Rmu RN2C
Rmu RN2C
07
Contents
page
General Symbols and meanings Schneider Electric at your service General description Handling, transportation and storage Storage Goods receiving Characteristics 2 2 3 4 5 6 7 8 Ringmaster operation RN2c, RE2c, RN6c essential checks Features Civil engineering Floor preparation Internal arc Cable trench 9 9 10 12 Switch and circuit breaker Earth switch Cable testing Circuit breaker reset Motorpack Installation Transformer mounting Connecting the HV cables Erection / connection Installation of pilot cables Removal of VIP relay Accessing VTs Earth fault flow indicator Actuators Accessories Fitting REC2 to Ringmaster range 13 14 15 20 22 23 24 25 26 27 28 Maintenance Recommendations and conditions Protection Time fuse link Operation VIP300 VAP6 43 43 44 46 52 Housing Circuit breaker Ringmaster range operation Main features Switch and circuit breaker Earth switch Cable testing and actuator control Actuator control Motorpack operation Neon indication Commissioning Checks and tests Tests Commissioning Ringmaster with VIP 300
page
54 54 55
65
69 69 70 71 72 73 75 76 77 78
79 80 81 82 83 84
85 85 86 87
Version 11 - Issue date November 2007 Note: This manual covers ring main units produced from June 1999. Designation RN2c/RN6c/RE2c. For ring main units designated RN2/RN6 see earlier manual. Ref: Version 005/December 98.
SCHNEIDER ELECTRIC
General
Symbols and meanings
The following symbols appear in this document to indicate the degree of hazard according to the situation.
DANGER
Danger: Failure to follow this instruction will result in death, serious injury or equipment damage
WARNING
Warning: Failure to follow this instruction can result in death, serious injury or equipment damage
CAUTION
SCHNEIDER ELECTRIC
General
Schneider Electric at your service
For technical support or advice current products please contact our customer service department: Tel: +44 (0) 113 290 3651 Fax: +44 (0) 113 290 3710 Email: GBMVCustomerServices@gb.schneider-electric.com
Spares and managed spares contracts Maintenance and service contracts Retrofit Installation Testing and commissioning System design Training
Tel: +44 (0) 113 290 3634 Fax: +44 (0) 113 290 3777 Email: GB-services-and-projects@gb.schneider-electric.com
Document guidelines
This document is not a commercial document, but a technical document prepared by Schneider Electric. The objective of this publication is to assist with the correct installation and operation of Ringmaster and Ringmaster Range. Reproduction either in full or partial of this document is prohibited and can only be undertaken with permission of Schneider Electric.
Safety requirements
CAUTION
All operations described hereafter must be carried out by respecting the safety requirements in full, under the responsibility an authorised person.
DANGER
Personnel undertaking installation and commissioning must be competent and understand local regulations and standards.
CAUTION
If the installation and operational team is unsure or not familiar with Ringmaster or Ringmaster Range switchgear please contact Schneider Electric.
SCHNEIDER ELECTRIC
General
General description
Introduction
These instructions cover all operations concerning handling, installation, operation and maintenance of the Ringmaster Range of equipment.
The range comprises:s s s s s s s s s s RN2c 630/200A non extensible compact ring main unit RN6c 630/630A non extensible compact ring main unit RE2c 630/200A extensible compact ring main unit CN2 200A non extensible circuit breaker SN6 630A non extensible switch CE2 200A extensible circuit breaker CE6 630A extensible circuit breaker SE6 630A extensible switch MU2 200A feeder metering unit non-extensible units CE2/CE6/SE6 with metering unit
Compact non extensible composite ring main unit s RN2c 630/200A s RN6c 630/630A
Extensible circuit breakers and switches s CE2 200A s CE6 630A s SE6 630A
When fully installed the equipment is suitable for outdoor use. It may therefore be necessary to protect the equipment from the environment during erection/commissioning. Please check equipment specification for clarification of indoor/outdoor use. Should the busbar chamber or cable box become exposed to the elements, they should be thoroughly cleaned prior to energising. Weights and dimensions
unit(s) average dimensions (mm) (packed) approx. weight (kg) h W I RN2c/RE2c CN2 RN6c 1510 1610 1750 520 771 960 842 280 350 SN6 1750 520 960 280 CE6 1750 520 960 280 SE6 1750 520 960 280 CE2 1750 520 960 280 MU6+CE6/ CE2/SE6 1750 1100 1100 520 MU2 1650 520 960 240 MU6 1750 520 960 240
Please refer to the appropriate pages in the Ringmaster selection guide Ref:MGMV5337 available from Schneider Electric or on line at www.schneider.co.uk
SCHNEIDER ELECTRIC
General
Handling, transportation and storage instructions
CAUTION
CAUTION
Use lifting lugs ONLY to lift Ringmaster
Units can be carried on open topped trucks or stored outside for short periods provided that all apertures are covered. Units should not be considered weatherproof until the paint work has been inspected and, if necessary any damage should be re-touched. Please refer to paintwork on page 7 for repairing damaged paintwork. If units are to be stored for long periods of time they should be stored in a warm, dry location and protected against dust and debris. All units can be off loaded by fork lift truck using the transport pallet. They can also be off loaded using the lifting lugs fitted at the top of the unit.
Storage
Ringmaster is only suitable for outdoor storage when packaged correctly or fully commissioned. The type of gland supplied will vary in accordance with specific contract requirements. The style of packaging will vary in accordance with the method of transportation and specific contract requirements. Please consult your commercial documentation to see how this equipment is packed.
SCHNEIDER ELECTRIC
General
Storage
Off loading
All units are delivered on pallets (secured by 4 x M8 screws and nuts) and fitted with lifting eyes, suitable for off loading by forklift truck or overhead crane.
Ancillary kits
Ancillary kits containing busbar, dyscon boots, glands, screws etc. are supplied loose with each unit or fastened to the panel leg or secured in the cable boxes.
Prior to operation
Prior to energising
It is recommended that prior to energising the unit all protection device are checked to ensure they are set correctly. For TFL units ensure fuses are fitted. VIP units must be set in accordance with the results of a protection co-ordination study.
SCHNEIDER ELECTRIC
General
Goods receiving
Goods receiving
s Before any equipment is accepted it should be inspected carefully for damage or loss incurred during transit s Where possible check the presence of accessories against the packaging list s Where possible check the information on the nameplate(s) and compare against the order confirmation s The packing must be in place and in good condition at the time of receipt. Wherever possible, damage should be recorded, photographed and witnessed. It may be necessary to unpack the equipment to establish the full extent of the problem.
In the event of an anomaly, please contact the transport/shipping company. The functional unit must remain on its base, in its original packing, during storage, and until installation.
CAUTION
In the event of any anomaly or apparent damage, do not install, please contact SCHNEIDER ELECTRIC. Contact details: are detailed on page 3.
Paintwork
Check for any damaged paintwork. Damaged areas should be cleaned and re-coated as follows: Rub down the area around the damage with medium glass paper. Clean the damaged area with emery paper ensuring the surface is clean and free of any corrosion. Apply one coat of zinc-rich epoxy primer (a two-pack system is recommended), the coating to be 35-45 microns thick. The recommended paint system is International Paints Interzinc EPA 072 and EPA 073. Leave to cure for 24 hours, then apply two, 35-45 micron coats (ie 70-80 microns in total) of two-pack polyurethane, Interphane PFR 764 is recommended. The standard colour employed is Dark Grey Code 632 to BS 381C:1996.
SCHNEIDER ELECTRIC
General
Characteristics
Check that the information contained on the rating plate corresponds to the equipment ordered.
Ringmaster
RN2C
123 Jack Lane Leeds LS10 1BS U.K. Tel +44 113 290 3500 Fax +44 113 290 3710
R
Ringmaster
Year 11kV 12kV 75kV 50/60HZ 300 kg 0.516 kg 0.35 bar G
N
Non extensible
X
Circuit breaker rating 2 = 200A 6 = 630A
C
Compact
Serial NO. Panel type no. Service voltage Highest system voltage Impulse voltage withstand level Frequency Mass of unit (max) Mass of SF6 Gas SF6 Gas filling pressure at 20C
Ratings
Normal current Peak making current Earth switch short time current 3 second Earth switch peak making current A kA Short time current 3 seconds kA
busbars
Switch
Circuit Breaker
630 16 40
kA kA
630 16 40 16 40
200 16 40 16 40
To Specification
Ringmaster
CE2 200A circuit breaker
Serial NO. Service voltage Highest system voltage Impulse voltage withstand level Frequency Mass (max) SF6 Gas filling pressure at 20C
To specification EA41-26 Leeds LS10 1BS U.K.
X
Year 12kV 12kV 75kV 50/60HZ 350 kg 0.80 bar G
X
N - Non extensible E - Extensible 2 = 200A 6 = 630A
X
rating
Ratings
Busbars
Normal current Short time current 3 second Peak making current A kA kA
Circuit breaker
630 16 40
kA kA
230 16 40 16 40
B.S.5311 IEC 56
Earth switch short time current 3 second Earth switch peak making current Testing standard
SCHNEIDER ELECTRIC
Civil engineering
Floor preparation
Floor preparation, equipment fixing dimensions and main cable position can be found in the Ringmaster selection guide reference MGMV5337. Or, if supplied the arrangement drawing for the switchboard or unit.
Both non extensible units and switchboards can be directly bolted to the concrete floor by use of 4 x 10mm (supplied) UNI-FIX or similar rag bolt fixings see diagram. The floor tolerance for extensible switchboards is 1mm over 1 metre.
41
70
41
Where it is not possible to guarantee that the floor is within the specified tolerance, we strongly recommend the use of foundation channels, i.e. Unistrut P3270 or similar.
