Service Design Lab Student's Manual 6
Service Design Lab Student's Manual 6
Service Design Lab Student's Manual 6
the heat gain to the building is not converted to cooling load instantaneously. CLTD (cooling load
temperature difference), SCL (solar cooling load factor), and CLF (cooling load factor): all include
the effect of (1) time-lag in conductive heat gain through opaque exterior surfaces and (2) time delay
by thermal storage in converting radiant heat gain to cooling load.
This approach allows cooling load to be calculated manually by use of simple multiplication factors.
a. CLTD is a theoretical temperature difference that accounts for the combined effects of inside
and outside air temp difference, daily temp range, solar radiation and heat storage in the
construction assembly/building mass. It is affected by orientation, tilt, month, day, hour,
latitude, etc. CLTD factors are used for adjustment to conductive heat gains from walls, roof,
floor and glass.
b. CLF accounts for the fact that all the radiant energy that enters the conditioned space at a
particular time does not become a part of the cooling load instantly. The CLF values for various
surfaces have been calculated as functions of solar time and orientation and are available in the
form of tables in ASHRAE Handbooks (The American Society of Heating, Refrigerating and
Air-Conditioning Engineers). CLF factors are used for adjustment to heat gains from internal
loads such as lights, occupancy, power appliances.
SCL factors are used for adjustment to transmission heat gains from glass.
As discussed before, the total cooling load on a building consists of external as well as internal loads.
The external loads consist of heat transfer by conduction through the building walls, roof, floor, doors
etc, heat transfer by radiation through fenestration such as windows and skylights. All these are
sensible heat transfers.
1.1 1 ROOF
The basic conduction equation for heat gain is q = U A ∆T.
Where
q = Heat gain in Btu/hr
U = Thermal Transmittance for roof in Btu/hr.ft2.°F A = area of roof in ft2
∆T = Temperature difference in °F
The heat gain is converted to cooling load using the room transfer functions (sol-air temperature) for
the rooms with light, medium and heavy thermal characteristics. The equation is modified as
Q = U * A * (CLTD) Where Q = cooling load, Btu/hr
U = Coefficient of heat transfer roof or wall or glass, Btu/hr.ft2.°F
A = area of roof, ft2
CLTD = cooling load temperature difference °F. The values are determined from tables available in
chapter 28 of AHSRAE fundamentals handbook.
Since the ASHRAE tables provide hourly CLTD values for one typical set of conditions i.e. outdoor
maximum temperature of 95°F with mean temperature of 85°C and daily range of 21°F, the equation
is further adjusted to apply correction factors for conditions other than the mentioned base case. Thus,
Step #1 Determine roof construction and overall heat transfer coefficient (U) (Chapter
28 ASHRAE 1997, Table A24-4, A29-5)
Step #2 Select roof no. from ASHRAE Table 31 or Text table 7-34 which is closest to
matching actual roof construction.
Step #3 Select CLTD Roof for time of interest, typically on an hourly basis (Chapter 28
ASHRAE Table A28-32, A28-34).
1.2 2 WALLS
The cooling load from walls is treated in a similar way as roof:
Q Wall = U * A * CLTD Wall Corrected
Where
Experiment 6 Lab Student’s Manual
Step # 2 Select wall type from ASHRAE Table 33 which is closest to matching actual
wall construction.
Pay attention to effect of mass distribution (inside insulation, outside insulation or evenly
distributed).
Step #3 Select CLTD Wall for time of interest, typically on an hourly basis (Chapter 28
ASHRAE Table A28-32, A28-34).
c. Outdoor maximum temperature of 95°F with mean daily temperature of 85°F and daily range of
21°F
CLTD Wall Corrected= [CLTD Wall+ (78 – TR) +(TM – 85)] Where (78 – TR) = indoor design
temperature correction ,
(TM – 85) = outdoor design temperature correction
Tm = Mean outdoor temperature
o Tmax = Maximum outdoor temperature o Tm = Tmax – (Daily Range) / 2
Step #5 Calculate walls area (A). Use the architectural drawings to determine how much
wall area you have. Since you will be finding window and door losses separately, exclude windows
and door and count only wall area.
