Instrument transformers –
Part 15: Additional requirements for voltage transformers for DC applications
Transformateurs de mesure –
Partie 15: Exigences supplémentaires concernant les transformateurs de
tension pour application en courant continu
IEC 61869-15:2018-07(en-fr)
THIS PUBLICATION IS COPYRIGHT PROTECTED
Copyright © 2018 IEC, Geneva, Switzerland
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form
or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from
either IEC or IEC's member National Committee in the country of the requester. If you have any questions about IEC
copyright or have an enquiry about obtaining additional rights to this publication, please contact the address below or
your local IEC member National Committee for further information.
Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite
ni utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie
et les microfilms, sans l'accord écrit de l'IEC ou du Comité national de l'IEC du pays du demandeur. Si vous avez des
questions sur le copyright de l'IEC ou si vous désirez obtenir des droits supplémentaires sur cette publication, utilisez
les coordonnées ci-après ou contactez le Comité national de l'IEC de votre pays de résidence.
A propos de l'IEC
La Commission Electrotechnique Internationale (IEC) est la première organisation mondiale qui élabore et publie des
Normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE colour
inside
Instrument transformers –
Part 15: Additional requirements for voltage transformers for DC applications
Transformateurs de mesure –
Partie 15: Exigences supplémentaires concernant les transformateurs de
tension pour application en courant continu
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
Warning! Make sure that you obtained this publication from an authorized distributor.
Attention! Veuillez vous assurer que vous avez obtenu cette publication via un distributeur agréé.
CONTENTS
FOREWORD ........................................................................................................................... 3
INTRODUCTION ..................................................................................................................... 6
1 Scope .............................................................................................................................. 8
2 Normative references ...................................................................................................... 8
3 Terms, definitions, abbreviated terms and symbols .......................................................... 8
5 Ratings .......................................................................................................................... 12
6 Design and construction ................................................................................................ 15
7 Tests ............................................................................................................................. 20
Annex 15A (informative) Proposed rated insulation level applicable to voltage
transformers for DC application............................................................................................. 34
Bibliography .......................................................................................................................... 35
INSTRUMENT TRANSFORMERS –
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as "IEC
Publication(s)"). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61869-15 has been prepared by IEC technical committee 38:
Instrument transformers.
Full information on the voting for the approval of this International Standard can be found in
the report on voting indicated in the above table.
This document has been drafted in accordance with the ISO/IEC Directives, Part 2.
–4– IEC 61869-15:2018 © IEC 2018
A list of all parts in the IEC 61869 series, published under the general title Instrument
transformers, can be found on the IEC website.
This Part 15 is to be used in conjunction with IEC 61869-1:2007, General Requirements, and
IEC 61869-6:2016, Additional general requirements for low-power instrument transformers –
however, the reader is encouraged to use the most recent edition.
This Part 15 follows the structure of IEC 61869-1:2007 and IEC 61869-6:2016 and
supplements or modifies their corresponding clauses.
When a subclause of Part 1 or Part 6 is not mentioned in this Part 15, that subclause applies.
When this standard states "addition", "modification" or "replacement", the relevant text in
Part 1 or Part 6 is to be adapted accordingly.
For additional clauses, subclauses, figures, tables, annexes or notes, the following numbering
system is used:
• clauses, subclauses, tables, figures and notes that are numbered starting from 1501 are
additional to those in Part 1 and Part 6;
• additional annexes are lettered 15A, 15B, etc.
An overview of the planned set of standards at the date of publication of this document is
given below. The updated list of standards issued by IEC TC 38 is available at the website:
www.iec.ch.
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under "http://webstore.iec.ch" in the data related to
the specific document. At this date, the document will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
IMPORTANT – The 'colour inside' logo on the cover page of this publication indicates
that it contains colours which are considered to be useful for the correct
understanding of its contents. Users should therefore print this document using a
colour printer.
–6– IEC 61869-15:2018 © IEC 2018
INTRODUCTION
Table 1501 gives an overview of the voltage waveshape as well as the main characteristics of
the VT.
Voltage Characteristics
Pure DC application
High-accuracy measurement
Harmonics measurement
Metering, control and protection purpose
IEC 61869-15:2018 © IEC 2018 –7–
The actual technology used for DCVT’s are resistive voltage dividers (with or without
additional capacitance). However, other technologies could be used in the future (for
example, optical voltage sensors).
This document includes some specific requirements applicable to resistive voltage dividers,
but can be applied to any technology.
–8– IEC 61869-15:2018 © IEC 2018
INSTRUMENT TRANSFORMERS –
1 Scope
This part of IEC 61869 provides all requirements specific to voltage transformers to be used
in DC applications (DCVTs), whatever the technology used. The output signal can be
analogue or digital.
This document covers passive voltage dividers as well as active voltage transformers, used
for measurement, control and protection.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their
content constitutes requirements of this document. For dated references, only the edition
cited applies. For undated references, the latest edition of the referenced document (including
any amendments) applies.
IEC TS 60815-4:2016, Selection and dimensioning of high-voltage insulators intended for use
in polluted conditions – Part 4: Insulators for DC systems
IEC TS 61245, Artificial pollution tests on high-voltage ceramic and glass insulators to be
used on DC systems
IEC 61869-6:2016, Instrument transformers – Part 6: Additional general requirements for low-
power instrument transformers
For the purposes of this document, the terms and definitions given in Clause 3 of IEC 61869-
1:2007, of IEC 61869-6:2016 and of IEC 61869-9:2016 are applicable with the following
additions and modifications.
ISO and IEC maintain terminological databases for use in standardization at the following
addresses:
IEC 61869-15:2018 © IEC 2018 –9–
3.1.1501
instrument transformer for DC application
instrument transformer intended to be used in DC applications with at least one of the
following functions:
3.1.1502
voltage transformer for DC application
DCVT
instrument transformer for DC application in which the secondary signal, under normal
conditions of use, is substantially proportional to the primary voltage
3.2.2
highest voltage for equipment
Um
Definition 3.2.2 of IEC 61869-1:2007 is replaced by the following one:
highest value of DC voltage for which the equipment is designed to operate continuously, in
respect of its insulation as well as other characteristics that relate to this voltage
3.3.1501
maximum peak fault current
I sc
maximum peak value of current occurring during a fault condition of the DC power system
3.4.1501
absolute error
εV
error (expressed in V) that a voltage transformer introduces into the measurement and which
arises from the fact that the actual transformation ratio is not equal to the rated transformation
ratio
εV = Kr ⋅ Us – Up
where
Kr is the rated transformation ratio;
Up is the DC value of the actual primary voltage in steady state;
Us is the DC value of the output voltage.
3.5.1501
step response
duration between the instant when the measurand (or quantity supplied) is subjected to a
specified abrupt change and the instant when the indication (or quantity supplied) reaches,
and remains within specified limits of, its final steady-state value
– 10 – IEC 61869-15:2018 © IEC 2018
3.5.1502
step response time
T sr
for a step response, the duration of the time interval between the instant of the step change of
an input variable and the instant when the output variable reaches for the first time a specified
percentage of the difference between the final and the initial steady-state values
Note 1 to entry: The step response time includes the delay time of the voltage transformer.
[SOURCE: IEC 60050-351:2013, 351-45-36 modified – Note 1 to entry of the source has been
deleted and a new Note 1 to entry has been added, and the symbol has been added.]
3.5.1503
settling time
Ts
for a step response, the duration of the time interval between the instant of the step change of
an input variable and the instant when the difference between the step response and their
steady-state value remains smaller than the transient value tolerance
Note 1 to entry: The settling time includes the delay time of the voltage transformer.
[SOURCE: IEC 60050-351:2013, 351-45-37 modified – Note 1 to entry of the source has been
deleted and a new Note 1 to entry has been added, and the symbol has been added.]
3.5.1504
overshoot
vm
for a step response of a transfer element, the maximum transient deviation from the final
steady-state value of the output variable, usually expressed in percent of the difference
between the final and the initial steady-state values and for reference-variable step response
or disturbance-variable step response of a control system the maximum transient deviation
from the desired value
[SOURCE: IEC 60050-351:2013, 351-45-38, modified – Note 1 to entry has been deleted and
the symbol has been replaced.]
ε ratio error
εV absolute error
5 Ratings
5.1 General
If applicable, the ratings of voltage transformers, including their auxiliary equipment, shall be
selected from the following ones:
The rating applies at the standardized reference atmosphere (temperature 20 °C, pressure
101,3 kPa, and humidity 11 g/m 3 ) as specified in IEC 60071-1.
NOTE The ratings are specified by the purchaser depending on the characteristics of the whole DC system
application.