Note: The floor must be 1mm below the top of the Unistrut.
SCHNEIDER ELECTRIC
Civil engineering
Internal arc
Internal arc
Kits to safely divert the flow of gasses outside the substation are not part of the supply of equipment. If required, kits will need to be adapted to each situation.
CAUTION
Arrows indicate direction of exhaust gases
Ringmaster
10
SCHNEIDER ELECTRIC
Civil engineering
Internal arc
If the unit is to be installed outdoors there are no special requirements for exhausting the arc gasses.
CAUTION
Where units are to be installed in an enclosed substation the following approximate free air volumes behind the units must be observed.
Minimum 112m
Minimum 152m
CAUTION
If the minimum free air space can not be guaranteed then arc vent trunking must be used. Typical trunking arrangements are detailed. Contact Schneider Electric for advice before designing and installing internal arc trunking. Note: Arc trunking is not part of our scope of supply.
The elbow and side/rear trunking is the same for both RN2c and CE/SE
SCHNEIDER ELECTRIC
11
Civil engineering
Cable trench
Cable trench
928 735 695
door
Where the equipment is to sit over a trench, details of the maximum cable trench width can be found in the selection guide.
223.5 54.5
1320
533
97
560
max. trench width
97
CAUTION
Care must be exercised with the cable bend, refer to cable manufacturers specification
1320
166
166
45
O
front entry
maincable trench
trench
maincable
rear entry
12
SCHNEIDER ELECTRIC
Installation
Standard units can be installed in environments which meet normal service conditions as defined by IEC 60694 section 2.1:Ambient temperature: -25C to +45C Altitude: up to 1,000 meters above sea level
CAUTION
If the location is outside the certified parameters please refer to the selection guide, alternatively contact Schneider Electric for advice. Where the units are to be installed in environments where the above parameters are exceeded, this must be declared to Schneider Electric so the appropriate de-rating factors can be applied. Failure to rate the equipment to the location may result in equipment failure.
CAUTION
Units may be installed indoors or outdoors but must not be subjected to regular extremes of weather e.g. heavy rain storms, heavy snow and ice, flooding, temperature cycles not greater than 55C and less than -25C, dense coastal fog or acid rain.
SCHNEIDER ELECTRIC
13
Installation
Transformer mounting
470
89 370 89
116
216
86
86
86
86
86
Adjust RMU stand height to suit. Under workshop conditions remove transformer lid screws. Pump oil out to below HV pocket height. (Pump into clean, dry drum). Remove blanking plate. Push units together. Insert bushing gasket and make firm connections on flanges and support brackets. Make off the 3 phase connections checking that these are tight and in the correct phase sequence, onto the M12 copper studs in the bushings. Pump clean oil back to the cold oil fill level marked on the transformer oil gauge. Re-fit tank cover ensuring that there is no damage to the gasket. Touch up paint as necessary. Perform primary winding resistance test in insulation resistance test.
569
973
40
771
516
ESI35-1 transformer
1510
1320
385.5
213
213
WARNING
14
263
267
537
936
SCHNEIDER ELECTRIC
1955
Installation
Connecting the HV cables
WARNING
Standard CE, CN, SE & SN cable box Standard cable entry directly from below
The RN2c/RE2c/RN6c is suitable for accepting 1 x 3 core or 3 x 1 core cable up to 240mm2 copper or aluminium approaching from below top entry available on request. Fit the gland plate and accessories in accordance with the instructions supplied with the ancillary kit.
Angled gland plates can be provided on all units to the front or rear, in order to simplify civil works.
Please refer to accessory kit instructions for details.
SCHNEIDER ELECTRIC
15
Installation
Connecting the HV cables
CE2, CE6, SE6, CN2, SN6 with top entry cable box.
1320
166
166
45
O
front entry
maincable trench
trench
maincable
rear entry
16
SCHNEIDER ELECTRIC
Installation
Connecting the HV cables
WARNING
Always clamp the cable with the appropriate glanding system before connecting the cable to the bushing. Proceeding otherwise will put unacceptable stress on the bushing and could damage the bushing, leading to equipment failure. The weight of the cable must always be supported by the cable gland.
WARNING
When using cable connectors use those supplied with the equipment, if others are used the long term dielectric withstand cannot be guaranteed.
DANGER
Ensure the bolt torques are adhered to, otherwise equipment failure may occur.
unit
boot type
cable socket fixing M12 stud M12 stud M12 clearance hole in palm M12 clearance hole in palm M12 tapped hole M12 clearance hole in palm M12 tapped hole
Installation note The most common cause of disruptive failure on this type of equipment is caused by incorrectly tightened cable connections ALWAYS double check cable connections with a calibrated torque wrench.
SCHNEIDER ELECTRIC
17
Installation
Connecting the HV cables
CAUTION
When connecting two cables per phase on RN2c and RN6c on a single bushing use the termination kit supplied by Schneider Electric. For all other units contact Schneider Electric for advice before proceeding.
WARNING
When cabling please ensure that the correct phase rotation is followed for all medium voltage cable boxes.
There are phase identification stickers in all accessible points throughout the equipment.
18
SCHNEIDER ELECTRIC
Installation
Connecting the HV cables
WARNING
The cut cable length of the cable must be adjusted for each phase (in particular 3 core cables). Never use a bar to pull the and fit a connection lug to the bushing. The bushing and hence the complete cubicle could irreversibly damaged.
Ensure all cable box fittings are replaced after installing cable.
To prevent vermin entering cable boxes ensure that the correct gland is fitted and tightened, cable box covers are fitted correctly and all bolts are replaced. If there are any visible spaces consult Schneider Electric on sealing advice.
SCHNEIDER ELECTRIC
19
Installation
Erection/connection
Remove the top cover on each unit and bolt each panel to the adjacent one. Use the 16 x M6 screws around the busbar aperture and the 2 x M8 screws by the cable test access/auxiliary compartment.
The busbar end cap is secured with 16 screws. Before fitting the end cap apply a line of silicon compound around the busbar aperture.
Please refer to accessory kit instructions for full details.
Connect the busbars as shown below. Connect the earth bars at the back of the units. Connect the main substation earth to the equipment main earth bar. Fit the main gland plates (see ancillary instructions). Erect the first unit under clean, dry conditions either directly to the floor, or on to the foundation channels.
430
430
Ensure that the environment is clean and dry. Remove busbar chamber covers.
Remove dyscon boots and clean bushings. Apply DC4 silicon grease to boots. Fit busbars into boots as shown above.
20
SCHNEIDER ELECTRIC
Installation
Erection/connection
busbar collar
busbar
busbar
busbar
busbar
Feeder metering Ensure that the environment is clean and dry. Remove busbar covers as shown above. Remove dyscon boots and clean bushings. Apply DC4, Dow Corning silicon grease to boots. Fit busbars into boots as shown above.
Busbar metering Ensure that the environment is clean and dry. Remove busbar covers as shown above. Remove dyscon boots and clean bushings. Apply DC4, Dow Corning silicon grease to boots. Fit busbars into boots as shown above.
CAUTION
Torque busbar screw to 54 Nm. Fit dyscon dust caps. Degrease and clean using a lint free cloth. Replace busbar chamber covers taking care not to damage nylon inserts. Ensure sealing strip is correctly fitted.
Connection of busbars RE2c When supplied pre-assembled the RE2c to CE6/CE2/SE6 busbars require a final torque during on site commissioning Please refer to the accessory kit instructions supplied with the product (ref: RMR-A369 "on site" busbar re-torquing procedure) Note: It is recommended prior to refitting busbar chamber covers that the busbars are tested - see pages 39, 42 and 54 for typical tests
SCHNEIDER ELECTRIC
21
Installation
Installation of pilot cables
The universal gland plate at the rear of the LV compartment will accommodate pilot cable glands upto 25.5mm2.
To fit gland and cable remove 4 gland plate screws. Slide top section of gland plate forward.
Insert gland and cable replace top gland plate and 4 fixing screws.
on switch/circuit breaker. Remove VIP relay if fitted, knock out the pre-punched gland plates from the inside as required. There is no need to re-touch with paint (the plates are stainless steel).
Note: 20.5mm = 1x7 core / 1x9 core pilot gland 25.5mm = 1x19 core pilot gland
on MU2 Knock out the pre-punched gland plates from the inside as required. There is no need to re-touch with paint (the plates are stainless steel).
on feeder/busbar metering units Knock out the pre-punched gland plates from the inside as required. There is no need to re-touch with paint (the plates are stainless steel).
22
SCHNEIDER ELECTRIC
Installation
Removal of VIP relay
B B A
Open cabinet door. Move shorting links on terminal rail, short circuiting the CT Secondaries. Remove top cover 3 x M6 x 20 screws.
Short circuiting of the CT secondaries. To short circuit the protection current transformers loosen test terminals A, and move shorting link B upwards.
Slide earthbar B to position above and tighten test terminals A. To isolate protection device from CTs loosen screw C and slide link to lower position.
Open up relay cover. Loosen two retaining bracket screws at top of VIP facia. Withdraw relay and remove secondary wiring.
Remove the 2 , M4 x 20mm pan head screws and washers from the front of the relay cover and the M6 x 20 mm screw from the top of the relay cover.
Remove the crimp terminals from the top of the relay. Rotate the two facia screws behind perspex window to release clamps and withdraw relay.
SCHNEIDER ELECTRIC
23
Installation
Accessing VT's
Accessing VTs
Before accessing the VT enclosure that you check the following: RN2c/RN6c/CN the circuit breaker is in circuit earth and padlocked in its position. Extensible CE/SE range ensure that the incoming supply breaker is padlocked in the open position. Ensure that the VT secondary circuit is isolated and earthed. See pages 71 to 83 for operation instructions.
