down, class III, indoor use only
Weight: 0.25 kg / 0.55 lb
Valve Size Compatibility: DN15 - DN32
Override: Yes, Electrical

5 31-00381-01
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

Measurements and Dimensions

Figure 3. Dimension drawing of MLP71MAA actuators.

Table 6. Dimensions for MLP71MAA actuators.


L W H Weight
Actuator T
mm (in) mm (in) mm (in) kg (lb)

MLP71MAA 86.5 (3.41) 48.5 (1.91) 80 (3.15) M30x1.5 0.25 (0.55)

Wiring Connections

MLP71MAA
0(2)-10V Modulating

Figure 4. Typical wiring connections of MLP71MAA actuators.

31-00381-01 6
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

Actuator Switch Function

The valve functions are adjusted with the DIP switches under the connection cover.

Table 7. Switch functions of MLP71MAA actuators.

Switch number Switch function Factory Settings


Switch 1 Auto cycle ON/OFF
If the plant specifications permit it, the auto cycle can be activated during
commissioning. Auto cycle prevents the valve from jamming when the valve is not OFF
moved for a longer period of inactivity, e.g. for heating systems during the summer.
When the auto cycle is activated, the actuator will perform 50% stroke cycle if no
stroke movement has occurred during a 3-week period.

Switch 2 Analog 2-10V DC / 0-10V DC


0-10V DC
Setting control range by the continuous actuating signal 0-10V DC or 2-10V DC.

Switch 3 Normally open / Normally closed


Normally closed; 0V
Setting actuating direction with 10V DC control signal to “valve open” or “valve DC = valve closed
closed” as well as the position feedback.

Switch 4 Equal % control / Linear control


Linear control
Setting of actuating control curve to either equal percentage or linear control.

Switch 5 No function. Close

Switch 6 Electrical override


Setting override function to ON and the actuator will open valve fully. When set to Off
OFF again, the actuator will re-calibrate and thereafter go into normal operation
mode.

7 31-00381-01
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

MLP71MNA Actuators

Technical Specifications

Table 8. Technical specifications of MLP71MNA actuators.


Parameter Specifications
Operation: Modulating

Supply Voltage: 24V AC/DC ±15%, 50/60 Hz

Failsafe Function: No

Control Signal: Analog 0(2)-10V DC, <0.5mA

Feedback: No

Actuating Force: 160N -10N/+70N


Stroke: 5.8 mm / 0.23 in (compensated)

Operation Time: 22 sec/mm

Power Consumption: 24V AC: 2.5VA operating (4.7VA maximum)


24V DC: 1.2W operating (2.2W maximum)

Ambient Temperature: 0°C to +50°C / +32°F to +122°F

Media temperature: 0°C to +120°C / +32°F to +248°F


Humidity Rating: 0-85% RH, no condensation

Position Indicator: Yes

Wire Connection: Fixed, 3 wires x 0.50 mm2, 1.5 meter cable

CE Conformity: EN 60730

Protection Rating: IP54 incl. upside-down, class III, indoor use only

Weight: 0.25 kg / 0.55 lb


Valve Size Compatibility: DN15 - DN32

Override: Yes, Electrical

31-00381-01 8
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

Measurements and Dimensions

Figure 5. Dimension drawing of MLP71MNA actuators

Table 9. Dimensions for MLP71MNA actuators.


L W H Weight
Actuator T
mm (in) mm (in) mm (in) kg (lb)

MLP71MNA 86.5 (3.41) 48.5 (1.91) 80 (3.15) M30x1.5 0.25 (0.55)

Wiring Connections

MLP71MNA
0(2)-10V Modulating

Figure 6. Typical connections of MLP71MNA actuators.

9 31-00381-01
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

MLP41MNA Actuators

Technical Specifications

Table 10. Technical specifications of MLP41MNA actuators.


Parameter Specifications
Operation: On/Off

Supply Voltage: 110/230V AC ±10%, 50/60 Hz


Failsafe Function: No

Control Signal: Digital (2-position / 3-point-floating)

Feedback: No

Actuating Force: High (230N -10N/+40N)

Operation Time: 50 Hz: 18.5 sec/mm

Power Consumption: 5VA


Ambient Temperature: +2°C to +50°C / +36°F to +122°F

Humidity Rating: <95% RH, no condensation

Wire Connection: Fixed, 3 wires x 0.30 mm2 halogen free, 1 meter cable
Protection Rating: IP54, class II

Weight: 0.25 kg / 0.55 lb


Valve Size Compatibility: DN15 - DN32

31-00381-01 10
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

Measurements and Dimensions

Figure 7. Dimension drawing of MLP41MNA Actuators.

