Roof Structural Analysis PDF
Roof Structural Analysis PDF
Roof Structural Analysis PDF
For
40x40 Structure
WIND LOADING
In accordance with ASCE7-16
Using the directional design method
Tedds calculation version 2.1.10
40 ft
16.5 ft
40 ft 40 ft
Plan Elevation
Building data
Type of roof; Gable
Length of building; b = 40.00 ft
Width of building; d = 40.00 ft
Height to eaves; H = 8.00 ft
Pitch of roof; 0 = 23.0 deg
Mean height; h = 12.24 ft
General wind load requirements
Basic wind speed; V = 110.0 mph
Risk category; III
Velocity pressure exponent coef (Table 26.6-1); Kd = 0.85
Ground elevation above sea level; zgl = 0 ft
Ground elevation factor; Ke = exp(-0.0000362 zgl/1ft) = 1.00
Exposure category (cl 26.7.3); C
Enclosure classification (cl.26.12); Enclosed buildings
Internal pressure coef +ve (Table 26.13-1); GCpi_p = 0.18
Internal pressure coef –ve (Table 26.13-1); GCpi_n = -0.18
Gust effect factor for rigid structures
Terrain exposure constants (Table 26.11-1)
Integral length scale factor; l = 500.0 ft
Turbulence intensity factor; c = 0.20
Minimum equivalent height; zmin = 15.0 ft
Peak factor for background response; gQ = 3.400
Peak factor for wind response; gv = 3.400
Project Job Ref.
125 Garnet Ave, Ridgecrest CA, 93555
Section Sheet no./rev.
WIND LOAD ANALYSIS 2
Calc. by Date Chk'd by Date App'd by Date
SAIF 08/03/2023
Overall loading
Projected vertical plan area of wall; Avert_w_0 = b H = 320.00 ft2
Projected vertical area of roof; Avert_r_0 = b d/2 tan(0) = 339.58 ft2
Minimum overall horizontal loading; Fw,total_min = pmin_w Avert_w_0 + pmin_r Avert_r_0 = 7.84 kips
Project Job Ref.
125 Garnet Ave, Ridgecrest CA, 93555
Section Sheet no./rev.
WIND LOAD ANALYSIS 3
Calc. by Date Chk'd by Date App'd by Date
SAIF 08/03/2023
Overall loading
Projected vertical plan area of wall; Avert_w_0 = b H = 320.00 ft2
Projected vertical area of roof; Avert_r_0 = b d/2 tan(0) = 339.58 ft2
Minimum overall horizontal loading; Fw,total_min = pmin_w Avert_w_0 + pmin_r Avert_r_0 = 7.84 kips
Leeward net force; Fl = Fw,wB = -1.9 kips
Windward net force; Fw = Fw,wA = 6.4 kips
Overall horizontal loading; Fw,total = max(Fw - Fl + Fw,h, Fw,total_min) = 13.8 kips
Roof load case 3 - Wind 90, GCpi 0.18, -cpe
Ref. Ext pressure Peak velocity Net pressure Area Net force
Zone height coefficient cpe pressure qp p Aref Fw
(ft) (psf) (psf) (ft2) (kips)
A (-ve) 12.24 -0.90 22.38 -21.87 266.04 -5.82
B (-ve) 12.24 -0.90 22.38 -21.87 266.04 -5.82
C (-ve) 12.24 -0.50 22.38 -13.94 532.09 -7.42
D (-ve) 12.24 -0.30 22.38 -9.98 674.00 -6.72
Total vertical net force; Fw,v = -23.73 kips
Total horizontal net force; Fw,h = 0.00 kips
Walls load case 3 - Wind 90, GCpi 0.18, -cpe
Ref. Ext pressure Peak velocity Net pressure Area Net force
Zone height coefficient cpe pressure qp p Aref Fw
(ft) (psf) (psf) (ft2) (kips)
A1 15.00 0.80 22.38 11.83 484.56 5.73
A2 16.49 0.80 22.77 12.11 5.23 0.06
Project Job Ref.
125 Garnet Ave, Ridgecrest CA, 93555
Section Sheet no./rev.
