Electrical Machines-II Lab Manual
Electrical Machines-II Lab Manual
PREPARED BY,
Er.N.VASANTHAKUMAR M.E,
MBA, (PhD)
HEAD\EEE\RVSPCET
ENGINEERING
RVSPCET
Acquire a good knowledge of the surrounding of your worktable. Know where the various
live points are situated in your table.
In case of any unwanted things happening, immediately switch off the mains in the
worktable.
This must be done when there is a power break during the experiment being carried out.
Before entering into the lab class, you must be well prepared for the experiment that you
are going to do on that day.
You must bring the related text book which may deal with the relevant experiment.
Get the circuit diagram approved.
Prepare the list of equipments and components required for the experiment and get the indent
approved.
Plan well the disposition of the various equipments on the worktable so that the experiment
can be carried out.
Make connections as per the approved circuit diagram and get the same verified. After
getting the approval only supply must be switched on.
Get the reading verified. Then inform the technician so that supply to the worktable can be
switched off.
You must get the observation note corrected within three days from the date of
completion of experiment. Write the answer for all the discussion questions in the
observation note. If not, marks for concerned observation will be proportionately reduced.
Submit the record note book for the experiment completed in the next class.
If you miss any practical class due to unavoidable reasons, intimate the staff in charge and do
the missed experiment in the repetition class.
Such of those students who fail to put in a minimum of 75% attendance in the laboratory
class will run the risk of not being allowed for the University Practical Examination. They
will have to repeat the lab course in subsequent semester after paying prescribed fee.
Use isolated supply for the measuring instruments like CRO in Power Electronics
Laboratory experiments.
LIST OF EXPERIMENTS
P = 45 Total = 45
TABLE OF CONTENTS
EXP.NO. 1
AIM:
To predetermine the regulation of 3-phase alternator by EMF and MMF methods and also
draw the vector diagrams.
APPARATURS REQUIRED:
THEORY:
The regulation of a 3-phase alternator may be predetermined by conducting the Open
Circuit (OC) and the Sort Circuit (SC) tests. The methods employed for determination of
regulation are EMF or synchronous impedance method, MMF or Ampere Turns method and the
ZPF or Potier triangle method. In this experiment, the EMF and MMF methods are used. The OC
and SC graphs are plotted from the two tests. The synchronous impedance is found from the OC
test. The regulation is then determined at different power factors by calculations using vector
diagrams. The EMF method is also called pessimistic method as the value of regulation obtained
is much more than the actual value. The MMF method is also called optimistic method as the
value of regulation obtained is much less than the actual value. In the MMF method the armature
leakage reactance is treated as an additional armature reaction. In both methods the OC and SC
test data are utilized.
PRECAUTIONS:
(i) The motor field rheostat should be kept in the minimum resistance position.
(ii) The alternator field potential divider should be kept in the minimum voltage
position.
(iii) Initially all switches are in open position.
1. Note down the name plate details of the motor and alternator.
2. Connections are made as per the circuit diagram.
3. Switch ON the supply by closing the DPST switch.
4. Using the Three point starter, start the motor to run at the synchronous speed by adjusting
the motor field rheostat.
5. Conduct Open Circuit test by varying the potential divider for various values of field
current and tabulate the corresponding Open Circuit Voltage readings.
6. Conduct Short Circuit test by closing the TPST switch and adjust the potential divider to
set the rated armature current and tabulate the corresponding field current.
7. The Stator resistance per phase is determined by connecting any one phase stator winding
of the alternator as per the circuit diagram using MC voltmeter and ammeter of suitable
ranges.
FORMULAE:
1. Armature Resistance Ra = Ω
4. Open circuit voltage for lagging p.f = √(VcosΦ + IaRa)2 + (VsinΦ + IaXs)2
5. Open circuit voltage for leading p.f. = √(VcosΦ + IaRa)2 + (VsinΦ – IaXs)2
TABLE:
TABLE:
EMF METHOD:
MMF METHOD:
RESULT:
Thus the regulation of 3-phase alternator has been predetermined by the EMF and MMF
methods.