Table 11. Dimensions for MLP41MNA actuators


L W H1 Weight
Actuator T
mm (in) mm (in) mm (in) kg (lb)

MLP41MNA 104 (4.09) 51 (2.01) 92 (3.62) M30x1.5 0.25 (0.55)

Wiring Connections

Figure 8. Typical wiring connections of MLP41MNA actuators.

11 31-00381-01
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

MLP75MAB Actuators

Technical Specifications

Table 12. Technical specifications of MLP75MAB actuators.


Parameter Specifications
Operation: Floating / Modulating (universal)

Supply Voltage: 24V AC/DC ±10%, 50/60 Hz

Failsafe Function: No

Control Signal: Analog 0(2)-10V DC, <0.5mA or digital 3-point floating and ON/OFF
Feedback: Yes, control signal (analog) or 0-10V DC (digital ON/OFF)

Actuating Force: 600N -50N/+100N

Stroke: 7 mm / 0.276 in

Operation Time: 22 sec/mm

Power Consumption: 24V AC: 6VA operating (8.5VA maximum)


24V DC: 2.6W operating (4.1W maximum)

Ambient Temperature: 0°C to +50°C / +32°F to +122°F


Media Temperature: 0°C to +120°C / +32°F to +248°F

Humidity Rating: 0-85% RH, no condensation

Position Indicator: Yes

Wire Connection: Fixed, 5 wires x 0.50 mm2, 1.5 meter cable

CE Conformity: EN 60730
Protection Rating: IP54 incl. upside-down, class III, indoor use only

Weight: 0.30 kg / 0.67 lb

Valve Size Compatibility: DN40 – DN50

Override: Manual

31-00381-01 12
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

Measurements and Dimensions

Figure 9. Dimension drawing of MLP75MAB Actuators.

Table 13. Dimensions for MLP75MAB actuators.


L W H1 Weight
Actuator T
mm (in) mm (in) mm (in) kg (lb)

MLP75MAB 96.0 (3.78) 56 (2.20) 91 (3.58) M30x1.5 0.30 (0.67)

Wiring Connections

Figure 10. Typical wiring connections of MLP75MAB Actuators.

13 31-00381-01
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

Actuator Function

Table 14. Switch functions of MLP75MAB actuators.

Switch number Switch function Factory Settings


Switch 1 Auto cycle ON/OFF
If the plant specifications permit it, the auto cycle can be activated during
commissioning. Auto cycle prevents the valve from jamming when the valve is not OFF
moved for a longer period of inactivity, e.g. for heating systems during the summer.
When the auto cycle is activated, the actuator will perform 50% stroke cycle if no
stroke movement has occurred during a 3-weeks period.

Switch 2 Analog 2-10V DC / 0-10V DC


0-10V DC
Setting control range by the continuous actuating signal 0-10V DC or 2-10V DC.

Switch 3 Normally open / Normally close


Normally closed; 0V
Setting actuating direction with 10V DC control signal to “valve open” or “valve DC = valve closed
closed” as well as the position feedback.

Switch 4 Equal % control / Linear control


Linear control
Setting of actuating control curve to either equal percentage or linear control.

Switch 5 No function. Close

Switch 6 Re-calibration
Setting is in different but flipping the switch will start re-calibration. After re- Off
calibration the actuator will automatically go into normal operation.

31-00381-01 14
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

HONEYWELL MLE ACTUATORS (ELECTRONIC FAIL-SAFE)


MLE71MAA Actuators

Technical Specifications

Table 15. Technical specifications of MLE71MAA actuators.