5.3.1 General
The standard values of insulation level of IEC 60071-1 are not applicable to DC systems.
Methods of calculation for applied dielectric test voltages are given in the relevant clauses of
this document.
Additionally, indication for impulse withstand voltage values are given in Annex 15A.
IEC 61869-15:2018 © IEC 2018 – 13 –
The partial discharge level measured during the power-frequency voltage withstand test, shall
not exceed the limits specified in Table 3.
1,2 U m /√2 5 20
5 µs – 25 µs – 100 µs
5 V – 10V – 50 V
The accuracy class is designated by the highest permissible percentage of voltage error at
rated primary voltage and with the rated burden.
The ratio error for the DC component, measured at the secondary terminals, shall not exceed
the values given in Table 1502, expressed as a percentage of the measured voltage. A
graphical representation of error limits is shown in Figure 1503.
The accuracy shall be guaranteed for the whole range of temperature, both for the outdoor
and the indoor part of the voltage transformer and for both polarities.
For voltage lower than 5 % of the rated voltage, the absolute error ε V shall not increase above
the value at 5 % of the rated voltage.
NOTE The purpose of this requirement is to consider a minimum value of error due to offset voltage and noise.
This subclause is applicable for the measurement of the ripple of the DC voltage.
IEC 61869-15:2018 © IEC 2018 – 15 –
The standard values for the rated step response time are:
25 µs – 100 µs – 500 µs
6.6.1 Pollution
The purchaser shall specify the minimum creepage distance or the minimum USCD
(see IEC TS 60815-4:2016) or, alternatively, the DC site pollution severity.
The necessary creepage distance shall be determined from the USCD by:
USCD × U m
where USCD is the minimum nominal unified specific creepage distance (mm/kV), see
IEC 60050-471:2007, 471-01-16.
For indoor voltage transformers, the minimum USCD value shall be 14 mm/kV.
For outdoor voltage transformers, if artificial pollution tests are required, they shall be
performed in accordance with 7.4.1501.
NOTE Values for USCD for outdoor voltage transformers are considered in IEC TS 60815-4:2016. These values
are strongly dependent on the insulator material. Additional factors relating to the insulator profile and insulator
material are also specified.
The required static load that voltage transformers shall be able to withstand is given in
Table 7. The figures include loads due to wind and ice.
The specified test loads are intended to be applied in any direction at the level of the primary
terminals.
– 16 – IEC 61869-15:2018 © IEC 2018
The sum of the loads acting in routinely operating conditions should not exceed 50 % of the specified withstand
test load.
In some applications, voltage transformers with through current terminals should withstand rarely occurring
extreme dynamic loads (e.g. short circuits) not exceeding 1,4 times the static test load.
For some applications, it may be necessary to establish the resistance to rotation of the primary terminals. The
moment to be applied during the test is agreed between the manufacturer and the purchaser.
NOTE Requirements and tests relate to the behaviour of the internal shields and connections carrying high-
frequency transient currents. The test can also be applied to ratings below this level.
If additionally specified, the instrument transformer shall be able to withstand an internal arc
of the specified current and duration.
The applied current is a symmetrical sinusoidal current. The r.m.s. current value is
I sc /√2
It shall be considered that compliance with these requirements is achieved if the instrument
transformer passes the test described in 7.4.6. of IEC 61869-1:2007.
IEC 61869-15:2018 © IEC 2018 – 17 –
Protection Arc fault Internal arc fault protection Internal arc fault protection
stage duration class I class II
s
Fracture of the housing and fire No external effect other than the
1 0,2 permitted, but all projected parts to be operation of suitable pressure relief
confined within the containment area device
No fragmentation (burn-through or fire
2 0,5
acceptable)
The RIV requirement applies to voltage transformers having U m equal to or above 100 kV to
be installed in air-insulated substations.
During test with power-frequency voltage, the radio interference voltage shall not exceed
2 500 µV at 1,1 × U m / √ 2.
6.13 Markings
The primary terminals shall be marked clearly and indelibly, either on their surface or in their
immediate vicinity. If possible, the secondary terminals shall be identified clearly and
indelibly, either on the surface of the DCVT or in the immediate vicinity of the terminals.
Secondary terminals
Secondary terminals
Subclause 6.13 of IEC 61869-1:2007 and IEC 61869-6:2016 is replaced by the following one:
a) manufacturer’s name or other mark by which the manufacturer can be readily identified;
b) year of manufacture and a serial number or a type designation, preferably both;
c) highest voltage for equipment (U m );
d) insulation level;
e) rated primary voltage (U pr );
f) accuracy class;
When the instrument transformer is intended for both DC and AC measurements, the
accuracy for both applications shall be marked separately.
g) temperature category;
h) mass in kg (when ≥ 25 kg);
i) thermal class of insulation if different from Class A.
If several classes of insulating material are used, the one which limits the temperature rise
should be indicated.
The rating plate of all DCVTs, where practicable, shall be readable from ground level and
carry the markings given in Tables 1504 to 1506.
All information shall be marked in an indelible manner on a rating plate securely attached to
the transformer (at least the common rating plate) or to the secondary auxiliary cabinet for the
secondary converter and auxiliary power supply, if present.
6.602 Requirements for electrical transmitting system and electrical wires for output
link
6.602.1 Connectors
NOTE Digital interfaces for DC applications are still under development, and the full adequacy of IEC 61869-9
has still to be improved.
The capacitors shall comply with Subclause 6.1 of IEC 60815-1, regarding their individual
insulation level.
7 Tests
7.1 General
Tests Subclause
Type tests 7.2
Temperature rise test 7.2.2
Impulse voltage withstand test on primary terminals 7.2.3
Wet test for outdoor type transformers 7.2.4
Polarity reversal test with partial discharge measurement 7.2.1501
Electromagnetic compatibility tests 7.2.5
Test for accuracy 7.2.6
Test for accuracy versus harmonics 7.2.1502
Verification of the degree of protection by enclosures 7.2.7
Enclosure tightness test at ambient temperature 7.2.8
Pressure test for the enclosure 7.2.9
Low-voltage component voltage withstand test 7.2.601
Measurement of the step response time 7.2.1503
Routine tests 7.3
Power-frequency voltage withstand test on primary terminals 7.3.1
Partial discharge measurement 7.3.2
Power-frequency voltage withstand test between sections 7.3.3
DC applied voltage withstand test with partial discharge measurement 7.3.1501
Power-frequency voltage withstand test on secondary terminals 7.3.4
Test for accuracy 7.3.5
Verification of markings 7.3.6
Enclosure tightness test at ambient temperature 7.3.7
Pressure test for the enclosure 7.3.8
Power-frequency voltage withstand test for low-voltage components 7.3.601
Measurement of capacitance 7.3.1502
Measurement of resistance 7.3.1503
Special tests 7.4
Chopped impulse voltage withstand test on primary terminals 7.4.1
Multiple chopped impulse test on primary terminals 7.4.2
Transmitted overvoltage test 7.4.4
Mechanical tests 7.4.5
Internal arc fault test 7.4.6
Enclosure tightness test at low and high temperatures 7.4.7
Gas dew point test 7.4.8
Corrosion test 7.4.9
Fire hazard test 7.4.10
Pollution tests 7.4.1501
Vibration tests 7.2.602
Test for accuracy on the composite signal 7.4.1502
Ageing test for R and C components 7.4.1503
– 22 – IEC 61869-15:2018 © IEC 2018
The sequence of tests is not specified and may be agreed between the purchaser and the
supplier.
Before starting the type test sequence, the following routine tests shall be performed:
After the type test sequence, the voltage transformer shall be subjected to all routine tests
detailed in 7.3.
The DC applied voltage test may be performed before the polarity reversal test. In this case, it
does not need to be repeated after the type test sequence.
The sequence of tests is not specified, but the accuracy tests shall be performed after the
dielectric tests.
7.2.1 General
Type tests on DCVTs are considered as valid if they have been performed on a device of
comparable design, with similar specific design stresses. Evidence shall to be provided by the
manufacturer.
The second and third paragraphs are replaced by the following ones:
For the temperature rise test, the following test methods may be used for temperature
measurement:
• for gas-insulated equipment: infrared camera and gas pressure variation measurements;
• for oil-insulated equipment: infrared camera measurement.
The voltage to be applied is the highest voltage for the equipment (U m ). The test shall be
continued until the temperature of the transformer has reached the steady-state temperature.
For voltage transformers having U m equal to or above 100 kV, the test shall be performed with
switching impulse voltage test of both polarities, with the voltage corresponding to the
insulation level.
For voltage transformers having U m < 100 kV, the test shall be performed with power-
frequency voltage defined in 7.3.1.
