MULTIMETER MULTIMETER

EPM-07 / EPM-07S EPM-07 / EPM-07S


TECHNICAL DATA General
EPM-07/07S is a microprocessor based device which developed for measuring Calculation Methods for Active / Reactive Power Values
Operating Voltage (Un) : Please look behind the device. the parameters in an electrical network. Measured parameters are displayed If the led on the most right side blinks it represents that active power’s / reactive
in 4 displays separately EPM-07S has an MODBUS serial communication power’s direction is negative.
Operating frequency (f) : 45-65 Hz There are two methods for calculating total active and total reactive powers :
interface.
Auxiliary supply Power Consumption: < 4 VA 1) Active / Reactive power can be calculated by summing import and export
values and displaying as a single value.
Measuring Input Power Consumption: < 1VA 2) Active / Reactive power can be calculated according to direction as
VIn : 10-300 V AC 45-65 Hz. (L-N) import / export.
Note :
: 10-500 V AC 45-65 Hz. (L-L) 1) The dot at the most right digit of the fourth display (During SW is
IIn : 0.05 - 5.5 A~ displayed) represents that displayed value is export active power value.
Vice versa, displayed value is import active power value.
2-120 A~ (for CT-25) 2) The dot at the most right digit of the fourth display (During SVAr is
Measuring Range : 10V...200 kV AC displayed) represents that displayed value is capacitive reactive power
: 0...215 M (W,VAr,VA) value. Vice versa, displayed value is inductive reactive power value.
3) The displayed parameter will not change if power is off after 30 seconds
: 99999999999.9 kWh, kVArh of stand-by (ie. W).
Class : 1% ± 1 digit [(10%-110%) xFull Scale] Measured Parameters:
Voltage Transformer Ratio (Vtr) : 0,1 ... 4000,0
ESC button VLN (Phase Voltage) Cosj Hz. (Frequency)
Current Transformer Ratio (Ctr) : 1 ... 2000
VLL (Phase to Phase Voltage) AI ( kWh) (Import Active Energy I) IN (Neutral Current)
Max. Ctr x Vtr : 40.000 Max. LED
A (Phase Current) AE (kWh) (Export Active Energy) SW (Total Active Power)
Demand Time : 1-60 min. (programmable) SET button W (Active Power) rI (kVArh) (Import Reactive Energy) SVAr (Total Reactive Power)
Serial Interface (for EPM-07S) : MODBUS RTU (RS 485) Minimum LED VAr (Reactive Power) rE(kVArh) (Export Reactive Energy) SVA (Total Apparent Power)
Demand LED VA (Apparent Power)
Optically Isolated, programmable
Baud Rate (for EPM-07S) : 2400-38400 bps FUNCTIONS OF BUTTONS
Address (for EPM-07S) : 1-247 In the monitoring mode, it is used to pass between (VLN, VLL, A, W,
Phase Total and UP DOWN VAr, VA, Cosj, kWh, kVarh) parameters.
Parity (for EPM-07S) : No , Odd, Even, 8 Data bits, 2 Stop Bits Displays Hz Display button button At the programming mode, it provides to increase value of desired
Pulse Output : NPN Transistor parameter and pass to the next menu.
Switch Period : Min. 100 msec pulse perriod Phase Displays In the monitoring mode, it is used to pass between (VLN, VLL, A, W,
80 msec pulse width VAr, VA, Cosj, kWh, kVarh) parameters.
At the programming mode, it provides to decrease value of desired
Operation Current : Max. 50 mA parameter and pass to the prevides menu.
UP button
Operation Voltage : 5.....24 V DC, max. 30 VDC It is used for passing between the instant values such as. When it
Input : 12...48 V AC / DC ESC button is pressed for 3 second, programming mode is entered. In the
Max. LED programming mode it is used for saving parameters and moving
Ambient Temperature : -5°C; +50°C the sub menu.
SET button
Display : Red LED Display
Minimum LED In displaying mode, it is used for; passing the instant values which
Dimensions : PR-19, PK-26 Demand LED are displayed for min., max. and demand values in displaying mode,
Total and Hz. Display DOWN button turn back to the previous menu turn back to the previous digit, when
Equipment Protection Class : Double Insulation-Class II ( )
changing the numerical values and quiting the programming mode
Box Protection Class : IP 40 (front panel) without saving.
Box Material : Non-flammable Using of EPM-07/07S:
Parameters (VLN; VLL; A; W; VAr; VA; Cosj; kWh, kVarh, THD) are monitored If user password is activated and set button is pressed for 3
Installation : Panel Mounted (PR-19) in L1, L2, L3 displays by scrolling UP/DOWN buttons. Total Active (SW), Total seconds, a pin code is required in order to enter to the menu.
Rail Mounted (PK-26) Reactive Power (SVAr), Total Apparent Power (SVA) and Frequency (Hz)
values and average values of these parameters are monitored in 4th display.
Current Transformer Ratio Setup
Wire Thickness (for terminal block) : 2.5 mm2 Note: VLN or VLL should be selected for displaying the frequency value. (This menu is not available in the devices which are adapted