Parameter Specifications
Operation: Modulating
Supply Voltage: 24V AC/DC ±10%, 50/60 Hz
Failsafe Function: Yes, optional open or close
Control Signal: Analog 0(2)-10V DC or digital 2-position with constant power supply
Feedback: Yes, control signal (analog) or 0-10V DC (digital)
Actuating Force: High (250N -30N/+70N)
Stroke: 5.8 mm / 0.23 in (compensated)
Operation Time: 22 sec/mm (failsafe mode: 5 sec/mm)
Power Consumption: 24V AC: 5.8VA operating (6.8VA maximum)
24V DC: 2.9W operating (3.3W maximum)
Ambient Temperature: 0°C to +50°C / +32°F to +122°F
Media temperature: 0°C to +120°C / +32°F to +248°F
Humidity rating: 0-85% RH, no condensation
Position Indicator: Yes
Wire Connection: Fixed, 5 wires x 0.50 mm2, 1.5 meter cable
CE Conformity: EN 60730
Protection Rating: IP54 incl. upside-down, class III, indoor use only
Weight: 0.27 kg / 0.60 lb
Valve Size Compatibility: DN15 - DN32
Override: Yes, Electrical

15 31-00381-01
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

Measurements and Dimensions

Figure 11. Dimension drawing of MLE71MAA Actuators.

Table 16. Dimensions for MLE71MAA actuators.


L W H1 Weight
Actuator T
mm (in) mm (in) mm (in) kg (lb)

MLE71MAA 86.5 (3.41) 48.5 (1.91) 80 (3.15) M30x1.5 0.27 (0.60)

Wiring Connections

Figure 12. Typical wiring connections of MLE71MAA Actuators.

31-00381-01 16
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

Actuator Function

The valve functions are adjusted with the DIP switches under the connection cover.

Table 17. Switch functions of MLE71MAA actuators.

Switch number Switch function Factory Settings


Switch 1 Auto cycle ON/OFF
If the plant specifications permit it, the auto cycle can be activated during
commissioning. Auto cycle prevents the valve from jamming when the valve is not OFF
moved for a longer period of inactivity, e.g. for heating systems during the summer.
When the auto cycle is activated, the actuator will perform 50% stroke cycle if no
stroke movement has occurred during a 3-week period.

Switch 2 Analog 2-10V DC / 0-10V DC


0-10V DC
Setting control range by the continuous actuating signal 0-10V DC or 2-10V DC.

Switch 3 Normally open / Normally closed


Normally closed; 0V
Setting actuating direction with 10V DC control signal to “valve open” or “valve DC = valve closed
closed” as well as the position feedback.

Switch 4 Equal % control / Linear control


Linear control
Setting of actuating control curve to either equal percentage or linear control.

Switch 5 Failsafe open/close


Close
Setting actuator direction at power failure to “valve open” or “valve closed”.

Switch 6 Electrical override


Setting override function to ON and the actuator will open valve fully. When set to Off
OFF again, the actuator will re- calibrate and thereafter go into normal operation
mode.

17 31-00381-01
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

MLE75MAB Actuators

Technical Specifications

Table 18. Technical specifications of MLE75MAB actuators.


Parameter Specifications
Operation: Floating / Modulating (universal)

Supply Voltage: 24V AC/DC ±10%, 50/60 Hz

Failsafe Function: Yes, optional open or close

Control Signal: Analog 0(2)-10V DC or digital 2-position with constant power supply
Feedback: Yes, control signal (analog) or 0-10V DC (digital)

Actuating Force: 600N -50N/+100N

Stroke: 7 mm / 0.276 in

Operation Time: 22 sec/mm (failsafe mode: 5 sec/mm)

Power Consumption: 24V AC: 7.9VA operating (9VA maximum) 24V DC: 3.7W operating (4.5W maximum)
Ambient Temperature: 0°C to +50°C / +32°F to +122°F

Media temperature: 0°C to +120°C / +32°F to +248°F

Humidity rating: 0-85% RH, no condensation


Position Indicator: Yes

Wire Connection: Fixed, 5 wires x 0.50 mm2, 1.5 meter cable


CE Conformity: EN 60730

Protection Rating: IP54 incl. upside-down, class III, indoor use only

Weight: 0.34 kg / 0.75 lb

Valve Size Compatibility: DN40 – DN50

Override: Electrical

31-00381-01 18
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

Measurements and Dimensions

Figure 13. Dimension drawing of MLE75MAB Actuators.

Table 19. Dimensions for MLE75MAB actuators.