WIND LOAD ANALYSIS 4
Calc. by Date Chk'd by Date App'd by Date
SAIF 08/03/2023
Ref. Ext pressure Peak velocity Net pressure Area Net force
Zone height coefficient cpe pressure qp p Aref Fw
(ft) (psf) (psf) (ft2) (kips)
B 12.24 -0.50 22.38 -13.94 489.79 -6.83
C 12.24 -0.70 22.38 -17.90 320.00 -5.73
D 12.24 -0.70 22.38 -17.90 320.00 -5.73
Overall loading
Projected vertical plan area of wall; Avert_w_90 = d H + d2 tan(0) / 4 = 489.79 ft2
Projected vertical area of roof; Avert_r_90 = 0.00 ft2
Minimum overall horizontal loading; Fw,total_min = pmin_w Avert_w_90 + pmin_r Avert_r_90 = 7.84 kips
Leeward net force; Fl = Fw,wB = -6.8 kips
Windward net force; Fw = Fw,wA_1 + Fw,wA_2 = 5.8 kips
Overall horizontal loading; Fw,total = max(Fw - Fl + Fw,h, Fw,total_min) = 12.6 kips
Roof load case 4 - Wind 90, GCpi -0.18, +cpe
Ref. Ext pressure Peak velocity Net pressure Area Net force
Zone height coefficient cpe pressure qp p Aref Fw
(ft) (psf) (psf) (ft2) (kips)
A (+ve) 12.24 -0.18 22.38 0.46 266.04 0.12
B (+ve) 12.24 -0.18 22.38 0.46 266.04 0.12
C (+ve) 12.24 -0.18 22.38 0.46 532.09 0.24
D (+ve) 12.24 -0.18 22.38 0.46 674.00 0.31
Total vertical net force; Fw,v = 0.74 kips
Total horizontal net force; Fw,h = 0.00 kips
Walls load case 4 - Wind 90, GCpi -0.18, +cpe
Ref. Ext pressure Peak velocity Net pressure Area Net force
Zone height coefficient cpe pressure qp p Aref Fw
(ft) (psf) (psf) (ft2) (kips)
A1 15.00 0.80 22.38 19.89 484.56 9.64
A2 16.49 0.80 22.77 20.17 5.23 0.11
B 12.24 -0.50 22.38 -5.88 489.79 -2.88
C 12.24 -0.70 22.38 -9.85 320.00 -3.15
D 12.24 -0.70 22.38 -9.85 320.00 -3.15
Overall loading
Projected vertical plan area of wall; Avert_w_90 = d H + d2 tan(0) / 4 = 489.79 ft2
Projected vertical area of roof; Avert_r_90 = 0.00 ft2
Minimum overall horizontal loading; Fw,total_min = pmin_w Avert_w_90 + pmin_r Avert_r_90 = 7.84 kips
Leeward net force; Fl = Fw,wB = -2.9 kips
Windward net force; Fw = Fw,wA_1 + Fw,wA_2 = 9.7 kips
Overall horizontal loading; Fw,total = max(Fw - Fl + Fw,h, Fw,total_min) = 12.6 kips
Project Job Ref.
125 Garnet Ave, Ridgecrest CA, 93555
Section Sheet no./rev.
WIND LOAD ANALYSIS 5
Calc. by Date Chk'd by Date App'd by Date
SAIF 08/03/2023
40 ft
20 ft
B
40 ft
20 ft
Wind - 0o
8 ft
A
40 ft
Windward face
8 ft
8 ft
C B
40 ft 40 ft
Side face Leeward face
Project Job Ref.
125 Garnet Ave, Ridgecrest CA, 93555
Section Sheet no./rev.
WIND LOAD ANALYSIS 6
Calc. by Date Chk'd by Date App'd by Date
SAIF 08/03/2023
40 ft
Wind - 90o
40 ft
A B C D
A2
A1
8 ft
40 ft
Windward face
8 ft
8 ft
C B
40 ft 40 ft
Side face Leeward face
Project Job Ref.
125 Garnet Ave, Ridgecrest CA, 93555
Section Sheet no./rev.
