lg2 Ds e 4 1 csm388
lg2 Ds e 4 1 csm388
lg2 Ds e 4 1 csm388
LG2 CSM_LG2_DS_E_4_1
Ordering Information
■ List of Models
Detected voltage Model
AC LG2-AB (100 VAC)
LG2-AB (200 VAC)
LG2-AB (110 VAC)
DC LG2-DB (12 VDC)
LG2-DB (24 VDC)
LG2-DB (48 VDC)
LG2-DB (100 VDC)
■ Connecting Socket
Socket Bracket
Type Model Model
Front-mounting socket PF083A PFC-A7
Back-mounting socket PL08 PLC-8
Note: Use the above sockets to mount the Voltage Sensor securely
and prevent problems, such as faulty contact.
1
LG2
Specifications
■ Ratings
Item Detected voltage Load Setting range Control output
Rated voltage Power/VA Must-operate Must-release Rated carry Switching capacity
consumption (SET) voltage (RESET) current Rated Rated operating current
(percentage voltage
of rated (percentage operating Resistive Inductive
voltage
value) of rated load load
value) (cosφ = 1) (cosφ = 0.4,
Model L/R = 7 ms)
LG2-AB 100 VAC 5 VA max. 75% to 120% 70% to 115% 5A 100 VAC 5A 3A
200 VAC 200 VAC 2A 1.2 A
50/60 Hz 28 VDC 5A 2A
110 VAC 80% to 110% 75% to 105% 110 VDC 0.2 A 0.1 A
50/60 Hz
LG2-DB 12 VDC 3 W max. 75% to 120% 70% to 115%
24 VDC
48 VDC
100 VDC
Note: 1. Set the must-operate voltage higher than the must-release voltage by at least 5% of the rated value.
2. Smoothing is required for the detected DC voltage.
3. The maximum applied voltage is 120% of the rated value.
4. Special models enabling a rated voltage of 220 V are available. The setting range for these models is 80% to 110%.
■ Characteristics
Repeat accuracy ±3% max. (with voltage fluctuations at the rate
of 1 V/s)
Variation due to ±5% max. (within the range 20 °C +20/−30 °C)
temperature
change
Operate time 0.5 s max. (when input changes from 0 V to
120% must-operate voltage)
Release time 0.5 s max. (when input changes from 120% of
the must-release voltage to 0 V)
Insulation 10 MΩ min. at 500 VDC (between electric
resistance circuitry and mounting panel)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between electric
circuitry and mounting panel)
Vibration Malfunction: 16.7 Hz, 1-mm double amplitude
Shock Destruction: 294 m/s2 (approx. 30 G)
Service life Mechanically:
10,000,000 operations min.
Electrically:
50,000 operations min. (at max. applicable
load)
Weight Approx. 100 g
Ambient −10 to 40°C (with no condensation)
operating
temperature
2
LG2
Connections
■ Terminal Arrangement
4 5 4 5
3 6 3 6
2 7 2 7
1 8
1 8
(+) (−)
The polarity indication for (The above diagram shows
terminals and applies the rear side of the Relay.)
to the DC model (LG2-DB).
(The above diagram shows
the rear side of the Relay.)
Note: 1. *Type LG2-DB is not equipped with the rectifier circuit.
2. With type LG2-DB, care should be taken to the polarity of
the power supply.
Nomenclature
LG2-DB
VOLTAGE SENSOR
Setting Method
Operate Value
Input the actual voltage to be set, and set the SET knob to the point
at which the Relay operates.
Release Value
• With the Relay operating, turn the RESET knob counterclockwise
as far as it will go, and adjust the voltage to the value to be set.
Then, gradually turn the RESET knob clockwise until it reaches the
point where the Relay is released.
Note: After completing the settings, check the settings for the operate
and release values by increasing/decreasing the input voltage.
• The LG2 can be used for undervoltage detection by using the
RESET knob for the operate value and the SET knob for the
release value. The Relay will normally be ON, however, and so the
internal temperature will rise, and this will affect the product service
life.
3
LG2
Dimensions
Note: All units are in millimeters unless otherwise indicated.
LG2-AB, LG2-DB
Mounting Height of
Sensor with Socket
50.5 max.
LG2 LG2
92.4
108.4
38.5 max. 86
13.6
(101)
16
35 max.
Approx. 20.5 (Top View)
15 25 10 25 25 10 25 15 (5)* 1
1,000 (500)*
* The dimensions given in parentheses are for the PFP-50N Socket Mounting Track.
In the interest of product improvement, specifications are subject to change without notice.
4
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
2014.1
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2014 All Right Reserved.