Saes J 200
Saes J 200
Saes J 200
SAES-J-200
Pressure
22 May 2013
Scope............................................................. 2
References..................................................... 2
Page 1 of 6
SAES-J-200
Pressure
Scope
This standard prescribes the minimum mandatory requirements governing the design
and installation of pressure and differential pressure (D/P) instruments.
The requirements of this standard are in addition to and supplement the requirements of
the Process Industry Practice PIP PCCPR001, Pressure Measurement Criteria
referenced in Section 3 of this standard.
Any conflicts between this Standard and other applicable Saudi Aramco
Engineering Standards (SAESs), Materials System Specifications (SAMSSs),
Standard Drawings (SASDs), or industry standards, codes, and forms shall be
resolved in writing by the Company or Buyer Representative through the
Manager, Process & Control Systems Department of Saudi Aramco, Dhahran.
2.2
Direct all requests to deviate from this standard in writing to the Company or
Buyer Representative, who shall follow internal company procedure SAEP-302
and forward such requests to the Manager, Process & Control Systems
Department of Saudi Aramco, Dhahran.
References
The selection of material and equipment, and the design, construction, maintenance, and
repair of equipment and facilities covered by this standard shall comply with the latest
edition of the references listed below, unless otherwise noted.
3.1
SAES-J-003
Page 2 of 6
SAES-J-200
Pressure
DC-950041
DC-950042
DD-950053
3.2
SA-8020-200
SA-8020-212
SA-8020-213
SA-2773
PCCPR001
PCIDP000
PCIDP100
PCIPR000
PCIPR100
Page 3 of 6
SAES-J-200
Pressure
2.2
4.1.1.3
4.1.12
(Additional Paragraph) All instruments and their accessories shall meet the
relevant requirements of SAES-J-003 pertaining to ambient conditions.
Locally mounted instruments and their accessories shall meet the relevant
electrical area classification requirements of SAES-B-068.
4.2.2
4.2.3
4.2.7
(Addition) Add the following sentence at the end of the paragraph: siphons
shall also be used for process fluids with a temperature over 250C (480F)
when the gauge is above the tap connection.
4.2.8
4.2.9
4.3.5
4.3.6
(Additional Paragraph) Electric switch contacts shall be snap acting, singlepole, double-throw (SPDT) as a minimum. The contact rating shall be
sufficient to operate solenoids, relays, or other devices as specified in the
data sheet without the need for additional or interposing relays.
Hermetically sealed switch contacts are preferable.
4.3.7
SAES-J-200
Pressure
4.4.1
(Addition) For gas and vapor services, pressure transmitters and instruments
shall be mounted above and as close to the pressure taps as possible.
Pressure taps shall be connected to the process piping at the 12 oclock
position.
4.4.2
4.4.6
4.5.3
4.6
4.7
4.7.1
All pulsation dampeners (or snubbers), siphons, diaphragm seals and similar
accessories shall be shown on P&IDs.
4.7.2
4.7.3
Gauge savers protecting instruments against pressures that are very high
compared to the operating range may be used, except on switches in critical
(e.g., ESD) service.
5.1
Branch connection up to and including the first block (root) valve shall meet
the applicable Saudi Aramco piping codes. If more than one instrument are
sharing a common root valve, means to isolate each instrument
independently shall be provided.
Commentary Note:
The device manifold is acceptable to provide the required isolation at the enduse device in clean/non-plugging services when multiple devices share a
common root valve connection.
Page 5 of 6
SAES-J-200
Pressure
5.2
5.3
5.4
5.5
5.6
22 May 2013
Revision Summary
Minor revision as the pressure transmitter tap locations were clarified to reduce confusion
and rework.
Revised the Next Planned Update.