The voltage shall then be decreased to 1,1 × U m / √ 2 in about 10 s and maintained at this
value for 30 s before measuring the radio interference voltage.
The voltage transformer shall be considered to have passed the test if the radio interference
level at 1,1 × U m / √ 2 is in accordance with 6.11.2.
7.2.6.1501 General
Test circuits are given in Annex 6D of IEC 61869-6:2016 for analogue outputs and Annex 9D
of IEC 61869-9:2016 for digital outputs.
To prove compliance with the specified accuracy class, the test shall be made at each value
of voltage given in Table 1502, at rated burden, and at ambient temperature, unless otherwise
specified.
In a first step, the accuracy shall be measured in a short time (less than 0,05 times the
thermal time constant), at ambient temperature, with increasing voltages.
– 24 – IEC 61869-15:2018 © IEC 2018
Then the voltage is reduced to U pr and maintained up to the thermal stabilization. The
accuracy is measured and the accuracy variation at U pr is determined.
From this result, the accuracy variation at intermediate voltages and maximum voltage
(125 %) is estimated according to the thermal characteristics of the resistors.
The errors shall be within the limits of the relevant accuracy class, both at the time the test
voltage is applied and after the correction of the accuracy variation.
The accuracy variations shall be noted on the type test report, as a characteristic of the
voltage divider.
The stability is considered after a period of 3 times the time constant, which shall be defined
by the supplier.
For primary voltage equal to zero, the measured absolute error shall not exceed the value of
the absolute error allowed at 0,05 × U pr .
NOTE This test can be performed together with the temperature-rise test.
For analogue output with rated delay time, it is not necessary to insert a delay time device
between the reference transformer and the accuracy measurement system.
Subclause 7.2.6 of IEC 61869-9:2016 is applicable with replacement of the two last
paragraphs by the following ones:
Accuracy tests shall be performed over a minimum period, during which several
measurements shall be averaged. The details of the test arrangement and timing and/or
bandwidth of the test system shall be provided in the accuracy test report.
A low-voltage component of a DCVT is the low voltage part of RC-dividers or R-dividers when
placed outside the main housing, as shown in Figure 1504.
IEC 61869-15:2018 © IEC 2018 – 25 –
Figure 1504 – RC divider with low-voltage part outside the main housing
To test this external secondary part, five positive and five negative lightning impulses 1,2/50
μs with the test value in accordance with 5.3.5 of IEC 61869-6:2016 shall be applied as
shown in Figure 1505. The voltage limitation device shall be disconnected. This test verifies
the voltage withstand of the complete external low voltage part to earth.
Connection to be open
Enclosure
during the voltage test
If not otherwise specified, this test is not applicable to DCVTs for VSC applications.
During the test, the ambient temperature shall be between 10 °C and 40 °C. Before the test,
the device shall be at ambient temperature.
No preconditioning of the insulation at lower voltage is permitted. After the DC applied voltage
withstand test, the voltage transformer shall normally be earthed and completely discharged
before the polarity reversal test is initiated. The time duration required for a complete
discharge shall be agreed between the parties depending on the type of voltage transformer
and shall be sufficient to avoid any undue influence of the trapped charges on the results of
this test.
However, to save time during routine tests and upon agreement between the parties, the
polarity reversal test may be initiated at any time after the DC applied voltage withstand test.
The time for the polarity reversal shall be as short as possible, consistent with the testing
equipment, but never more than 2 min. The polarity reversal is considered as complete when
the voltage has reached 100 % of the test value. The partial discharge levels shall be
monitored during the entire test sequence.
U rp = 1,25 × U m
The voltage transformer shall be considered to have passed the test if the following conditions
are met:
• No more than 10 pulses of partial discharge with a magnitude equal to or greater than
2 000 pC are recorded during the last 30 min of the test time. Pulses that are proven to be
external to the test object shall be disregarded.
• No disruptive discharges on the non-self-restoring insulation shall occur. If there is an
internal breakdown, the voltage transformer shall be considered to have failed the test. It
is assumed that an internal breakdown has occurred if the value of the resistance and the
– 28 – IEC 61869-15:2018 © IEC 2018
capacitance of the HV part, measured after the test, differ from the values measured
before the test by more than 2 %. If a flashover occurs, the test shall be repeated once
only. If, during the repetition of the test, no flashover or internal breakdown occurs, the
voltage transformer shall be considered to have passed the test.
The test shall be performed on the voltage transformer completely assembled. The step
response test shall be performed with the rated burden and the original transmission cable, if
they exist.
The primary test voltage should be the rated primary voltage and represents an impulse
voltage characteristic with an accuracy of ±3 %. The step voltage can be generated by an
impulse voltage generator. In case of difficulties in generating the primary signal with the
specified rise time, the test procedure may be adapted, using a reduced input voltage signal,
provided that the linearity of the system is proven, and the secondary signal level permits an
accurate measurement.
The front time corresponds to the definitions of lightning impulse definition with a front time of
1,2 μs, with a relative tolerance of ±30 %.
The time to half value corresponds to the definitions of switching impulse definition with a time
to half value of 2 500 μs, with a relative tolerance of ±60 %.
The test shall be performed one time for each polarity. Each test shall be recorded with the
reference curve together with the step response curve of the test object.
The primary voltage is measured with a reference divider. The output of the reference divider
and the output voltage of the DCVT is measured with a transient recorder (see Figure 1507).
The tolerance limit ∆V s is defined as 5 % of the steady-state value of the output signal V∞ .
NOTE A reduced tolerance limit can be defined by agreement between the purchaser and the manufacturer.
The voltage transformer shall be considered to have passed the test if:
• the measured step response time T sr is lower than the rated step response time;
• the settling time T s is less than 10 times the rated step response time T sr .
IEC 61869-15:2018 © IEC 2018 – 29 –
Key:
u(t) Input voltage
v(t) Output voltage of test object
a For periodic behaviour
b For aperiodic behaviour
The power-frequency withstand test shall be performed in accordance with IEC 60060-1.
U AC = 1,5/√2 × U m
NOTE In some special applications (example: some neutral voltage measurement applications), the specified test
voltage can be insufficient.
The test voltage shall be applied between the primary terminal and the earth.
– 30 – IEC 61869-15:2018 © IEC 2018
The frame and the case (if any) shall be connected to earth.
When there is an internal galvanic link between the secondary terminal "n" and ground, this
test is required only as a type test. In this case, the connection between the secondary
terminal "n" and ground shall be opened for the test.
The routine tests for accuracy are in principle the same as the type tests in 7.2.6. The
accuracy shall be measured in a short time (less than 0,05 times the thermal time constant),
at ambient temperature. The accuracy measurement shall be adjusted with the corrections
defined during the type test.
This method is applicable for a passive voltage divider. The resistances of the high and low
voltage part of the voltage transformer shall be determined at low voltage with a precision
resistance-measurement device.
The measurement of the low-voltage part shall include the transmitting cable.
The measurement of the resistance values shall be performed for both the positive and
negative polarities of the measuring equipment source and the resistance shall be taken as
the average value of these two measurements.
The resistance values shall be measured before and after the high-voltage tests.
The maximum resistance variation between the voltage measurements shall not be more than
0,2 times the limit of ratio error at U pr corresponding to the accuracy class.
For the calculation of the divider ratio of the DCVT, the resistance values based on the
measurements after the high-voltage tests shall be used.
Recommended test voltages for resistance measurement of the HV and LV arm are as
follows:
< 100 kΩ < 100 MΩ < 300 MΩ < 400 MΩ < 700 MΩ
U test > 10 V DC U test > 100 V DC U test > 200 V DC U test > 250 V DC U test > 280 V DC
IEC 61869-15:2018 © IEC 2018 – 31 –
During the test, the temperature of the voltage transformer shall be between 10 °C and 40 °C.
No preconditioning of the voltage transformer at a lower voltage level is permitted and the DC
voltage shall be raised to the test level within a period not exceeding 1 min. The DC voltage
shall then be held for 1 h, after which the voltage shall be reduced to zero within a period not
exceeding 1 min. Positive polarity shall be used.
U DC = 1,5 × U m
The voltage transformer shall be considered to have passed the test if the following conditions
are met:
• No more than 10 pulses of partial discharge with a magnitude equal to or greater than
2 000 pC are recorded during the last 30 min of the test. Pulses that are proven to be
external to the test object shall be disregarded. If this condition is not met, then the test
may be extended for 30 min, with the same criteria applying. Only one 30-min extension is
allowed.
• No disruptive discharges on non-self-restoring insulation shall occur. If there is an internal
breakdown, the voltage transformer shall be considered to have failed the test. It is
assumed that an internal breakdown has occurred if the value of the resistance and the
capacitance of the HV part, measured after the test, differ from the values previously
measured by more than 2 %. If a flashover occurs, the test shall be repeated once only. If,
during the repetition of the test, no flashover or puncture occurs, the voltage transformer
shall be considered to have passed the test.