WARNING
Pull back the V.T. insulating boot, and loosen the top V.T. connection using an 6mm allen key as indicated. Pull back the lower fuse link insulating boot and disconnect the V.T. link.
24
SCHNEIDER ELECTRIC
Installation
Earth fault flow indicator
For C.T.'s mounted inside the cable box, gland insulation is not required. For C.T.'s fitted outside the cable box gland insulation must be fitted. Split core C.T.'s can be installed after the main cable has been made off outside the cable box. However please note gland insulation must be fitted if mounted outside the cable box. Installation instructions for the units are supplied with the ancillary kits.
SCHNEIDER ELECTRIC
25
Installation
Actuators
Procedure for fitting and setting of actuators fitted to the Ringmaster range of switchgear CN2, SN6, CE2, CE6, SE6
1 Fix the actuator to the top mounting bracket ensuring that the distance from the top of the actuator to the top of the mounting bracket is approximately 9mm (as shown in the drawing below) and tighten the fixing screw. Note: this is only an approximate preliminary setting. 2 Also ensure there is approximately 3mm of clearance between the body of the actuator and the facia of the unit (as shown in the drawing below). 3 Rotate the bottom of the actuator in a clockwise direction (if looking from below as shown in the drawing) until resistance against the actuator motor can be felt. 4 Then rotate the actuator in an anti clockwise direction approximately one half of a full rotation making sure that the actuator motor is not rotating (this has the effect of lengthening actuator i.e. gap a on the drawing should increase). 5 Fit the actuator operating bracket assembly to the bottom of the actuator locating the operating bracket spigot in the operating handle socket (as shown in the drawing below) and tighten up the fixing screw. 6 Connect the actuator plug and per form a few electrical operations. 7 Remove the plug and check that the actuator can be withdrawn and replaced with relative ease. 8 If not, adjust the positioning of the actuator by loosening either the mounting bracket or operating bracket and moving either part so that the actuator can be withdrawn easily. Repeat this process until it is possible to withdraw the actuator with relative ease.
IMPORTANT In the event that the actuator fails to complete a closing or opening operation, DO NOT attempt to disconnect the actuator operating bracket spigot from the operating handle socket. Contact Schneider Electric, details on page 3.
26
SCHNEIDER ELECTRIC
Installation
Accessories
Accessories
Available accessories are detailed in the Ringmaster selection guide Ref: MGMV 5337. Accessories will be detailed with individual confirmation orders.
Accessories will be despatched either: s Fitted to the unit within the works, i.e. too bulky or need testing prior to despatch s Loose boxed for assembly on site
Anti-vandal measures Padlock points are provided to prevent un-authorised access to the unit, padlocks can be supplied with the unit if required at the time of enquiry or order.
SCHNEIDER ELECTRIC
27
Installation
Fitting RE2c to Ringmaster range
Remove the 13 off fully tightened M6 x 20 hex head screws (Ref.102) and nylite seals (Ref.103) from the extensible bushing cover top (Ref.2) then remove the extensible bushing cover top. See Fig. 1
102 103
102 103
Fig.1
Remove the 4 off M6 x 20 hex head screws (Ref.102) from the support plate (Ref.5) and remove the support plate complete with the 3 off extensible bushing sleeves and bushing sleeve covers (Ref.1). See Fig. 2
Remove the 2 off M6x20 hex head screws (Ref.102) from the extensible bushing cover bottom (Ref.3) and remove the extensible bushing cover bottom Insert the cable socket studs into the L3, L2 and L1 bushings and tighten up.
102 103
Fig.2
28
SCHNEIDER ELECTRIC
Installation
Fitting RE2c to Ringmaster range
A B
Fig.3
Loosen off hardware at the main door hinge (Ref.C) and slide out the 2 off main door hinge pivots (Ref.D) which retain the main door. See Fig. 4
C D
CAUTION
NOTE: This door is heavy! Care must be taken when removing it.
Fig.4
Remove the M8 & M6 (Ref.E) hardware retaining the lid in position and place lid to one side. See Fig. 5
Fig.5
SCHNEIDER ELECTRIC
29
Installation
Fitting RE2c to Ringmaster range
103 105
Secure in position with 2 off M6 x 20 hex screws (Ref.103) with 1 off M6 nyltite seal (Ref.105) placed over the threads of each. See Fig. 6
Dimple
103 105
Fig.6
Apply phase dots (Ref.122, 123, 124) to the extensible transition plate (Ref.11) just above the extensible bushings. See Fig. 7
122 11
123
124
NOTE: To re-fit lid follow steps in first three paragraphs of blanking kit removal see page 28.
NOTE: When re-fitting lid it is important to replace the correct length screws in each location.
Fig.7
30
SCHNEIDER ELECTRIC
Installation
Fitting RE2c to Ringmaster range
106A
10 106B
Fig.8
111
Smear approximately 1 mm thickness of DC4 silicon compound (Ref.111) around the inside of 3 off bushing sleeves (Ref.23) before inserting them into bushing sleeve securing plate (Ref.22). See Fig. 9
23
22
Fig.9
119 104
Slide bushing sleeve plate assembly over phase bushings and secure in position using 4 off M6 x 25 hex head screws (Ref.104) with nyltite seals (Ref.105) under the heads and a stack of 7 off M6 form C washers (Ref.119) over the threads of each M6 screw between the bushing sleeve plate and the unit. See Fig. 10
Fig.10
SCHNEIDER ELECTRIC
31
Installation
Fitting RE2c to Ringmaster range
106
106
14
101
101
Fig.11
Fasten lengths of EPDM seal strip (Ref.106) around the bend of the extensible trunking lid (Ref.12) as shown in Fig.12 Lay sub assembled extensible left hand side sheet (Ref.14) on one side. Offer sub assembled extensible trunking lid (Ref.12) so the bend is flush with the side sheet. See Fig.12 Secure using 7 off M6 x 20 hex Hd screws (Ref.103) together with 1 off M6 nyltite seal (Ref.105) under the heads of each.
106
14
103 105
12
Fig.12
32
SCHNEIDER ELECTRIC
Installation
Fitting RE2c to Ringmaster range
103 105 12
103 105
103 105
10
Fig.13
121
108
Fig.14
SCHNEIDER ELECTRIC
33
Installation
Fitting RE2c to Ringmaster range
5 4
16 15
3 110
Fig.15
128
107
109
NOTE: Using a tyewrap or similar, insert tyewrap behind econ boot cap (Ref.16) to ensure air is expelled whilst fitting cap. See Fig.16
16
Fig.16
34
SCHNEIDER ELECTRIC
Installation
Fitting RE2c to Ringmaster range
106
Fig.17
Secure all inserts in position using the correct insert tool. See Fig 18.
106
Fasten lengths of EPDM seal strip (Ref.106) around the top of the trunking main body (Ref.13). See Fig. 18
101 13
Fig.18
Offer trunking main body (Ref.13) to the side of the Ringmaster range unit. Secure in position with 16 off M6 x 20 hex Hd screws (Ref.103) and 16 off fully tightened M6 nuts (Ref.112) with 1 off M6 washers (Ref.113) under the heads of each M6 screw and under each M6 nut. See Fig.19 Secure left hand side sheet (Ref.14) and lid sub assembly to trunking main body(Ref.13) and trunking base (Ref.10) with 34 off M6 x 20 hex Hd screws (Ref.103) together with 1 off M6 nyltite seal (Ref.105) under the head of each screw. See Fig. 19
103 105
Fig.19
SCHNEIDER ELECTRIC
35
Installation
Fitting RE2c to Ringmaster range
Final assembly
Offer up blanking plate (Ref.17) to the left hand side (viewed from the front) of the Ringmaster range unit and secure with 2 off 3/16 monobolt (Ref.118). Smear approximately 1mm thickness of DC4 silicon compound (Ref.111) around the stems and dyscon boots (Ref.18) of the Ringmaster range before sliding them into position. NOTE: The lower side of the dyscon boot should face the left hand side of the Ringmaster range unit when viewed from the front. Position the Ringmaster range unit and the extensible unit together so the holes in the main trunking body line up with the holes in the left hand side sheet on the Ringmaster range unit. See Fig 20 NOTE: At this stage the lid on the Ringmaster range unit should be removed to aid access for assembly.
118
17
Fig.20
Secure the main trunking body and left hand side sheet on the Ringmaster range unit in position with 16 off M6 x 20 hex screws (Ref.103) and 16 off M6 nuts (Ref.112) with 1 off M6 washers (Ref.113) under the heads of each M6 screw and under each M6 nut. Fully tighten these components up. NOTE: The orientation of the screws the top row should have the heads facing outwards as in the photo. See Fig. 21
Fig.21
Screw heads
36
SCHNEIDER ELECTRIC
Installation
Fitting RE2c to Ringmaster range
20
21
Offer up the vertical earth bar (Ref.21) to the rear of the Ringmaster range unit. Secure one end to the Ringmaster range unit in front of earth bar (Ref B) and the other end behind the horizontal earth bar (Ref.20) using 1 off M10 x 30 hex Hd screw (Ref.127) with 1 off M10 form A washer (Ref.125) under the head and a further 1 off M10 form A washer (Ref.125) under 1 off M10 hex full nut (Ref.126). See Fig. 22
Fig.22
127
126
125
SCHNEIDER ELECTRIC
37
Installation
Fitting RE2c to Ringmaster range
D 9
Fig.23
38
SCHNEIDER ELECTRIC
Installation
Fitting RE2c to Ringmaster range
19
Slide the 3 off extensible conductor Cap up the busbars and locate in position in the rear of the boots. These caps are not visible in Fig 24 and are part of the bought in, L3, L2 and L1 sub assemblies. Push dyscon dust caps (Ref.19) in the front and top of the dyscon boots (Ref.18). See Fig. 24
109 114
120
At this point perform the three following tests: s High voltage partial discharge test s High voltage frequency test s Resistance test NOTE: For transportation purposes on completion of the above the Ringmaster range side of the busbar assembly must be un-torqued as it is to be fully torqued up when in position on site.