with CT-25.)
Weight : 0.45 kg (PR-19, PK-26) Digital Inputs In this menu, current transformer ratio is set between 1 - 2000.
Installation Category : Class III EPM-07/07S has 2 digital inputs. Digital inputs have 2 functions: Note: If the current transformer is not used between the system
- When a remote device has activated, situation of this device which is and EPM-07/07S, current transformer ratio is entered as ‘1’.
conncected to the digital input, can be monitored according to data register Example: If a current transformer which has a ratio of 250/5A is
Factory Settings (Battery, thermostat, circuit breaker and motor position). used between the system and EPM-07/07S; Current transformer
Trafo (Transformer) : Eng Cnt : - When the digital inputs have activated in Energy Count menu, device will ratio is entered as “50” (250/5).
control the Energy Counters.
Ctr (Current Transformer Ratio) : 0001 E-1 (Energy Counter 1) : on
trn (Turn number for CT-25 device) : 01 E-2 (Energy Counter 2) : on Energy Pulse Outputs Press SET button for 3 seconds (trA Fo menu is displayed)
EPM-07/07S has 2 Energy Pulse Outputs. These outputs give the pulses only
Utr (Voltage Transformer Ratio) : 0001.0 for E-1 (Energy Counter). Press SET button; trA Fo Ctr menu is displayed (In CT-25 adapted
CAL (Calculation Method) : 1 PULSE : Pul1 and Pul2: In “o-1 (Pulse1)”, “o-2 (Pulse2)” menus which are in the pulse devices, trA Fo trn is displayed instead.)
menu, device give pulse according to selected energy parameters as [Active (Not: trA Fo Utr menu can be displayed by scrolling the UP/DOWN
rAt (Ratio) : 1 energy (ACt, A-I, A-E), Reactive energy (rEA, r-L, r-C)].
Pin : 0000 (Not Activated) buttons.)
o-1 (Output 1) : A-I Please refer to the pulse menu for the coefficients of energies.
o-2 (Output 2) : r-L Monitoring Min.- Max. and Max. Demand Values:
RS-485 : Min. and Max. values are defined for VLN, VLL, A, W, VAr, VA, SW, SVAr, SVA.
Demand values are defined for A, W, VAr, VA, SW, SVA, SVAr. Press SET button. Blinking the first digit of displayed value appears. (trA Fo
Adr (Address) : 1 dEtý (Delay Time) : 15 Utr menu can be programmed similarly.)
If measured instant value is smaller than min. value which was stored before,
Bau (Baud Rate) : 9600 it is stored as new min. value. If measured instant value is greater than max. Enter the blinking digit value by scrolling UP/DOWN buttons.
PAr (Parity) : no value which was stored before, it is stored as new max. value. Switch to the other digits by using SET button, use ESC button to
Demand value is the average value of the measured values in demand time go to previous digit. After you entered the last digit press SET
PRECAUTIONS FOR INSTALLATION AND SAFE USE (15 minute). button, “Pýn ACt oF” is displayed. “on” can be selected by scrolling
If one of defined parameters is displayed (ie. “W”) when deman button is UP/DOWN buttons. (Data is entered but is not activated yet. For
The current terminal connections must be implemented with using CT-25. pressed min., max or max. demand values are displayed. When an undefined activating the new data please follow the below steps).
Failure to follow those instructions will result in death or serious injury. parameter is displayed (ie. “Cosj”) if demand button is pressed, instant value
- Disconnect all power before working on equipment.. is continued to display. Press ESC button one by one until “SAU E SEt yES” is displayed.
- When the device is connected to the network, do not remove the front panel. H-L-M LEDs Press SET button. When “SAU E SEt yES” is displayed, if you press
- Do not try to clean the device with solvent or the like.Only clean with dry cloth. H-L-M LEDs are dedicated to displaying the min., max. and max. demand ESC button or choose “no” option instead of “yES” option by using
- Verify correct terminal connections when wiring. values according to selected parameters. UP-DOWN buttons, new data will be cancelled and previous value
- Electrical equipment should be serviced only by your component seller. H: Maximum Value, L: Minimum Value, M: Max. Demand Value will be activated.
- No responsibility is assured by manufacturer or any of its subsidiaries for any consequences arising out of the use of this material.
- Only for rack panel mounting.
8 A4019/Rev.3 1
MULTIMETER MULTIMETER
EPM-07 / EPM-07S EPM-07 / EPM-07S
Programming the Turn Number: Demand Time Setup:
This menu is available for CT-25 adapted devices. User enter
the turn number, which is the number of how many tour the current In this menu,demand time is set between 1-60 minutes. PK 26 Box Connection Diagram
cable has rounded into the CT-25. Numbers can be selected
between 1-20. Greater the number of turn means greater the
sensivity. Max: 30 VDC Max: 30 VDC