The capacitance shall be measured using a method that excludes errors due to harmonics
and to accessories in the measuring circuit.
For DCVTs, the resistance R 1 of the primary part shall be measured with a voltage > 100 V
DC before and after the dielectric tests.
The resistance of the secondary part R 2 shall be measured before and after the dielectric
tests. The DC test voltage shall have at least the same value as the rated secondary voltage,
but not be higher than twice the rated secondary voltage.
This test may be replaced by the accuracy measurement in accordance with 7.3.5.1502.
The test shall be carried out with negative polarity only and combined with the negative
polarity lightning impulse test in the manner described below.
The voltage shall be a standard lightning impulse as defined in IEC 60060-1, chopped
between 2 µs and 5 µs. The chopping circuit shall be so arranged that the amount of
overswing of opposite polarity of the recorded impulse shall be limited to approximately 30 %
of the peak value.
The test voltage of the full impulse shall be in accordance with the rated lightning impulse
withstand voltage.
The chopped impulse test voltage shall be in accordance with 5.3.3.2 of IEC 61869-1:2007.
After the test, the voltage transformer shall pass successfully the test for accuracy in
accordance with 7.3.5.
The test is applicable to voltage transformers having U m equal to or above 100 kV.
An artificial pollution test may be applied to voltage transformers having porcelain insulators
to be used outdoors and exposed to polluted atmospheres.
If a test is deemed necessary, the specific test method to be applied and the degree of
pollution severity shall be specified or agreed upon between the purchaser and the
manufacturer at the time of ordering. Proposals for artificial pollution test methods are
described in IEC TS 61245.
NOTE The reproducibility of artificial pollution tests on insulators, with weather sheds of silicon rubber, performed
in different laboratories has not been established in a manner consistent with other standardized tests. However,
further guidance will become available as research continues and when appropriate inter-laboratory comparisons
are made. The problem is under consideration by the IEC.
The DC withstand test voltage shall be specified. In general, it coincides with the highest
voltage for equipment. The tests are usually carried out at negative polarity.
The even-wetting test may be applied to all outdoor voltage transformers having U m equal to
or above 100 kV.
IEC 61869-15:2018 © IEC 2018 – 33 –
The standard even-wetting test procedure described in IEC 60060-1 shall be used, except for
the test duration.
Rain with different characteristics representing very light or light conductive layers on the
insulator surface or having different precipitation rates may be agreed between the
manufacturer and the purchaser. The rain precipitation shall be adjusted before starting the
test.
The test voltage to be applied to the voltage transformer shall be equal to 1,25 U m .
The voltage transformer shall be considered to have passed the test if no flashover or
puncture occurs. If there is a puncture, the voltage transformer shall be considered to have
failed the test. If a flashover occurs, the test shall be repeated once only, after verifying the
rain conditions. The voltage transformer shall be considered to have passed the test if no
further flashover or puncture occurs.
The purpose of the test is to measure the accuracy on the DC component and on harmonic
components, when supplied simultaneously.
The accuracy on the DC voltage component shall comply with the specifications of 5.6.1503,
while pure sinusoidal harmonic components are supplied (one at a time) to the primary side.
The 5-kV voltage components shall be supplied with the following frequencies:
• for low-bandwidth DC applications: 100 Hz, 500 Hz, 1kHz, 1,5 kHz, 3 kHz;
• for high-bandwidth DC applications: 100 Hz, 2,5 kHz, 5 kHz, 7,5 kHz, 10 kHz, 15 kHz,
20 kHz.
The accuracy of the AC voltage components shall comply with the specifications of Annex 6A
of IEC 61869-6:2016, while the rated DC primary voltage is supplied to the primary side.
This test is intended to prove that the voltage divider accuracy is not influenced by ageing.
This test shall be performed on three samples of resistance elements and a capacitor
element. It consists of five cycles as follows:
After five cycles, the values shall be measured and the maximum variation shall be less than
5 % for the capacitor, and less than the maximum error corresponding to the accuracy class
for the resistor.
– 34 – IEC 61869-15:2018 © IEC 2018
Annex 15A
(informative)
Insulation coordination for HVDC systems is currently under consideration by the IEC.
However, instrument transformer manufacturers need references for the design and testing of
their devices.
For AC and DC applied dielectric tests, test voltage is defined in 7.2 and 7.3.
The present annex proposes a test voltage for impulse tests, based on generally adopted
system voltages and test voltages. These are indicative values, and system designers could
be forced to define other insulation levels, based on specific insulation coordination
conditions.
For a system voltage below 200 kV, too many applications exist and it is not possible to
define any standard values. Insulation levels shall be defined by the system designer.
After publication of the rated system voltages and rated insulation levels, the present annex
will be disregarded.
Rated system voltage Highest voltage for Rated lightning impulse Rated switching
equipment Um withstand voltage (peak) withstand voltage (peak)
kV kV kV kV
200 210 500 390
250 262 750 650
320 336 900 650
750 612
a
660 -- a
400 412 1 175 950
a a
790 760
500 515 1 425 1 175
a
1 300 1 360 a
600 617 1 650 1 280
2 100 1 675
800 816 1 950 1 600
2 300 1 800
1 100 1 120 2 300 2 100
a cable connection
IEC 61869-15:2018 © IEC 2018 – 35 –
Bibliography
IEC 60358-1:2012, Coupling capacitors and capacitor dividers – Part 1: General rules
___________
– 36 – IEC 61869-15:2018 © IEC 2018
SOMMAIRE
AVANT-PROPOS .................................................................................................................. 37
INTRODUCTION ................................................................................................................... 41
1 Domaine d'application ................................................................................................... 43
2 Références normatives .................................................................................................. 43
3 Termes, définitions, termes abrégés et symboles .......................................................... 43
5 Caractéristiques assignées ............................................................................................ 47
6 Conception et construction ............................................................................................ 50
7 Essais ........................................................................................................................... 55
Annexe 15A (informative) Proposition de niveau d'isolement assigné applicable aux
transformateurs de tension pour courant continu ................................................................... 70
Bibliographie ......................................................................................................................... 71
Tableau 1501 – Tension sur les transformateurs de tension à courant continu ...................... 42
Tableau 3 – Tensions d'essai de décharge partielle et niveaux admissibles .......................... 48
Tableau 1502 – Limites de l'erreur de rapport des transformateurs de tension à
courant continu (classes de 0,1 à 3) ..................................................................................... 49
Tableau 7 – Charges d'essai de tenue statique ..................................................................... 51
Tableau 8 – Durée de défaut d'arc et critères de performance .............................................. 52
Tableau 1503 – Marquage des bornes .................................................................................. 53
Tableau 1504 – Marquage de plaque signalétique – plaque signalétique commune .............. 54
Tableau 1505 – Marquage de plaque signalétique pour chaque convertisseur
secondaire ............................................................................................................................ 54
Tableau 1506 – Marquage de plaque signalétique pour alimentation auxiliaire ...................... 55
Tableau 10 – Liste des essais ............................................................................................... 56
Tableau 15A.1 – Propositions de niveaux assignés d'isolement des bornes primaires
pour les transformateurs de tension pour courant continu ..................................................... 70
IEC 61869-15:2018 © IEC 2018 – 37 –
TRANSFORMATEURS DE MESURE –
AVANT-PROPOS
1) La Commission Electrotechnique Internationale (IEC) est une organisation mondiale de normalisation
composée de l'ensemble des comités électrotechniques nationaux (Comités nationaux de l’IEC). L’IEC a pour
objet de favoriser la coopération internationale pour toutes les questions de normalisation dans les domaines
de l'électricité et de l'électronique. A cet effet, l’IEC – entre autres activités – publie des Normes
internationales, des Spécifications techniques, des Rapports techniques, des Spécifications accessibles au
public (PAS) et des Guides (ci-après dénommés "Publication(s) de l’IEC"). Leur élaboration est confiée à des
comités d'études, aux travaux desquels tout Comité national intéressé par le sujet traité peut participer. Les
organisations internationales, gouvernementales et non gouvernementales, en liaison avec l’IEC, participent
également aux travaux. L’IEC collabore étroitement avec l'Organisation Internationale de Normalisation (ISO),
selon des conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de l’IEC concernant les questions techniques représentent, dans la mesure
du possible, un accord international sur les sujets étudiés, étant donné que les Comités nationaux de l’IEC
intéressés sont représentés dans chaque comité d’études.