Fig.24
SCHNEIDER ELECTRIC
39
Installation
Fitting RE2c to Ringmaster range
25
Fig.25
40
SCHNEIDER ELECTRIC
Installation
Fitting RE2c to Ringmaster range
Fig.26
131 D
131
116 117
116 117
SCHNEIDER ELECTRIC
41
Installation
Fitting RE2c to Ringmaster range
When unit is in position on site remove dyscon boot caps (Ref.19) from the top of the dyscon boots (Ref.18). See Fig. 27
Fully secure each busbar assembly by torquing the M12 x 40 hex head set screw inside the dyscon boots to 54Nm. See Fig. 27
19
Replace dyscon boot caps (Ref.19) in the top of the dyscon boots (Ref.18).
18
Phase L1 L2 L3
120
42
SCHNEIDER ELECTRIC
Protection
Time fuse link
Protection systems
All circuit breakers can be fitted with various forms of protection system 1. VIP self powered IDMT protection - refer to VIP user guides VIP 30 - provides protection against phase-to-phase faults VIP 35 - provides protection against phase-to-phase faults and earth faults VIP 300 - three phase overcurrent and earth fault protection 2. Time fuse link (TFL) protection system to EA 41-26 (time fuse links to EA 12-6).
Time fuse link protection provides a cost effective way of protecting a transformer of 1600kVA or less. It is a recognised method of protection and the fuses are covered by EA 12-6 (1973). The arrangements in the Ringmaster range is of 2 phase overcurrent and earth fault.
TFL selection
Schneider Electric recommend TFL sizes in accordance with the table below. The table also includes our recommendations for the maximum LV fuse size to ensure discrimination. Note that the size of this fuse is less than the full load current of the transformer, however, it would normally be expected to have a number of LV fuses fed from the LV side of the transformer.
Important note: Please ensure TFL fuses are fitted prior to energising the equipment.
WARNING
TLF protection will not work correctly unless the recommended fuses are fitted.
500 15A 400A 10A 400A 10A 400A 15A 400A 7.5A 400A 5A 400A 5A 400A
1000 -
1250 -
1600 TFL LV fuse TFL LV fuse TFL LV fuse TFL LV fuse TFL LV fuse TFL LV fuse TFL LV fuse TFL LV fuse
6.6
5A 150A
11
3A 200A
13.8
3A 200A
CT ratio = 100/5
3.3
5A 150A
6.6
12.5A 15A 560A 7.5A 560A 7.5A 560A 560A 10A 630A 10A 630A
11
13.8
SCHNEIDER ELECTRIC
43
Protection
Operation
Operation
The circuit consists of 3 dual ratio C.T.'s, 2 Direct Acting Trip (DAT) solenoid type overcurrent coils connected in parallel with associated Time Fuse Links (TFL's) and 1 instantaneous earthfault DAT solenoid Coil. Under normal load conditions on, say an 11000 volt 1000KVA transformer, 52 amps will flow in the C.T. primaries (1000kVA(11kv/3). If the C.T. ratio is set on 50/5 Amp ratio, then approximately 5 Amps will flow in the C.T. Secondaries. As the overcurrent coils are shorted out by the fuses, no current will flow through the coils. Assuming that there was no earth leakage, the red, yellow and blue phases will balance, and no current will flow through the earth fault coil. In the event of a phase to phase fault of, say, 500 Amps, 50Amps would flow through the C.T. secondaries. This would blow the 15Amp fuse links shunting all of the current through the DAT coils, which would operate and trip the 3 phase circuit breaker. The tripped on fault flag would operate, and the CB would have to be re-set and the fuses replaced. Two overcurrent coils are required to cover all phase fault combinations, i.e. for a R-Y phase fault, the CB will trip on the red phase coil. Under earth fault conditions, there will be an imbalance between the red, yellow and blue phases, and current will flow down the residual path of the C.T.'s and through the earth fault coil. The unit will trip instantaneously. If a TFL is fitted in parallel with the earthfault coil then the tripping time will follow the TFL characteristics. Alternatively, the fuse can be removed.
Terminal block
C11 C31 C51
50/5A Ratio
R1 Y1 B1
EARTH FAULT TFL (IF FITTED) C11 C 31 P1 S1 S2 P2 S3 100/5A RATIO C110 C130
C150
C12 RED O/C COIL C32 BLUE O/C COIL C52 EARTH FAULT COIL
C 51
44
SCHNEIDER ELECTRIC
Protection
Operation
Dual ratio 100/50/5Amp C.T.'s are fitted as standard, to the Ring Main Units and 200 Amp circuit breakers with TFL protection. Selection of the appropriate C.T. ratio can be easily achieved by moving the auxiliary link in the pilot cable box. Note that the circuit must be off load when changing ratios.
WARNING
Current transformers (T200E and earth fault flow indicator) that are not going to be used during commissioning or during service, they must be shorted out otherwise irreversible damage may occur to current transformers and/or the unit.
SCHNEIDER ELECTRIC
45
Protection
VIP 300
3 C B
4 A
10
phase overcurrent
I>
I>
VI SI RI DT off EI
DT only
1.8 1.5 1.2 1 2.1 2.4 2.7
I>>
9 6 4 3 12 15 20
VIP300
VIP 300 Equivalent Time Settings Multiplier
t> to>
0.05 0.07 0.1 0.15 0.2 0.3 0.4 0.05 0.6 0.07 0.1 0.15 0.2 0.3 0.4 0.6 x1 x1 x1 x1 x1 x1 x1 x10 x1 x10 x10 x10 x10 x10 x10 x10
SI
0.02 0.02 0.03 0.05 0.07 0.10 0.13 0.17 0.20 0.24 0.34 0.50 0.67 1.01 1.35 2.02
VI
0.03 0.05 0.07 0.10 0.13 0.20 0.27 0.33 0.40 0.47 0.67 1.00 1.33 2.0 2.67 4.00
EI
0.06 0.09 0.12 0.19 0.25 0.37 0.50 0.62 0.74 0.87 1.24 1.86 2.48 3.71 4.95 7.43
curve selection
(x Is)
(x Is) off
trip
42 48 56 36 64 30 72 24 80 20 100 90 (A)
warning
not time multiplier
Is
reset
minimum operating phase current: 20A
t> Io>
VI SI RI
(s)
0.6
see table
t>> Io>>
(s)
1.5
DT only
EI 1.5 off 1.2 1 1.8 2.1 2.4 2.7
9 6 4 3
12 15 20
trip
DT
(x Ios) 3
(x Ios) off
curve selection
Io>
16 24 32 12 40 8 50 4 60 2 80 70 (A)
0.15 0.2 0.1 0.07 0.05 (s) 0.3 0.4 0.6 x10 x1
warning
not time multiplier
earth fault
Ios
to>
see table
to>>
(s)
D 11 12 13 14 15 17 18 16 19 20
Other functions
A. B. C. D. E.
Current setting scale label. Current transformer and range information. Indicator reset button. Minimum operating current. VAP6 test plug socket.
46
SCHNEIDER ELECTRIC
Protection
VIP 300
WARNING
VIP 300 relay will not work without the appropriate settings
G SI, VI, EI RI
t>
K t>> L
Is F
1.2 Is
10 Is
I>>
DT curve selection
t G
H t>
DT
Operation
K t>> L
The high and low set elements operate separately. The tripping order results from the logical OR between the two settings.
Is 1.2 Is F
I>
I>>
SCHNEIDER ELECTRIC
47
Protection
VIP 300
Phase overcurrent
phase overcurrent
I>
I>
VI SI RI DT off EI
DT only
1.8 1.5 1.2 1 2.1 2.4 2.7
VIP300
9 12 15 20
6 4 3
t> to>
0.05 0.07 0.1 0.15 0.2 0.3 0.4 0.05 0.6 0.07 0.1 0.15 0.2 0.3 0.4 0.6 x1 x1 x1 x1 x1 x1 x1 x10 x1 x10 x10 x10 x10 x10 x10 x10
SI
0.02 0.02 0.03 0.05 0.07 0.10 0.13 0.17 0.20 0.24 0.34 0.50 0.67 1.01 1.35 2.02
VI
0.03 0.05 0.07 0.10 0.13 0.20 0.27 0.33 0.40 0.47 0.67 1.00 1.33 2.0 2.67 4.00
EI
0.06 0.09 0.12 0.19 0.25 0.37 0.50 0.62 0.74 0.87 1.24 1.86 2.48 3.71 4.95 7.43
curve selection
(x Is) 3
(x Is) off
trip
42 48 56 36 64 30 72 24 80 20 100 90 (A)
warning
not time multiplier
Is
reset
t>
(s)
0.6
see table
t>>
(s)
1.5
All information concerning the phase overcurrent is grouped together in the upper half of the front panel. The section numbers below are related to the numbering on the drawing shown on page 46.
the value shown is the low set time delay. s For IDMT curves the value displayed is the tripping time for a phase current equal to 10 x Is.
4 Setting current Is
The setting depends on the current transformer (CT) used, and the range selected via the connections made to the back of the relay. The scale label inserted should match the CT and range selected. The switch can then be positioned to the primary current magnitude required in amperes.