Step #6 Q Wall = U * A * CLTD Wall Corrected
Experiment 6 Lab Student’s Manual
Step # 3 Corrections:
CLTD Glass Corrected= [CLTD Glass+ (78 – TR) +(TM – 85)] Where
o (78 – TR) = indoor design temperature correction o (TM – 85) = outdoor design temperature
correction o TR = Indoor room temperature
o Tm = Mean outdoor temperature
o Tmax = Maximum outdoor temperature o Tm = Tmax – (Daily Range) / 2 Step # 4 Calculate
glass area (A) from architectural plans
Experiment 6 Lab Student’s Manual
Step # 1 Determine shading coefficient (SC) from ASHRAE 1997 Chapter 27, Table 11
Step # 2 Determine zone type from ASHRAE 1997 Chapter 29, Table 35 B
Step # 3 Determine solar cooling load factor (SCL) from ASHRAE 1997 Chapter 28,
Table A28-36
Step # 4 Calculate glass area (A) from architectural plans Step # 5Q Glass Solar = A *
SC * SCL
for the time lag of the cooling load caused by the building mass. The weighting factors equation
determines the CLF factors.
CLF = Q cooling load / Q internal gains
Note that the latent heat gains are considered instantaneous.
2.1 1 People
Q sensible = N (QS) (CLF) Q latent = N (QL) Where
• N = number of people in space from ASHRAE, Table A28-3
QS, QL = Sensible and Latent heat gain from occupancy is given in 1997 ASHRAE Fundamentals
Chapter 28, Table 3)
CLF = Cooling Load Factor, by hour of occupancy. See 1997 ASHRAE Fundamentals, Chapter 28,
Table 37
Note: CLF = 1.0, if operation is 24 hours or of cooling is off at night or during weekends.
The table below gives representative rates at which heat and moisture are given off by human beings
in different states of activity. Often these sensible and latent heat gains constitute a large fraction of
the total load. Even for short-term occupancy, the extra heat and moisture brought in by people may
be significant.
Snapshot of Occupancy Heat gain values in ASHRAE
Heat Gain from Occupants at Various Activities (At Indoor Air Temperature of 78°F)
Activity Total heat, Btu/h Sensible heat, Latent heat,
Btu/h
Adult, male Adjusted Btu/h
Seated at rest 400 350 210 140
Seated, very light work, 480 420 230 190
writing
Seated, eating 520 580 255 325
Seated, light work, typing, 640 510 255 255
Standing, light work or 800 640 315 325
walking
slowly, 880 780 345 435
Light bench work 1040 1040 345 695
Light machine work, 1360 1280 405 875
walking 3mi/hr
Moderate dancing 1600 1600 565 1035
Experiment 6 Lab Student’s Manual
2.1 2 Lights
The primary source of heat from lighting comes from light-emitting elements. Calculation of this load
component is not straightforward; the rate of heat gain at any given moment can be quite different
from the heat equivalent of power supplied instantaneously to those lights. Only part of the energy
from lights is in the form of convective heat, which is picked up instantaneously by the air-
conditioning apparatus. The remaining portion is in the form of radiation, which affects the
conditioned space only after having been absorbed and re-released by walls, floors, furniture, etc.
This absorbed energy contributes to space cooling load only after a time lag, with some part of such
energy still present and reradiating after the lights have been switched off.
Generally, the instantaneous rate of heat gain from electric lighting may be calculated from: Q
= 3.41 x W x FUT x FSA
Cooling load factors are used to convert instantaneous heat gain from lighting to the sensible cooling
load; thus the equation is modified to
Q = 3.41 x W x FUT x FSA x (CLF) , Where
W = Watts input from electrical lighting plan or lighting load data FUT = Lighting use factor, as
appropriate
FSA = special ballast allowance factor, as appropriate
CLF = Cooling Load Factor, by hour of occupancy. See 1997 ASHRAE Fundamentals, Chapter 28,
Table 38
Note: CLF = 1.0, if operation is 24 hours or if cooling is off at night or during weekends.
2.2 Power Loads
The industrial and commercial applications use various equipments such as fans, pumps, machine
tools, elevators, escalators and other machinery, which add significantly to the heat gain. There are 5
equations in use for different scenarios.
Case #1
If the motor and the machine are in the room the heat transferred can be calculated as
Q = 2545 * (P / Eff) * FUM * FLM
P = Horsepower rating from electrical power plans or manufacturer’s data Eff = Equipment motor
efficiency, as decimal fraction
FUM = Motor use factor (normally = 1.0)
FLM = Motor load factor (normally = 1.0) Note: FUM = 1.0, if operation is 24 hours
In this situation the total power are transferred as heat to the room.
Note! If the machine is a pump or a fan most of the power are transferred as energy to the medium
and may be transported out of the room. For such cases, case 4 shall be used.