3) Les Publications de l’IEC se présentent sous la forme de recommandations internationales et sont agréées
comme telles par les Comités nationaux de l’IEC. Tous les efforts raisonnables sont entrepris afin que l’IEC
s'assure de l'exactitude du contenu technique de ses publications; l’IEC ne peut pas être tenue responsable de
l'éventuelle mauvaise utilisation ou interprétation qui en est faite par un quelconque utilisateur final.
4) Dans le but d'encourager l'uniformité internationale, les Comités nationaux de l’IEC s'engagent, dans toute la
mesure possible, à appliquer de façon transparente les Publications de l’IEC dans leurs publications nationales
et régionales. Toutes divergences entre toutes Publications de l’IEC et toutes publications nationales ou
régionales correspondantes doivent être indiquées en termes clairs dans ces dernières.
5) L’IEC elle-même ne fournit aucune attestation de conformité. Des organismes de certification indépendants
fournissent des services d'évaluation de conformité et, dans certains secteurs, accèdent aux marques de
conformité de l’IEC. L’IEC n'est responsable d'aucun des services effectués par les organismes de certification
indépendants.
6) Tous les utilisateurs doivent s'assurer qu'ils sont en possession de la dernière édition de cette publication.
7) Aucune responsabilité ne doit être imputée à l’IEC, à ses administrateurs, employés, auxiliaires ou
mandataires, y compris ses experts particuliers et les membres de ses comités d'études et des Comités
nationaux de l’IEC, pour tout préjudice causé en cas de dommages corporels et matériels, ou de tout autre
dommage de quelque nature que ce soit, directe ou indirecte, ou pour supporter les coûts (y compris les frais
de justice) et les dépenses découlant de la publication ou de l'utilisation de cette Publication de l’IEC ou de
toute autre Publication de l’IEC, ou au crédit qui lui est accordé.
8) L'attention est attirée sur les références normatives citées dans cette publication. L'utilisation de publications
référencées est obligatoire pour une application correcte de la présente publication.
9) L’attention est attirée sur le fait que certains des éléments de la présente Publication de l’IEC peuvent faire
l’objet de droits de brevet. L’IEC ne saurait être tenue pour responsable de ne pas avoir identifié de tels droits
de brevets et de ne pas avoir signalé leur existence.
La Norme internationale IEC 61869-15 a été établie par le comité d'études 38 de l'IEC:
Transformateurs de mesure.
Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à l'approbation de cette Norme internationale.
Une liste de toutes les parties de la série IEC 61869, publiées sous le titre général
Transformateurs de mesure, peut être consultée sur le site web de l'IEC.
La présente Partie 15 doit être utilisée conjointement avec l'IEC 61869-1:2007, Exigences
générales, et l'IEC 61869-6:2016, Exigences générales supplémentaires concernant les
transformateurs de mesure de faible puissance. Le lecteur est toutefois encouragé à utiliser
l'édition la plus récente.
• les articles, paragraphes, tableaux, figures et notes numérotés à partir de 1501 s'ajoutent
à ceux de la Partie 1 et de la Partie 6;
• les annexes supplémentaires sont numérotées 15A, 15B, etc.
Le comité a décidé que le contenu de ce document ne sera pas modifié avant la date de
stabilité indiquée sur le site web de l’IEC sous "http://webstore.iec.ch" dans les données
relatives au document recherché. A cette date, le document sera
• reconduit,
• supprimé,
• remplacé par une édition révisée, ou
• amendé.
INTRODUCTION
Le présent document s'applique aux transformateurs de tension destinés à être utilisés dans
les applications en courant continu comportant les fonctions suivantes:
• Les convertisseurs commutés par le réseau (LCC) sont basés sur les convertisseurs à
thyristor. Ils se caractérisent par un flux de courant unidirectionnel et la possibilité
d'inverser la polarité de la tension. Des harmoniques de tension et de courant élevées
existent jusqu'à des fréquences d'environ 3 kHz à 4 kHz.
• Les convertisseurs de source de tension (VSC) sont basés sur les convertisseurs à
transistor. Ils se caractérisent par un flux de courant bidirectionnel et une polarité de
tension unique. Des harmoniques de tension et de courant élevées existent jusqu'à des
fréquences d'environ 20 kHz.
Le Tableau 1501 donne une vue d'ensemble de la forme d'onde de la tension, ainsi que des
principales caractéristiques du transformateur de tension.
– 42 – IEC 61869-15:2018 © IEC 2018
Tension Caractéristiques
Applications en courant continu pur
Mesure d'une grande précision
Mesure des harmoniques
Utilisé à des fins de mesure, de commande et de
protection
TRANSFORMATEURS DE MESURE –
1 Domaine d'application
La présente partie de l'IEC 61869 couvre toutes les exigences particulières concernant les
transformateurs de tension utilisés dans les applications en courant continu, quelle que soit la
technologie utilisée. Le signal de sortie peut être analogique ou numérique.
Elle s'applique aux transformateurs de tension fabriqués récemment et utilisés pour des
applications de mesure, de protection et/ou de commande sur des systèmes d'alimentation
électrique en courant continu dont la tension assignée est supérieure à 1,5 kV.
Le présent document couvre les diviseurs de tension passifs et les transformateurs de tension
actifs utilisés à des fins de mesure, de commande et de protection.
2 Références normatives
Les documents suivants cités dans le texte constituent, pour tout ou partie de leur contenu,
des exigences du présent document. Pour les références datées, seule l’édition citée
s’applique. Pour les références non datées, la dernière édition du document de référence
s'applique (y compris les éventuels amendements).
IEC TS 60815-4:2016, Selection and dimensioning of high-voltage insulators intended for use
in polluted conditions – Part 4: Insulators for DC systems (disponible en anglais seulement)
IEC TS 61245, Artificial pollution tests on high-voltage ceramic and glass insulators to be
used on DC systems (disponible en anglais seulement)
Pour les besoins du présent document, les termes et les définitions de L'Article 3 de
l'IEC 61869-1:2007, de l'IEC 61869-6:2016 et de l'IEC 61869-9:2016 s'appliquent, avec les
ajouts et modifications suivants.
L'ISO et l'IEC tiennent à jour des bases de données terminologiques destinées à être utilisées
en normalisation, consultables aux adresses suivantes:
– 44 – IEC 61869-15:2018 © IEC 2018
3.1.1501
transformateur de mesure pour application en courant continu
transformateur de mesure destiné à être utilisé dans les applications en courant continu
comportant au moins l'une des fonctions suivantes:
3.1.1502
transformateur de tension pour application en courant continu
DCVT
transformateur de mesure pour application en courant continu dans lequel le signal
secondaire, dans des conditions normales d'utilisation, est sensiblement proportionnel à la
tension primaire
3.2.2
tension la plus élevée pour le matériel
Um
La définition 3.2.2 de l'IEC 61869-1:2007 est remplacée par la définition suivante:
3.3.1501
courant de crête maximal de défaut
I sc
valeur de crête maximale du courant observée au cours d'une condition de défaut du système
électrique à courant continu
3.4.1501
erreur absolue
εV
erreur (exprimée en V) introduite dans la mesure par un transformateur de tension et qui
découle du fait que le rapport de transformation réel n'est pas égal au rapport de
transformation assigné
εV = Kr ⋅ Us – Up
où
Kr est le rapport de transformation assigné;
Up est la valeur en courant continu de la tension primaire réelle en régime établi;
Us est la valeur en courant continu de la tension de sortie.
IEC 61869-15:2018 © IEC 2018 – 45 –
3.5.1501
réponse à un échelon
durée comprise entre l’instant où le mesurande (ou la grandeur fournie) subit un changement
brusque spécifié et l’instant où l'indication (ou la grandeur fournie) atteint, et se maintient
dans une plage de limites spécifiées autour de sa valeur finale, en régime établi
vm taux de dépassement
3.5.1502
temps de réponse à un échelon
T sr
pour une réponse à un échelon, durée de l'intervalle de temps compris entre l'instant où une
variation en échelon est appliquée à une variable d'entrée, et l'instant où la variable de sortie
atteint pour la première fois un pourcentage spécifié de la différence entre ses valeurs finale
et initiale de régime établi
Note 1 à l'article: Le temps de réponse à un échelon inclut le temps de retard du transformateur de tension.