48
SCHNEIDER ELECTRIC
Protection
VIP 300
Earth fault
reset
minimum operating phase current: 20A
DT only
1.8 2.1 2.4 2.7
Io>>
9 6 4 3 12 15 20
trip
DT
(x Ios) 3
(x Ios) off
curve selection
Io>
16 24 32 12 40 8 50 4 60 2 80 70 (A)
0.15 0.2 0.1 0.07 0.05 (s) 0.3 0.4 0.6 x10 x1
warning
not time multiplier
earth fault
Ios
to>
see table
to>>
(s)
If the DT curve is selected, the value shown is the low set time delay. For IDMT curves the value displayed is the tripping time for a phase current equal to 10 x Ios.
SCHNEIDER ELECTRIC
49
Protection
VIP 300
Other functions
Reversible scale label for Ringmaster fitted with 200/1A CTs
Is
48 42 56 36 64 30 72 24 80 20 100 90 (A) minimum operating phase current: 20A
Is
96 84 112 72 128 60 144 48 160 40 200 180 (A) minimum operating phase current: 40A
Ios
24 16 32 12 40 8 50 4 60 2 80 70 (A)
Ios
48 32 64 24 80 16 100 8 120 4 160 140 (A)
the phase overcurrent and earth fault primary amp settings. It is inserted from the top, behind the transparent part of the front panel. s The label is reversible and is printed with the x2 range setting currents on one side, and the x4 range setting currents on the other. The scale label when inserted should match the CT and terminal positions on the rear of the relay, for the range required. Also refer to testing and commissioning.
The CT and range are given on each side of the setting scale label. The label will match the appropriate CT for the Ringmaster panel type supplied. This information is hidden when the label is inserted.
Is
96 84 112 72 128 60 144 48 160 40 200 180 (A) minimum operating phase current: 40A
Is
192 168 224 144 256 120 288 96 320 80 400 360 (A) minimum operating phase current: 80A
Ios
48 32 64 24 80 16 100 8 120 4 160 140 (A)
Ios
96 64 128 48 160 32 200 16 240 8 320 280 (A)
given on the top of the label matches: 1 - The current transformer used: 200/1A, 400/1A or 800/1A 2 - The range used. x2 or x4 This information is hidden when the label is in position.
s For help with the choice of range
x 2 range
x 4 range
Installation
s Slide the setting scale into
Is
192 168 224 144 256 120 288 96 320 80 400 360 (A) minimum operating phase current: 80A
Is
384 336 448 288 512 240 576 192 640 160 800 720 (A) minimum operating phase current: 160A
Ios
96 64 128 48 160 32 200 16 240 8 320 280 (A)
Ios
192 256 128 96 320 64 400 32 480 16 640 560 (A)
position behind the transparent part of the front face. s Make sure the label is pushed right into the bottom of the slot. To remove the label, use the hole in the top, if necessary with the help of the tip of a pencil or a screwdriver.
x 2 range
x 4 range
50
SCHNEIDER ELECTRIC
Protection
VIP 300
SCHNEIDER ELECTRIC
51
Protection
VAP6
+
I>
on battery test
A B C 4
1 2 3
The VAP6 is a portable unit which is connected to the VIP 300 to carry out simplified testing. The test can be carried out in the following two cases: - the VIP 300 is already powered up by the sensors (CTs). - The VIP 300 is not supplied. In this case, the VAP6 batteries supply power to the relay.
Indicators
A s On: Indicates that the batteries are operating. Also lights up when the battery test is carried out by pressing battery test. B s Test in progress: Confirms sending of the test stimulus to the VIP 300. C s Trip: Is used to test other relays in the VIP range. It is not to be considered for the VIP 300 test (it lights up for a transient period when the VIP 300 sends a tripping order; whether or not the circuit breaker is inhibited). D s External MITOP output: This feature may be used to connect an external MITOP trip coil which could be used to operate a timer etc. The external coil is triggered at the same time as the circuit breaker MITOP. The trip inhibit button does not effect the external coil.
Push buttons:
trip inhibition earth fault
trip
trip inhibition
external mitop
1 s Battery test: If the batteries are healthy, the on indicator(A) lights up when the button is pressed. 2 s Phase overcurrent: Sends the phase overcurrent test stimulus, which is equivalent to 20 times the setting current Is. 3 s Earth fault: Sends the earth fault test stimulus, which is equivalent to 20 times the earth setting current Ios. 4 s Trip inhibition: By pressing and holding this button down the relay can be tested with the VAP6 without tripping the circuit breaker. This facility will inhibit the circuit breaker tripping even if a real fault occurs during the test.
VAP6
Batteries:
s
The batteries are normally deactivated and are automatically activated when the VAP6 is connected to the VIP 300. They are activated in the following cases: - Pressing the battery test button. - Direct connection to a VIP 300 relay. To install or change the batteries, open the unit by removing the 4 screws on the bottom of the unit. Be sure to use the correct polarities.
Technical characteristics:
Supply: Weight: Dimensions: 3 x 9V 6LR61 batteries 0.45KG 93 X 157 X 45mm
52
SCHNEIDER ELECTRIC
Protection
VAP6
The test may be carried out with or without the relay energised by the Ringmaster current transformers, and all the relay settings are effective. During the test, the relay remains operational and will give a tripping order in the event of a fault, unless the trip inhibit button is pressed and held down.
The test consists of: - Initiation of the VIP 300 self monitoring and diagnostic routine. - Injecting a stimulus to stimulate a phase fault. - Check tripping The VAP6 is supplied by batteries. Therefore the parts of the VIP 300 that run on AC current are not checked using this method (input and supply circuits). Press the phase overcurrent button to send the test stimulus. - Continue pressing the button throughout the duration of the stimulus. The stimulus represents about 20 times the setting current Is. -The VAP6 test in progress indicator lights up to confirm the sending of the stimulus to the VIP300 relay. - The red I> indicator of the VIP300 blinks during the time relay delay period. - Then the VIP 300 phase trip indicator turns yellow. - The circuit breaker trips if it is not inhibited. N.B. If the phase overcurrent button is held down after tripping, the VIP300 starts the time delay/tripping cycle again; this is normal operation. In that case: - The VAP6 red trip indicator lights up for a transient period each time there is a trip. - Depending on the time delay setting, the VIP 300 red I> indicator may be off or blink rapidly and/or in an irregular manner. Press earth fault to test the relays operation. The stimulus injected is equal to 20 times the setting current Ios. Use the procedure as for the phase overcurrent test. Disconnect the VAP6. In order to save batteries, do not leave the VAP6 connected to the relay unnecessarily.
Connect the VAP6 to the VAP6 test plug. The VAP6 batteries are activated and the on indicator lights up. Press the trip inhibition button if the test should be carried out without tripping the circuit breaker. Be sure to continue pressing the trip inhibition button throughout the time it takes to send the stimulus.
SCHNEIDER ELECTRIC
53
Commissioning
Checks and tests
Commissioning
All equipment is subject to stringent quality and operational checks prior to despatch. However it is the owners responsibility to ensure that commissioning tests have been completed to IEC60694. The following is a resume of those tests. Remove all packaging and transit labels from the equipment. Check the data plate details against the specification. Check the operation of the switches/circuit breaker, test access and various interlocks. Check confirmation of auxiliary switch contacts and remote indication in accordance with the schematic diagram. Confirm the phase relationship of the neon indicator sockets. Check the pick up voltage of auxiliary coils if fitted, a.c. coils should operate between 85% and 110% of the rated voltage, d.c. coils should operate between 70% and110% of the rated voltage.
Note: All voltages should be applied instantaneously unless otherwise specified.
Physical checks
Functional checks
Connect the H.V. test set as shown in the diagrams an carry out the withstand tests in accordance with the following tables.
R2 Y2 B2
R3 Y3 B3
FRONT
R1 Y1 B1 RN2c/RE2c/RN6c
RN2c B1 Y1 R1
R2 Y2 B2 CE2/CE6/SE6 or SN6/CN2
54
SCHNEIDER ELECTRIC
Commissioning
Tests
Test connection - circuit breaker/switch - CE2/CE6/SN6 test number 1 2 3 4 5 6 CB / switch closed closed closed closed open open live terminals R, Y, B R, Y Y, B B, R R1, Y1, B1 R2, Y2, B2 earthed terminals frame B, frame R, frame Y, frame R2, Y2, B2, frame R1, Y1, B1, frame
Test connection - ring main unit - RN2c/RN6c test number 1 2 3 4 5 6 ring switch 1 closed closed closed closed open open ring switch 2 closed closed closed closed open open circuit breaker closed closed open open closed closed live terminals R1, B1 Y1 R1, Y1 B1 R2, Y2, B2 R2, Y2, B2 R1, Y1, B1, R3, Y3, B3 earthed terminals Y1, frame R1, B1, frame R2, Y2, B2, frame R1, Y1, B1, frame R1, Y1, B1, R3, Y3, B3 frame R2, Y2, B2, frame
SCHNEIDER ELECTRIC
55
Commissioning
Tests
x
R2, Y2, B2 R2, Y2, B2
Diagram of connections - RN2 Diagram of connections circuit breaker / switch
CAUTION
When applying AC/DC test voltages greater than 12kV additional insulation must be added to the bushing sleeve to prevent damage. The bushing sleeve is designed to be used in conjunction with some additional method of insulation, such as econ boot or heatshrink termination boots. Due to the compact design of the bushing, permanent damage could result from high voltage stress if additional insulation is not used during testing.
56
SCHNEIDER ELECTRIC
Commissioning
Tests
All secondary wiring has been 2kV insulation tested at our works. We therefore recommend that testing on site is done with a 1,000 volt megger and not re-stressed at 2kV.
Select phase
Remove all earth connections and test the wiring to earth. For units fitted with a VIP relay please refer to the VIP user guide.
R1 Y1 B1
Select phase
50/100A a.c.