+ +
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Press SET button for 3 seconds (trA Fo menu is displayed) _ _

2.00 1.00 0.66 0.50 0.40 0.33 0.28 0.24 0.22 0.20 0.18 0.16 0.15 0.14 0.13 0.12 0.11 0.11 0.10 0.10 (12-48V DC) (12-48V DC)
120 60.0 40.0 30.0 24.0 20.0 17.1 15.0 13.3 12.0 10.9 10.0 9.23 8.57 8.00 7.50 7.05 6.66 6.31 6.00 - + - + - + - +
By using UP-DOWN buttons find “dE tý” menu.
Voltage Transformer Ratio Setup Gnd A B TR Gnd A B TR

PUL1L
PUL1H
PUL2L
PUL2H
IN1L
IN1H
IN2L
IN2H

PUL1L
PUL1H
PUL2L
PUL2H
IN1L
IN1H
IN2L
IN2H
In this menu, voltage transformer ratio is set between RS-485 RS-485
0000,1 - 4000,0. Press SET button (First digit blinks.)
Auxiliary Current Measuring Input Auxiliary Current Measuring Input
Note: If the voltage transformer is not used between the system Supply Voltage Measuring Input Supply Voltage Measuring Input
and EPM-07/07S, voltage transformer ratio is entered as ‘1’. Un Un
IL1 IL2 IL3 IL1 IL2 IL3
Example: If a voltage transformer which has a ratio of 34.5KV/100V By using UP-DOWN buttons, enter the value to the first digit. ~ L1 L2 L3 N ~ L1 L2 L3 N
is used between the system and EPM-07/07S; Voltage transformer
ratio is entered as 345. (34500/100) N
1A 1A
k l
L1
Reactive Energy Calculation Method Setting Press SET button (Second digit blinks) K L
k l k
L2 L1 l
Three different methods exist for reactive energy calculation in EPM-07/07S. Brief K L K L
k l k l
informations about these methods are explained in below table. L3 L2
K L K L
Related values which must be entered in the menu are also indicated in the table By using UP-DOWN buttons, enter the value to the second digit. N L3
in order to select reactive power calculation method for mechanical and digital
energymeters.
3 Phase neutral 3 Phase without neutral current input with
Press SET button, “dE tý” is displayed. (Data is entered but is not Aron wiring configuration
Mechanical Energymeter Digital Energymeter Reactive Energy Description activated yet. For activating the new data please follow the below
(Vectoral summation of 3-phase) (Each phase seperately) (Q) steps).
90° rotation of It is the most preferred reactive power calculation
0 1 voltage vector and methode.
Press ESC button one by one until (SAU E SEt yES) is displayed.
multiply with current

¥ Total value of the multiplication of Vn and In values up Press SET button. When “SAU E SEt yES” is displayed, if you press
2 3 Sn=1Vn.In.sin(jn) topreferred
19 th harmonics. This calculation methode is mostly
for network analysers.
ESC button or choose “no” option instead of “yES” option by using
UP-DOWN buttons, new data will be cancelled and previous value
will be activated. Max: 30 VDC Max: 30 VDC
Power Triangle Methode : According to this methode;
4 5 Q = S2-P2 Monitoring and Erasing of minimum, maximum and
S2-P2 (Q : Reactive power, S : Active power, P : Apparent power) energy values:
+
_
+
_

(12-48V DC) (12-48V DC)


In this menu, values of min.,max. or energy counters are erased. - + - +
- + - +
It saves the instantaneously measured min. and max. values of
Press SET button for 3 seconds (trA Fo menu is displayed) EPM-07/07S into its memory. Please kindly look at to the section
Gnd A B TR

PUL1L
PUL1H
PUL2L
PUL2H
IN1L
IN1H
IN2L
IN2H
Gnd A B TR

PUL1L
PUL1H
PUL2L
PUL2H
IN1L
IN1H
IN2L
IN2H
of FUNCTIONS OF BUTTONS for min. and max. values. RS-485 RS-485
Note : Measured electrical parameters which are saved to the
memory are not affected from the electric interruptions. Auxiliary Auxiliary
Press SET button (trA Fo Ctr menu is displayed) Current Measuring Input Current Measuring Input
In the “rESEt” menu; when you quit from all menus, if you confirm Supply Voltage Measuring Input Supply Voltage Measuring Input
the changes,min. and max. values of all parameters or energy Un Un IL1 IL2
IL1 IL2 IL3 IL3
counter values are erased at the same time. ~ L1 L2 L3 N ~ L1 L2 L3 N

By using UP-DOWN buttons, find “CAL CLt” For erasing the values of min. and max. or energy counter,
menu. N N
In the measurement mode : 1A
k l 1A
L1
K L
k l k l
L2 L1
Press SET button. Press SET button for 3 seconds (trA Fo menu is displayed) K L K L
L3 k l L2
K L k l
L3
By using UP-DOWN buttons, 3 Phase without neutral K L
3 Phase without neutral current input with
By using UP-DOWN buttons, select energy calculation method. find “rES Et” menu. Aron wiring configuration
Press SET button.
(“rESEt HL” menu is displayed) *Available only for EPM-07S
Press SET button.

By using UP-DOWN buttons, select Note: For CT-25 models:


which parameter you want to reset. k: When CT-25 is used, Red cable is connected to k terminal.
Press ESC button one by one until “SAU E SEt yES” is displayed.
l: When CT-25 is used, Black cable is connected to l terminal.
Press SET button
Press SET button. When “SAU E SEt yES” is displayed, if you
press ESC button or choose “no” option instead of “yES” option By using UP-DOWN buttons, if you
by using UP-DOWN buttons, new data will be cancelled and want to delete the parameter select
previous value will be activated. “yES” option otherwise select “no”
option.
Press SET button. (“rES Et” is displayed)

Press ESC button one by one until (SAU E SEt yES) is displayed.

Press SET button. When “SAU E SEt yES” is displayed, if you


press ESC button or choose “no” option instead of “yES” option
by using UP-DOWN buttons, new data will be cancelled and
previous value will be activated.