L W H Weight
Actuator T
mm (in) mm (in) mm (in) kg (lb)

MLE75MAB 96.0 (3.78) 56 (2.20) 91 (3.58) M30x1.5 0.34 (0.75)

Wiring Connections

Figure 14. Typical wiring connections of MLE75MAB Actuators.


19 31-00381-01
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

Actuator Function

The valve functions are adjusted with the DIP switches under the connection cover.

Table 20. Switch functions of MLE75MAB actuators.

Switch number Switch function Factory Settings


Switch 1 Auto cycle ON/OFF
If the plant specifications permit it, the auto cycle can be activated during
commissioning. Auto cycle prevents the valve from jamming when the valve is not OFF
moved for a longer period of inactivity, e.g. for heating systems during the summer.
When the auto cycle is activated, the actuator will perform 50% stroke cycle if no
stroke movement has occurred during a 3-weeks period.

Switch 2 Analog 2-10V DC / 0-10V DC


0-10V DC
Setting control range by the continuous actuating signal 0-10V DC or 2-10V DC.

Switch 3 Normally open / Normally close


Normally closed; 0V
Setting actuating direction with 10V DC control signal to “valve open” or “valve DC = valve closed
closed” as well as the position feedback.

Switch 4 Equal % control / Linear control


Linear control
Setting of actuating control curve to either equal percentage or linear control.

Switch 5 Failsafe open/close


Close
Setting actuator direction at power failure to “valve open” or “valve closed”.

Switch 6 Electrical override


Setting override function to ON and the actuator will open valve fully. When set to Off
OFF again, the actuator will re- calibrate and thereafter go into normal operation
mode.

31-00381-01 20
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

HONEYWELL ML ACTUATORS - THERMOELECTRICAL


MLP41TNA Actuator

Table 21. Technical specification of MLP41TNA actuators.


Parameter Specifications
Operation: On/Off

Supply Voltage: 230V AC ±10%, 50/60 Hz

Failsafe Function: Yes, normally closed3


Control Signal: ON/OFF, normally closed

Actuating Force 140 N

Stroke: 6.5 mm /0.256 in

Operation Time: Approximately 4.5 minutes4

Power Consumption: 1.2W


Ambient Temperature: 0°C to +60°C / +32°F to +140°F

Wire Connection: Fixed, 2 wires x 0.75 mm2, 1 meter cable

Protection Rating: IP54 including upside-down, class II

Weight: 0.11 kg / 0.24 lb

Valve Size Compatibility: DN15-DN32

Note 3: To ensure that the valve is in an open position during commissioning of the system, the actuator will be delivered in open position and
remain in this position until it is electrically operated first time.
Note 4: Closing time is approximately the double dependent on ambient temperature.

21 31-00381-01
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

Measurements and Dimensions

Figure 15. Dimension drawing of MLP41TNA Actuator.

Table 22. Dimensions for MLP41TNA actuators.


L Ø W H Weight
Actuator Minimum Maximum
mm (in) mm (in) mm (in) kg (lb)
mm (in) mm (in)

MLP41TNA 48.4 (1.91) 38.0 (1.50) 44.1 (1.74) 61.0 (2.40) 69.3 (2.73) 0.11 (0.24)

Wiring Connections

Figure 16. Typical wiring connections of MLP41TNA Actuator.

31-00381-01 22
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

MLP71TNA Actuator

Technical Specifications

Table 23. Technical specification of MLP71TNA actuators.


Parameter Specifications
Operation: Modulating

Supply Voltage: 24V AC -10%...+20%, 50/60 Hz

Failsafe Function: Yes, normally closed5

Control Signal: Analog 0-10V, normally closed

Actuating Force: 140 N


Stroke: 6.5 mm /0.256 in

Operation Time: Approximately 3.5 minutes6

Power Consumption: 1.2W

Ambient Temperature: 0°C to +60°C / +32°F to +140°F

Wire Connection: Plug-in, 3 wires x 0.22 mm2, 1 meter cable


Protection Rating: IP54 including upside-down, class III

Weight: 0.12 kg / 0.27 lb

Valve Size Compatibility: DN15-DN32

Note 5: To ensure that the valve is in an open position during commissioning of the system, the actuator will be delivered in open position and
remain in this position until it is electrically operated first time.
Note 6: Closing time is approximately the double dependent on ambient temperature.