S3
50/5A Ratio
A
0 - 5A
R2
Y2
B2
SCHNEIDER ELECTRIC
57
Commissioning
Tests
Select phase
R1 Y1 B1
Select phase
50/5A Ratio
-ve
mA
+ve
d.c. milliammeter
R2
Y2
B2
58
SCHNEIDER ELECTRIC
Commissioning
Tests
R1 Y1
Three phase shorting link
(100A rated)
B1
Select phase
C250
50/5A Ratio
mA
50/100A a.c. Removable Earth Link 0 - 10mA a.c.
R2
Y2
B2
SCHNEIDER ELECTRIC
59
Commissioning
Tests
R1 Y1
B1
Select phase
C250
50/5A Ratio
R2
Y2
B2
Out cct
B R R B B R
60
SCHNEIDER ELECTRIC
Commissioning
Tests
R1 Y1 B1
0-50A a.c.
S3
5 6 7
50/5A Ratio
R2
Y2
B2
C.T. ratio
50/5A 50/5A 50/5A 100/5A 100/5A 100/5A
trip levels
20 - 26.5 A 20 - 26.5 A 20 - 26.5 A 25 - 31 A 25 - 31 A 25 - 31 A
C.T. ratio
50/5A 50/5A 50/5A 100/5A 100/5A 100/5A
trip levels
19 - 28 A 19 - 28 A 19 - 28 A 24 - 33 A 24 - 33 A 24 - 33 A
SCHNEIDER ELECTRIC
61
Commissioning
Tests
R1
Y1 B1
0 - 5A a.c.
4 5 6 7
50/5A Ratio
R2
Y2
B2
Out cct
B R R B B R
62
SCHNEIDER ELECTRIC
Commissioning
Tests
R1
Y1 B1
Select phase
0 - 5A a.c.
Earth fault TFL (if lifted)
4 5 6 7
50/5A Ratio
R2
Y2
B2
C.T. ratio
50/5A 50/5A 50/5A 100/5A 100/5A 100/5A
trip levels
2.0 - 2.65 A 2.0 - 2.65 A 2.0 - 2.65 A 1.25 - 1.55 A 1.25 - 1.55 A 1.25 - 1.55 A
C.T. ratio
50/5A 50/5A 50/5A 100/5A 100/5A 100/5A
trip levels
1.7 - 2.8 A 1.7 - 2.8 A 1.7 - 2.8 A 1.1 - 1.65 A 1.1 - 1.65 A 1.1 - 1.65 A
SCHNEIDER ELECTRIC
63
Commissioning
Tests
1 Remove C70 test link. 2 Remove ratio link. 3 Increase test voltage to 1.3 x the knee point voltage. 4 Decrease voltage to the appropriate knee point voltage (detailed below) for the respective CT ratio under test. Ratio Knee point voltage Typical magnetisation current 470mA + - 10% 940mA + - 10%
64
SCHNEIDER ELECTRIC
Commissioning
Commissioning Ringmaster with VIP 300
Factory tests:
All Ringmaster panel types are fully tested before leaving the factory. These tests include the whole protection system including current transformers, wiring harness, relay, trip coil and the circuit breaker itself using primary injection to energise the system. Tripping tests are carried out using different settings for each of the IDMT and DT curves available on the relay. The tripping times are measured with a chronometer and its accuracy is verified against the theoretical times calculated. Since the system is fully tested it is only necessary to prove the relay on site at the service settings, therefore reducing commissioning time to a minimum. Once the switchgear has been installed and cabled up, it is impractical or sometimes impossible to carry out injection tests. It is suggested that for commissioning and maintenance purposes either of the following two methods can be used. 1. Simple trip test using the VAP6 test unit (described previously). 2. Secondary injection using standard equipment with an output filter. Testing using secondary injection is used to test the following parts of the protection system: s The electronic circuit. s s The integrity of the power supply of the VIP 300. The link to the mitop trip coil and also the circuit breaker mechanical tripping mechanism. s The integrity of the switches on the front panel to ensure they give the correct tripping times for the curves selected.
Reduced commissioning
Secondary injection
The injection set is connected to the VIP 300 relay without disconnecting the CTs. This is done via the sockets on the terminal rail located in the pilot cable box, just above the relay itself. To test the overcurrent protection the connection should be made across two CTs (terminal rails nos 4 to 5, 5 to 6 or 6 to 4). To test the earth fault protection, the connection should be made across one CT (terminal rail nos 4 to 7, 5 to 7, or 6 to 7). These terminal numbers should be cross checked with the relevant circuit breaker schematic diagram. Terminals 15 and 16 (not shown above - see Ringmaster selection guide) give access to a normally open contact, which is normally open when the CB is in the open position. This can be used to connect a timing device to measure the opening time of the relay and circuit breaker. The type of test plug used to connect to the DIN rail connectors is a standard 2mm 19A test plug. s The MITOP trip coil must be used only in conjunction with the VIP relay. s Voltage withstand testing of the a u x i l i a r y and control circuits at 2000V AC for 1 minute should never be carried out without disconnecting the MITOP trip coil or VIP relay. s Secondary injection facilities are provided on the terminal rail in the pilot cable box. s No external connections should be made to the VIP 300 or theMITOP trip coil.
52
7 5 minimum 3 current 1
x4 range 40A,80A or 160A operating
CAUTION
Note: When using a secondary injection set with VIP 300 a filter (e.g. Foster SF30) should be used to improve the wave form. If a filter is not used the operating time of the relay may not follow the theoretical operating times.
C11 C31
P1 S1 S2 P1 S1 P1 S1
4 5 6 7 8 9
8
x2 range 20A,40A or 80A minimum operating 4 current
C51 C10
CT1
P2
R
S2 P2
Y
S2 P2
B
S2
C70
10
N.B. - Always check against the relevant CB schematic diagram before carrying out tests MITOP - CB trip coil
MITOP - ITC
K8 K7
(-VE) (+VE)
15 16
CB auxiliary contact
(for timing purposes)
SCHNEIDER ELECTRIC
65
Commissioning
Commissioning Ringmaster with VIP 300
The test procedure outlined here is only a guide and may need modifying to suit the different test sets available. The manufacturers instructions should be read before attempting to secondary inject the VIP 300 relay. The VIP 300 relay can be secondary injected like any conventional 1A relay, therefore the output recommended for 1A relays should be used. Calculate the secondary current to be injected from the equivalent primary current, taking into account the CTs used and the range selected by connections to the terminals on the back of the relay. With the VIP 300 connected so as to present the correct burden, the following tests can be carried out: 1. Pick-up check - Increase the current slowly until the appropriate LED indicator starts to blink. Setting check: - Set the current to be injected (a true RMS ammeter should be used to measure the current). - The CB should then be closed and the counter/timer reset. The current should then be applied. - When the CB has operated, the applied current should be turned off if not done automatically. - The time shown on the counter display includes the operating time of the circuit breaker >80ms or <100ms. The actual relay operating time can then be calculated by subtracting this time from the counter reading.
2.
Note: No connection should be made to the MITOP trip coil from the secondary injection test set.