2
7
MULTIMETER MULTIMETER
EPM-07 / EPM-07S EPM-07 / EPM-07S
Pulse Menu User password Setup:
In this menu user password is defined and activated.
In this menu, three parameters can be selected : “PUL SE rAt You must define and activate a 4 digit user password for
PR 19 Box Connection Diagram ýo”, “PUL SE o-1”, “PUL SE o-2” preventing device settings from the illegal usage.
PUL SE rAt ýo : Pulse ratio can be set as : There are 2 sub menus under the “Pýn” menu.
1, 10, 100 (wh/VArh/VA); 1, 10, 100 (kwh/kVArh/kVA);
1 Mwh/MVArh/MVA. Changing of User Password:
PUL SE o-1 : If this parameter is selected, in every increase in output 1, This menu is used to change the user password .
L1 K L L1 K L
one pulse is counted. Output 1 parameter can be set as : Note: Factory default value for user password is
L2 k l K L
L2 k l K L ACt (Export/Import), A-I (Active Import), A-E (Active Export), rEA (Inductive “0000”
k l K L / Capacitive), r-L (Reactive Inductive), r-C (Reactive Capacitive).
L3 L3 k l
PUL SE o-2 : If this parameter is selected, in every increase in output 2,
k l one pulse is counted. Output 2 parameter can be set as : To change the user password,
N ACt (Export/Import), A-I (Active Import), A-E (Active Export), rEA (Inductive In the monitoring mode :
1 2 3 4 5 6 / Capacitive), r-L (Reactive Inductive), r-C (Reactive Capacitive).
IL1 IL2 IL3 Press SET button for 3 seconds (trA Fo menu is displayed)
1 2 3 4 5 6 Press SET button for 3 seconds (trA Fo menu is displayed)
Current Measuring Input IL1 IL2 IL3
Max: 30 VDC
( 12-48V DC ) Current Measuring Input Bu using UP-DOWN buttons, find “Pýn” menu.
Pul C InC In1 In2 RS485
_ Max: 30 VDC By using UP-DOWN buttons, find “PULSE” menu.
+ 13 14 15 16 17 18 19 20 21 22 ( 12-48V DC )
GND B A TR Pul C InC In1 In2 RS485
Pul 1 Pul 2
_
+ 13 14 15 16 17 18 19 20 21 22 Press SET button (“Pýn ACt IUA tE” menu is displayed)
GND B A TR
Auxiliary Pul 1 Pul 2 Press SET button (”PUL SE rAt ýo” menu is displayed)
Voltage Measuring Input
L1 L2 N
Supply By using the UP-DOWN buttons, find “Pýn CHA ngE” menu.
L3
Voltage Measuring Input Auxiliary
7 8 9 10 11 12 L1 L2 N
Supply By using UP-DOWN buttons, select “PUL SE rAt ýo”, “PUL SE o-1”
L3
or “PUL SE o-2”.
1A

7 8 9 10 11 12
L1
By using UP-DOWN-SET buttons, enter the old password

1A
N L1 Press SET button.

3 Phase neutral 3 Phase without neutral current input with N


Aron wiring configuration By using UP-DOWN buttons, By using UP-DOWN-SET buttons, enter the new password
select required parameter.

Press SET button. By using UP-DOWN-SET buttons, re-enter the new password.

Press ESC button one by one until “SAU E SEt yES” is displayed. Press SET button, “Pýn CHA ngE” is displayed. (Data is entered
but is not activated yet. For activating the new data please follow
Press SET button. When “SAU E SEt yES” is displayed, if you the below steps).
press ESC button or choose “no” option instead of “yES” option Press ESC button one by one until
by using UP-DOWN buttons, new data will be cancelled and (SAU E SEt yES) is displayed.
K L L1 K L previous value will be activated.
L1
K L
Energy Counter (Eng Cnt) Menu Press SET button. When “SAU E SEt yES” is displayed, if you
L2 k l L2 k l
press ESC button or choose “no” option instead of “yES” option
k l K L K L EPM-07/07S has 2 energy counters : by using UP-DOWN buttons, new data will be cancelled and
L3 L3 Energy counter 1 (E-1), Energy counter 2 (E-2). previous value will be activated.
k l k l “E-1 / E-2” have 4 parameters :
on : Activate “E-1 / E-2” counters for energy counting without depending Activating the user password:
1 2 3 4 5 6 on any parameter. This menu is used for activating the user password.
IL1 IL2 IL3 ý-1 : Activate “E-1 / E-2” counters, when digital input 1 is on (=1). After the user password is activated, while the instant values are
1 2 3 4 5 6 ý-2 : Activate “E-1 / E-2” counters, when digital input 2 is on (=1).
Current Measuring Input observed,user password is required in order to enter to the
IL1 IL2 IL3 E-2: “E-1” does not count when “E-2” is activated. (Only for “E-1”)
Max: 30 VDC menu. If the wrong user password is entered, user can not enter
( 12-48V DC ) Current Measuring Input E-1: “E-2” does not count when “E-1” is activated. (Only for “E-2”) to the menu.
Pul C InC In1 In2 RS485
_
13 14 15 16 17 18 19 20 21 22 Max: 30 VDC Note: Factory default value of user password is “0000”
( 12-48V DC ) Note: Counting status is undefned if E-2 is selected on E-1 and if E-1 is selected
+
GND B A TR Pul C InC In1 In2 RS485
Pul 1 Pul 2
_
+ 13 14 15 16 17 18 19 20 21 22 on E-2. When the status is defined as above, both energy counters count while
GND B A TR digital input is not on (=1), but if either one or both digital inputs are on (=1) then
Voltage Measuring Input Auxiliary Pul 1 Pul 2 counters will not count.
L1 L2 N
Supply
L3 Auxiliary Press SET button for 3 seconds (trA Fo menu is displayed) Press SET button for 3 seconds (trA Fo menu is displayed)
Voltage Measuring Input
7 8 9 10 11 12
L1 L2 N
Supply
L3
1A

7 8 9 10 11 12
L1 By using UP-DOWN buttons, find “Eng Cnt” menu. Bu using UP-DOWN buttons, find “Pýn” menu.
1A

N L1
3 Phase without neutral N Press SET button (”Eng Cnt E-1” menu is displayed)
3 Phase without neutral current input with Press SET button
Aron wiring configuration (“Pýn ACt IUA tE” menu is displayed)
*Available only for EPM-07S By using UP-DOWN buttons, select “E-1” or “E-2”.