23 31-00381-01
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

Measurements and Dimensions

Figure 17. Dimension drawing of MLP71TNA Actuator

Table 24. Dimensions for MLP71TNA actuators.


L Ø W H Weight
Actuator Minimum Maximum
mm (in) mm (in) mm (in) kg (lb)
mm (in) mm (in)

MLP71TNA (FT.0.2) 63.5 (2.5) 38.0 (1.50) 44.1 (1.74) 63.5 (2.5) 71.8 (2.83) 0.12 (0.27)

Wiring Connections

Figure 18. Typical wiring connections of MLP71TNA Actuator.

31-00381-01 24
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

FLOW-RATE SETTINGS
Table 25. Flow rates for DN15-DN50.
Valve Maximum Flow Rate Close-Off Differential
Model No. diameter Pressure Pressure PN Rating End Connection
mm lph m3/h gpm kPa kPaD
VPI015TWL2 DN15 1110 1.11 4.89 800 800 PN25 Fixed female threaded ISO
VPI015TWL2 DN15 1110 1.11 4.89 800 800 PN25 Fixed female threaded ISO
VPI015TWH2 DN15 2650 2.7 11.7 800 800 PN25 Fixed female threaded ISO
VPI015TPH2 DN15 2650 2.7 11.7 800 800 PN25 Fixed female threaded ISO
VPI020TWL2 DN20 1110 1.11 4.89 800 800 PN25 Fixed female threaded ISO
VPI020TPL2 DN20 1110 1.11 4.89 800 800 PN25 Fixed female threaded ISO
VPI020TWH2 DN20 2650 2.7 11.7 800 800 PN25 Fixed female threaded ISO
VPI020TPH2 DN20 2650 2.7 11.7 800 800 PN25 Fixed female threaded ISO
VPI025TWH2 DN25 2650 2.7 11.7 800 800 PN25 Fixed female threaded ISO
VPI025TPH2 DN25 2650 2.7 11.7 800 800 PN25 Fixed female threaded ISO
VPI032TWH2 DN32 4630 4.6 20.4 800 800 PN25 Fixed female threaded ISO
VPI032TPH2 DN32 4630 4.6 20.4 800 800 PN25 Fixed female threaded ISO
VPI040TPH2 DN40 13647 13.6 60.1 800 600 PN25 Fixed female threaded ISO
VPI050TPL2 DN50 13647 13.6 60.1 800 600 PN25 Fixed female threaded ISO

Flow Setting Dial


Honeywell VPI series Pressure Independent Control Valves offers selection of wide range of flow settings. These valves are
specially equipped with Scale setting dials on top of the valve body. To adjust the preferred flow settings, adjust the below shown
dials (as per valve model) with a unique adjustment key.

DN15/20 (LF) and DN32 DN15/20/25 (HF) DN 40/50 (Threaded)

For example - A micrometer For example - A micrometer For example - A micrometer


setting of 3.2 (DN32 valve) on setting of 2.3 on dial, setting of 3.7 on dial,
dial, corresponds to a corresponds to a maximum corresponds to a maximum
maximum flow rate of: 3350 flow rate of: 1430 LPH (6.28 flow rate of: 11142 LPH (49
LPH (17.7 GPM) GPM) GPM)

Maximum flow Settings:


DN15/DN20 (LF) Models – 64 LPH – 1110 LPH
DN15/DN20/DN25 (HF) Models – 620 LPH – 2650 LPH
DN32 Models – 865 LPH – 4630 LPH
DN40/DN50 Models – 1900 LPH – 13647 LPH

Working Differential Pressure:


DN15/DN20 (LF) Models – 30 kPaD – 800 kPaD
DN15/DN20/DN25 (HF) Models – 35 kPaD – 800 kPaD
DN32 – 16 kPaD – 800 kPaD
DN40/DN50 Models – 16 kPaD – 600 kPaD
25 31-00381-01
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

Maximum Flow-Rate Limitation settings (DN15 – DN 32)


Table 26. Flow rates as per settings for DN15-DN32.