Range x 4
Minimum Operating Current=40A
Secondary injected current Equivalent primary current
Range x 4
Minimum Operating Current=80A
Secondary injected current Equivalent primary current
Range x 4
Minimum Operating Current=160A
Secondary injected current Equivalent primary current
100mA 120mA 150mA 180mA 210mA 240mA 280mA 320mA 360mA 400mA 450mA 500mA
20A 24A 30A 36A 42A 48A 56A 64A 72A 80A 90A 100A
200mA 240mA 300mA 360mA 420mA 480mA 560mA 640mA 720mA 800mA 900mA 1A
40A 48A 60A 72A 84A 96A 112A 128A 144A 160A 180A 200A
100mA 120mA 150mA 180mA 210mA 240mA 280mA 320mA 360mA 400mA 450mA 500mA
40A 48A 60A 72A 84A 96A 112A 128A 144A 160A 180A 200A
200mA 240mA 300mA 360mA 420mA 480mA 560mA 640mA 720mA 800mA 900mA 1A
80A 96A 120A 144A 168A 192A 224A 256A 288A 320A 360A 400A
100mA 120mA 150mA 180mA 210mA 240mA 280mA 320mA 360mA 400mA 450mA 500mA
80A 96A 120A 144A 168A 192A 224A 256A 288A 320A 360A 400A
200mA 240mA 300mA 360mA 420mA 480mA 560mA 640mA 720mA 800mA 900mA 1A
160A 192A 240A 288A 336A 384A 448A 512A 576A 640A 720A 800A * * *
66
SCHNEIDER ELECTRIC
Commissioning
Commissioning Ringmaster with VIP 300
Setting range, minimum operating current x2, 20A x4, 40A x2, 40A x4, 80A x2, 80A x4, 160A
Note: Ensure connections on the rear of the relay are made to the appropriate terminals for the x2 or x4 setting ranges and that the scale labels are inserted correctly to match the range selected. Indicate on the diagram below actual settings. Carry out tests and record the results in the table provided. 200/1A
sensor 200/1: 4509996A0 VIP 300LH range: x2 sensor 200/1: 4509996A0 VIP 300LHrange: x4
400/1A
sensor 400/1: 451101200 VIP 300LH range: x2 sensor 400/1: 451101200 VIP 300LHrange: x4
800/1A
sensor 800/1: 4509169A0 VIP 300LH range: x2 sensor 800/1: 4509169A0 VIP 300LHrange: x4
Is
Is
96 84 112 72 128 60 144 48 160 40 200 180 (A) minimum operating phase current: 40A
Is
96 84 112 72 128 60 144 48 160 40 200 180 (A) minimum operating phase current: 40A
Is
192 168 224 144 256 120 288 96 320 80 400 360 (A) minimum operating phase current: 80A
Is
192 168 224 144 256 120 288 96 320 80 400 360 (A) minimum operating phase current: 80A
Is
384 336 448 288 512 240 576 192 640 160 800 720 (A) minimum operating phase current: 160A
68
Ios
24 16 32 12 40 8 50 4 60 2 80 70 (A)
Ios
48 32 64 24 80 16 100 8 120 4 160 140 (A)
Ios
48 32 64 24 80 16 100 8 120 4 160 140 (A)
Ios
96 64 128 48 160 32 200 16 240 8 320 280 (A)
Ios
96 64 128 48 160 32 200 16 240 8 320 280 (A)
Ios
192 256 128 96 320 64 400 32 480 16 640 560 (A)
Setting scale label selection to be located at point A for appropriate CT type 200/1A, 400/1A & 800/1A
phase overcurrent
I>
I>
VI SI RI DT off EI
DT only
1.8 1.5 1.2 1 2.1 2.4 2.7
I>>
9 6 4 3 12 15 20
VIP 300
VIP 300 Equivalent Time Settings Multiplier
t> to>
0.05 0.07 0.1 0.15 0.2 0.3 0.4 0.05 0.6 0.07 0.1 0.15 0.2 0.3 0.4 0.6 x1 x1 x1 x1 x1 x1 x1 x10 x1 x10 x10 x10 x10 x10 x10 x10
SI
0.02 0.02 0.03 0.05 0.07 0.10 0.13 0.17 0.20 0.24 0.34 0.50 0.67 1.01 1.35 2.02
VI
0.03 0.05 0.07 0.10 0.13 0.20 0.27 0.33 0.40 0.47 0.67 1.00 1.33 2.0 2.67 4.00
EI
0.06 0.09 0.12 0.19 0.25 0.37 0.50 0.62 0.74 0.87 1.24 1.86 2.48 3.71 4.95 7.43
(x Is) 3
(x Is) off
trip
0.15 0.2 0.1 0.07 0.05 0.3 0.4 0.6 x10 x1
warning
not time multiplier
t>
reset
see table
t>> Io>>
(s)
1.5
Io>
VI SI RI off EI
DT only
1.8 1.5 1.2 1 2.1 2.4 2.7
9 6 4 3
12 15 20
trip
DT
(s)
(x Ios) off
curve selection
0.15 0.2
Io>
warning
not time multiplier
earth fault
to>
see table
to>>
(s)
SCHNEIDER ELECTRIC
67
Commissioning
Commissioning Ringmaster with VIP 300
Curve............... Phase A-B 1. Pick-up current at setting 2. Operating time and curve at final selected setting 3. Current level to trip high set
Curve........... T.............. EF
Commissioning engineer
Date
Customer witness
Date
68
SCHNEIDER ELECTRIC
Ringmaster operation
RN2c, RE2c, RN6c essential checks
DANGER
Do not operate this equipment if needle is in the red zone or at zero. Equipment must be isolated and earth before removing any external covers. Please refer to your local Schneider Electric office or UK customer service team, contact details can be found atthe front of this document. The option of voltage presence indicator (VPIS) system must be used as indication only. It should not beused as absolute proof of isolation. Do not earth a live cable which is being fed from the remote end. Check voltage of the respective breaker/switch before any operation of a Ringmaster unit. Failure to follow these instructions may result in personal injury.
!
WARNING
DO NOT OPERATE THIS EQUIPMENT IF THE NEEDLE IS IN THE RED ZONE OR AT ZERO. EQUIPMENT MUST BE EARTHED BEFORE REMOVING ANY EXTERNAL COVERS. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN PERSONAL INJURY.
Prior to energising
It is recommended that to energising the unit all protection devices are checked to ensure they are set correctly. For TLF units ensure that fuses are fitted. VIP units must be set in accordance with the results of a protection co-ordination study.
WARNING
Note: This manual covers ring main units produced from June 1999, designated RN2c/RN6c/RE6c. For ring main units designated RN2/RN6 see earlier manual Ref: version 005 December
SCHNEIDER ELECTRIC
69
Ringmaster operation
Main features
Key
1 2 3 4 5 6 7 8 9 facia operating handle (padlockable)
2
auxiliary/Protection LV compartment test access key data plate main circuit label gas pressure indicator tripped on fault flag main earth selector lever
4 3 5 1
RN2c
6 8 7
operating handle
Note: The operating handle can be used in two positions: 1. With the handle protruding outside the unit dimensions. 2. With the handle within the constraints of the unit.
70
SCHNEIDER ELECTRIC
Ringmaster operation
Switch and circuit breaker
Lift up hinged door. Check that the gas indicator is in the green, "healthy condition". Check the facia diagram for the service condition. Remove padlocks if fitted.
Move selector to "Main Switch/Circuit breaker" position. To operate selector slide padlock sleeve towards selector pivot point and rotate selector to required position.
Insert handle as shown, aligning handle profile and direction of operation (arrow) to unit operational socket, for direction of operation. Firmly operate, in a rotational movement, the operating handle until the circuit breaker/switch closes.
Note:
To operate to the main on position the operating handle must be rotated in a clockwise direction for the circuit breaker/right hand ring switch and in an anti-clock wise direction for the left hand ring switch (as marked on the unit facia).
The selector lever will be locked in the main switch/circuit breaker position when in the closed in service position.
Padlock fitted to circuit breaker/main switch in the close in service position. To open, remove closed in service position padlock, if fitted, rotate handle through 180 and reverse procedure.
Note: The fitting of padlocks does not affect the electrical tripping of the unit.
SCHNEIDER ELECTRIC
71
Ringmaster operation
Earth switch
Lift up hinged door. Check that the gas indicator is in the green, "healthy condition". Check the facia diagram for the off service condition. Remove padlocks if fitted. Move selector to Earth Switch position. To operate selector slide padlock sleeve towards selector pivot point and rotate selector to required position.
Note:
Insert handle as shown, aligning handle profile and direction of operation (arrow), to unit operational socket for direction of operation. Firmly operate, in a rotational movement, the operating handle until the earth switch closes.
The selector lever will be locked in the earth switch position when in the closed in earth position.
To operate to the earth on position the operating handle must be rotated in an anti-clockwise direction for the circuit breaker/right hand ring switch and clockwise direction for the left hand ring switch (as marked on the unit facia).
Padlock fitted to earth switch in the closed in earth position. To open, remove closed in earth position padlock, if fitted, rotate handle through 180 and reverse procedure.
Note: The unit will not electrically trip if an earth is applied onto a fault.
72
SCHNEIDER ELECTRIC
Ringmaster operation
Cable testing
Open LV compartment by depressing lever on lower edge of LV compartment. Remove padlock if fitted, at this point.
Key way Ensure that the main earth switch is in the earth on position. This will open the key way.
Pull test access cover down, utilising operating handle, to remove cable earth and provide access to the testing bushings (marked with red, yellow and blue phase dots).
The test access key will be locked in position until the cover is firmly closed. Reverse procedure to return to service condition. Note: ensure cables are
discharged before touching bushings after testing.
SCHNEIDER ELECTRIC
73
Ringmaster operation
Cable testing
Ensure that the CB earth switch is in the earth on position. This will open the key way for the test key.
The test key is located on the RN6c fascia as shown above. To remove the key, turn the black lever 90 anti-clockwise.
Insert the test key as shown and turn the black lever 90 in a clockwise direction to lock in position.
Remove test access padlock (if fitted). Whilst holding black lever of test key down, raise the CB test access cover. Note that some resistance will be encountered.
Lift CB test access cover clear of test contacts. Note that the test key is now locked in position until the access cover is firmly closed. Reverse procedure to return CB to service.
74
SCHNEIDER ELECTRIC
Ringmaster operation
Circuit breaker reset
Following a circuit breaker electrical trip/tripped on fault operation the tripping spring has to be reset prior to a close operation. The orange tripped on fault flag (indicated with arrow) will be displayed following the electrical trip.
Insert handle as shown, aligning handle profile and direction of operation (arrow) to unit operational socket, for direction of operation. Firmly operate, in an anti-clockwise rotational movement, the operating handle until the orange tripped on fault flag changes to the white normal service condition, and the handle reaches the end stop.
On the resetting of the flag to white allow the operating handle to return clockwise to the off position. To close the circuit breaker to the service/earth condition, refer to relevant section regarding manual operation.
When a trip operation has occured, the motor intelligence will automatically reset the circuit breaker.
Note: To manually reset circuit breaker remove motorpack and follow above procedure.
SCHNEIDER ELECTRIC
75
Ringmaster operation
Motorpack
Prior to connecting the motorpack check the facia diagram for service conditions. The service selector padlock, if fitted, can remain fitted with the application of the motorpack.
Note: The motorpack can only be fitted when the main switch/circuit breaker position is selected and not when the earth position is selected.
Align both the motorpack male drive shaft and the electrical connector with the female switch operating socket and electrical connector on the unit facia.
Note: The motorpack can be removed and replaced in both the Main On and Main Off service conditions.
Offer motorpack to unit until full engagement of both the drive and electrical connection are achieved. For electrical operation of the motorpack with Easergy T200E refer to the Easergy T200E manual.
Note:
Only manual operation of the earth switch can be undertaken. To operate earth switch remove motorpack and follow manual operation of earth switch instructions.
The motorpack protection fuse is located at the bottom right hand corner as above when the motor is removed.
The motorpack is fitted with a manual drive, to release mechanism spring tension, should the motor fail during electrical operation. Remove allen screws (indicated with arrows) on motorpack cover to access manual drive screw.
76
SCHNEIDER ELECTRIC
Ringmaster operation
Motorpack operation
voltage 24V d.c. 24V d.c. 24V d.c. + 30% - 10% + 30% - 10% + 30% - 10%
current 4A 4A 3.5A
Values given are typical and may vary slightly between units.