EXP.NO. 2
AIM:
To predetermine the regulation of three phase alternator by ZPF method and also to draw
the vector diagrams.
APPARATURS REQUIRED:
FORMULAE USED:
Percentage regulation = Eo – Vrated x 100 (For both POTIER & ASA methods)
Vrated
PRECAUTION:
(i) The motor field rheostat should be kept in the minimum resistance position.
(ii) The Alternator field potential divider should be in the position of minimum
potential.
(iii) Initially all switches are in open position.
1. Draw the Open Circuit Characteristics (Generated Voltage per phase VS Field Current)
2. Mark the point A at X-axis, which is obtained from short circuit test with full load
armature current.
3. From the ZPF test, mark the point B for the field current to the corresponding rated
armature current and the rated voltage.
4. Draw the ZPF curve which passing through the point A and B in such a way parallel to
the open circuit characteristics curve.
5. Draw the tangent for the OCC curve from the origin (i.e.) air gap line.
6. Draw the line BC from B towards Y-axis, which is parallel and equal to OA.
7. Draw the parallel line for the tangent from C to the OCC curve.
8. Join the points B and D also drop the perpendicular line DE to BC, where the line DE
represents armature leakage reactance drop (IXL)
BE represents armature reaction excitation (Ifa).
DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGG. , RVSPCET Page 11
. of 48
Page 11
ELECTRICAL MACHINES-II LABORATORY MANUAL 2015
RESULT:
Thus the regulation of 3-phase alternator has been predetermined by the Potier methods.
EXP.NO. 3
AIM:
To conduct a slip test on 3-Ф alternator and pre-determine the regulation through vector
diagram.
APPARATUS REQUIRED:
FUSE RATING:
THEORY:
In a salient pole alternator, the reactance of magnetic circuit along is along its quad stator axis.
The alternator is driven by auxiliary prime mover at a speed slightly less than the synchronous
speed under these conditions. The armature current is when the armature current mmf is in line
with the field poles. The reactance by the magnetic field current is minimum. The ratio of
maximum voltage to minimum current gives the direct axis impedance and the ratio of minimum
voltage to maximum current gives the armature axis impedance.
PRECAUTIONS:
PROCEDURE:
FORMULAE USED:
1. Rac=1.6Rac Ω
2. Zd = Vmax/Imin Ω
3. Zq = Vmin/Imax Ω
Xd = √Zd2 – Rd2 Ω
4. Xq = √Zq2 – Rd2 Ω
5. Id = Ia sinФ amps
6. Iq = Ia cos Ф amps
7. %Reg = (Eo-V/V)*100
Where,
Zd = direct axis impedance in Ω
Zq = quadrate axis impedance in Ω
Xd = direct axis reactance in Ω
Xq = quadrate axis reactance in Ω
Id = direct axis current in amps
Ia = quadrate axis current in amps
GRAPH:
TABLE:
(i) To find the Direct Axis and Quadrature axis impedances:
S.NO Vmax Vmin Imax Imin
S.NO
Power Factor % Regulation
1 0.2 --
2 0.4 --
3 0.6 --
4 0.8 --
5 1.0
RESULT:
EXP.NO. 4
AIM
To draw the V and inverted V curves of a 3 phase Synchronous Motor.
APPARATUS REQUIRED:
1 Ammeter MI (0-5)A 2
2. Voltmeter MI (0-600)V 2
3. Ammeter MC (0-2)A 1
4. Rheostat 200Ω,15A 1
PRECAUTION:
(1) The Potential barrier should be in maximum position.
(2) The motor should be started without load .
(3) Initially TPST switch is in open position.
PROCEDURE:
(1) Note down the name plate details of the motor.
(2) Connections are made as pr the circuit diagram..