DN15LF-DN20LF DN15HF-DN25HF DN32


Setting
l/sec l/hr GPM l/sec l/hr GPM l/sec l/hr GPM
0.0178 64 0.282 - - - 0.240 865 3.81 1.0
0.0393 142 0.624 - - - 0.282 1010 4.46 1.1
0.0580 209 0.920 - - - 0.322 1160 5.10 1.2
0.0743 268 1.180 - - - 0.361 1300 5.72 1.3
0.0887 319 1.41 - - - 0.399 1430 6.32 1.4
0.102 366 1.61 0.172 620 2.73 0.435 1570 6.90 1.5
0.113 408 1.80 0.200 720 3.17 0.471 1700 7.47 1.6
0.124 446 1.96 0.228 820 3.61 0.506 1820 8.02 1.7
0.134 482 2.12 0.258 930 4.10 0.540 1940 8.56 1.8
0.143 516 2.27 0.294 1060 4.67 0.573 2060 9.08 1.9
0.152 549 2.42 0.325 1170 5.15 0.605 2180 9.59 2.0
0.161 580 2.56 0.350 1260 5.55 0.636 2290 10.1 2.1
0.170 611 2.69 0.375 1350 5.95 0.667 2400 10.6 2.2
0.178 641 2.82 0.396 1430 6.28 0.696 2510 11.0 2.3
0.186 671 2.95 0.417 1500 6.61 0.725 2610 11.5 2.4
0.194 700 3.08 0.439 1580 6.96 0.753 2710 11.9 2.5
0.202 728 3.21 0.458 1650 7.27 0.780 2810 12.4 2.6
0.210 756 3.33 0.481 1730 7.62 0.807 2900 12.8 2.7
0.218 783 3.45 0.500 1800 7.93 0.832 3000 13.2 2.8
0.225 810 3.56 0.522 1880 8.28 0.858 3090 13.6 2.9
0.232 835 3.68 0.542 1950 8.59 0.882 3180 14.0 3.0
0.239 860 3.79 0.550 1980 8.72 0.906 3260 14.4 3.1
0.245 883 3.89 0.558 2010 8.85 0.930 3350 14.7 3.2
0.252 906 3.99 0.567 2040 8.99 0.953 3430 15.1 3.3
0.257 927 4.08 0.575 2070 9.12 0.975 3510 15.5 3.4
0.263 946 4.17 0.583 2100 9.25 0.997 3590 15.8 3.5
0.268 965 4.25 0.597 2150 9.47 1.02 3670 16.1 3.6
0.273 982 4.32 0.611 2200 9.69 1.04 3740 16.5 3.7
0.277 998 4.39 0.625 2250 9.91 1.06 3820 16.8 3.8
0.281 1010 4.46 0.639 2300 10.1 1.08 3890 17.1 3.9
0.285 1020 4.51 0.653 2350 10.4 1.10 3960 17.4 4.0
0.288 1040 4.57 0.661 2380 10.5 1.12 4030 17.7 4.1
0.291 1050 4.61 0.669 2410 10.6 1.14 4100 18.1 4.2
0.294 1060 4.66 0.678 2440 10.7 1.16 4170 18.4 4.3
0.296 1070 4.70 0.686 2470 10.9 1.18 4240 18.7 4.4
0.299 1080 4.73 0.694 2500 11.0 1.20 4300 19.0 4.5
0.301 1080 4.77 0.703 2530 11.1 1.21 4370 19.2 4.6
0.303 1090 4.80 0.711 2560 11.3 1.23 4440 19.5 4.7
0.305 1100 4.83 0.719 2590 11.4 1.25 4500 19.8 4.8
0.307 1100 4.86 0.728 2620 11.5 1.27 4570 20.1 4.9
0.308 1110 4.89 0.736 2650 11.7 1.29 4630 20.4 5.0
Accuracy: Greatest of either ±10% of controlled flow rate or ±5% of maximum flow rate.

31-00381-01 26
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

Maximum Flow-Rate Limitation settings (DN40 – DN50) Threaded


Table 27. Flow rates as per settings for DN40-DN50.