Press SET button. First digit of the displayed value is blinking.


Press SET button.
Note: For CT-25 models: Enter the blinking digit value by scrolling UP/DOWN buttons.
k: When CT-25 is used, Red cable is connected to k terminal. Switch to the other digits by using SET button, use ESC button
l: When CT-25 is used, Black cable is connected to l terminal. By using UP-DOWN buttons, select to go to previous digit. After you entered the last digit press SET
“on”, “ý-1”, “ý-2” or “E-1 / E-2”. button, “Pýn ACt oF” is displayed. “on” can be selected by
scrolling UP/DOWN buttons. (Data is entered but is not activated
yet. For activating the new data please follow the below steps).
Press SET button.
Press ESC button one by one until “SAU E SEt yES” is displayed.
Press ESC button one by one until “SAU E SEt yES” is displayed.
Press SET button. When “SAU E SEt yES” is displayed, if you
Press SET button. When “SAU E SEt yES” is displayed, if you press ESC button or choose “no” option instead of “yES” option
press ESC button or choose “no” option instead of “yES” option by using UP-DOWN buttons, new data will be cancelled and
by using UP-DOWN buttons, new data will be cancelled and previous value will be activated.
previous value will be activated. 3
6
MULTIMETER MULTIMETER
EPM-07 / EPM-07S EPM-07 / EPM-07S
Preset Single Register (06) function is used for writting the setting values,
Serial Communication (Available only for EPM-07S) erasing the energy counter or resetting the min., max., demand values. EPM-07S COMPUTER CONNECTION
EPM-07S has MODBUS RTU communication protocol which is optical Current transformers ratio can be set 0-2000, voltage transformer ratio can 31 DEVICES CAN BE CONNECTED AT THE SAME LINE
isolated. All measured parameters can be transfer to the be set 1-40000. Min., Max. and Demand values can be only clear. If sent
computer.Transformer ratios and communication parameters can be value is outside of this range device responds with an error message.
set. Saved demand and energy values can be reset. i.e. Setting CT as 100;
Parameter Settings 01 06 80 02 00 64 XX XX MAX. 1200 mt.
01 Device address
RS485/RS232
Address Parameters : Value can be enter between 001-247. CONVERTER
Baud Rate Parameters : Value can be selected as 2400, 4800, 9600, 06 Function
19200 and 38400 bps. 80 MSB address
Parity Parameters : “no”, “odd” and “EUEn” can be selected. 02 LSB address
00 Data MSB B
Press SET button for 3 seconds (trA Fo menu is displayed)
64 Data LSB
XX CRC MSB A PC
XX CRC LSB
GND
Bu using UP-DOWN buttons, Preset Multiple Register(10H) is used to set more then one register at same
find “RS-485” menu. time.
i.e. Setting CT as 100, Ut as 20.0;

...
01 10 80 00 00 02 04 00 C8 00 64 XX XX
Press SET button (“Adr ESS” menu is displayed) 01 Device Address
10 Function
TR B A GND TR B A GND TR B A GND
80 MSB address
Find the menu which is programmed in Adr ESS / bAU d / PArýty 00 LSB address
menus by scrolling UP-DOWN buttons. 00 Register number MSB
02 Register number LSB
04 Byte count
Press SET button (”001 / 9600 / no” is displayed.)
00 Data MSB
C8 Data LSB EPM-07S-31 EPM-07S-2 EPM-07S-1
00 Data MSB
Enter the value of related parameters by scrolling UP/DOWN 64 Data LSB
buttons (001...247 / 2400...38400 /no, EUEn, odd). XX CRC MSB
XX CRC LSB
Press SET button, Adr ESS / bAU d / PArýty is displayed. (Data is M A X . 2 4 7 D E V I C E S C A N B E C O N N E C T E D AT S A M E L I N E B Y U S I N G R E P E AT E R .
entered but is not activated yet. For activating the new data please Digital Inputs (Available only for EPM-07S)
follow the below steps). Digital input are sent in 16 bit hexadecimal format as below:
input 1 MAX. 1200 mt.
RS485/RS232
55H 15 1 0 MAX. 1200 mt.
Press ESC button one by one until “SAU E SEt yES” is displayed.
U U U U U U U U U U U U U U DIN2 DIN1 CONVERTER
MSB LSB
Press SET button. When “SAU E SEt yES” is displayed, if you (Most Significant Byte) (Least Significant Byte) input 2
B
press ESC button or choose “no” option instead of “yES” option
by using UP-DOWN buttons, new data will be cancelled and
U: undefined
A PC
If 12-48 V AC / DC is applied to ln1 (Input 1), 0 (zero) bit of DIN register
previous value will be activated.
is set as “1”. Otherwise, 0 (zero) bit is set as “0”. GND
If 12-48 V AC / DC is applied to ln2 (Input 2), 1st bit of DIN register is
MODBUS RTU PROTOCOL (Available only for EPM-07S) set as “1”. Otherwise, 1st bit is set as “0”.
Standart MODBUS RTU message is shown below.