Experiment 6 Lab Student’s Manual
Case #2
If the motor is outside and the machine is in the room the heat transferred can be calculated as
Q = 2545 * P * FUM * FLM
P = Horsepower rating from electrical power plans or manufacturer’s data FUM = Motor use factor
FLM = Motor load factor
Note: FUM = 1.0, if operation is 24 hours
Case #3
If the motor is belt driven and the motor and belt is outside and the machine is in the room the heat
transferred can be calculated as
Q = 2545 * P * Belt Eff * FUM * FLM
P = Horsepower rating from electrical power plans or manufacturer’s data Belt Eff = Belt
transmission efficiency, as decimal fraction
FUM = Motor use factor FLM = Motor load factor
Note: FUM = 1.0, if operation is 24 hours
Case #4
If the motor is in the room and the machine is outside the heat transferred can be calculated as
Q = 2545 * [P/Eff - P] * FUM * FLM
P = Horsepower rating from electrical power plans or manufacturer’s data
Eff = Motor efficiency, as decimal fraction FUM = Motor use factor
FLM = Motor load factor
Note: FUM = 1.0, if operation is 24 hours
Case #5
If the motor is belt driven and the motor and belt is in the room and the machine is outside the heat
transferred can be calculated as
Q = 2545 * [P/ (motor Eff) – P/ (belt Eff)] * FUM * FLM
P = Horsepower rating from electrical power plans or manufacturer’s data FUM = Motor use factor,
FLM = Motor load factor
2.2 Appliances
In a cooling load estimate, heat gain from all appliances-electrical, gas, or steam-should be taken into
account. Because of the variety of appliances, applications, schedules, use, and installations,
estimates can be very subjective. Often, the only information available about heat gain from
equipment is that on its name-plate.
Experiment 6 Lab Student’s Manual
Fu = Usage factor. See 1997 ASHRAE Fundamentals, Chapter 28, Table 6 and 7
Fr = Radiation factor. See 1997 ASHRAE Fundamentals, Chapter 28, Table 6 and 7
CLF = Cooling Load Factor, by hour of occupancy. See 1997 ASHRAE Fundamentals, Chapter 28,
Table 37 and 39
Note 1: CLF = 1.0, if operation is 24 hours or of cooling is off at night or during weekends. Note 2:
Set latent load = 0 if appliance under exhaust hood
Experiment 6 Lab Student’s Manual
Q sensible = 1.08 x CFM x (To – Tc), Q latent = 4840 x CFM x (Wo – Wc) Q total = 4.5 x CFM
x (ho – hc) Where
Commercial type or existing older systems can have leakage from 10% to 20% of the total system airflow.
Per energy conservation guidelines, in a new installation, the duct system should not leak more than 1% to
3% of total system airflow.
The engineer or designer is cautioned to make sure that the proper allowance for leakages is included in the
calculations in order to ensure that the equipment selected is properly sized.
2.4 Diversity Factors
Diversity of cooling load results from not using part of the load on a design day. Therefore, diversity factors
are factors of usage and are applied to the refrigeration capacity of large air conditioning systems. These
factors vary with location, type and size of application. Generally, diversity factors can be applied to loads
from people and lights as there is neither 100% occupancy nor total lighting at the time of such other peak
loads as peak solar and transmission loads. The reduction in cooling loads from non-use is real and should
be accounted for. Listed are some average typical diversity factors for large buildings during occupied
periods.
In the case of Industrial, diversity should also be applied to the machinery load.
4. SUPPLY AIR CALCULATIONS
Calculations for the design supply air quantities are dependent on the type of system used. Some
generalizations and assumptions need to be made to assist in the use of the cooling load calculations for
equipment selection and sizing. For constant air volumes with reheat type of system, the design supply air
quantities required are based on the peak requirements for each space. However, if the system selected
allows for air flow to each zone to vary based on load, the peak load on an air conditioning unit serving
several zones or spaces is not equal to the sum of the peak loads of each zone, but will be that amount
necessary to handle the maximum coincident load on the system at a given time. Determining the maximum
coincident load may require additional calculation and analysis.
Supply air flow rate to a space is based only on the total space sensible heat load, thus CFM =
1.08
x [Q sensible / (TR – Ts)]
Experiment 6 Lab Student’s Manual
Where
CFM = air flow in cubic feet per minute
1.08 = conversion constant = 0.244 X (60/13.5)
0.244 = specific heat of moist air, Btu/lb d.a.
13.5 = specific volume of moist air, cu-ft. per lb. d.a. (@70°F, 50% RH) Q sensible = total room sensible
heat gain, BTU per hr.
TR = Room dry bulb temperature, °F
Ts = Room supply air dry bulb temperature, °F (not necessarily the same as the temperature of the air
leaving the cooling coil).