DN40-DN50
Setting
l/sec l/hr GPM
0.528 1900 8.36 1.0
0.633 2278 10.0 1.1
0.738 2655 11.7 1.2
0.843 3033 13.3 1.3
0.947 3410 15.0 1.4
1.05 3787 16.7 1.5
1.16 4163 18.3 1.6
1.26 4537 20.0 1.7
1.36 4909 21.6 1.8
1.47 5279 23.2 1.9
1.57 5646 24.8 2.0
1.67 6011 26.4 2.1
1.77 6372 28.0 2.2
1.87 6730 29.6 2.3
1.97 7083 31.2 2.4
2.06 7432 32.7 2.5
2.16 7776 34.2 2.6
2.25 8115 35.7 2.7
2.35 8449 37.2 2.8
2.44 8777 38.6 2.9
2.53 9098 40.0 3.0
2.61 9413 41.4 3.1
2.70 9721 42.8 3.2
2.78 10021 44.1 3.3
2.86 10314 45.4 3.4
2.94 10599 46.6 3.5
3.02 10875 47.8 3.6
3.10 11142 49.0 3.7
3.17 11400 50.2 3.8
3.24 11649 51.3 3.9
3.30 11888 52.3 4.0
3.37 12116 53.3 4.1
3.43 12334 54.3 4.2
3.48 12540 55.2 4.3
3.54 12735 56.0 4.4
3.59 12919 56.8 4.5
3.64 13090 57.6 4.6
3.68 13249 58.3 4.7
3.72 13395 58.9 4.8
3.76 13527 59.5 4.9
3.79 13647 60.0 5.0

27 31-00381-01
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

MODEL SELECTION (PART NOMENCLATURE)


VPI Series Valve Bodies

Valve Maximum Flow


Valve Size Connection Type Pressure Test Ports Pressure Class
Type Rate

VPI - Valve Pressure Independent

015 - DN15 / 0.5 inch

020 - DN20 / 0.75 inch

025 - DN25 / 1 inch

032 - DN32 / 1.25 inch

040 - DN40 / 1.5 inch

050 - DN50 / 2 inch

T - Threaded DN Size

P - With Pressure Ports

W - Without Pressure Ports

L - Low Max Flow

H - High Max Flow

2 - PN25
VPI 015 T P H 2

Example: VPI015TPH2
- without Pressure Test Port models are available only for DN15-DN32
- Low Flow (LF) models are available only for DN15 and DN20.

VPI Series Actuators

Actuator Control and Actuator Valve Size


Fail-Safe Feedback
Type Power Voltage Technology Compatibility

ML - Motor Linear

P - Power Failure 'In place'

E - Electronic Fail-Safe

41 - On/Off 230Vac

71 - Modulating (0)2-10Vdc

75 - Floating / Modulating (universal)

T - Thermo-Electric Actuator

M - Electric Actuator

A - Analog feedback

N - No feedback

A - DN15-DN32 (Threaded)

B - DN40-DN50 (Threaded)
ML P 71 M N A

Example: MLP71MNA

31-00381-01 28
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

VALVE AND ACTUATOR COMPATIBILITY


DN15 – DN32 Valve and Actuator Compatibility

Actuator Part Number


MLP71MAA MLE71MAA MLP71MNA MLP41MNA MLP41TNA MLP71TNA
110/230 110/230
24 Vac/dc 24 Vac/dc 24 Vac/dc 24 Vac/dc
Vac Vac
Voltage +/-10%, +/-10%, +/-15%, +/-10%,
Power Supply +/-10%, +/-10%,
50/60Hz 50/60Hz 50/60Hz 50/60Hz
50/60Hz 50/60Hz
Power (Peak) 4.7VA 6.8VA 4.7VA 5VA 1.2W 1.2W
0-10 Vdc ● ● ● ●
2-10 Vdc ● ● ●
Control 2-Position SPDT ● ●
On-Off / 2-

Position SPST
Feedback (0)2-10Vdc ● ●
Actuator Force/Torque (N/Nm) 240 N 250 N 160 N 230 N 140 N 140 N
18.5
Running Time (sec/mm) 22 sec/mm 22 sec/mm 22 sec/mm 270 sec 210 sec
sec/mm
Electronic
Power Fail Safe Action Fail In Place Fail In Place Fail In Place Fail Safe Fail Safe
Fail-Safe
Cable length
Electrical Connection 1.5m 1.5m 1.5m 1m 1m 1m
(meter)
QMAX Valve Model
Valve Size Compatibility
(l/h) Number
DN15 LF 1110 VPI015TWL2 ● ● ● ● ● ●
DN15P LF 1110 VPI015TPL2 ● ● ● ● ● ●
DN15 HF 2,650 VPI015TWH2 ● ● ● ● ● ●
DN15P HF 2,650 VPI015TPH2 ● ● ● ● ● ●
DN20 LF 1110 VPI020TWL2 ● ● ● ● ● ●
DN20P LF 1110 VPI020TPL2 ● ● ● ● ● ●
DN20 HF 2,650 VPI020TWH2 ● ● ● ● ● ●
DN20P HF 2,650 VPI020TPH2 ● ● ● ● ● ●
DN25 2,650 VPI025TWH2 ● ● ● ● ● ●
DN25P 2,650 VPI025TPH2 ● ● ● ● ● ●
DN32 4,630 VPI032TWH2 ● ● ● ● ● ●
DN32P 4,630 VPI032TPH2 ● ● ● ● ● ●

