Ha431892002v0f1 (Cable Routing Details)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

SAUDIARAMCO.

NOTES:
TREFOIL CLAMP 13.8kV, 3-1Cx400SQ.MM
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
(AL. ALLOY) (TYP) XLPE Cu. CABLE
OTHERWISE NOTED.
1-1Cx240SQ.MM, XLPE Cu.
1500 GROUND CONTINUITY CABLE
PLASTIC 2. THIS DRAWING TO BE REFERED TO THE EXTENT
(NEOPRIN) (TYP) OF DETAILS INDICATED FOR CABLE ROUTING LAYOUT
150 300 300 300 300 150
ONLY.

OF
2-STACKS FABRICATED 3. FOR DETAILS OF OPENINGS IN GROUND FLOOR SLAB,
UNISTRUT SUPPORTS REFER TO RESPECTIVE CIVIL DRAWING.
SPACE SPACE

CONSENT
(TYP)
4. HV & MV POWER CABLE SHALL BE SUPPORTED @
115KV, 1-1Cx630SQ.MM 115KV, 1-1Cx630SQ.MM
1-1Cx300SQ.MM, XLPE Cu. EVERY 1.5M INTERVAL.
XLPE Cu. CABLE XLPE Cu. CABLE
GROUND CONTINUITY CABLE
1-1Cx300SQ.MM, XLPE Cu. 1-1Cx300SQ.MM, XLPE Cu. 5. STEEL BRIDGES OVER FLOOR SUPPORTED CABLES
GROUND CONTINUITY CABLE GROUND CONTINUITY CABLE CLAMP (SEE DETAIL-1) SHALL BE FABRICATED & TO BE PROVIDED AS PER

TTEN
150 300 300 150 1800 150 300 300 150 50 200 150 200 150 200 50 SITE REQUIREMENTS BY THE CONTRACTOR.

780
115KV, 1-1Cx630SQ.MM

WRI
CLAMP (SEE DETAIL-1) 6. CABLE SUPPORTS EXACT NUMBER, LOCATION &
2-STACKS FABRICATED 2-STACKS FABRICATED XLPE Cu. CABLE
ELEVATION OF THE SAME SHALL BE SUITABLY
UNISTRUT SUPPORTS UNISTRUT SUPPORTS DECIDED AT SITE.

THE
7. ALL CABLES FROM 13.8kV SWGR SHOULD BE

300

300

300
ROUTED HORIZONTALY BY CABLE LADDERS FROM

THOUT
UNISTRUT POST BASE UNISTRUT POST BASE UNISTRUT POST BASE THE CEILING IN ORDER KEEP SPACE FOR MOVEMENT
BELOW THE SWGR AREA.
F.F.L F.F.L F.F.L F.F.L
(-1.65) (-1.65)

WI
LEGEND

NG
AL. ALUMINUM

DRAWI
COND. CONDUCTOR
A S E C T I O N B S E C T I O N C S E C T I O N Cu. COPPER
HA-431892 HA-431892 HA-431892
SCALE N.T.S SCALE N.T.S SCALE N.T.S
SH 001 SH 001 SH 001 FFL FINSHED FLOOR LEVEL

S
SWGR SWITCHGEAR

THI
1-1Cx240SQ.MM, XLPE Cu. TYP TYPICAL
GROUND CONTINUITY CABLE
U/G UNDERGROUND

FROM
TREFOIL CLAMP 13.8kV, 3-1Cx400SQ.MM XLPE CROSS-LINKED POLYETHYLENE
2-STACKS FABRICATED PLASTIC 13.8kV, 3-1Cx400SQ.MM
(AL. ALLOY) (TYP) XLPE Cu. CABLE (TYP)
UNISTRUT SUPPORTS (NEOPRIN) (TYP) XLPE Cu. CABLE TREFOIL CLAMP
(AL. ALLOY) (TYP)

NED
(TYP)
2400
1-1Cx240SQ.MM, XLPE Cu.

OBTAI
PLASTIC 1200 GROUND CONTINUITY CABLE
150 300 300 300 300 300 300 30 150
(NEOPRIN) (TYP)
150 300 300 300 150

BE
2-STACKS FABRICATED CLAMP (SEE DETAIL-1)
SPACE
UNISTRUT SUPPORTS 1-1Cx630SQ.MM, XLPE Cu.
SPACE

PART,SHALL
(TYP) GROUND CONTINUITY CABLE
1-1Cx240SQ.MM, XLPE Cu.
GROUND CONTINUITY CABLE
115KV, 1-1Cx1000SQ.MM
XLPE Cu. CABLE (TYP)
CABLE CLAMP
250 150 (SEE DETAIL-1) 150 300 300 150