3.5.1503
durée d'établissement
Ts
pour une réponse à un échelon, durée de l'intervalle de temps compris entre l'instant où une
variation en échelon est appliquée à une variable d'entrée, et l'instant où la différence entre la
réponse à un échelon et sa valeur en régime établi se maintient à un niveau inférieur à la
tolérance de la valeur transitoire
3.5.1504
taux de dépassement
vm
pour une réponse à un échelon d’un élément de transfert, l'écart transitoire maximal par
rapport à la valeur de régime établi final de la variable de sortie, habituellement exprimé en
pourcentage de la différence entre les valeurs finale et initiale de régime établi; pour la
réponse à un échelon de la variable de référence ou pour la réponse à un échelon de la
variable perturbatrice d’un système de commande, l'écart transitoire maximal par rapport à la
valeur souhaitée
5 Caractéristiques assignées
5.1 Généralités
Le cas échéant, les caractéristiques assignées des DCVT, y compris celles de leur
équipement auxiliaire, doivent être choisies dans la liste suivante::
NOTE Les caractéristiques assignées sont définies par l'acheteur en fonction des caractéristiques de l’application
de l'ensemble du système à courant continu.
5.3.1 Généralités
Les valeurs standards de niveaux d'isolement de la CEI 60071-1 ne sont pas applicables aux
systèmes à courant continu.
– 48 – IEC 61869-15:2018 © IEC 2018
Des méthodes permettant de calculer les tensions d'essai diélectrique sont présentées dans
les articles correspondants du présent document.
En outre, des indications concernant les valeurs de tension de tenue aux chocs sont données
en Annexe 15A.
1,2 U m /√2 5 20
5 µs – 25 µs – 100 µs
Dans le cas d'un transformateur de tension à courant continu purement passif, le temps de
retard assigné est nul.
5 V – 10V – 50 V
IEC 61869-15:2018 © IEC 2018 – 49 –
La classe de précision est désignée par le pourcentage d'erreur de tension le plus élevé
admis pour la tension primaire assignée et avec la charge assignée. Une représentation
graphique des limites d'erreur est présentée à la Figure 1503.
L'erreur de rapport pour la composante continue, mesurée au niveau des bornes secondaires,
ne doit pas dépasser les valeurs données dans le Tableau 1502, exprimées en pourcentage
de la tension mesurée.
La précision doit être garantie pour l'ensemble de la gamme de températures, pour les parties
du transformateur de tension situées en extérieur et en intérieur et pour les deux polarités.
Pour une tension inférieure à 5 % de la tension assignée, l'erreur absolue ε V ne doit pas
augmenter au-delà de la valeur existant à 5 % de la tension assignée.
NOTE Cette exigence doit permettre de prendre en compte une valeur d'erreur minimale due à la tension de
décalage et au bruit.
– 50 – IEC 61869-15:2018 © IEC 2018
25 µs – 100 µs – 500 µs
6 Conception et construction
6.6.1 Pollution
Le présent paragraphe s'applique aux transformateurs de tension dont la valeur U m est égale
ou supérieure à 20 kV.
La ligne de fuite nécessaire doit être déterminée à partir de la ligne de fuite spécifique unifiée
à l'aide de la formule suivante:
USCD × U m
IEC 61869-15:2018 © IEC 2018 – 51 –
où USCD est la ligne de fuite spécifique unifiée nominale minimale (mm/kV), voir IEC 60050-
471:2007, 471-01-16.
Pour les transformateurs de tension pour l'intérieur, la valeur de ligne de fuite spécifique
unifiée minimale doit être de 14 mm/kV.
Pour les transformateurs de tension pour l'extérieur, si des essais de pollution artificielle sont
exigés, ils doivent être réalisés conformément au 7.4.1501.
NOTE Les valeurs de ligne de fuite spécifique unifiée pour les transformateurs de tension pour l'extérieur sont
traitées dans l'IEC TS 60815-4:2016. Ces valeurs sont fortement dépendantes du matériau de l'isolateur. D'autres
facteurs relatifs au profil et au matériau de l'isolateur sont également spécifiés.
La charge statique exigée à laquelle les transformateurs de tension doivent pouvoir résister
est indiquée dans le Tableau 7. Les figures incluent les charges dues au vent et à la glace.
Les charges d'essai spécifiées sont destinées à être appliquées dans n'importe quelle
direction au niveau des bornes primaires.
Il convient que la somme des charges qui agissent dans des conditions d'exploitation habituelles n'excède pas
50 % de la charge d'essai de tenue spécifiée.
Dans certaines applications, il convient que les transformateurs de tension équipés de bornes à courants
traversants supportent des charges dynamiques extrêmes rares (par exemple, des courts-circuits) qui
n'excèdent pas 1,4 fois la charge d'essai statique.
Pour certaines applications, il peut être nécessaire d'établir la résistance à la rotation des bornes primaires. Le
moment à appliquer pendant l'essai est convenu entre le fabricant et l'acheteur.
Si cela est spécifié en complément, les bornes primaires des transformateurs de tension
immergés dans l'huile dont la valeur U m est égale ou supérieure à 100 kV doivent résister aux
chocs coupés multiples conformément au 7.4.2 de l'IEC 61869-1:2007.
NOTE Les exigences et les essais sont relatives au comportement des écrans internes et des raccordements
transportant des courants transitoires à haute fréquence. L'essai peut également être appliqué aux caractéristiques
assignées inférieures à ce niveau.
Si cela est spécifié en complément, le transformateur de mesure doit pouvoir résister à un arc
interne dont le courant et la durée ont été spécifiés.
Le courant appliqué est un courant sinusoïdal symétrique. La valeur efficace du courant est la
suivante:
I sc /√2
La conformité à ces exigences doit être considérée comme respectée si l'essai décrit en 7.4.6
de l'IEC 61869-1:2007 est validé par le transformateur de mesure.
Etape de la Durée de Protection de défaut d'arc interne de Protection de défaut d'arc interne
protection défaut d'arc classe I de classe II
s
Rupture de l'enveloppe et feu Aucun effet externe autre que le
1 0,2 autorisés, mais toutes les parties fonctionnement du dispositif limiteur
projetées à maintenir dans la zone de de pression approprié
confinement
Aucune fragmentation (enveloppe
2 0,5
percée ou incendie acceptable)
NOTE Cette exigence est introduite pour satisfaire à certaines réglementations en matière de compatibilité
électromagnétique.
6.13 Marquages
Les bornes primaires doivent être marquées de façon claire et indélébile, sur leur surface ou
à proximité immédiate. Si possible, les bornes secondaires doivent être identifiées de façon
claire et indélébile sur la surface du transformateur de tension à courant continu ou à
proximité immédiate des bornes.
IEC 61869-15:2018 © IEC 2018 – 53 –
Bornes secondaires
Bornes secondaires
Tous les transformateurs de tension doivent comporter au moins les marquages suivants:
a) nom du fabricant ou toute autre marque qui peut être facilement identifiée;
b) année de fabrication et numéro de série ou désignation type, de préférence les deux;
c) tension la plus élevée pour le matériel (U m );
d) niveau d'isolement;
e) tension primaire assignée (U pr );
f) classe de précision;
g) catégorie de température;
h) masse en kg (lorsque ≥ 25 kg);
i) classe thermique d'isolation si différente de la Classe A.
Si plusieurs classes de matériaux d'isolation sont utilisées, il convient que celle qui limite
l'échauffement soit indiquée.
Pour une sortie secondaire analogique, les informations suivantes doivent être fournies:
Toutes les informations doivent être indiquées de manière indélébile sur une plaque
signalétique fixée solidement sur le transformateur (au moins pour la plaque signalétique
commune) ou sur l'armoire auxiliaire secondaire du convertisseur secondaire et de
l'alimentation auxiliaire, le cas échéant.
6.602.1 Connecteurs
Pour les applications exigeant une bande passante élevée, il est préférable d'utiliser un
connecteur coaxial. Dans ce cas, la broche centrale doit correspondre à la borne "a".
NOTE Les interfaces numériques destinées aux applications en courant continu sont toujours en cours de
développement et le contenu de l'IEC 61869-9 est toujours en cours d'amélioration.
Les condensateurs doivent être conformes au Paragraphe 6.1 de l'IEC 60815-1 pour ce qui
est de leur niveau d'isolement individuel.
