Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Enset Ngine: Performances

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

GENSET ENGINE 8061i06

PERFORMANCES
50 Hz 60 Hz
RATINGS
PRIME STAND-BY PRIME STAND-BY
Rated output kWm 56 62 63 69
Ratings in accordance with ISO 8528 - Standard reference conditions : 25°C air inlet temperature ; 1000 mbar ; 30% relative humidity - Power factor 0.8

PRIME POWER STAND-BY POWER


The Prime Power is the maximum power available with varying loads for an This is the maximum power available for a period of 500 hours/year
unlimited number of hours. The average power output during a 24 h period of with a mean load factor of 90% of the declared stand-by power.
operation must not exceed 80% of the declared prime power between the No kind of overload is permissible for this use.
prescribed maintenance intervals and at standard environmental conditions.
A 10% overload is permissible for 1 hour every 12 hours of operation.

TECHNICAL DATA
Engine model 8061i06 Cooling system liquid (water + 50% Paraflu11)
Diesel 4 stroke - Injection type direct Lube oil specifications ACEA E3-API CF4/MILL2104E/F
N° of cylinders 6 in line Lube oil consumption < 0.3% of fuel consumption
Total displacement L 5.9 Fuel specifications EN 590
Bore x Stroke mm 104 x 115 Speed governor mechanical (G2 class)
Compression ratio 18 : 1 Engine rotating mass moment of inertia kg.m2 1.179
Aspiration natural Flywheel housing / Flywheel SAE3 /11” ½
8061i06
TECHNICAL DATA
RPM 1500 1800 LUBRICATION SYSTEM
BMEP kPa 755 716 Lube oil total system incl. sump, filters etc. kg (l) ~ 10 (11)
Fuel consumption at : 100% load l/h 15.1 17.1 Oil capacity of standard sump :
75% load l/h 11.4 13.4 at min. level kg (l) ~ 6 (6.6)
at max level kg (l) ~ 8.1 (8.9)
50% load l/h 8.2 9.7
Maximum oil temperature °C 120
Oil pressure (min/max) kPa 196

AIR INDUCTION SYSTEM


Intake air flow. m3/h 240 290 RPM 1500 1800

Maximum suggested intake restriction : HEAT REJECTION (at full load conditions)
with clean air filter kPa 2.45 Engine to coolant (water + oil) kcal/kWh 560 563
with dirty air filter kPa 4.9
Engine to exhaust kcal/kWh 650 650
Radiated to ambient kcal/kWh 205 203
INJECTION
Injection system mechanical
Max speed drop steady conditions 4%
ELECTRIC STARTING SYSTEM
Max fuel feed pump suction head m 0.8
Cranking motor rating kW 3

EXHAUST SYSTEM Auxiliary voltage Vcc 12

Exhaust gas flow kg/h 290 360 Battery-charge alternator A 45

Max exhaust temperature Starting batteries :


at full load (at 25°C - after turbine) °C 530 550 Recommended capacity Ah 100
Max allowable exhaut backpressure kPa 14.7 Discharge current A 650

COOLING SYSTEM
Coolant capacity : engine only liters ~ 10
engine + radiator liters ~ 18,5 DIMENSIONS AND WEIGHTS
Cooling water flow rate l/min 85 105
Max allowable pressure drop
on external water circuit Pa 5.9 9.8
Max head of cooling radiator m 3

Pusher fan air flow m3/s 0.9 1.3


Pusher fan head (static) Pa 294
Pusher fan absorbed power kW 1 1.6
Specifications subject to change without notice
Illustrations may include optional equipment.

Max engine outlet water


temperature (Alarm) °C 100
Publication P4A048003E - 01.04

ATB (without canopy) - nominal rating °C 50


Engine dry weight, standard configuration kg 560

Local distributor

www.ivecomotors.com