Report: Make An office building in Montreal area requires air conditioning for a single-story building. The
following data is gathered:
Location: Montreal
Type of building: Office
Number of floors: 1
Floor area: 64 ft x 80 ft = 5120 ft2
Floor-to-floor Height: 15 ft
Window area: 20 % of the wall area
Windows: Double glazed
Experiment 6 Lab Student’s Manual
Wall: Wall number 13 [U= 0.2 Btu/h.ft2.F, as per table 33A*, pg 28.46
Roof: Roof number 13 [U= 0.2 Btu/h.ft2.F as per table 31, pg 28.42]
Windows: U= 0.55 Btu/h.ft2.F
Recommended ventilation: ½ air change per hour (min) or 20 cfm/person Occupancy: 7 persons per
1000 sq-ft
Working: 8 hrs of working - 9.00 to 17.00 hrs
Estimate the cooling load using the Cooling Load Temperature Difference / Solar Cooling Load/ Cooling
Load Factor (CLTD/SCL/CLF) method.
DESIGN CONDITIONS:
Outdoor design conditions for Montreal area [Reference: 1997 ASHARE Handbook - Fundamentals Table-
2, pp.26.25]
Location: (45° N 73° 45’W) [for simplicity consider 40° N latitude]
Outdoor design dry-bulb: 90 °F
Outdoor design wet-bulb: 75 °F
Indoor design Dry-bulb: 78 °F
Daily Range: 20 °F
Relative humidity: 50%
Wind velocity: 7½ mph
DESIGN BASIS
Zone Division:
Due to solar exposure and sun movement, the heat gain through exterior walls (in perimetric areas) will be
much higher than the interior zones. As such the supply air requirements for exterior zones shall be much
higher than the interior zones. This aspect is very important in sizing and control of air-conditioning
equipment especially when single equipment (AHU) is feeding the entire area.
For this job, the building envelope is divided into 5 zones having 20 rooms of equal areas (It’s assumed the
two corners in each zone as a one room with the same situation with the other rooms on that zone). The
central zone heat gain conduction through the walls are zero due to ∆T=0 (There isn’t exterior walls in
central zone)
Experiment 6 Lab Student’s Manual
Zone Description:
1 1 N 3 192 48 256
2 1 E 4 192 48 256
3 1 S 3 192 48 256
16
© Dept. of EEE, Faculty of Engineering, American International University-Bangladesh (AIUB)
Experiment 6 Lab Student’s Manual
4 1 W 4 192 48 256
5 - Interior 6 - 48 256
Window area for each wall is 48 ft² which is 20 % of gross wall area of 240 sq-ft (16 *15 * 0.2=48 ft²) Net area
for each wall is 192 sq. ft, which is gross wall area minus window area (240 ft² - 48 ft²=192 ft²)
ASSUMPTIONS
17
© Dept. of EEE, Faculty of Engineering, American International University-Bangladesh (AIUB)
Experiment 6 Lab Student’s Manual
vi. Roof number is 13 as per Table 31t page-28.42 and U value for roof is 0.055 Btu/h.ft2. °F.
vii. Wall number is 13 as per Table 33A, page-28.46 and U value for wall is 0.2 Btu/h.ft2.°F.
viii. Window is un-coated double glazed and U value is 0.55 which is found from Table 11, page-29.8
ix. Values of Cooling Load Temperature Difference (CLTD) for roof are taken from Table30, Page-28.42
x. Values of Cooling Load Temperature Difference (CLTD) for wall are taken from Table32, Page-28.45
xi. Values of Cooling Load Temperature Difference (CLTD) for glass are taken from Table34, Page-
28.49
xii. Values of Shading Coefficient (SC) are taken from Table 11, page-29.25
xiii. Values of Solar Cooling Load (SCL) are taken from Table 36, page-28.50, zone Type C
xiv. Values of Cooling Load Factor (CLF) for lighting are taken from Table38 based on lights on for 8
hours,
Page-28.52, zone Type C
xv. Values of Cooling Load Factor (CLF) for people are taken from Table37 based on 8 hours in space,
18
© Dept. of EEE, Faculty of Engineering, American International University-Bangladesh (AIUB)
Experiment 6 Lab Student’s Manual
xvi. Rates of Sensible Heat Gain (SHG) and Latent Heat Gain (LHG) from people are taken from Table 3,
page-28.8
xvii. It is assumed that there will be one Computer in each room also assumed that heat gain will be 680
Btu/hr
*Source: ASHRAE Handbook- 1997 Fundamentals
Discussion:
Make discussion about the data which has been found during the calculations
Conclusion:
Summarize the experiment here and discuss whether the objectives were fulfilled or not within a short
paragraph.
References:
2001 ASHRAE Handbook of Fundamentals
19
© Dept. of EEE, Faculty of Engineering, American International University-Bangladesh (AIUB)