SCHNEIDER ELECTRIC
77
Ringmaster operation
Neon indication
Neon indication
Neon indication can be fitted as an optional item on the ring switches and circuit breaker on the RN2c. The test sockets are located in the pilot cable box.
A garter spring is fitted to the relevant cable bushing which forms a capacitive coupling with the HV conductor, deriving the neon voltage.
Note: Circuit breaker neons cannot be fitted to transformer mounted units. Note: To achieve correct reading when using a phase comparitor please use Pfisterer Electronic Phase Comparator EPV LRM System No.827 189-007 (available as kit RMR-A25)
78
SCHNEIDER ELECTRIC
DANGER
Do not operate this equipment if needle is in the red zone or at zero. Equipment must be isolated and earth before removing any external covers. Please refer to your local Schneider Electric office or UK customer service team, contact details can be found atthe front of this document. The option of voltage presence indicator (VPIS) system must be used as indication only. It should not be used as absolute proof of isolation. Do not earth a live cable which is being fed from the remote end. Check voltage of the respective breaker/switch before any operation of a Ringmaster unit. Failure to follow these instructions may result in personal injury.
!
WARNING
DO NOT OPERATE THIS EQUIPMENT IF THE NEEDLE IS IN THE RED ZONE OR AT ZERO. EQUIPMENT MUST BE EARTHED BEFORE REMOVING ANY EXTERNAL COVERS. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN PERSONAL INJURY.
Prior to energising
It is recommended that to energising the unit all protection devices are checked to ensure they are set correctly. For TLF units ensure that fuses are fitted. VIP units must be set in accordance with the results of a protection co-ordination study.
WARNING
SCHNEIDER ELECTRIC
79
Key
1 2 3 4 facia operating handle (padlockable) auxiliary/Protection compartment test access key (within LV pilot box) 5 6 7 8 9 data plate/pilot box main circuit label on pilot box transformer earth switch gas pressure indicator tripped on fault flag
10 7 8
3 8 CN2/SN6 9
10
2 5 4/6
CE2/CE6/SE6
80
SCHNEIDER ELECTRIC
Lift up hinged door. Check that the gas indicator is in the green, "healthy condition". Check the facia diagram for the service condition. Remove padlocks if fitted.
Move select to "Main Switch" position. Insert handle as shown and pull down firmly until the circuit breaker/switch closes. The selector lever will be locked into the "main switch" position. Fit padlock into "CB closed in service" position if required.
Note: That this does not affect electrical tripping of the unit.
To open, rotate the handle through 180 and reverse the procedure.
Lift up hinged door. Check that the gas indicator is in the green, "healthy condition". Check the facia diagram for the service condition. Remove padlocks if fitted.
With the switch/circuit breaker in the open position, move selector lever to "earth switch position". Insert handle as shown and pull down firmly until the switch closes. The selector will be locked in the "earth switch" position. Fit padlock into "circuit breaker/switch main cable earthed" if required.
Note: That the unit will not trip on fault.
To open, rotate the handle through 180 and reverse the procedure.
SCHNEIDER ELECTRIC
81
Open the main switch/circuit breaker. Move the selector lever (see page 81) to earth position. Do not re-close the main earth switch unless incoming cable earth is required. Move transformer earth selector lever as shown above.
Pull lever forwards as shown to close earth switch. Push back to rest position. The main selector lever should be locked in the earth position.
Remove padlock if fitted. Move transformer earth selector lever as shown above.
Turn lever clockwise as shown above until flag show "off" and mechanism is reset. Turn lever back to the rest position.
The transformer earth can now be padlocked off as shown above. The main selector lever is now free to move.
82
SCHNEIDER ELECTRIC
Cable testing main cable - CE6, CE2, SE6, CN2, SN6 and ring cables
Ensure that the main earth switch is "earth on". This will open the key way.
Insert test key (located in pilot cable box compartment) into key way and turn lever anti-clockwise. Remove test access cover padlock if fitted.
Pull test access cover down to remove cable earth and provide access to the testing bushings, (marked with red, yellow and blue phase spots). The test access key will be locked in position until the cover is firmly closed. Reverse procedure to return to service condition.
Note: Ensure cables are discharged before touching bushings after testing.
Actuator control
For electrical operation of the actuator see page 84 (if using Easergy T200E refer to the Easergy manual). To earth the main cable, the actuator must be removed. With the switch/circuit breaker in the open position, disconnect the actuator supply.
Rotate actuator mechanism anti-clockwise away from the handle socket. Manual operation can be performed as normal. Reverse the procedure to fit the actuator.
SCHNEIDER ELECTRIC
83
voltage 24V d.c. 24V d.c. 24V d.c. 24V d.c. + 30% - 10% + 30% - 10% + 30% - 10% + 30% - 10%
current 9A 5A 5A 5A
84
SCHNEIDER ELECTRIC
Maintenance
Recommendations and conditions
Routine maintenance will depend on the conditions to which the unit is subjected and to the relevant codes and practice. Periodic inspection of the substation and equipment will be necessary to establish the conditions to which the units are subjected to.
ideal conditions standard conditions no attention periodic inspection every 5 years every 5 years aggressive conditions no attention every 5 years every 2 years every 5 years
Ideal conditions
Environmental conditions
Unit installed and commissioned in accordance with the manufacturers instructions Indoors, completely protected from the weather. Humidity below 40% and no dripping water. Minimal dust and air circulation. Ambient temperature between -5oC and +40oC. No contact with any chemical agents (eg. salt). No infestation of any animal life (eg. insects). No contact with any plant life (eg. mould). No earth movements. No damage to the unit of any kind.
Operational conditions
No No No No mal-operation of any kind. abnormally high number of operations - refer to the graph on page 87. abnormally high number of faults - refer to the graph on page 87. over-voltage or over-current (above rating).
Standard conditions
Environmental conditions
Unit installed and commissioned in accordance with the manufacturers conditions. Humidity below 60%. Unit may be indoors or outdoors but must not be subjected to regular extremes of weather eg. heavy rain storms, dust storms, heavy snow and ice, flooding, temperature cycles greater than 40oC or less than -20oC, dense coastal fog or acid rain. No regular or thick covering of leaves or other debris. No contact with any chemical agents (eg. salt). No infestation of animal or plant life. No earth movements. No damage to the unit of any kind.
Operational conditions
No No No No mal-operation of any kind. abnormally high number of operations - refer to the graph. abnormally high number of faults - refer to the graph. over-voltage or over-current (above rating).
Aggressive conditions
Any environmental or operational conditions which do not satisfy either of the above two descriptions must be deemed aggressive.
We recommend that after 50% of its rated fault operations the following is checked: s Gas pressure s Trip opening time s Contact resistance The maximum number of fault interruptions can be calculated from the interrupting capacity graph on page 88.
Note: Local legislation may dictate maintenance be carried out with greater frequency, irrespective of site conditions. Please contact your local Schneider Electric representative for further details.
SCHNEIDER ELECTRIC
85
Maintenance
Housing
Housing exterior
Check all external fixings, labels and earth connections are present and tight. Check inside the main door (if fitted) and pilot cable box for heavy deposits of dust, ingress of water or contamination by animal or plant life. Check that the gas indicator is reading in the green zone. Clean the units thoroughly and touch up paint work as necessary.
Housing interior
Open the main and pilot cable box door. Check that the gas indicator is in the green zone and the protector cap is fitted over the gas filler valve. For circuit breaker panels check the electrical protection system - refer to commissioning instructions. Check the operation of the unit and all mechanical interlocks.
filler point
filler point
O rings must be scrupulously clean and well greased with petroleum jelly
86
SCHNEIDER ELECTRIC
Maintenance
Circuit breaker
Leakage of SF6 gas In the extremely unlikely event of a gas leak contact your local Schneider Electric office or UK customer service team immediately. Contact details can be found in the front of this document. New SF6 gas is nontoxic and non combustible. However when exposed to an electric arc SF6 breaks down and becomes toxic.
Service life If correctly installed and maintained the Ringmaster range of switchgear has a service life expectancy of 25 years.
100
10
16kA version 21kA version
The above applies to: RE2c, RE6c, CE2, CE6 and CN2 circuit breakers. It is not applicable to the ring switches of the ring main units or the SE6.
SCHNEIDER ELECTRIC
87
Notes
88
SCHNEIDER ELECTRIC
Merlin Gerin is a world leader in the manufacture and supply of high, medium and low voltage products for the distribution, protection, control and management of electrical systems and is focused on the needs of both the commercial and industrial sectors. The newly launched VDI Network Solutions offer provides flexible, configurable ethernet systems for all communication needs.
Square D is a total quality organisation and its business is to put electricity to work productively and effectively, protecting people, buildings and equipment. Its low voltage electrical distribution equipment, systems and services are used extensively in residential and commercial applications.
Telemecanique is a UK market leader and world expert in automation and control. It provides complete solutions, with its range of components, Modicon range of high technology programmable controllers (PLCs), multiple fieldbus and ethernet communication networks, HMI, motion control systems, variable speed drives and communications software. In addition, it offers power distribution through prefabricated busbar trunking.
Product showrooms
Industrial systems and solutions showroom Schneider Electric Ltd, University of Warwick Science Park, Sir William Lyons Road, Coventry CV4 7EZ Building systems and solutions showroom Schneider Electric Ltd, Stafford Park 5, Telford, Shropshire TF3 3BL Energy and Infrastructure systems and solutions showroom Schneider Electric Ltd, 123 Jack Lane, Hunslet, Leeds LS10 1BS
member of .co.uk
www.schneider-electric.co.uk SE6251 NOV 2007