(3) Close the TPST switch.
(4) By adjustingthe autotransformer from the minimum position to the maximum
position the rated supply is given to motor. The motor starts as an induction motor.
(5) In order to give the excitation to the field for making it to run as the synchronous
motor, close the DPST switch.
(6) By varying the field rheostat note down the excitation current, armature current and
the power factor for various values of excitation.
(7) The same process has to be repeatedfor loaded condition.
(8) Later the motor is switched offand the graph is drawn.
GRAPH:
The graph is drawn for-
(1) Armature current Vs Excitation current.
(2) Power factor Vs Excitation current.
RESULT:
The V-curves and inverted V-curves of the 4 phase synchronous motor have been drawn.
EXP.NO. 5
LOAD TEST ON 3-PHASE SQUIRREL CAGE INDUCTION MOTOR
AIM:
To draw the performance characteristics of 3-phase squirrel cage induction motor by
conducting load test.
APPARATUS REQUIRED:
FUSE RATING;
125% of 4.8A=6A=10A
THEORY:
A 3-phase induction motor consists of stator and rotor with the other associated parts. In the
stator, a 3-phase winding is provided. The windings of the three phase are displaced in space by
120º.A 3-phase current is fed to the 3-phase winding. These windings produce a resultant
magnetic flux and it rotates in space like a solid magnetic poles being rotated magnetically.
PRECAUTIONS:
PROCEDURE-
FORMULAE USED-
1) % slip= (Ns-N/Ns)*100
2) Input Power = (W1+W2)watts
3) Output Power = 2∏NT/60 watts
4) Torque = 9.81*(S1-S2)*R N-m
5) % efficiency = (o/p power/i/p power)* 100
GRAPHS-
RESULT
Thus the performance characteristic of a 3-Ф squirrel cage induction motor by conducting load
test has been drawn.
EXP.NO. 6
AIM :
To conduct a direct load test on a 3-phase slip ring induction motor and to draw the
performance characteristics.
APPARATUS REQUIRED:
FUSE RATING:
THEORY:
Slip ring induction motor is also called as phase wound motor. The motor is wound
for as many poles as the no. of stator poles and always wound 3-Ф even while the stator is
wound two-phase. The other three windings are brought out and connected to three insulated
slip-rings mounted on the shaft with brushes resting on them. These three brushes are further
externally connected to a three phase star connected rheostat. This makes possible the
introduction of an additional resistance in the rotor circuit during starting period for increasing
starting torque of the motor.
PRECAUTIONS:
PROCEDURE:
1. Connections are given as per circuit diagram.
2. After observing precautions motor is started on no load.
3. As speed increases, the external resistance is gradually cut out.
4. The no-load readings are taken.
5. If the pointer in one of the wattmeter reverses, interchange the current coil terminals and
take the reading as negative.
6. The meter readings are then noted for various load conditions.
FORMULAE USED:
GRAPHS:
RESULT:
The load test on 3-Ф slip ring induction motor was conducted and the performance
characteristics curves were plotted.
EXP.NO. 7
AIM: To conduct the no load & blocked rotor test on 3- phase induction motor
& to draw the equivalent circuit of 3- phase squirrel cage induction motor.
APPARATUS REQUIRED :-
z
S.NO NAME OF RANGE TYPE QTY
APPARATUS
1. Voltmeter (0-600)V MI 01
(0-150)V MI 01
2. Ammeter (0-10)A MI 01
3. Wattmeter (600V,5A) UPF 01
(150V,10A) LPF 01
4. Connecting wire As required
FUSE RATING :
THEORY :-
A 3-phase induction motor consists of stator, rotor & other associated parts. In the stator
,a 3- phase winding (provided) are displaced in space by 120. A3- phase current is fed to the
winding so that a resultant rotating magnetic flux is generated. The rotor starts rotating due to the
induction effect produced due the relative velocity between the rotor
Winding & the rotating flux.