Note 7: DN32 valves when used with MLP41TNA or MLP71TNA might exceed specified leakage rate.

Note 8: Thermal Actuators closing time is approximately double dependent on ambient temperature.

29 31-00381-01
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

DN40 – DN50 Valve and Actuator Compatibility

Actuator Part Number


MLP75MAB MLE75MAB
24 Vac/dc 24 Vac/dc
Voltage
Power Supply +/-10%, 50/60Hz +/-10%, 50/60Hz
Power (Peak) 9VA 9VA
0-10 Vdc ● ●
Control 2-10 Vdc ● ●
2-Position SPDT ● ●
Feedback (0)2-10Vdc ● ●
Actuator Force/Torque (N/Nm) 600 N 600 N
Running Time (sec./sec/mm) 22 sec/mm 22 sec/mm
Power Fail Safe Action Fail In Place Electronic Fail-Safe
Electrical Connection Cable length 1.5m 1.5m
QMAX
Valve Size Valve Model Number Compatibility
(l/h)
DN40 13,647 VPI040TPH2 ● ●
DN50 13,647 VPI050TPL2 ● ●

Accessories
Table 28. List of available accessories.
Part Code Part Name
VPI-PP-TP VPI Series Pressure Ports - Test Plugs

VPI-FSK VPI Series Flow Setting Key

31-00381-01 30
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

APPLICATION AND SCHEMATIC EXAMPLE

Figure 19. Application and Schematic example connections of DN15-DN50 PICVs

31 31-00381-01
VPI SERIES PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS

ORDERING INFORMATION
UNITED ARAB EMIRATES INDIA PACIFIC
Honeywell Building Technologies Honeywell HBT India Buildings Honeywell
Building Management Systems Unitech Trade Center, 5th Floor, Sector-43, 2 Richardson Pl, North Ryde NSW 2113,
Emaar Business Park, Sheikh Zayed Road, Block C, Sushant Lok Phase - I, Australia.
Building No. 2, 2nd floor, 201 Gurgaon - 122 002, India. Call: 1300 363 936
Post Office Box 232362, Call: 1-800-103-0339 Email: pacificustomercare@honeywell.com
Dubai, United Arab Emirates. Email: HBTIndiabuildings@honeywell.com
Call: +971 44541704

TURKEY ASEAN KOREA


Honeywell Teknoloji A.Ş. Honeywell Building Technologies (ASEAN) Honeywell HBT Buildings Technologies
Cayir Cad. No:7 Kat:1 Honeywell International Sdn Bhd 5F SangAm IT Tower, 434 Worldcup buk-ro,
Icerenkoy 34752 Istanbul, Turkey. Level 25, UOA Corp Tower, Lobby B Mapo-gu, Seoul 03922, Korea.
Call: +90 216 578 71 10 Avenue 10, The Vertical, Bangsar South City Call: 0082-2-799-6271, 6009, 6158, 3535, 6361
Faks: +90 216 575 66 37 59200, Kuala Lumpur, Malaysia. Email: info.btkorea@Honeywell.com
Call: +60 3-2777 3100
Email: buildings.asean@honeywell.com
QATAR
Honeywell Technology Solutions
P.O. Box 63757, Doha, Qatar
Phone: +974 4 4066 200
Fax: +974 4 4066 711

By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or
modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against
any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature
by you.

VPI PRESSURE INDEPENDENT


CONTROL VALVES AND ACTUATORS

31-00381-01
August 2020
© 2020 Honeywell International Inc.

You might also like