... ...
The Parameters are sent in 32bit Hexadecimal format. For Example,
230.0V voltage will be sent as 000008FCH. Cosj values shall be divided TR B A GND
T ADDRESS FUNCTION DATA CRCH CRCL T to 1000.
8 BIT 8 BIT NX8BIT 0.980 Cosj will be sent as 000003D4H. Energy values are sent in 64
bytes.
The T times corresponds to a time in which data must not be exchanged 1234567890123456789 Wh = AB 54 A9 8C EB 1F 0A 02 Wh
on the communication bus to allow the connected devices to recognize the
end of one message and the beginning of another. This time must be at Specifications for data cable ;
least 3.5 characters at the selected baud rate. Adress range (1-247 ) is - 24 AWG or thicker EPM-07S-247 REPEATER EPM-07S-31 EPM-07S-2 EPM-07S-1
address of the connected device. The data field contains data sent to the - Less than 100 ohm/ km
slave by master or data sent to master by slave. - Nominal characteristic impedance at 100 kHz of 100 ohms
CRC is a error check method by using MODBUS RTU protocol and consists - Less than 60 pF/m mutual capacitance (between two wires in a pair)
of 2 bytes. - Less than 120 pF/m mutual pair capacitance ( the capacitance between
one wire and all others connected to earth).
Available Modbus Function: - Twisted Pair Dimensions
ERROR CODES (Available only for EPM-07S) 10.8 30.1 7.6 9.5
03H READ HOLD REGISTERS
Slave device (EPM-07S) sends error message when receive any missing query.
Error codes are given below. 79.3mm
06H PRESET SINGLE REGISTER
01 Invalid Function: If any message except given above is used, then 01 error 60.6
messages will be sent. 70mm
10H PRESET MULTIPLE REGISTERS 02 Invalid Register: Error 02 will be send when a reading of a register is
requested, except the registers which mentioned in table.
Read Hold (03) function is used for reading measured values and set value. If 03 Invalid data: If any different value is been set for dedicated Transformer values

96mm
any request of reading of a register, excepted mentioned in register table, and nonzero for demand value, then error message 03 will be sent.

45.0
90.0

device will send an error message. For example to read phase1 voltage by
sending a message to the device.

90mm
01 03 00 00 00 02 XX XX
01 Device address
03 Function
14.0

8.5
00 MSB address 106.0
00 LSB address 96mm
00 Register number 10.0
MSB 26.5 21.5
02 Register number LSB 53.0 Type PK 26 Type PR 19
XX CRC MSB 58.0
XX CRC LSB