780
13.8KV 1Cx500SQ.MM

780

N
I
CU. COND. XLPE CABLE

FULL,OR
2-STACKS FABRICATED

300
300
UNISTRUT SUPPORTS

UNISTRUT UNISTRUT
POST BASE POST BASE
F.F.L UNISTRUT F.F.L F.F.L
(-1.65)

N
(-1.65) POST BASE (-1.65)

I
F.F.L
(-1.65)

ON
REPRODUCTI
D S E C T I O N C S E C T I O N F S E C T I O N G S E C T I O N
HA-431892 HA-431892 HA-431892 HA-431892
SCALE N.T.S SCALE N.T.S SCALE N.T.S SCALE N.T.S
SH 001 SH 001 SH 001 SH 001

SAUDIARAMCO.NO
CABLE CLAMP WITH RESPECTIVE
CABLE OUTER DIA SIZE (MIN),
ELECTRO GALVANIZED FINISH WITH
NT
ARTME HORIZONTAL CROSS SLOTTED HEX HEAD SCREW & NUT
P 13.8kV 1-CORE
COM MEMEBER SUPPORT
LE
R CAB CABLE
GEA CABLE
SW. LINK BOX
13.8kV 3-CORE
115kV GIS REFERENCE DRAWINGS
CABLE
R Y HORIZONTAL CROSS
DWG. CONTROL FOR J.O. 10-10041-0002 HD-431720
250

MEMEBER SUPPORT

OF
B
13.8kV SWGR ROOM OVERALL ONE LINE DIAGRAM HA-431885
FINISHED FLOOR ELECTRICAL EQUIOMENT LAYOUT PLAN HA-431890
TREFOIL CLAMPS

PROPERTY
150 250 150 CABLE CLAMP
(NON-MAGNETIC) UNISTRUT OVERALL CABLE ROUTING PLAN HA-431924
(SEE DETAIL-1)
R Y
CABLE ROUTING PLAN HA-431925
R PH-CABLE B PH-CABLE B
500

Y PH-CABLE TREFOIL CLAMPS


(NON-MAGNETIC)

SOLE
X S E C T I O N
HA-431892
SCALE N.T.S
SEE DETAIL-2 SH 002

THE
1 D E T A I L
300 HA-431892
SCALE N.T.S
Y
SH -002
Y S E C T I O N
HA-431892

ARE
HA-431892
1500

SH 002 SCALE N.T.S


914 SH 002

N
VERTICAL SUPPORT

HEREI
STRUCTURE TREFOIL CABLE CLAMP
Y
VERTICAL SUPPORT
(NON-MEGNATIC)
STRUCTURE
X CONCRETE FLOOR.
3600

LINK BOX

NED
SCALE: N.T.S

CONTAI
914
HA-431892
SH 002 REVISION VALIDATION

0
0
5
THIS REVISION NO. 0F1 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION

2
BASE PLATE 115kV CABLE FROM 115kV CABLE FROM REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:
ANCHOR BOLT

R
TOP STACK (TYP)

ON
BOTTOM STACK (TYP) 10-10041-0002-001

NFORMATI
300 300
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
0 (DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)
8
5 ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE
1 CABLE CLAMP
R UNISTRUT SUPPORT RCM JRB KI JSA
(SEE DETAIL-1) 07/28/22 07/28/22
01/26/22 07/28/22
01/26/22 07/28/22
01/26/22

REV.NO. DATE REVISION DESCRIPTION


13.8KV 3-1/Cx400SQ.MM

I
0F1 07/28/22
01/26/22 RE-ISSUED FOR CONSTRUCTION

300
Cu. COND. XLPE CABLE

THE
JOB ORDER/EWO NO.
13.8kV, 3-1/Cx400SQ.MM THIS REVISION IS NOT TO BE USED FOR
CABLE ENTRY ROOM 10-10041-0002 CONSTRUCTION UNTIL CERTIFIED AND DATED
XLPE Cu. CABLE (TYP)
FINISHED FLOOR LEVEL
SAUDI ARABIAN OIL COMPANY

AND
CABLE ENTRY ROOM DRAWING TYPE
UNISTRUT
FINISHED FLOOR LEVEL
2 CABLE ROUTING PLAN & DETAILS CBL
SUPPORT D E T A I L HORIZONTAL SUPPORT

NG
HA-431892 STRUCTURE UPGRADE SS 6 & 40 POWER SUPP. SOURCE

DRAWI
SCALE N.T.S
SH -002

SUBSTATIONS ELEC.POWER & DIST.SYS.

TYPICAL ARRANGEMENT FOR 13.8kV OUTGOING FEEDERS DHAHRAN SAUDI ARABIA


TYPICAL ARRANGEMENT FOR 115kV OUTGOING FEEDERS

S
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
SCALE N.T.S SCALE N.T.S

208 P HA-431892 002 0F1


Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-01