7 Essais
7.1 Généralités
Essais Paragraphe
Essais de type 7.2
Essai d'échauffement 7.2.2
Essai de tenue à la tension de choc sur les bornes primaires 7.2.3
Essai sous pluie pour les transformateurs de type extérieur 7.2.4
Essai d'inversion de polarité avec mesure de décharges partielles 7.2.1501
Essais de compatibilité électromagnétique 7.2.5
Essai concernant la précision 7.2.6
Essai de précision en fonction des harmoniques 7.2.1502
Vérification du degré de protection fourni par les enveloppes 7.2.7
Essai d'étanchéité des enveloppes à température ambiante 7.2.8
Essai de pression de l'enveloppe 7.2.9
Essai de tenue en tension des composants basse tension 7.2.601
Mesure du temps de réponse à un échelon 7.2.1503
Essais individuels 7.3
Essai de tenue en tension à fréquence industrielle sur les bornes primaires 7.3.1
Mesure des décharges partielles 7.3.2
Essai de tenue en tension à fréquence industrielle entre les sections 7.3.3
Essai de tenue en tension continue avec mesure de décharges partielles 7.3.1501
Essai de tenue en tension à fréquence industrielle sur les bornes secondaires 7.3.4
Essai concernant la précision 7.3.5
Vérification des marquages 7.3.6
Essais d'étanchéité des enveloppes à température ambiante 7.3.7
Essai de pression de l'enveloppe 7.3.8
Essai de tenue en tension à fréquence industrielle des composants basse tension 7.3.601
Mesure de la capacité 7.3.1502
Mesure de la résistance 7.3.1503
Essais spéciaux 7.4
Essai de tenue à la tension de choc coupé sur les bornes primaires 7.4.1
Essai de chocs coupés multiples sur les bornes primaires 7.4.2
Essai de surtensions transmises 7.4.4
Essais mécaniques 7.4.5
Essai de défaut d'arc interne 7.4.6
Essai d'étanchéité de l'enveloppe à basse et haute températures 7.4.7
Mesure du point de rosée 7.4.8
Essai de corrosion 7.4.9
Essai relatif au danger d'incendie 7.4.10
Essais de pollution 7.4.1501
Essais de vibration 7.2.602
Essai de précision du signal composite 7.4.1502
Essai de vieillissement pour les composantes R et C 7.4.1503
IEC 61869-15:2018 © IEC 2018 – 57 –
La séquence d'essais n'est pas spécifiée et peut être convenue entre l'acheteur et le
fournisseur.
Avant de commencer la séquence d'essais de type, les essais individuels suivants doivent
être réalisés:
Il est permis de réaliser l'essai de tension continue avant l'essai d'inversion de polarité. Dans
ce cas, il n'est pas nécessaire de renouveler cet essai après la séquence d'essais de type.
La séquence d'essais n'est pas précisée, mais les essais de précision doivent être réalisés
après les essais diélectriques.
7.2.1 Généralités
Les essais de type réalisés sur les DCVT sont considérés comme valides s'ils ont été
effectués sur un dispositif de conception comparable présentant des contraintes particulières
de conception similaires. La preuve doit en être apportée par le fabricant.
Les deuxième et troisième alinéas sont remplacés par les alinéas suivants:
Pour l'essai d'échauffement, les méthodes d'essai suivantes peuvent être utilisées pour
mesurer la température:
La tension à appliquer est la tension la plus élevée pour l'équipement (U m ). L'essai doit être
poursuivi jusqu'à ce que la température du transformateur atteigne la température en régime
établi.
Pour les transformateurs de tension dont la valeur U m est égale ou supérieure à 100 kV,
l'essai doit consister en un essai de tension de choc de manœuvre des deux polarités, à la
tension correspondant au niveau d'isolement.
Pour les transformateurs de tension dont la valeur U m est inférieure à 100 kV, l'essai doit être
réalisé à la tension à fréquence industrielle définie en 7.3.1.
Une tension de précontrainte d'une valeur de 1,25 × U m /√2 doit être appliquée et maintenue
pendant 30 s.
La tension doit ensuite être diminuée à 1,1 × U m /√2 en 10 s environ, et maintenue à cette
valeur pendant 30 s avant que le niveau des perturbations radioélectriques ne soit mesurée.
L'essai doit être considéré comme validé par le transformateur de tension si le niveau de
perturbations radioélectriques pour la valeur 1,1 × U dm / √ 2 est conforme au 6.11.2.
7.2.6.1501 Généralités
Les circuits d'essai sont présentés à l'Annexe 6D de l'IEC 61869-6:2016 pour les sorties
analogiques et à l'Annexe 9D de l'IEC 61869-9:2016 pour les sorties numériques.
Pour démontrer la conformité avec la classe de précision spécifiée, l'essai doit être réalisé
pour chaque valeur de tension donnée dans le Tableau 1502, avec une charge assignée et à
température ambiante, sauf indication contraire.
IEC 61869-15:2018 © IEC 2018 – 59 –
Dans un premier temps, la précision doit être mesurée dans une courte durée (moins de
0,05 fois la constante de temps thermique), à température ambiante, avec des tensions
croissantes.
Dans un second temps, la tension est diminuée jusqu'à atteindre la valeur U pr et maintenue
jusqu'à stabilisation thermique. La précision est mesurée et l'écart de précision pour la
valeur U pr est déterminé.
Les erreurs doivent être comprises dans les limites de la classe de précision applicable, au
moment de l'application de la tension d'essai ainsi qu'à la suite de la correction de l'écart de
précision.
Les écarts de précision doivent être notés dans le rapport d'essai de type sous forme de
caractéristiques du diviseur de tension.
La stabilité est prise en compte après une durée équivalente à 3 fois la constante de temps.
Cette dernière doit être définie par le fournisseur.
Lorsque la tension primaire est égale à zéro, l'erreur absolue mesurée ne doit pas dépasser
la valeur de l'erreur absolue admise, soit 0,05 × U pr .
NOTE Cet essai peut être réalisé en même temps que l'essai d'échauffement.
Pour les sorties analogiques avec temps de retard assigné, il n'est pas nécessaire d'insérer
un dispositif de temporisation entre le transformateur de référence et le système de mesure
de précision.
Le Paragraphe 7.2.6 de l'IEC 61869-9:2016 s'applique, les deux derniers alinéas étant
remplacés par les suivants:
Les essais de précision doivent être réalisés sur une durée minimale, au cours de laquelle
plusieurs mesures doivent permettre de calculer une moyenne. Les détails de disposition et
de planification de l'essai et/ou de bande passante du système d'essai doivent être
communiqués dans le rapport d'essai de précision.
La durée de mesure doit être suffisante pour garantir la précision des mesures, compte tenu
des oscillations de l'onde et de l'effet de l'échantillonnage. Il convient que la durée de cette
mesure soit inférieure à 10 s.
7.2.601 Essai de tenue à la tension de choc pour les composantes basse tension
Un composant basse tension d’un DCVT est la partie basse tension de diviseurs RC ou R,
lorsqu'elle est placée en dehors du boîtier principal, comme le montre la Figure 1504.
– 60 – IEC 61869-15:2018 © IEC 2018
Pour soumettre cette partie secondaire externe à l'essai, cinq chocs de foudre positifs et cinq
chocs de foudre négatifs de 1,2/50 μs dont la valeur d'essai sera conforme au
Paragraphe 5.3.5 de l'IEC 61869-6:2016 doivent être appliqués, comme le montre la
Figure 1505. Le dispositif limiteur de tension doit être déconnecté. Cet essai vérifie la tenue
en tension de l'ensemble de la partie externe à basse tension par rapport à la terre.
Cet essai s'applique aux transformateurs de tension à courant continu dont la valeur U m est
égale ou supérieure à 100 kV.
Sauf spécification contraire, cet essai ne s'applique pas aux transformateurs de tension à
courant continu pour applications VSC.
Lors de l'essai, la température ambiante doit être comprise entre 10 °C et 40 °C. Avant
l'essai, le dispositif doit être à température ambiante.
Un double essai d'inversion de polarité doit être utilisé, comme le montre la Figure 1506.
– 62 – IEC 61869-15:2018 © IEC 2018
Cependant, afin de gagner du temps lors des essais individuels de série, et avec l'accord des
différentes parties, l'essai d'inversion de polarité peut être lancé à tout moment après l'essai
de tenue en tension continue.
La durée d'inversion de polarité doit être aussi courte que possible et cohérente avec
l'équipement d'essai utilisé, mais elle ne doit jamais dépasser 2 min. L'inversion de polarité
est considérée comme terminée lorsque la tension a atteint 100 % de la valeur d'essai. Les
niveaux de décharge partielle doivent être surveillés pendant la totalité de la séquence
d'essai.
U rp = 1,25 × U m
L'essai du transformateur de tension doit être considéré comme validési les conditions
suivantes sont satisfaites:
L'essai doit être réalisé sur le transformateur de tension complètement assemblé. L'essai de
réponse à un échelon doit être réalisé avec la charge assignée et le câble de transmission
d'origine, s'ils existent.
Il convient que la tension d'essai primaire soit la tension primaire assignée et qu'elle
représente une caractéristique de tension de choc d'une précision de ±3 %. Un échelon de
tension peut être généré par un générateur de tension de choc. En cas de difficulté à générer
le signal primaire avec le temps de montée spécifié, la procédure d'essai peut être adaptée à
l'aide d'un signal de tension d'entrée réduit, à condition que la linéarité du système soit
prouvée et que le niveau de signal secondaire permette une mesure précise.