4 5
MULTIMETER MODBUS REGISTER MAP
EPM-07 / EPM-07S

MODBUS REGISTER MAP MODBUS REGISTER MAP


ADDRESS ADDRESS REGISTER R/W RANGE UNIT MULTIPLIER FORMAT ADDRESS ADDRESS REGISTER R/W RANGE UNIT MULTIPLIER FORMAT
(HEX) (HEX)
0 0000 L1 PHASE VOLTAGE R (0-3000)xUT Volt 0.1 unsigned int 152 0098 L3 PHASE MIN. APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int
2 0002 L2 PHASE VOLTAGE R (0-3000)xUT Volt 0.1 unsigned int 154 009A TOTAL MIN. IMPORT ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
4 0004 L3 PHASE VOLTAGE R (0-3000)xUT Volt 0.1 unsigned int 156 009C TOTAL MIN. EXPORT ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
6 0006 L1 PHASE CURRENT R (0-6000)xCT Amper 0.001 unsigned int 158 009E TOTAL MIN. IMPORT REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
8 0008 L2 PHASE CURRENT R (0-6000)xCT Amper 0.001 unsigned int 160 00A0 TOTAL MIN. EXPORT REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
10 000A L3 PHASE CURRENT R (0-6000)xCT Amper 0.001 unsigned int 162 00A2 TOTAL MIN. APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int
12 000C NEUTRAL CURRENT R (0-6000)xCT Amper 0.001 unsigned int 164 00A4 L1 PHASE MAX. VOLTAGE R/W (0-3000)xUT Volt 0.1 unsigned int
14 000E L1-L2 PHASE-PHASE VOLTAGE R (0-5000)xUT Volt 0.1 unsigned int 166 00A6 L2 PHASE MAX. VOLTAGE R/W (0-3000)xUT Volt 0.1 unsigned int
16 0010 L2-L3 PHASE-PHASE VOLTAGE R (0-5000)xUT Volt 0.1 unsigned int 168 00A8 L3 PHASE MAX. VOLTAGE R/W (0-3000)xUT Volt 0.1 unsigned int
18 0012 L3-L1 PHASE-PHASE VOLTAGE R (0-5000)xUT Volt 0.1 unsigned int 170 00AA L1-L2 PHASE-PHASE MAX. VOLTAGE R/W (0-5000)xUT Volt 0.1 unsigned int
20 0014 L1 PHASE ACTIVE POWER R (-18000 - 18000)xCTxVT Watt 0.1 int 172 00AC L2-L3 PHASE-PHASE MAX. VOLTAGE R/W (0-5000)xUT Volt 0.1 unsigned int
22 0016 L2 PHASE ACTIVE POWER R (-18000 - 18000)xCTxVT Watt 0.1 int 174 00AE L3-L1 PHASE-PHASE MAX. VOLTAGE R/W (0-5000)xUT Volt 0.1 unsigned int
24 0018 L3 PHASE ACTIVE POWER R (-18000 - 18000)xCTxVT Watt 0.1 int 176 00B0 L1 PHASE MAX. CURRENT R/W (0-6000)xCT Amper 0.001 unsigned int
26 001A L1 PHASE REACTIVE POWER R (-18000 - 18000)xCTxVT Var 0.1 int 178 00B2 L2 PHASE MAX. CURRENT R/W (0-6000)xCT Amper 0.001 unsigned int
28 001C L2 PHASE REACTIVE POWER R (-18000 - 18000)xCTxVT Var 0.1 int 180 00B4 L3 PHASE MAX. CURRENT R/W (0-6000)xCT Amper 0.001 unsigned int
30 001E L3 PHASE REACTIVE POWER R (-18000 - 18000)xCTxVT Var 0.1 int 182 00B6 L1 PHASE MAX. ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
32 0020 L1 PHASE APPARENT POWER R (0 -18000)xCTxVT VA 0.1 unsigned int 184 00B8 L2 PHASE MAX. ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
34 0022 L2 PHASE APPARENT POWER R (0 -18000)xCTxVT VA 0.1 unsigned int 186 00BA L3 PHASE MAX. ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
36 0024 L3 PHASE APPARENT POWER R (0 -18000)xCTxVT VA 0.1 unsigned int 188 00BC L1 PHASE MAX. REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
38 0026 L1 PHASE COSj R (-1000 -1000) - 0.001 int 190 00BE L2 PHASE MAX. REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
40 0028 L2 PHASE COSj R (-1000 -1000) - 0.001 int 192 00C0 L3 PHASE MAX. REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
42 002A L3 PHASE COSj R (-1000 -1000) - 0.001 int 194 00C2 L1 PHASE MAX. APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int
44 002C TOTAL IMPORT ACTIVE POWER R (0 -54000)xCTxVT Watt 0.1 int 196 00C4 L2 PHASE MAX. APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int
46 002E TOTAL EXPORT ACTIVE POWER R (0 -54000)xCTxVT Watt 0.1 int 198 00C6 L3 PHASE MAX. APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int
48 0030 TOTAL INDUCTIVE REACTIVE POWER R (0 -54000)xCTxVT Var 0.1 int 200 00C8 TOTAL MAX. IMPORT ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
50 0032 TOTAL CAPACITIVE REACTIVE POWER R (0 -54000)xCTxVT Var 0.1 int 202 00CA TOTAL MAX. EXPORT ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
52 0034 TOTAL APPARENT POWER R (0 -54000)xCTxVT VA 0.1 unsigned int 204 00CC TOTAL MAX. IMPORT REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
54 0036 AVERAGE INDUCTIVE COSj R (-1000 -1000) - 0.001 int 206 00CE TOTAL MAX. EXPORT REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
56 0038 AVERAGE CAPACITIVE COSj R (-1000 -1000) - 0.001 int 208 00D0 TOTAL MAX. APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int
58 003A FREQUENCY R (4000 -7000) Hz 0.01 unsigned int 210 00D2 L1 PHASE MAX. CURRENT DEMAND R/W (0-6000)xCT Amper 0.001 unsigned int
60 003C L1 PHASE VOLTAGE ANGLE R 0-360 Degre 1 unsigned int 212 00D4 L2 PHASE MAX. CURRENT DEMAND R/W (0-6000)xCT Amper 0.001 unsigned int
62 003E L2 PHASE VOLTAGE ANGLE R 0-360 Degre 1 unsigned int 214 00D6 L3 PHASE MAX. CURRENT DEMAND R/W (0-6000)xCT Amper 0.001 unsigned int
64 0040 L3 PHASE VOLTAGE ANGLE R 0-360 Degre 1 unsigned int 216 00D8 L1 PHASE IMPORT MAX. DEMAND ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
66 0042 L1 PHASE CURRENT ANGLE R 0-360 Degre 1 unsigned int 218 00DA L1 PHASE EXPORT MAX. DEMAND ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
68 0044 L2 PHASE CURRENT ANGLE R 0-360 Degre 1 unsigned int 220 00DC L2 PHASE IMPORT MAX. DEMAND ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
70 0046 L3 PHASE CURRENT ANGLE R 0-360 Degre 1 unsigned int 222 00DE L2 PHASE EXPORT MAX. DEMAND ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
72 0048 224 00E0 L3 PHASE IMPORT MAX. DEMAND ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