4X6 PURLINS 1
Calc. by Date Chk'd by Date App'd by Date
SAIF 08/03/2023
Design section 1
Member details
Service condition; Wet
Load duration - Table 2.3.2; Permanent
Span details
Unbraced length - Major axis; Lx = 20 ft
Effective bending length - Major axis; Le,x = 1.63 Lx + 3 b = 33.475 ft
Column buckling length - Major axis; Lb,x = Lx = 20 ft
Unbraced length - Minor axis; Ly = 0 ft
Bearing length; Lb = 4 in
Analysis results
Design bending moment - Major axis; Mx = 1172 lb_ft
Design shear force - Major axis; Vx = 230 lb
Design perpendicular compression - Major axis; Rx = 240 lb
All locations are measured from the outside face of left support (or left cantilever end). All dimensions are horizontal.
Design Results Actual @ Location Allowed Result LDF Load: Combination (Pattern) System : Floor
Member Type : Drop Beam
Member Reaction (lbs) 242 @ 3 1/2" 3281 (1.50") Passed (7%) -- 1.0 D + 0.6 W (All Spans)
Building Use : Residential
Shear (lbs) 230 @ 9" 3696 Passed (6%) 1.60 1.0 D + 0.6 W (All Spans)
Building Code : IBC 2021
Moment (Ft-lbs) 1172 @ 10' 3059 Passed (38%) 1.60 1.0 D + 0.6 W (All Spans) Design Methodology : ASD
Live Load Defl. (in) 0.436 @ 10' 0.647 Passed (L/534) -- 1.0 D + 0.6 W (All Spans)
Total Load Defl. (in) 0.964 @ 10' 0.971 Passed (L/242) -- 1.0 D + 0.6 W (All Spans)
• Deflection criteria: LL (L/360) and TL (L/240).
• Allowed moment does not reflect the adjustment for the beam stability factor.
• Applicable calculations are based on NDS.
1 - Hanger on 5 1/2" DF beam 3.50" Hanger¹ 1.50" 135 188 247 See note ¹
2 - Hanger on 5 1/2" DF beam 3.50" Hanger¹ 1.50" 135 188 247 See note ¹
• At hanger supports, the Total Bearing dimension is equal to the width of the material that is supporting the hanger
• ¹ See Connector grid below for additional information and/or requirements.
Dead Wind
Weyerhaeuser Notes
Weyerhaeuser warrants that the sizing of its products will be in accordance with Weyerhaeuser product design criteria and published design values. Weyerhaeuser expressly disclaims any other warranties
related to the software. Use of this software is not intended to circumvent the need for a design professional as determined by the authority having jurisdiction. The designer of record, builder or framer is
responsible to assure that this calculation is compatible with the overall project. Accessories (Rim Board, Blocking Panels and Squash Blocks) are not designed by this software. Products manufactured at
Weyerhaeuser facilities are third-party certified to sustainable forestry standards. Weyerhaeuser Engineered Lumber Products have been evaluated by ICC-ES under evaluation reports ESR-1153 and ESR-1387
and/or tested in accordance with applicable ASTM standards. For current code evaluation reports, Weyerhaeuser product literature and installation details refer to
www.weyerhaeuser.com/woodproducts/document-library.
The product application, input design loads, dimensions and support information have been provided by ForteWEB Software Operator
Lateral Connections
Supports Connector Type/Model Quantity Connector Nailing
Top Nails 8d (0.113" x 2 1/2") (Toe) 2 N/A
Base Nails 8d (0.113" x 2 1/2") (Toe) 2 N/A
• Nailed connection at the top of the member is assumed to be nailed through the bottom 2x plate prior to placement of the top 2x of the double top plate assembly.
Dead
Wind
Weyerhaeuser Notes
Weyerhaeuser warrants that the sizing of its products will be in accordance with Weyerhaeuser product design criteria and published design values. Weyerhaeuser expressly disclaims any other warranties
related to the software. Use of this software is not intended to circumvent the need for a design professional as determined by the authority having jurisdiction. The designer of record, builder or framer is
responsible to assure that this calculation is compatible with the overall project. Accessories (Rim Board, Blocking Panels and Squash Blocks) are not designed by this software. Products manufactured at
Weyerhaeuser facilities are third-party certified to sustainable forestry standards. Weyerhaeuser Engineered Lumber Products have been evaluated by ICC-ES under evaluation reports ESR-1153 and ESR-1387
and/or tested in accordance with applicable ASTM standards. For current code evaluation reports, Weyerhaeuser product literature and installation details refer to
www.weyerhaeuser.com/woodproducts/document-library.
The product application, input design loads, dimensions and support information have been provided by ForteWEB Software Operator