La durée de front correspond à la définition du choc de foudre pour une durée de front de
1,2 μs, avec une tolérance relative de ±30 %.
L'essai doit être réalisé une fois pour chaque polarité. Pour chaque essai réalisé, la courbe de
référence doit être enregistrée avec la courbe de réponse de l'objet soumis à l'essai.
NOTE Une limite de tolérance réduite peut être définie par un accord entre l'acheteur et le fabricant.
Légende:
u(t) tension d'entrée
v(t) tension de sortie de l'objet soumis à l'essai
a Pour un comportement périodique
b Pour un comportement apériodique
7.3.1 Essais de tenue en tension à fréquence industrielle sur les bornes primaires
U AC = 1,5/√2 × U m
Dans les cas d'applications spéciales, d'autres valeurs peuvent être spécifiées.
NOTE Pour certaines applications spéciales (par exemple: certaines applications de mesure de la tension
neutre), la tension d'essai spécifiée peut être insuffisante.
Les essais diélectriques doivent être réalisés sur un transformateur de tension complètement
assemblé, comme en service.
IEC 61869-15:2018 © IEC 2018 – 65 –
Le châssis et le circuit magnétique (le cas échéant) doivent être connectés à la terre.
7.3.4 Essais de tenue de la tension à fréquence industrielle sur les bornes secondaires
Si un dispositif limiteur de basse tension est connecté à la terre, il doit en être déconnecté
lors de l'essai.
Lorsqu'il existe une liaison galvanique interne entre la borne secondaire "n" et la terre, cet
essai est exigé uniquement en tant qu'essai de type. Dans ce cas, la connexion entre la borne
secondaire "n" et la terre doit être ouverte pour l'essai.
En principe, les essais individuels de précision sont identiques aux essais de type décrits en
7.2.6. La précision doit être mesurée dans une courte durée (moins de 0,05 fois la constante
de temps thermique), à température ambiante. La mesure de la précision doit être ajusté avec
les corrections définies au cours de l'essai de type.
Cette méthode s'applique aux diviseurs de tension passifs. La résistance de chaque partie (à
haute tension et à basse tension) du transformateur de tension doit être déterminée à basse
tension à l'aide d'un dispositif de mesure de la résistance de précision.
La mesure des valeurs de résistance doit être réalisé pour les polarités positive et négative
de la source du dispositif de mesure et la résistance doit correspondre à la moyenne de ces
deux mesures.
Les valeurs de résistance doivent être mesurées avant et après les essais à haute tension.
L'écart de résistance maximal entre les mesures de tension ne doit pas dépasser 0,2 fois la
limite de l'erreur de rapport à la valeur U pr correspondant à la classe de précision.
Pour le calcul du rapport de diviseur du DCVT, les valeurs de résistance calculées à partir
des mesures effectuées après les essais à haute tension doivent être utilisées.
– 66 – IEC 61869-15:2018 © IEC 2018
< 100 kΩ < 100 MΩ < 300 MΩ < 400 MΩ < 700 MΩ
U essai > 10 V DC U essai > 100 V DC U essai > 200 V DC U essai > 250 V DC U essai > 280 V DC
Cet essai s'applique aux transformateurs de tension à courant continu dont la valeur U m est
égale ou supérieure à 20 kV.
Les essais diélectriques doivent être réalisés sur un transformateur de tension complètement
assemblé.
U DC = 1,5 × U m
L'essai du transformateur de tension doit être considéré comme validé si les conditions
suivantes sont satisfaites:
Dans le cas d'un transformateur de tension à courant continu, la capacité C 1 doit être
mesurée à des tensions égales à 10 % et à 100 % de la valeur U pr avant et après l'essai
diélectrique afin d'identifier toute variation de la capacité due à une perforation d'un ou
plusieurs éléments. Ces mesures doivent être effectuées à la fréquence industrielle assignée.
La capacité doit être mesurée à l'aide d'une méthode excluant les erreurs liées aux
harmoniques et aux accessoires du circuit de mesure.
IEC 61869-15:2018 © IEC 2018 – 67 –
La résistance de la partie secondaire R 2 doit être mesurée avant et après les essais
diélectriques. La tension d'essai continue doit avoir une valeur au moins égale à celle de la
tension secondaire assignée, mais ne doit pas être plus de deux fois supérieure à celle-ci.
Cet essai peut être remplacé par la mesure de la précision, conformément au 7.3.5.1502.
7.4.1 Essai de tenue à la tension de choc coupé sur les bornes primaires
L'essai s'applique aux transformateurs de tension dont la valeur U m est égale ou supérieure
à 20 kV.
L'essai doit être exécuté avec une polarité négative uniquement et être combiné avec essai
de tenue au choc de foudre de polarité négative de la manière décrite ci-dessous.
La tension doit être un choc de foudre normal défini dans l'IEC 60060-1, coupé entre 2 µs et
5 µs. Le circuit de coupure doit être conçu de telle sorte que l’amplitude de l'oscillation de
polarité opposée du choc enregistré doit être limité à environ 30 % de la valeur de crête.
La tension d'essai du choc plein doit être conforme à la tension assignée de tenue au choc de
foudre.
La tension d'essai du choc coupé doit être conforme au 5.3.3.2 de l'IEC 61869-1:2007.
• un choc complet;
• deux chocs coupés;
• quatorze chocs pleins.
Après l'essai, le transformateur de tension doit passer avec succès l'essai de précision
conformément au 7.3.5.
L'essai s'applique aux transformateurs de tension dont la valeur U m est égale ou supérieure
à 100 kV.
Un essai de pollution artificielle peut être réalisé sur les transformateurs de tension disposant
d'isolateurs en porcelaine destinés à une utilisation en extérieur et exposés à des
atmosphères polluées.
NOTE La reproductibilité des essais de pollution artificielle sur les isolateurs qui sont équipés de protections en
silicone contre les intempéries réalisés dans différents laboratoires n'a pas été établie de manière cohérente avec
d'autres essais normalisés. Cependant, des recommandations supplémentaires seront disponibles puisque la
recherche continue et, le cas échéant, des comparaisons inter-laboratoires seront établies. Le problème est étudié
par l'IEC.
La tension continue d'essai de tenue doit être spécifiée. En règle générale, elle coïncide avec
la tension la plus élevée de l'équipement. Les essais sont habituellement réalisés à polarité
négative.
L'essai de trempage régulier peut être appliqué à tous les transformateurs de tension pour
l'extérieur dont la valeur U m est égale ou supérieure à 100 kV.
La procédure d'essai de trempage régulier normalisée décrite dans l'IEC 60060-1 doit être
utilisée, excepté pour la durée de l'essai.
• pour les applications en courant continu de faible bande passante: 100 Hz, 500 Hz, 1kHz,
1,5 kHz, 3 kHz;
• pour les applications en courant continu de bande passante élevée: 100 Hz, 2,5 kHz,
5 kHz, 7,5 kHz, 10 kHz, 15 kHz, 20 kHz.
La précision des composantes de tension en courant alternatif doit être conforme aux
spécifications de l'Annexe 6A de l'IEC 61869-6:2016, alors que la tension continue primaire
assignée est fournie côté primaire.
Cet essai a pour objectif de prouver que la précision du diviseur de tension n'est pas
influencée par le vieillissement.
Cet essai doit être réalisé sur trois échantillons d'éléments de résistance et un élément de
condensateur. Il compte cinq cycles, décomposés de la manière suivante:
Une fois les cinq cycles écoulés, les valeurs doivent être mesurées. Pour le condensateur,
l'écart maximal doit être inférieur à 5 %. En ce qui concerne la résistance, il doit être inférieur
à l'erreur maximale correspondant à la classe de précision.
– 70 – IEC 61869-15:2018 © IEC 2018
Annexe 15A
(informative)
La coordination de l'isolement dans les systèmes CCHT est actuellement étudiée par l'IEC.
Pour les essais diélectriques de courant alternatif et de courant continu, la tension d'essai est
définie aux Paragraphes 7.2 et 7.3.
La présente annexe propose une tension d'essai pour les essais de choc basée sur les
tensions généralement adoptées sur les systèmes et lors des essais. Ces valeurs sont
indicatives et les concepteurs des systèmes pourraient être contraints à définir d'autres
niveaux d'isolement dans des conditions particulières de coordination de l'isolement.
Pour une tension du système inférieure à 200 kV, un trop grand nombre d'applications
existent et des valeurs normalisées ne peuvent pas être définies. Les niveaux d'isolement
doivent être définis par le concepteur du système.
Lorsque les tensions assignées pour le système et les niveaux d'isolement assignés auront
été publiés, la présente annexe sera ignorée.
Bibliographie
___________