PRECAUTIONS:
NO LOAD TEST:
PROCEDURE:
NO LOAD TEST:
FORMULA USED:
TABLE:
NO LOAD TEST:
RESULT:
Thus the no load and blocked rotor test on 3-Фsquirrel cage induction motor is performed
and the equivalent circuit of 3-phase squirrel cage induction motor has been drawn.
EXP.NO. 8
AIM:
To separate the no load losses of a 3 phase squirrel cage induction motor as iron losses
and mechanical losses.
APPARATUS REQUIRED:
1. Ammeter MI (0-10)A 1
MC (0-1)A 1
2. Voltmeter MI (0-600)V 1
MC (0-5)V 1
PRECAUTIONS:
(1) The autotransformer should be kept in minimum voltage position.
(2) the motor should not be loaded throughout the experiment.
PROCEDURE:
GRAPH:
The graph drawn between constant losses (watts) and input voltage (volts).
MODEL CALCULATIONS:
RESULT:
Thus the no load losses of 3-phase squirrel cage induction motor was separated as core
losses and mechanical losses.
EXP.NO. 9
APPARATUS REQUIRED:
1 Voltmeter (0-300) V MI 1
2 Ammeter (0-10) A MI 1
4 Tachometer 1
FUSE RATING:
THEORY:
The single phase induction motor is more or less a polyphase induction motor. The only
difference is that is given supply in single phase. This motor connect and motor function without
any initial start the motor having some part which is called starter and rotor. These are two types
of starting a 1 phase induction motor namely capacitor-start and other is split-phase. These
motors are widely used in domestic purpose.
PRECAUTION:
PROCEDURE:
1. Connections are given as per the circuit diagram.
2. Switch on the supply at no load condition.
3. Apply the rotor voltage to the motor using the variac and note down the readings at
ammeter and wattmeter.
4. Vary the load in suitable steps and note down all the meter readings till full load
condition.
FORMULA USED:
1) Torque ,T = (S1~S2)*9.81*R N.m
2) Output power = 2π NT/60*W
3) Effecting (η%) = 0/P Power / I/p Power*100
4) Slip (%S) = NS – N/NS*100
5) Power factor = Cos φ=W/VI
GRAPH :
TABLE:
Sl.No. VL IL Speed S1 S2 S1 ̃~ S2 Torque Wattmeter Reading Output
V A RPM Kg Kg Kg N-m Power η PF= cosΦ
Observed Actual W %
1
MODEL CALCULATION:
RESULT:
Thus load test on the single phase induction motor has been conducted and its
performance characteristics determined.
EXP.NO. 10
AIM:
To draw the performance characteristics of a single phase induction motor by conducting
the no-load and blocked rotor test.
APPARATUS REQUIRED:
FUSE RATING:
125% of 7.6A=10A
THEORY:
A 1-Ф induction motor consists of stator,rotor and other associated parts.In the rotor of a single
phase winding is provided.The windings of a 1- Ф winding(provided) are displaced in space by
120º.A single phase current is fed to the windings so that a resultant rotating magnetic flux is
generated.The rotor starts rotating due to the induction effect produced due to the relative
velocity between the rotor winding and the rotating flux.
PRECAUTIONS:
NO LOAD TEST:
PROCEDURE:
NO LOAD TEST:
Reff = 1.5*Rdc
FORMULAE:
NO LOAD TEST:
cos Ф = Wo/VoIo
Iw = Io cosФ
Im = Io sin Ф
Ro = Vo/Iw
Xo = Vo/Im
BLOCKED ROTOR TEST:
Zsc = Vsc/Isc Ω
Rsc = Wsc/Isc2 Ω
Xsc = √(Zsc2 – Rsc2) Ω
TABLE:
NO LOAD TEST
RESULT:
Thus the no load and blocked rotor test on the single phase induction motor has been conducted
and the equivalent circuit has been drawn.