74 004A 226 00E2 L3 PHASE EXPORT MAX. DEMAND ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
76 004C 228 00E4 L1 PHASE IMPORT MAX. DEMAND REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
78 004E 230 00E6 L1 PHASE EXPORT MAX. DEMAND REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
80 0050 232 00E8 L2 PHASE IMPORT MAX. DEMAND REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
82 0052 234 00EA L2 PHASE EXPORT MAX. DEMAND REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
84 0054 DIGITAL INPUT STATUS R - - - - 236 00EC L3 PHASE IMPORT MAX. DEMAND REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
86 0056 R/W 0-FFFFFFFFFFFFFFFF Wh 1 long int 238 00EE L3 PHASE EXPORT MAX. DEMAND REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
IMPORT ACTIVE ENERGY-1
88 0058 R/W 0-FFFFFFFFFFFFFFFF Wh 1 long int 240 00F0 L1 PHASE MAX. DEMAND APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int
90 005A R/W 0-FFFFFFFFFFFFFFFF Wh 1 long int 242 00F2 L2 PHASE MAX. DEMAND APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int
EXPORT ACTIVE ENERGY-1
92 005C R/W 0-FFFFFFFFFFFFFFFF Wh 1 long int 244 00F4 L3 PHASE MAX. DEMAND APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int
94 005E R/W 0-FFFFFFFFFFFFFFFF VArh 1 long int 246 00F6 TOTAL IMPORT MAX. DEMAND ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
INDUCTIVE REACTIVE ENERGY-1
96 0060 R/W 0-FFFFFFFFFFFFFFFF VArh 1 long int 248 00F8 TOTAL EXPORT MAX. DEMAND ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
98 0062 R/W 0-FFFFFFFFFFFFFFFF VArh 1 long int 250 00FA TOTAL IMPORT MAX. DEMAND REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
CAPACITIVE REACTIVE ENERGY-1
100 0064 R/W 0-FFFFFFFFFFFFFFFF VArh 1 long int 252 00FC TOTAL EXPORT MAX. DEMAND REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
102 0066 R/W 0-FFFFFFFFFFFFFFFF Wh 1 long int 254 00FE TOTAL MAX. DEMAND APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int
IMPORT ACTIVE ENERGY-2
104 0068 R/W 0-FFFFFFFFFFFFFFFF Wh 1 long int
106 006A
EXPORT ACTIVE ENERGY-2
R/W 0-FFFFFFFFFFFFFFFF Wh 1 long int
ADDRESS ADDRESS REGISTER R/W RANGE UNIT MULTIPLIER FORMAT
108 006C R/W 0-FFFFFFFFFFFFFFFF Wh 1 long int (HEX)
110 006E R/W 0-FFFFFFFFFFFFFFFF VArh 1 long int 32768 8000 VOLTAGE TRANSFORMER RATIO R/W 0-40000 - 0.1 short-int
INDUCTIVE REACTIVE ENERGY-2
112 0070 R/W 0-FFFFFFFFFFFFFFFF VArh 1 long int 32769 8001 CURRENT TRANSFORMER RATIO R/W 0-2000 - 1 short-int
114 0072 R/W 0-FFFFFFFFFFFFFFFF VArh 1 long int 32770 8002 CALCULATION METHOD R/W 0-5 - - short-int
CAPACITIVE REACTIVE ENERGY-2
116 0074 R/W 0-FFFFFFFFFFFFFFFF VArh 1 long int 32771 8003 DEMAND TIME R/W 1-60 minute 1 short-int
118 0076 L1 PHASE MIN. VOLTAGE R/W (0-3000)xUT Volt 0.1 unsigned int 32772 8004 PULSE RATIO R/W 0-6 - - short-int
120 0078 L2 PHASE MIN. VOLTAGE R/W (0-3000)xUT Volt 0.1 unsigned int 32773 8005 PULSE OUTPUT 1 PARAMETER SETTING R/W 0-5 - - short-int
122 007A L3 PHASE MIN. VOLTAGE R/W (0-3000)xUT Volt 0.1 unsigned int 32774 8006 PULSE OUTPUT 2 PARAMETER SETTING R/W 0-5 - - short-int
124 007C L1-L2 PHASE-PHASE MIN. VOLTAGE R/W (0-3000)xUT Volt 0.1 unsigned int 32775 8007 ENERGY COUNTER 1 SELECTION R/W 0-3 - - short-int
126 007E L2-L3 PHASE-PHASE MIN. VOLTAGE R/W (0-3000)xUT Volt 0.1 unsigned int 32776 8008 ENERGY COUNTER 2 SELECTION R/W 0-3 - - short-int
128 0080 L3-L1 PHASE-PHASE MIN. VOLTAGE R/W (0-3000)xUT Volt 0.1 unsigned int 32777 8009 COMMUNICATION ADDRESS R/W 0 - 247 - - short-int
130 0082 L1 PHASE MIN. CURRENT R/W (0-6000)xCT Amper 0.001 unsigned int 32778 800A BAUD RATE R/W 1-5 - - short-int
132 0084 L2 PHASE MIN. CURRENT R/W (0-6000)xCT Amper 0.001 unsigned int 32779 800B PARITY R/W 0-2 - - short-int
134 0086 L3 PHASE MIN. CURRENT R/W (0-6000)xCT Amper 0.001 unsigned int 32780 800C PASSWORD ENABLE R/W 0-1 - - short-int
136 0088 L1 PHASE MIN. ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int 32781 800D PASSWORD R/W 0-9999 - - short-int
138 008A L2 PHASE MIN. ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
140 008C L3 PHASE MIN. ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
PULSE OUTPUT 1-2 PULSE RATIO 0-6 : ENERGY COUNTER 1 SELECTION 0-3 : BAUD RATE 1-5 :
142 008E L1 PHASE MIN. REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int PARAMETER SETTING 0-5 : 0: 1 Watt / Pulse 0 : On (EC -Energy counter- will count on all conditions) 1: 38400 bps
144 0090 L2 PHASE MIN. REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int 0: Active 1: 10 Watt / Pulse 1: EC will count when Digital Input1 is 1 (1=active) 2: 19200 bps
146 0092 L3 PHASE MIN. REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int 1: Active Import 2: 100 Watt / Pulse 2: EC will count when Digital Input2 is 1 (1=active) 3: 9600 bps
148 0094 L1 PHASE MIN. APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int 2: Active Export 3: 1 kW / Pulse 3: Inverse Energy Counter 2 (It will count when EC2 is not counted) 4: 4800 bps
150 0096 L2 PHASE MIN. APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int 3: Reactive 4: 10 kW / Pulse ENERGY COUNTER 2 SELECTION 0-3 : 5: 2400 bps
4: Reactive Import 5: 100 kW / Pulse 0 : On (EC -Energy counter- will count on all conditions) PARITY 0-2 :
*Available only for EPM-07S 5: Reactive Export 6: 1 MW / Pulse 1: EC will count when Digital Input1 is 1 (1=active) 0: No
2: EC will count when Digital Input2 is 1 (1=active) 1: Odd
CALCULATION 0-5 : 3: Inverse Energy Counter 1 (It will count when EC1 is not counted) 2: Even
Refer to “Reactive Energy Calculation Method Setting” on page 2. PASSWORD ENABLE 0-1 :
0: Disable